HomeMy WebLinkAboutB14-0436 Balance Report.pdfTEST, ADJUST AND BALANCE REPORT PROJECT INSPIRATO PRE TAB #1124 PREPARED FOR R&H MECHANIC,l\L REPORT ISSUE DATE 12/16/2014 PREPARED BY HVAC TAB lie · P.O. BOX 1926 VAIL, CO 81658 PHONE: 970-376-5198 E-MAlL: mrichardson@hvactab.co \17\~/D~S~ HVAC TAB lie TEST, ADJUST AND BALANCE REPORT THE DATA PRESENTED IN THIS REPORT IS AN EXA.CT RECORD OF SYSTEM PERFORMANCE AND \VAS OBTAThTED IN COl\1PLIANCE \VITH NBC PROCEDlJRAL STAAllARDS. ANY VARIANCES FROM THE DESIGN REQUIREMENTS ARE NOTED THROUGHOUT THIS REPORT. THE RESULTS SHOWN AND INFORMATION PRESENTED IN THIS REPORT IS CERTIFIED TO BE ACCURATE AND COMPLETE, TO THE EXTENT POSSIBLE BY EQlJIP1\1ENT AND PROCEDURES USED THROUGH- OUT THIS SURVEY. THE FINAL AIR DISTRIBUTION SYSTEI\'I MEASUREMENTS ARE IN COMPLIANCE \VITH NBC PROCEDURAL STA~DARDS FOR TESTING, ADJUSTING AND BALANCING OF ENVIRONMENT AL SYSTEMS AND THE PROJECT SPECIFICATIONS. //" /:?"" // ~ /;/',,/ i/k,/?$~7 CERTIFIED BY: /j! //(! ,/ ~P ,,/~ (__ DATE: /)/fl/! L( l THE FINAL HYDRONIC DISTRIBUTION SYSTEl\1 l\1EASUREMENTS ARE IN COMPLIANCE WITH NBC PROCEDURAL STANDARDS FOR TESTING, ADUSTING AND BALANCING' OF ENVIRONMENTAL SYSTEMS AND THE PROJECT SPECIFICATIONS. / /if/. . . /2 ,/~ _r:<I?'/ wJf,4'~/ / /,if?/.,,<,/, .. I 2/;t/! ct' CERTIFIED BY: /' t / // .. , z_.-DA TE. ----- HVAC TAB lie \VARRANTS THAT THE AIR AND HYDRONIC SYSTEM EVALUATED DURING THIS SURVEY IS OPERA TING AT THE SPECIFIED LEVELS AS SHO\VN WTIHIN THIS REPORT, AT AND ONLY AT THIS TIME. HVAC TAB lie c\1AKES NO OTHER W.A.RRANTIES, STATED OR IMPLIED, CONCERNING THE CONTINUED PERFORMANCE, OPERATION OR SAFETY IN THE USE OF THIS EQUJPMENT PASS THIS TIME. Page: I .HVAC TAB lie DATE: 12/15/2014 PROJECT : INSPIRA TO PROJECT ALTITUDE: "HG INSTRUMENT/ SERIAL# APPLICATION SHORTRIDGE ADM-870C I #M0921 l AIR FLOW READINGS ANEMOMETER #RV A501416001 AIR FLOW READINGS SHORTRIDGE FLOW HOOD Alf FLOW READINGS TH-720 HYGROMETER/ #TH7200950003 AIR TEMP I HUMIDITY PITOT TUBE 18" PRES. READINGS PITOT TUBE 24" PRES. READINGS PITOT TUBE 36" PRES. READINGS PITOT TUBE 48" PRES. READINGS SHIMPO TACHOMETER I #Cl05BOOIO RPM READINGS FLUKE 375 I #21290229 VOLT/AMP SHORTRIDGE HDM-250/ #W08162 WATER PRES. READINGS ASCROFT I 0-100 PSI I #D068332-06 WATER PRES. READINGS FLUKE 52-II #99780167 TEMP. READINGS ~ RACTOMETER RHA-100 I #RHA-GLYCOL % READINGS lVli DATE OF USE 12/15/2014 NOT USED NOT USED NOT USED 12/15/2014 . NOT USED NOT USED NOT USED 12/15/2014 12/15/2014 12/15/2014 NOT USED 12/15/2014 NOT USED INSTRUMENT CALIBRATION REPORT CALIBRATION CALIBRATION DATE DUE DATE 06/12/2014 06/012/2015 04/14/2014 04/14/2015 * * 06/04/2014 06/04/2015 NIA NIA NIA NIA NIA NIA NA NA 06/18/2014 06/18/2015 06/04/2014 06/04/2015 06/12/2014 06/12/2015 * * 02/3/2014 02/3/2015 NIA NIA * CHECKED TO CALIBRATED METER REMARKS: ALL READINGS WITH SHORTRIDGE INSTRUMENTS ARE CORRECTED FOR TEMPERATURE AND ALTITUDE. PAGE: · HVAC TAB lie DATE: 12/15/2014 PROJECT: INSPIRATO AIR HANDLER UNIT DATA MANUFACTURER CARRIER MODEL SHK03CYRFC44FCXF SERIAL 2214R43633 FAN TYPE CENTRIFUGAL RATING/OUTLET TOTAL 1.270CFM@0.5"ESP MIN OSACFM 100 CFM STARTER DATA MANUFACTURER GE MODEL CLASS 20 SIZE/THERMAL NO. - l.NGE (AMPS) 1.8 -2.7 SET AT (AMPS) 2.5 REQ. THERMAL - RA TING (AMPS) - AIRFLOW DATA SUPPLY CFM 1323 OSA CFM 0 RETURN CFM 1323 -0.02" )TES: OSA DAMPER HANDEL BROKEN F I L T E R AIR APPARATUS TEST REPORT MOTOR NAMEPLATE DATA MANUFACTURER MARATHON HP R.P.M .. 314 1725 PHASE FRAME 3 56 S.F. TYPE 1.25 - VOLTS AMPS 200/230/460 2.5/2.4/1.2 THERMALLY PROTECTED - DRIVE DATA MOTOR DRIVE 1 VP 3 3/4" MOTOR BORE 5/8" FAN DRIVE 1 FP 4" H FAN BORE 3/4" H NO. BEL TS & SIZE 1 I A 34 ROTATION CORRECT CENTERLINE MOTOR ADJ PULLEY SPEED+ 2 12" +1 -11.2 TURNS TEST DATA INITIAL FINAL FAN R.P.M. 1428 VOLTAGE 210/211/209 AMPERAGE 1.4/1.2/1. 7 (§7 -0.33" fF\ \d) 0.24" BUZZING NOISE COMING FROM SERVICE DISCONNECT BOX DURING OPERATION NOT OPERATING IN AUTO FROM THERMOSTAT PAGE: · HVAC TAB lie DATE: 12/15/2014 PROJECT: INSPIRATO AIR HANDLER UNIT DATA MANUFACTURER CARRIER MODEL 39SH K04'-6W-2W SERIAL 1910R33930 FAN TYPE CENTRIFUGAL RATING/OUTLET TOTAL 1400CFM@0.5"ESP MIN OSACFM 100 CFM STARTER DATA MANUFACTURER NONE MODEL NONE SIZE/THERMAL NO. NONE l.NGE (AMPS) NONE SET AT (AMPS) NONE REQ. THERMAL NONE RA TING (AMPS) NONE AIRFLOW DATA SUPPLY CFM 2098 OSA CFM 0 RETURN CFM 2098 AIR APPARATUS TEST REPORT · MOTOR NAMEPLATE DATA MANUFACTURER LEESON ·. HP R.P.M: 314 1725 PHASE FRAME 3 s 56 S.F. TYPE 1.25 - VOLTS. AMP.S . 208/230/460., 7.2/8.2/4.1 THERMALLY PROTECTED - DRIVE DATA MOTOR DRIVE 1VP4 1/2" MOTOR BORE 518" FAN DRIVE 1 FP 6 1/2" H FAN BORE 3/4" H NO. BEL TS & SIZE 1 I 4L460 ROTATION CORRECT CENTERLINE MOTOR ADJ PULLEY 14 1/2" +1 1/2 -1 SPEED+ 2 TURNS TEST DATA INITIAL FINAL FAN R.P.M. 1128 VOLTAGE 209/212/210 AMPERAGE 3.0/2.7/2.7 -0.18" F ! EJ -0.M" @/ 0.17" R )TES: NO THERMOSTAT INSTALLED PAGE: . . HVAC TAB lie DATE: 12/15/2014 PROJECT: INSPIRATO BALANCE VALVE TEST· REPORT· SYSTEM: FC-1 I FC-2 FLOW METER DESIGN MEASURED DESIGN. DESIGN· VALVE LOCATION TYPE· SIZE ,6p GPM FINAL.6 P POSITION .. FINAL GPM %OPEN FC-1 HW ARMSTRONG 3/4" 1.5 0.60' 5.4 4.2 FC-1 CW TACO 3/4" 3.6 43.7" 100% 3.96 FC-2 HW TACO 3/4" 1.5 71.2" 100% 5.04 FC-2 CW TACO 1" 3.6 -2.5" 100% ? 2.1 ")TES: . C-2 CW NEGATIVE READ SEEMS TO BE PIPED IN REVERSE PAGE: HVAC TAB lie DATE: 12/15/2014 PROJECT: INSPIRATO SYSTEM: FC-1 I FC-2 AIRDATA ADM-870 I HYGROMETER HM40 DESIGN DESIGN DESIGN E.A.T. LOCATION E.A.T. L.A.T. DB/WB DB/WB DB/WB FC-1 HW 77.5 FC-1 CW 70.8 FC-2 HW 77.4 FC-2 CW 77.5 NOTES: E.A.T. I L.A.T. TEST REPORT MEASURED L.A.T. D. T DB/WB DB/WB 102.5 25.0 67.1 3.7 117.3 39.9 61.7 15.8 PAGE: · · HVAC TAB lie DATE: 12/15/2014 PROJECT: INSPIRATO SYSTEM: FC-1 I FC-2 HYDRODATA HDM-250 DESIGN LOCATION DESIGN ACTUAL DESIGN DESIGN E.W.T. GPM GPM E.W.T. L.W.T. FC-1 HW 1.5 4.2 168.5 FC-1 CW 3.6 3.96 48.6 FC-2 HW 1.5 5.04 167.3 FC-2 CW 3.6 ? 2.1 60.3 NOTES: FC-2 CW NEGATIVE READ SEEMS TO BE PIPED IN REVERSE E.W.T. / L.W.T TEST" REP'ORT MEASURED L.W.T. 6Tw 155.3 13.2 49.3 1.3 154.8 12.5 52.0 -8.3 PAGE: