HomeMy WebLinkAboutB14-0436 Balance Report.pdfTEST, ADJUST AND BALANCE REPORT
PROJECT
INSPIRATO PRE TAB
#1124
PREPARED FOR
R&H MECHANIC,l\L
REPORT ISSUE DATE
12/16/2014
PREPARED BY
HVAC TAB lie
· P.O. BOX 1926
VAIL, CO 81658
PHONE: 970-376-5198
E-MAlL: mrichardson@hvactab.co
\17\~/D~S~
HVAC TAB lie
TEST, ADJUST AND BALANCE REPORT
THE DATA PRESENTED IN THIS REPORT IS AN EXA.CT RECORD OF
SYSTEM PERFORMANCE AND \VAS OBTAThTED IN COl\1PLIANCE \VITH
NBC PROCEDlJRAL STAAllARDS. ANY VARIANCES FROM THE DESIGN
REQUIREMENTS ARE NOTED THROUGHOUT THIS REPORT.
THE RESULTS SHOWN AND INFORMATION PRESENTED IN THIS
REPORT IS CERTIFIED TO BE ACCURATE AND COMPLETE, TO THE
EXTENT POSSIBLE BY EQlJIP1\1ENT AND PROCEDURES USED THROUGH-
OUT THIS SURVEY.
THE FINAL AIR DISTRIBUTION SYSTEI\'I MEASUREMENTS ARE IN
COMPLIANCE \VITH NBC PROCEDURAL STA~DARDS FOR TESTING,
ADJUSTING AND BALANCING OF ENVIRONMENT AL SYSTEMS AND THE
PROJECT SPECIFICATIONS.
//" /:?"" // ~ /;/',,/ i/k,/?$~7
CERTIFIED BY: /j! //(! ,/ ~P ,,/~ (__ DATE: /)/fl/! L(
l
THE FINAL HYDRONIC DISTRIBUTION SYSTEl\1 l\1EASUREMENTS
ARE IN COMPLIANCE WITH NBC PROCEDURAL STANDARDS FOR
TESTING, ADUSTING AND BALANCING' OF ENVIRONMENTAL SYSTEMS
AND THE PROJECT SPECIFICATIONS.
/ /if/. . .
/2 ,/~ _r:<I?'/ wJf,4'~/ / /,if?/.,,<,/, .. I 2/;t/! ct' CERTIFIED BY: /' t / // .. , z_.-DA TE. -----
HVAC TAB lie \VARRANTS THAT THE AIR AND HYDRONIC SYSTEM
EVALUATED DURING THIS SURVEY IS OPERA TING AT THE SPECIFIED LEVELS
AS SHO\VN WTIHIN THIS REPORT, AT AND ONLY AT THIS TIME. HVAC TAB lie
c\1AKES NO OTHER W.A.RRANTIES, STATED OR IMPLIED, CONCERNING THE
CONTINUED PERFORMANCE, OPERATION OR SAFETY IN THE USE OF THIS
EQUJPMENT PASS THIS TIME.
Page: I
.HVAC TAB lie
DATE: 12/15/2014
PROJECT : INSPIRA TO
PROJECT ALTITUDE: "HG
INSTRUMENT/ SERIAL# APPLICATION
SHORTRIDGE ADM-870C I #M0921 l AIR FLOW READINGS
ANEMOMETER #RV A501416001 AIR FLOW READINGS
SHORTRIDGE FLOW HOOD Alf FLOW READINGS
TH-720 HYGROMETER/ #TH7200950003 AIR TEMP I HUMIDITY
PITOT TUBE 18" PRES. READINGS
PITOT TUBE 24" PRES. READINGS
PITOT TUBE 36" PRES. READINGS
PITOT TUBE 48" PRES. READINGS
SHIMPO TACHOMETER I #Cl05BOOIO RPM READINGS
FLUKE 375 I #21290229 VOLT/AMP
SHORTRIDGE HDM-250/ #W08162 WATER PRES. READINGS
ASCROFT I 0-100 PSI I #D068332-06 WATER PRES. READINGS
FLUKE 52-II #99780167 TEMP. READINGS
~
RACTOMETER RHA-100 I #RHA-GLYCOL % READINGS
lVli
DATE OF USE
12/15/2014
NOT USED
NOT USED
NOT USED
12/15/2014 .
NOT USED
NOT USED
NOT USED
12/15/2014
12/15/2014
12/15/2014
NOT USED
12/15/2014
NOT USED
INSTRUMENT
CALIBRATION REPORT
CALIBRATION CALIBRATION
DATE DUE DATE
06/12/2014 06/012/2015
04/14/2014 04/14/2015
* *
06/04/2014 06/04/2015
NIA NIA
NIA NIA
NIA NIA
NA NA
06/18/2014 06/18/2015
06/04/2014 06/04/2015
06/12/2014 06/12/2015
* *
02/3/2014 02/3/2015
NIA NIA
* CHECKED TO CALIBRATED METER
REMARKS: ALL READINGS WITH SHORTRIDGE INSTRUMENTS ARE CORRECTED FOR
TEMPERATURE AND ALTITUDE. PAGE:
· HVAC TAB lie
DATE: 12/15/2014
PROJECT: INSPIRATO
AIR HANDLER UNIT DATA
MANUFACTURER CARRIER
MODEL SHK03CYRFC44FCXF
SERIAL 2214R43633
FAN TYPE CENTRIFUGAL
RATING/OUTLET TOTAL 1.270CFM@0.5"ESP
MIN OSACFM 100 CFM
STARTER DATA
MANUFACTURER GE
MODEL CLASS 20
SIZE/THERMAL NO. -
l.NGE (AMPS) 1.8 -2.7
SET AT (AMPS) 2.5
REQ. THERMAL -
RA TING (AMPS) -
AIRFLOW DATA
SUPPLY CFM 1323
OSA CFM 0
RETURN CFM 1323
-0.02"
)TES:
OSA DAMPER HANDEL BROKEN
F
I
L
T
E
R
AIR APPARATUS
TEST REPORT
MOTOR NAMEPLATE DATA
MANUFACTURER MARATHON
HP R.P.M .. 314 1725
PHASE FRAME 3 56
S.F. TYPE 1.25 -
VOLTS AMPS 200/230/460 2.5/2.4/1.2
THERMALLY PROTECTED -
DRIVE DATA
MOTOR DRIVE 1 VP 3 3/4"
MOTOR BORE 5/8"
FAN DRIVE 1 FP 4" H
FAN BORE 3/4" H
NO. BEL TS & SIZE 1 I A 34
ROTATION CORRECT
CENTERLINE MOTOR ADJ PULLEY
SPEED+ 2 12" +1 -11.2 TURNS
TEST DATA INITIAL FINAL
FAN R.P.M. 1428
VOLTAGE 210/211/209
AMPERAGE 1.4/1.2/1. 7
(§7 -0.33" fF\
\d)
0.24"
BUZZING NOISE COMING FROM SERVICE DISCONNECT BOX DURING OPERATION
NOT OPERATING IN AUTO FROM THERMOSTAT
PAGE:
· HVAC TAB lie
DATE: 12/15/2014
PROJECT: INSPIRATO
AIR HANDLER UNIT DATA
MANUFACTURER CARRIER
MODEL 39SH K04'-6W-2W
SERIAL 1910R33930
FAN TYPE CENTRIFUGAL
RATING/OUTLET TOTAL 1400CFM@0.5"ESP
MIN OSACFM 100 CFM
STARTER DATA
MANUFACTURER NONE
MODEL NONE
SIZE/THERMAL NO. NONE
l.NGE (AMPS) NONE
SET AT (AMPS) NONE
REQ. THERMAL NONE
RA TING (AMPS) NONE
AIRFLOW DATA
SUPPLY CFM 2098
OSA CFM 0
RETURN CFM 2098
AIR APPARATUS
TEST REPORT ·
MOTOR NAMEPLATE DATA
MANUFACTURER LEESON
·.
HP R.P.M: 314 1725
PHASE FRAME 3 s 56
S.F. TYPE 1.25 -
VOLTS. AMP.S . 208/230/460., 7.2/8.2/4.1
THERMALLY PROTECTED -
DRIVE DATA
MOTOR DRIVE 1VP4 1/2"
MOTOR BORE 518"
FAN DRIVE 1 FP 6 1/2" H
FAN BORE 3/4" H
NO. BEL TS & SIZE 1 I 4L460
ROTATION CORRECT
CENTERLINE MOTOR ADJ PULLEY
14 1/2" +1 1/2 -1 SPEED+ 2
TURNS
TEST DATA INITIAL FINAL
FAN R.P.M. 1128
VOLTAGE 209/212/210
AMPERAGE 3.0/2.7/2.7
-0.18"
F ! EJ -0.M" @/ 0.17"
R
)TES:
NO THERMOSTAT INSTALLED
PAGE:
. .
HVAC TAB lie
DATE: 12/15/2014
PROJECT: INSPIRATO
BALANCE VALVE
TEST· REPORT·
SYSTEM: FC-1 I FC-2
FLOW METER DESIGN MEASURED
DESIGN. DESIGN· VALVE
LOCATION TYPE· SIZE ,6p GPM FINAL.6 P POSITION .. FINAL GPM
%OPEN
FC-1 HW ARMSTRONG 3/4" 1.5 0.60' 5.4 4.2
FC-1 CW TACO 3/4" 3.6 43.7" 100% 3.96
FC-2 HW TACO 3/4" 1.5 71.2" 100% 5.04
FC-2 CW TACO 1" 3.6 -2.5" 100% ? 2.1
")TES:
. C-2 CW NEGATIVE READ SEEMS TO BE PIPED IN REVERSE
PAGE:
HVAC TAB lie
DATE: 12/15/2014
PROJECT: INSPIRATO SYSTEM: FC-1 I FC-2
AIRDATA ADM-870 I HYGROMETER HM40 DESIGN
DESIGN DESIGN E.A.T. LOCATION E.A.T. L.A.T.
DB/WB DB/WB DB/WB
FC-1 HW 77.5
FC-1 CW 70.8
FC-2 HW 77.4
FC-2 CW 77.5
NOTES:
E.A.T. I L.A.T.
TEST REPORT
MEASURED
L.A.T. D. T
DB/WB DB/WB
102.5 25.0
67.1 3.7
117.3 39.9
61.7 15.8
PAGE:
· · HVAC TAB lie
DATE: 12/15/2014
PROJECT: INSPIRATO SYSTEM: FC-1 I FC-2
HYDRODATA HDM-250 DESIGN
LOCATION DESIGN ACTUAL DESIGN DESIGN E.W.T. GPM GPM E.W.T. L.W.T.
FC-1 HW 1.5 4.2 168.5
FC-1 CW 3.6 3.96 48.6
FC-2 HW 1.5 5.04 167.3
FC-2 CW 3.6 ? 2.1 60.3
NOTES:
FC-2 CW NEGATIVE READ SEEMS TO BE PIPED IN REVERSE
E.W.T. / L.W.T
TEST" REP'ORT
MEASURED
L.W.T. 6Tw
155.3 13.2
49.3 1.3
154.8 12.5
52.0 -8.3
PAGE: