HomeMy WebLinkAboutB14-0445 cut sheets.pdfGAS FURNACESEL296UHE ELITE® SERIES Upflow / Horizontal - Two-Stage Heat - High Efficiency Blower AFUE - Up to 96% Input - 44,000 to 132,000 BtuhNominal Add-on Cooling - 1.5 to 5 Tons EL 2 96 UH 070 X E 36 B - 01 Unit Type EL = Elite® Series Stages 2 = Two-Stage Nominal Gas Heat Input 045 = 44,000 Btuh 070 = 66,000 Btuh 090 = 88,000 Btuh 110 = 110,000 Btuh 135 = 132,000 Btuh Configuration UH = Upflow/Horizontal MODEL NUMBER IDENTIFICATION 1 Indoor coils with the same letter designation will physically match the furnace. AFUE 96 = 96% Bulletin No. 210647 March 2014 Supersedes December 2013 PRODUCT SPECIFICATIONS Blower E = High Efficiency Constant Torque Blower Motor Nominal Add-On Cooling Capacity 36 = 1.5-3 tons 48 = 2.5-4 tons 60 = 3-5 tons 1 Cabinet Width B = 17-1/2 in. C = 21 in. D = 24-1/2 in. Low NOx = Units meet California Nitrogen Oxides standards Minor Revision Number EL296UHE / Page 2 OFFONC CHIII LO HI WARRANTY Duralok Plus™ Aluminized Steel Heat Exchanger - Limited Lifetime warranty in residential applications (twenty year transferable), ten years in non-residential applications. All other covered components - Limited Five Year warranty in residential applications, one year in non- residential applications. Refer to Lennox Equipment Limited Warranty certificate included with equipment for details. APPROVALS Units are Certified by AHRI. Units are Certified by CSA International. Units tested and rated according to US DOE test procedures and FTC labeling regulations. Approved by the California Energy Commission and meets California Nitrogen Oxides (NOx) Standards. EnErgy Star® certified units are designed to use less energy, help save money on utility bills, and help protect the environment. ISO 9001 Registered Manufacturing Quality System. Blower data from unit tests conducted in Lennox Laboratory air test chamber. APPLICATIONS Input capacities of 44,000, 66,000, 88,000, 110,000 and 132,000 Btuh. Energy efficiency (AFUE) up to 96%. Compact cabinet for upflow, horizontal-left or horizontal- right applications without any modifications. Removable bottom seal panel shipped in place for side return air is easily removed for bottom/end return air applications. Utility room, alcove, closet, crawl space, basement or attic installation. Lennox add-on indoor coils, high-efficiency air cleaners and humidifiers can easily be added to furnace. Shipped factory assembled with all controls installed and wired. Each unit factory test operated to ensure proper operation. NOTE - FURNACES CANNOT BE TWINNED! A FEATURES B C D EF G H I J K L M CONTENTS Blower Data .................................................................21 Dimensions - Upflow Position ......................................14 Features.........................................................................2 Gas Heat Accessories .................................................10 High Altitude Derate .....................................................10 Installation Clearances ................................................13 Model Number Identification ..........................................1 Optional Accessories .....................................................9 Optional Accessory Dimensions ..................................16 Specifications.................................................................8 Vent Lengths ................................................................11 EL296UHE / Page 3 HEATING SYSTEM Lennox Duralok Plus™ Heat Exchanger Assembly Lennox developed heat exchanger assembly consists of primary heat exchanger and secondary condenser coil assembly. Main multi-pass crimped seam design clamshell type heat exchanger. Constructed of heavy- gauge, aluminized steel. Designed for normal expansion and contraction with maximum efficiency and minimum resistance to air flow. Secondary heat exchanger condenser coil constructed of aluminum fins fitted to stainless steel tubes. Complete heat exchanger assembly is pressure tested at the factory for leaks. Condensate drain header box assembly located on front of coil. Compact size of complete heat exchanger assembly permits low overall design of furnace cabinet. Heat exchanger assembly has been laboratory life cycle tested in excess of industry standards. Lennox Designed Header Box Header box on end of condenser coil collects flue condensate for disposal through condensate drains. The drains are located on each side of the cabinet for easy field installation of condensate drain trap. Only one drain is used, the other drain is sealed. Condensate drain trap is included with the unit for field installation. Lennox Designed Flue Condensate Trap Assembly Condensate trap assembly is mounted outside the conditioned air stream. Assembly can be mounted on either side of cabinet in upflow applications. Assembly is mounted below the cabinet in horizontal applications. Can also be mounted remotely (up to 5 ft. away) from unit. See Installation Instructions. 90° street elbow furnished for ease of drain trap installation. Drain connection can be made with field provided PVC pipe, PVC coupling, or vinyl tubing with hose clamp. Drain cap on trap allows easy cleaning and winterizing. Inshot Burners Aluminized steel inshot burners provide efficient, trouble-free operation. Burner venturi mixes air and gas in correct proportion for proper combustion. Burner assembly is removable from the unit as a single component for ease of service. B C D SureLight® Hot Surface Ignitor Tough, reliable, long-life, trouble-free performance. Silicon nitride ignitor. Cemented to steatite block for protection against current leakage. Ignition leads are constructed of nickel plated copper and are enclosed in high temperature Teflon® insulation for dependable operation. Two-Stage Gas Control Valve 24 volt redundant combination two-stage gas control valve combines manual shut off switch (On-Off), automatic electric valve (dual) and gas pressure regulation into a compact combination control. Two-Speed Combustion Air Inducer Permanent split capacitor (PSC), heavy duty blower prepurges heat exchanger and safely vents flue products. Dual pressure switches (low fire/high fire) prove blower operation before allowing gas valve to open. Operates only during heating cycle. Flame Rollout Switches (2) Manual reset switches are factory installed on burner box. Switch provides protection from abnormal operating conditions. Limit Control Automatic reset, primary limit is accurately located on vestibule panel on all units. Optional Accessories High Altitude Orifice Kits Required on all units for proper unit operation at altitudes from 7501 to 10,000 ft. Kits are available for natural gas and LPG/propane. High Altitude Pressure Switch Kit Required for proper unit operation on installations above 4500 ft. Natural Gas to LPG/Propane Conversion Kit Required for field changeover from natural gas to LPG/ Propane. LPG/Propane to Natural Gas Conversion Kit Required for field changeover from LPG/Propane to natural gas. E F G H FEATURES EL296UHE / Page 4 DIRECT VENT / NON-DIRECT VENT SEALED COMBUSTION SYSTEM Furnace features a “sealed combustion” system and can be installed in either Direct Vent or Non-Direct applications. In Direct Vent applications, combustion air is supplied from outdoors and flue gases are discharged outdoors. In Non-Direct Vent applications, combustion air is supplied from indoors and flue gases are discharged outdoors. NOTE - Lennox® has approved the use of DuraVent® PolyPro® manufactured vent pipe and terminations as an alternative to PVC vent pipe. Must be ordered separately. Tested and listed to the ULC S636 standard in Canada. The PolyPro venting system must follow the uninsulated and unconditioned space vent lengths listed in the table on . Refer to the Installation Instructions for additional details. Optional Accessories Termination Kits Facilitates installation of combustion air intake pipe and flue exhaust pipe. Refer to venting table in this bulletin to determine pipe size needed and proper termination kit required. Certain Termination Kits are certified to ULC S636 standard for use in Canada only. See Optional Accessories table and dimension drawings. Termination Kit - Concentric - Direct Vent Applications 2 or 3 inch kit contains concentric termination assembly, reducer bushing and 45 degree elbow. 2 inch kit for -045-070 models contains an outdoor exhaust accelerator. Kit requires single hole penetration of roof or wall for installation. Roof Termination Flashing Kit is available for use with 2 inch Kits. CSA certified. Termination Kit - Flush-Mount Kit contains flush-mount termination, accelerator, mounting template and hardware. Kit may be used with 2, 2-1/2 or 3 in. pipe. Termination Kits - Wall Assembly Close Couple (US Only) - Direct Vent Applications 2 or 3 inch kit consists of close-couple, side-by-side PVC piping with galvanized steel wall cover plate for sealing and isolating piping penetration of the wall. Piping spacing and length is sized for proper wall installations. CSA certified. Close Couple WTK (Canada Only) - Direct Vent FEATURES Applications 2 or 3 inch kit contains one insulated faceplate, one insulated exhaust pipe, elbow and fittings. Certified to ULC S636 standard. Wall Ring - Direct Vent or Non-Direct Vent Applications 2 inch kit contains 2 stainless steel outside seal caps, 2 galvanized steel inside seal caps, 4 seal rings for the caps and 18 inch insulation sleeve for sealing and isolating intake and exhaust piping penetration of wall. Maintain a maximum of 6 inches between the inlet and outlet openings in the installation of the pipes. Roof Termination Flashing Kit 3 inch kit contains two neoprene rubber roof flashings for vertical venting through a roof. Vent pipe and insulation not furnished. Flashing Kit can also be used with 2 inch Concentric Vent Termination Kits used in vertical venting rooftop applications.. CONTROLS SureLight® Integrated Furnace Control Contains all necessary controls and relays to operate furnace. Combustion air inducer is operated by the integrated furnace control. Prior to ignition, a pre-purge cycle for 15 seconds is initiated. After the main burners are turned off, a post-purge cycle for 5 seconds is run. Safety Controls - Flame sensor utilizes flame rectification for safe and reliable operation. Should loss of flame occur, the integrated furnace control will initiate 4 re-attempts at ignition before locking out unit operation for 60 minutes. Watchguard type circuit automatically resets ignition controls after one hour of continuous thermostat demand after unit lockout, eliminating nuisance calls for service. Thermostat Control - For optimal performance, the use of a high-quality, digital two-stage thermostat with adjustable settings for first stage/second stage, on/off differentials and adjustable stage timers is recommended. Furnace Input Staging Options Thermostat Type Input Staging Available Two-Stage (Conventional)Determined by thermostat demand Single-Stage (Conventional) 2nd-stage heat ON delay (DIP switch setting) OFF - 7 minutes (factory) ON - 12 minutes I EL296UHE / Page 5 FEATURES CONTROLS (continued) Display LED - Seven segment LED displays alpha- numeric information related to diagnostics as well as system operation and status. Diagnostic codes are held in non-volatile memory, immune from power interruptions. Holds up to ten diagnostic codes in order of occurrence for recall on demand. Port on blower door allows for easy viewing. DIP Switch Settings Select Thermostat used - Single-Stage or Two-Stage. Two selectable second stage recognition times (7 and 12 minutes) are available on the control when the furnace is used with a single-stage thermostat. When used with a two-stage thermostat, furnace will only initiate second stage operation with a second stage thermostat demand. Second Stage Delay - Used with single-stage thermostat only. See Furnace Input Staging Options table for details. Blower On/Off Time (Heating) - Blower on time is fixed at 30 seconds, blower off time is adjustable from 60, 90, 120 and 180 seconds (factory setting - 90 seconds). Blower On/Off Time (Cooling) - For air-conditioning applications, blower on time is 2 seconds following thermostat demand for cooling. Blower off time in cooling mode is adjustable from 2 or 45 seconds (factory setting - 45 sec). For air-conditioning applications, blower is automatically energized on thermostat demand for cooling. Heating Speeds - Low Heat or High Heat. Cooling Speeds - Low Cool or High Cool. Continuous Speed - Low Heat (factory setting) - adjustable. Dehumidification - A jumper on the control must be clipped to enable dehumidification. A humidity controlling thermostat or device is also required. During a call for cooling, air volume is automatically reduced, forcing humidity removal by the air conditioner or heat pump system (single stage units or two-stage units running at 2nd stage). After the humidity has reached the desired set-point the cooling air volume returns to its designed rate. Dual-Fuel Operation - A jumper on the control must be clipped to enable operation with a single or two-stage heat pump. The indoor blower is started without delay when a call for heat is received. Two Stage Compressor Operation - A jumper on the control must be clipped to enable operation with a two- stage compressor. Accessory Terminal - One accessory terminal furnished for additional power supply requirements for 120 volt (less than 1 amp) powered air cleaners. One unpowered pair of contacts are provided for humidifier connections and may be connected to 24V or 120V. Control is factory installed in the unit control box. 24 Volt Transformer Furnished and factory installed in control box. 40VA transformer has circuit breaker wired in series. Field Wiring Make-up Box Furnished for line voltage wiring. Factory installed internally on left side of furnace. Box may be installed internally or externally on either side of furnace. Optional Accessories Thermostat Thermostat (programmable/non-programmable) is not furnished with unit. See Thermostat bulletins in Controls Section and Lennox Price Book for selection. Night Service Kit Contains most commonly used service parts: • Furnace control • Igniter • Flame sensor • Gas valve • Transformer • Service Manual Universal Service Kit - Switches Kit contains: • Primary limits (for each model) • Pressure switches (for each model) • Flame rollout switches (for each model) EL296UHE / Page 6 FEATURES BLOWER Direct drive blower. Statically and dynamically balanced. Resiliently mounted. Blower assembly easily removed for servicing. DC Brushless Motor High Efficiency Constant Torque. ECM (Electronically Commutated Motor). Motor is programmed to provide constant torque at each of the selectable speeds. Motor is controlled by the SureLight® Integrated Furnace Control. Blower speeds are easily changed on the integrated furnace control. See Blower Data tables. J CABINET Low-profile, narrow width cabinet allows easy installation in upflow or horizontal applications. Heavy-gauge, cold rolled steel construction. Pre-painted cabinet finish. Flanges provided on supply air opening for ease of plenum connection or alignment with indoor coil. Fully insulated cabinet with foil faced insulation on sides and back of heating compartment and mat faced insulation in blower compartment. Sealed blower compartment. Inner blower compartment access panel seals blower compartment from air leakage. Cabinet door can be removed without any tools.. Complete service access. Safety interlock switch automatically shuts off power to unit when blower compartment access door is removed. Gas piping and electrical inlets are provided in both sides of cabinet. Return Air Entry: For bottom/end return-air entry for upflow/horizontal applications, remove furnished bottom seal panel from cabinet. For side return-air entry (upflow applications only), corners are marked on either side of cabinet for return air cut-outs. See Dimension Drawing. NOTE - 60C and 60D size units that require air volumes over 1800 cfm must have one of the following: 1. Single side return air with transition, to accommodate 20 x 25 x 1 in. cleanable air filter. Required to maintain proper air velocity. 2. Single side return air with Optional Return Air Base 3. Bottom return air. 4. Return air from both sides. 5. Bottom and one side return air. See Blower Data Tables for additional information. Coil Match-Up All furnaces exactly match C33 and CX34 cased upflow indoor coils and CH33 horizontal indoor coils with same letter designation in model number. No adaptor required. Engaging holes furnished on cabinet for alignment. C33 uncased coils match furnaces without any overhang but require an optional adaptor base or field fabricated transition to match furnace opening. See C33 coil bulletin for additional information. K L M EL296UHE / Page 7 FEATURES CABINET (continued) Optional Accessories Condensate Drain Heat Cable Kits Self-limiting wattage heat cable prevents condensate drain from freezing in unconditioned areas. Available in 6 or 24 ft. lengths. Heat Cable Tape: 66 ft. length, 1/2 in. wide fiberglass. Horizontal Suspension Kit Provides suspension of unit and indoor coil in horizontal applications. Allows complete service access. Consists of corner mounted hanging brackets with vibration isolators, return air end support rail and hardware for assembly. Metal hanging straps must be field provided. Crawl Space Vent Drain Kit Allows venting through a crawl space for upflow and horizontal applications. Includes 2 or 3 in. sanitary tee, 2 in. PVC assembly, PVC boot and clamp. Return Air Base On furnaces with side return air and condensate trap on the same side of the cabinet, a field fabricated transition or Return Air Base is required when using an IAQ product higher than 14-3/16 in. installed next to the unit and serviced from the front. IAQ products higher than 20 in. require a field fabricated transition. Must be used for 60C and 60D models with air volumes over 1800 cfm in upflow applications when only one side return is required. Cabinet is shipped flat for easy field assembly and is pre-painted steel to match the furnace. See Dimension Drawing. FILTER (not furnished) Filter and provisions for external mounting must be field provided. Optional Accessories Air Filter and Rack Kit for Horizontal Return Air (End) Applications Washable or vacuum cleanable polyurethane frame type filter and external end return air rack available for field installation. Rack has filter door for easy filter servicing. Flanges on rack allow easy duct connection. See Dimension Drawing. Air Filter and Rack Kit for Upflow Side Return Air Applications - Not for use with Return Air Base Washable or vacuum cleanable polyurethane frame type filter and external side return air rack available for field installation. Available in single and ten pack kits. Rack has filter door for easy filter servicing. Flanges on rack allow easy duct connection. Field installs on either side of unit cabinet. See Dimension Drawing. EL296UHE / Page 8 SPECIFICATIONS Gas Heating Performance Model No.EL296UH045XE36B EL296UH070XE36B EL296UH090XE48C 1 AFUE 96%95.5%96% High Fire Input - Btuh 44,000 66,000 88,000 Output - Btuh 43,000 64,000 84,000 Temperature rise range - °F 30-60 35-65 40-70 Gas Manifold Pressure (in. w.g.) Nat. Gas / LPG/Propane 3.5 / 10.0 3.5 / 10.0 3.5 / 10.0 Low Fire Input - Btuh 29,000 43,000 57,000 Output - Btuh 28,000 42,000 55,000 Temperature rise range - °F 20 - 50 25 - 55 30 - 60 Gas Manifold Pressure (in. w.g.) Nat. Gas / LPG/Propane 1.7 / 4.9 1.7 / 4.9 1.7 / 4.9 High static - in. w.g.0.5 0.5 0.5 Connections in.Intake / Exhaust Pipe (PVC)2 / 2 2 / 2 2 / 2 Gas pipe size IPS 1/2 1/2 1/2 Condensate Drain Trap (PVC pipe) - i.d.3/4 3/4 3/4 with furnished 90° street elbow 3/4 slip x 3/4 Mipt 3/4 slip x 3/4 Mipt 3/4 slip x 3/4 Mipt with field supplied (PVC coupling) - o.d.3/4 slip x 3/4 MPT 3/4 slip x 3/4 MPT 3/4 slip x 3/4 MPT Indoor Blower Wheel nominal diameter x width - in.10 x 8 10 x 8 10 x 10 Motor Type DC Brushless DC Brushless DC Brushless Motor output - hp 1/2 1/2 3/4 Tons of add-on cooling 1.5 - 3 1.5 - 3 2.5 - 4 Air Volume Range - cfm 520 - 1345 550 - 1380 760 - 1740 Electrical Data Voltage 120 volts - 60 hertz - 1 phase Blower motor full load amps 6.8 6.8 8.4 Maximum overcurrent protection 15 15 15 Shipping Data lbs. - 1 package 129 137 161 NOTE - Filters and provisions for mounting are not furnished and must be field provided. 1 Annual Fuel Utilization Efficiency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized furnaces. SPECIFICATIONS Gas Heating Performance Model No.EL296UH110XE60C EL296UH135XE60D 1 AFUE 96%96% High Fire Input - Btuh 110,000 132,000 Output - Btuh 106,000 127,000 Temperature rise range - °F 40-70 45-75 Gas Manifold Pressure (in. w.g.) Nat. Gas / LPG/Propane 3.5 / 10.0 3.5 / 10.0 Low Fire Input - Btuh 72,000 86,000 Output - Btuh 70,000 84,000 Temperature rise range - °F 35-65 35-65 Gas Manifold Pressure (in. w.g.) Nat. Gas / LPG/Propane 1.7 / 4.9 1.7 / 4.9 High static - in. w.g.0.5 0.5 Connections in.Intake / Exhaust Pipe (PVC)2 / 2 2 / 2 Gas pipe size IPS 1/2 1/2 Condensate Drain Trap (PVC pipe) - i.d.3/4 3/4 with furnished 90° street elbow 3/4 slip x 3/4 Mipt 3/4 slip x 3/4 Mipt with field supplied (PVC coupling) - o.d.3/4 slip x 3/4 MPT 3/4 slip x 3/4 MPT Indoor Blower Wheel nominal diameter x width - in.11-1/2 x 10 11-1/2 x 10 Motor Type DC Brushless DC Brushless Motor output - hp 1 1 Tons of add-on cooling 3 - 5 3.5 - 5 Air Volume Range - cfm 1055 - 2220 1260 - 2405 Electrical Data Voltage 120 volts - 60 hertz - 1 phase Blower motor full load amps 10.9 10.9 Maximum overcurrent protection 15 15 Shipping Data lbs. - 1 package 174 189 NOTE - Filters and provisions for mounting are not furnished and must be field provided. 1 Annual Fuel Utilization Efficiency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized furnaces. EL296UHE / Page 9 OPTIONAL ACCESSORIES - ORDER SEPARATELY NOTE - FURNACES CANNOT BE TWINNED! “B” Width Models “C” Width Models “D” Width Models CABINET ACCESSORIES Horizontal Suspension Kit - Horizontal only 51W10 51W10 51W10 Return Air Base - Upflow only 50W98 50W99 51W00 CONDENSATE DRAIN KITS Condensate Drain Heat Cable 6 ft. 26K68 26K68 26K68 24 ft.26K69 26K69 26K69 Heat Cable Tape Fiberglass - 1/2 in. x 66 ft.36G53 36G53 36G53 Crawl Space Vent Drain Kit 51W18 51W18 51W18 FILTER KITS 1 Air Filter and Rack Kit Horizontal (end)Size of filter - in.87L96 - 18 x 25 x 1 87L97 - 20 x 25 x 1 87L98 - 25 x 25 x 1 Side Return Single 44J22 44J22 44J22 Ten Pack 66K63 66K63 66K63 Size of filter - in.16 x 25 x 1 16 x 25 x 1 16 x 25 x 1 SERVICE KITS Night Service Kit 10B39 10B39 10B39 Universal Service Kit - Switches 89W20 89W20 89W20 TERMINATION KITS See Installation Instructions for specific venting information. Termination Kits - Direct Vent Applications Only Concentric US - 2 in.71M80 69M29 - - - 3 in.- - -60L46 60L46 Canada - 2 in.44W92 44W92 - - - 3 in.- - -44W93 44W93 Flush-Mount US - 2, 2-1/2 or 3 in.51W11 51W11 51W11 Canada - 2, 2-1/2 or 3 in.51W12 51W12 51W12 Wall - Close Couple US - 2 in.22G44 - - -- - - 3 in.44J40 44J40 44J40 Wall - Close Couple WTK Canada - 2 in.30G28 - - -- - - 3 in.81J20 81J20 81J20 Termination Kits - Direct or Non- Direct Vent Roof 2 in.15F75 15F75 - - - Wall Ring Kit 2 in.15F74 3 15F74 - - - 2 Roof Termination Flashing Kit - Direct or Non-Direct Vent (2 flashings)3 in.44J41 44J41 44J41 1 Cleanable polyurethane, frame-type filter. 5 Kits contain enough parts for two, non-direct vent installations. 3 Non-direct vent only. NOTE - Termination Kits 44W92, 44W93, 30G28, 51W12, 51W19, 81J20 are certified to ULC S636 standard for use in Canada only. EL296UHE / Page 10 GAS HEAT ACCESSORIES Input High Altitude Pressure Switch Kit Natural Gas to LPG/Propane Kit LPG/Propane to Natural Gas Kit Natural Gas High Altitude Orifice Kit LPG/Propane High Altitude Orifice Kit 4501 - 7500 ft.7501 - 10,000 ft.0 - 7500 ft.0 - 7500 ft.7501 - 10,000 ft.7501 - 10,000 ft. 045 93W81 93W84 78W93 77W09 73W37 78W96 070 93W80 93W85 78W93 77W09 73W37 78W96 090 93W82 93W80 78W93 77W09 73W37 78W96 110 93W80 93W85 78W93 77W09 73W37 78W96 135 93W83 93W85 78W93 77W09 73W37 78W96 HIGH ALTITUDE DERATE NOTE - Units may be installed at altitudes up to 10,000 ft. At altitudes above 4501 ft. the unit must be derated to match the manifold pressure information shown below. Units installed at altitudes of 4501 to 10,000 ft. require a pressure switch change. Units installed at altitudes of 7501 to 10,000 ft. require an orifice change. See the Gas Heat Accessories table for ordering information. NOTE - This is the only permissible derate for these units. NOTE - In Canada, certification for installations at elevations over 4500 feet is the jurisdiction of local authorities. Input Gas Manifold Pressure in. w.g.Supply Line Pressure in. w.g. 0 - 10,000 ft.0 - 4500 ft.4501 - 5500 ft.5501 - 6500 ft.6501 - 7500 ft.7501 - 10,000 ft. Low Fire High Fire Low Fire High Fire Low Fire High Fire Low Fire High Fire Low Fire High Fire Min.Max. All Sizes Natural 1.7 3.5 1.6 3.3 1.5 3.2 1.5 3.1 1.7 3.5 4.5 13.0 LPG/Propane 4.9 10.0 4.6 9.4 4.4 9.1 4.3 8.9 4.9 10.0 11.0 13.0 EL296UHE / Page 11 VENT LENGTHS - UNINSULATED EXHAUST PIPE IN UNCONDITIONED SPACE Winter Design Temperatures Vent Pipe Diameter Unit Input Size 045 070 090 110 135 Maximum Un-Insulated Exhaust Vent Length (ft.) 32 to 21°F 2 in.20 30 40 24 N/A 2-1/2 in.15 22 30 40 N/A 3 in.12 18 25 32 32 20 to 1°F 2 in.12 20 25 24 N/A 2-1/2 in.10 14 20 24 N/A 3 in.6 10 15 20 20 0 to –20°F 2 in.8 12 18 22 N/A 2-1/2 in.6 8 12 16 N/A 3 in.2 6 10 12 12 OUTDOOR TERMINATION KIT USAGE Input Size Vent Pipe Diameter (in.) Standard Terminations Concentric Terminations Flush Mount Kit Wall Kit Wall Ring Kit Field Fabricated Exhaust Accelerator Size Required Concentric Kit 1-1/2 inch 2 inch 3 inch2 inch 3 inch 2 inch 51W11 (US) 4 51W12 (CA)22G44 (US) 4 30G28 (CA)44J40 (US) 4 81J20 (CA)15F74 71M80 (US) 4 44W92 (CA)69M29 (US) 4 44W92 (CA)60L46 (US) 4 44W93 (CA) 045 2 3 YES YES 1 YES YES 1-1/2 in.2 YES - - -- - - 2-1/2 3 YES YES 1 YES YES 1-1/2 in.2 YES - - -- - - 3 3 YES YES 1 YES YES 1-1/2 in.2 YES - - -- - - 070 2 3 YES YES 1 YES YES 1-1/2 in.2 YES - - -- - - 2-1/2 3 YES YES 1 YES YES 1-1/2 in.2 YES - - -- - - 3 3 YES YES 1 YES YES 1-1/2 in.2 YES - - -- - - 090 2 3 YES - - -YES 1 YES 2 in.- - -YES YES 2-1/2 3 YES - - -YES 1 YES 2 in.- - -YES YES 3 3 YES - - -YES 1 YES 2 in.- - -YES YES 110 2 YES - - -YES YES 2 in.- - -YES YES 2-1/2 YES - - -YES - - -2 in.- - -YES YES 3 YES - - -YES - - -2 in.- - -YES YES 135 3 YES - - -YES - - -2 in.- - -- - -YES NOTE - Standard Terminations do not include any vent pipe or elbows external to the structure. Any vent pipe or elbows external to the structure must be included in total vent length calculations. See Vent Length Tables. 1 Requires field provided 1-1/2 in. outdoor exhaust accelerator. 2 Concentric Kits 71M80 and 44W92 include 1-1/2 in. outdoor exhaust accelerator, required when used with 045 and 070 input models. Accelerator is not used with 090, 110, 135 input models. 3 Flush Mount Kit 51W11 and 51W12 includes 1-1/2 in. outdoor exhaust accelerator, required when used with 045, 070 and 090 input models. Accelerator is not used with 110 or 135 input models. 4 Termination Kits 30G28, 44W92, 44W93, 51W12 and 81J20 are certified to ULC S636 standard for use in Canada only. EL296UHE / Page 12 VENT LENGTHS - FEET STANDARD TERMINATION AT ELEVATION 0 - 4500 ft. Pipe Size 2 in.2-1/2 in.3 in. Input 045 070 090 110 135 045 070 090 110 135 045 070 090 110 135 No. of 90 ELL 1 81 66 44 24 N/A 115 115 93 58 N/A 138 137 118 118 114 2 76 61 39 19 N/A 110 110 88 53 N/A 133 132 113 113 109 3 71 56 34 14 N/A 105 105 83 48 N/A 128 127 108 108 104 4 66 51 29 N/A N/A 100 100 78 43 N/A 123 122 103 103 99 5 61 46 24 N/A N/A 95 95 73 38 N/A 118 117 98 98 94 6 56 41 19 N/A N/A 90 90 68 33 N/A 113 112 93 93 89 7 51 36 14 N/A N/A 85 85 63 28 N/A 108 107 88 88 84 8 46 31 N/A N/A N/A 80 80 58 23 N/A 103 102 83 83 79 9 41 26 N/A N/A N/A 75 75 53 18 N/A 98 97 78 78 74 10 36 21 N/A N/A N/A 70 70 48 13 N/A 93 92 73 73 69 STANDARD TERMINATION ELEVATION 4501 - 10,000 ft. Pipe Size 2 in.2-1/2 in.3 in. Input 045 070 090 110 135 045 070 090 110 135 045 070 090 110 135 No. of 90 ELL 1 81 66 44 N/A N/A 115 115 93 58 N/A 138 137 118 118 114 2 76 61 39 N/A N/A 110 110 88 53 N/A 133 132 113 113 109 3 71 56 34 N/A N/A 105 105 83 48 N/A 128 127 108 108 104 4 66 51 29 N/A N/A 100 100 78 43 N/A 123 122 103 103 99 5 61 46 24 N/A N/A 95 95 73 38 N/A 118 117 98 98 94 6 56 41 19 N/A N/A 90 90 68 33 N/A 113 112 93 93 89 7 51 36 14 N/A N/A 85 85 63 28 N/A 108 107 88 88 84 8 46 31 N/A N/A N/A 80 80 58 23 N/A 103 102 83 83 79 9 41 26 N/A N/A N/A 75 75 53 18 N/A 98 97 78 78 74 10 36 21 N/A N/A N/A 70 70 48 13 N/A 93 92 73 73 69 CONCENTRIC TERMINATION AT ELEVATION 0 - 4500 ft. Pipe Size 2 in.2-1/2 in.3 in. Input 045 070 090 110 135 045 070 090 110 135 045 070 090 110 135 No. of 90 ELL 1 73 58 42 22 N/A 105 105 89 54 N/A 121 121 114 114 105 2 68 53 37 17 N/A 100 100 84 49 N/A 116 116 109 109 100 3 63 48 32 12 N/A 95 95 79 44 N/A 111 111 104 104 95 4 58 43 27 N/A N/A 90 90 74 39 N/A 106 106 99 99 90 5 53 38 22 N/A N/A 85 85 69 34 N/A 101 101 94 94 85 6 48 33 17 N/A N/A 80 80 64 29 N/A 96 96 89 89 80 7 43 28 12 N/A N/A 75 75 59 24 N/A 91 91 84 84 75 8 38 23 N/A N/A N/A 70 70 54 19 N/A 86 86 79 79 70 9 33 18 N/A N/A N/A 65 65 49 14 N/A 81 81 74 74 65 10 28 13 N/A N/A N/A 60 60 44 N/A N/A 76 76 69 69 60 CONCENTRIC TERMINATION ELEVATION 4501 - 10,000 ft. Pipe Size 2 in.2-1/2 in.3 in. Input 045 070 090 110 135 045 070 090 110 135 045 070 090 110 135 No. of 90 ELL 1 73 58 42 N/A N/A 105 105 89 54 N/A 121 121 114 114 105 2 68 53 37 N/A N/A 100 100 84 49 N/A 116 116 109 109 100 3 63 48 32 N/A N/A 95 95 79 44 N/A 111 111 104 104 95 4 58 43 27 N/A N/A 90 90 74 39 N/A 106 106 99 99 90 5 53 38 22 N/A N/A 85 85 69 34 N/A 101 101 94 94 85 6 48 33 17 N/A N/A 80 80 64 29 N/A 96 96 89 89 80 7 43 28 12 N/A N/A 75 75 59 24 N/A 91 91 84 84 75 8 38 23 N/A N/A N/A 70 70 54 19 N/A 86 86 79 79 70 9 33 18 N/A N/A N/A 65 65 49 14 N/A 81 81 74 74 65 10 28 13 N/A N/A N/A 60 60 44 N/A N/A 76 76 69 69 60 EL296UHE / Page 13 VENT LENGTHS (EXHAUST) - VENTILATED ATTIC OR CRAWLSPACE INTAKE AIR - FEET STANDARD TERMINATION AT ELEVATION 0 - 4500 ft. Pipe Size 2 in.2-1/2 in.3 in. Input 045 070 090 110 135 045 070 090 110 135 045 070 090 110 135 No. of 90 ELL 1 71 56 34 14 N/A 100 100 78 43 N/A 118 117 98 98 94 2 66 51 29 9 N/A 95 95 73 38 N/A 113 112 93 93 89 3 61 46 24 4 N/A 90 90 68 33 N/A 108 107 88 88 84 4 56 41 19 N/A N/A 85 85 63 28 N/A 103 102 83 83 79 5 51 36 14 N/A N/A 80 80 58 23 N/A 98 97 78 78 74 6 46 31 9 N/A N/A 85 75 63 18 N/A 93 92 73 73 69 7 41 26 4 N/A N/A 70 70 48 13 N/A 88 87 68 68 64 8 36 21 N/A N/A N/A 65 65 43 8 N/A 83 82 63 63 59 9 31 16 N/A N/A N/A 60 60 38 3 N/A 78 77 58 58 54 10 26 11 N/A N/A N/A 55 55 33 N/A N/A 73 72 53 53 49 STANDARD TERMINATION ELEVATION 4501 - 10,000 ft. Pipe Size 2 in.2-1/2 in.3 in. Input 045 070 090 110 135 045 070 090 110 135 045 070 090 110 135 No. of 90 ELL 1 71 56 34 N/A N/A 100 100 78 43 N/A 118 117 98 98 94 2 66 51 29 N/A N/A 95 95 73 38 N/A 113 112 93 93 89 3 61 46 24 N/A N/A 90 90 68 33 N/A 118 107 88 88 84 4 56 41 19 N/A N/A 85 85 63 28 N/A 113 102 83 83 79 5 51 36 14 N/A N/A 80 80 58 23 N/A 98 97 78 78 74 6 46 31 9 N/A N/A 85 85 53 18 N/A 93 92 73 73 69 7 41 26 4 N/A N/A 70 70 48 13 N/A 98 87 68 68 64 8 36 21 N/A N/A N/A 65 65 43 8 N/A 93 82 63 63 59 9 31 16 N/A N/A N/A 60 60 38 3 N/A 78 77 58 58 54 10 26 11 N/A N/A N/A 55 55 33 N/A N/A 73 72 53 53 49 INSTALLATION CLEARANCES - INCHES (MM) Sides 1 0 inches (0 mm) Rear 0 inches (0 mm) Top/Plenum 1 inch (25 mm) Front 0 inches (0 mm) Front (service/alcove) 24 inches (610 mm) Floor 2 Combustible NOTE − Air for combustion must conform to the methods outlined in the National Fuel Gas Code (NFPA 54/ANSI−Z223.1) or the National Standard of Canada CAN/CSA−B149.1 Natural Gas and Propane Installation Code”. NOTE − In the U.S. flue sizing must conform to the methods outlined in the current National Fuel Gas Code (NFPA 54/ANSI−Z223.1) or applicable provisions of local building codes. In Canada flue sizing must conform to the methods outlined in National Standard of Canada CAN/CSA−B149.1. 1 Allow proper clearances to accommodate condensate trap and vent pipe installation. 2 Do not install the furnace directly on carpeting, tile, or other combustible materials other than wood flooring. EL296UHE / Page 14 DIMENSIONS - INCHES (MM) - UPFLOW POSITION Model No.A B C D in.mm in.mm in.mm in.mm EL296UH045XE36B EL296UH070XE36B 17-1/2 446 16-3/8 416 16 406 7-5/8 194 EL296UH090XE48C EL296UH110XE60C 21 533 19-7/8 505 19-1/2 495 9-3/8 238 EL296UH135XE60D 24-1/2 622 23-3/8 594 23 584 11-1/8 283 AIR FLOW 6-9/16 (167)Left9 (229)Right 23(584) (19)3/4(19)1 Bottom ReturnAir Opening GAS PIPING INLET(Either Side) Side ReturnAir Opening(Either Side) 1 Bottom ReturnAir Opening EXHAUST AIROUTLET ELECTRICALINLET(Either Side) SUPPLY AIROPENING FRONT VIEW SIDE VIEW TOP VIEW A B 9/16 (14) C3/4 27-3/4(705)19-7/16(494) 23-1/2(597) 1-1/2(38) 6-1/2 (165)(Either Side) 33(838) 3-1/4(83) 1-15/16 (49) 14(356) 9/16(14) 12-5/8 (321)(Either Side) 2 OPTIONALSIDE RETURNAIR FILTER KIT(Either Side) 16(406) 14-3/4(375) 2 OPTIONALSIDE RETURNAIR FILTER KIT(Either Side) 5/8(16) 1 3-1/4(83) 23-3/4(603) 25(635) D 1-1/2 (38)Front Panel COMBUSTIONAIR INTAKE 2 (51)(Either Side) 1-7/8 (48) CONDENSATETRAP CONNECTION(Either Side) 2 Optional Side Return Air Filter Kit is not for usewith the Optional Return Air Base. 1 NOTE - 60C and 60D size units that require second stageair volumes over 1800 cfm must have oneof the following:1.Single side return air with transition, to accommodate20 x 25 x 1 in. cleanable air filter.Required to maintain proper air velocity.2.Single side return air with Optional Return Air Base3.Bottom return air.4.Return air from both sides.5.Bottom and one side return air.See Blower Performance Tables for additional information. Flue Condensate Trap AssemblyFurnished for external field installationon either side of unit. (See installation instructions for additionalinformation.) 7 (178) EL296UHE / Page 15 DIMENSIONS - INCHES (MM) - HORIZONTAL POSITION D A TOP VIEW 27-3/4 (705)33(838) 27-3/4(705) 27-3/4(705) A GAS PIPING INLET(Top or Bottom) RETURNAIROPENING ELECTRICAL INLET(Top or Bottom) SUPPLYAIROPENING FRONT VIEW TOP VIEW CA END VIEWEND VIEW 33(838) 27-3/4(705) 19-7/16(494)9/16(14) B 23-1/2(591)3-1/4 (95) (19) 2 (51)Top or Bottom 6-1/2 (165)Bottom 3-1/4 (83) EXHAUST AIROUTLET LEFT-HAND AIR DISCHARGE FRONT VIEWEND VIEW END VIEW AIRFLOW ELECTRICAL INLET(Top or Bottom) RIGHT-HAND AIR DISCHARGE 9/16(14)3/4 AIRFLOW AIRFLOW 19-7/16(494)9/16(14)B 9/16(14) D A (83)3-1/4 SUPPLYAIROPENING RETURNAIROPENING C 23-1/2(591)3-1/4(95) (19)3/4 AIRFLOW COMBUSTIONAIR INTAKE EXHAUST AIROUTLET COMBUSTIONAIR INTAKE 1-7/8 (48) 1-7/8(48) 6-9/16 (167) Top9 (229) Bottom 12-5/8 (321)Bottom CONDENSATETRAP CONNECTION 6-9/16 (167) Bottom 9 (229) Top 12-5/8 (321)Bottom 2 (51)Top or Bottom 6-1/2 (165)Bottom (Bottom) GAS PIPING INLET(Top or Bottom) CONDENSATETRAP CONNECTION(Bottom) 1-1/2 (38)Front Panel 1-1/2 (38)Front Panel Model No.A B C D in.mm in.mm in.mm in.mm EL296UH045XE36B EL296UH070XE36B 17-1/2 446 16-3/8 416 16 406 7-5/8 194 EL296UH090XE48C EL296UH110XE60C 21 533 19-7/8 505 19-1/2 495 9-3/8 238 EL296UH135XE60D 24-1/2 622 23-3/8 594 23 584 11-1/8 283 EL296UHE / Page 16 OPTIONAL ACCESSORY DIMENSIONS - INCHES (MM) 1-1/4HORIZONTAL (END) FILTER KIT FRONT VIEW 24-3/4(629) A B 23-1/2(597) 5/8(16) RETURNAIROPENING SIDE VIEW AIR FLOW AIR FILTER(Furnished) (32) 5/8(16) 5/8(16) 5/8(16) Optional Return Air Base(Upflow Applications Only - For use with B, C and D cabinets) NOTE- Optional Side Return Air Filter Kits are not for use with Optional Return Air Base.1 Both the unit return air opening and the base return air opening must be covered by a single plenum or IAQ cabinet. Minimum unit side return air opening dimensions for units requiring 1800 cfm or more of air (W x H): 23 x 11 in. (584 x 279 mm).The opening can be cut as needed to accommodate plenum or IAQ cabinet while maintaining dimensions shown.Side return air openings must be cut in the field. There are cutting guides stenciled on the cabinet for the side return airopening. The size of the opening must not extend beyond the markings on the furnace cabinet.2 To minimize pressure drop, the largest opening height possible, up to 14 in. (356 mm), is preferred. FURNACEFRONT 1 Unit side return airOpening SIDE VIEW 3-1/4(83) 1 23 (584)Overall(Maximum) (584)23 3/4(19) 1 22-7/16(570)Overall(Maximum) SIDE RETURNAIR OPENINGS(Either Side) 5-5/8(143) 1 Minimum11 (279) 2 Maximum14 (356) (683)26-7/8 7-1/4(184) IF BASEIS USEDWITHOUTIAQ CABINET,A SINGLERETURN AIRPLENUMMUSTCOVER BOTHUNIT ANDRETURNAIR BASEOPENINGS INDOOR AIRQUALITYCABINET(PCO, FilterCabinet, etc.) AIR BASE OPTIONALRETURN CONDENSATETRAP 17-1/2 (446) B Width (50W98) 21 (533) C Width (50W99)24-1/2 (622) D Width (51W00) Furnace Cabinet Width Catalog Number A B in.mm in.mm B 87L96 18 457 16-3/4 425 C 87L97 21 533 18-3/4 476 D 87L98 25 635 23-3/4 603 EL296UHE / Page 17 DIMENSIONS - INCHES (MM) - FURNACE/COIL COMBINED DIMENSIONS UPFLOW POSITION Model No Cased Uncased (CX34 - cased only) A B A B CX34 C33 in.mm in.mm in.mm in.mm CX34-18/24B-6F CX34-18/24C-6F C33-24B C33-24C 16-1/2 419 49-1/2 1257 13-7/8 352 46-7/8 1191 CX34-25B-6F C33-25B 18-1/2 470 51-1/2 1308 15-7/8 403 48-7/8 1241 CX34-30B-6F CX34-30C-6F C33-30B C33-30C 20-1/2 521 53-1/2 1359 17-3/4 451 50-3/4 1289 CX34-31B-6F C33-31B 22-1/2 572 55-1/2 1410 20-1/4 514 53-1/4 1353 CX34-36B-6F C33-36B 24-1/2 622 57-1/2 1461 21-7/8 556 54-7/8 1394 CX34-36C-6F C33-36C 24-1/2 622 57-1/2 1461 21-1/4 540 54-1/4 1378 CX34-38B-6F C33-38B 24-1/2 622 57-1/2 1461 22 559 55 1397 CX34-42B-6F C33-42B 24-1/2 622 57-1/2 1461 21-7/8 556 54-7/8 1394 CX34-43B-6F C33-43B 27-1/2 699 60-1/2 1537 26-1/4 667 59-1/4 1505 CX34-43C-6F C33-43C 27-1/2 699 60-1/2 1537 25-3/4 654 58-3/4 1492 - - -C33-44C 24-1/2 622 57-1/2 1461 21-1/2 546 54-1/2 1384 CX34-44/48B-6F C33-48B 24-1/2 622 57-1/2 1461 22-1/8 562 55-1/8 1400 CX34-44/48C-6F C33-48C 24-1/2 622 57-1/2 1461 21-1/2 546 54-1/2 1384 CX34-49C-6F C33-49C 29-1/2 749 62-1/2 1588 28-1/2 724 61-1/2 1562 CX34-50/60C-6F C33-50/60C 27-1/2 699 60-1/2 1537 24-3/4 629 57-3/4 1467 CX43-60D-6F C33-60D 25-1/2 648 58-1/2 1486 24-3/4 629 57-3/4 1467 CX34-62C-6F C33-62C 31-1/2 800 64-1/2 1638 30-5/8 778 63-5/8 1616 CX34-62D-6F C33-62D 29-1/2 749 62-1/2 1588 28-3/4 730 61-3/4 1568 HORIZONTAL POSITION Model No.A B in.mm in.mm CH33-36B-2F CH33-36C-2F CH33-42B-2F CH33-48C-2F CH33-60D-2F 26-1/2 673 59-1/2 1511 CH33-44/48B-2F CH33-50/60C-2F CH33-62D 31-1/2 800 64-1/2 1638 33(838) A B 33(838) A B EL296UHE / Page 18 OPTIONAL ACCESSORY DIMENSIONS - INCHES (MM) FLUSH-MOUNT VENT TERMINATION KIT 51W11 (US) or 51W12 (CANADA) With 2 or 2-1/2 in. (51 or 64 mm) PVC pipe With 3 in. (76 mm) PVC pipe 3 (76) PVC pipe2 (51) PVC pipe 2-1/2 (64) PVC pipe When required UseField Provided2-1/2 to 2 in. (64 to 51 mm)Coupling Seal all openings(typical) 2-3/8 (60) 12 (305) minimum(recommended) Intake (Behind Plate) Exhaust Intake (Behind Plate) Exhaust NOTE - PVC pipe and fittings are not furnishedand must be field furnished. EL296UHE / Page 19 OPTIONAL ACCESSORY DIMENSIONS - INCHES (MM) CONCENTRIC WALLTERMINATION APPLICATIONS INTAKEAIREXHAUSTAIR INTAKEAIRINTAKEAIR EXHAUSTAIR OUTSIDEWALL 12 (305)MinimumAbove Gradeor Average SnowAccumulation 12 (305)MinimumAbove AverageSnowAccumulation SHEET METAL STRAP (Clamp and sheet metal strap must be field installed to support the weight of the termination kit.) FLASHING(Not Furnished) CLAMP GRADE 6-1/2(165) (Field Supplied)ELBOW INTAKE AIR EXHAUSTAIR TERMINATIONASSEMBLY(Furnished) 71M80 / 69M29 / 44W92 - 2 inch kits60L46 / 44W93 - 3 inch kitsSee Installation Instructions for additional information. CONCENTRIC ROOFTERMINATION APPLICATIONS CLAMP(Not Furnished) 6(152) A 3-1/2 (89) - 2 in. kits4-1/2 (114) - 3 in. kits Outdoor Exhaust Acceleratorincluded with 71M80/44W92 NOTE - Typical illustration for dimensions only. Design may vary depending on kit ordered. Cat. No.A B in.mm in.mm 71M8069M29 33-3/8 848 16-3/4 425 44W92(Canada)29 737 15-1/2 394 60L46 38-7/8 987 21-3/16 538 44W93(Canada)36-1/8 918 19-1/2 495 Note - Field provided reducer may be required to adapt larger vent pipe size to termination. B 12 in. (305 mm) - 2 in. (51 mm) dia. exhaust pipe 20 in. (508 mm) - 3 in. (76 mm) dia. exhaust pipe maximum length withoutsupport NON-DIRECT VENT APPLICATION NOTE - EXHAUST PIPE SHOWN Kit Contains Enough Parts For Two Installations 8 in. (203 mm)minimum 6 in. (152 mm)maximum DIRECT VENT APPLICATION WALL ASSEMBLY TERMINATION KIT - RING KIT 15F74 - 2 inch (51 mm)See Installation Instructions for additional information. NOTE - 12 in. (305 mm) minimum height above average snow accumulation(from bottom of vent pipe). 12 in. (305 mm) - 2 in. (51 mm) dia. exhaust pipe20 in. (508 mm) - 3 in. (76 mm) dia. exhaust pipe maximum length without support NOTE - 12 in. (305 mm) minimum height above average snow accumulation(from bottom of vent pipe). Note - Field provided reducer may be required to adapt larger vent pipe size to termination. EL296UHE / Page 20 OPTIONAL ACCESSORY DIMENSIONS - INCHES (MM) 12 (305) MinimumAbove Grade or AverageSnow Accumulation 1/2 (13)FOAM INSULATION(Field Furnished) 5(127) 5-1/2 (140) EXHAUSTAIR INTAKEAIR GRADE 12 (305) INTAKEAIR EXHAUSTAIR GRADE 8 (203) MIN. Between Ends of Exhaust and Intake Pipe 12 (305) MAX. for 2 (51) Dia. Exhaust20 (508) MAX. for 3 (76) Dia. ExhaustWALL SUPPORT 12 (305) MAX. for 2 (51) Dia. Exhaust20 (508) MAX. for 3 (76) Dia. Exhaust 12 (305) MinimumAbove Grade or Average Snow Accumulation WALL TERMINATION KITS (CLOSE-COUPLE)EXTENDED VENT FOR GRADE CLEARANCE2 inch (51 mm) 22G44 (US) 3 inch (76 mm) 44J40 (US)See Installation Instructions for additional information. 6 (152) Maximum If Intake and Exhaust Pipe is less than12 in. (305 mm) above snow accumulation or other obstructions, field fabricated piping must be installed. 8 (203) MIN. Note - Field provided reducer may be required to adapt larger vent pipe size to termination. 12 (305) MinimumAbove Grade or AverageSnow Accumulation 1/2 (13)FOAM INSULATION(Field Furnished) 5(127) 5-1/2 (140) EXHAUSTAIR INTAKEAIR GRADE 12 (305) INTAKEAIR EXHAUSTAIR GRADE WALL SUPPORT 12 (305) MinimumAbove Grade or Average Snow Accumulation WALL TERMINATION KITS (CLOSE-COUPLE)EXTENDED VENT FOR GRADE CLEARANCE2 inch (51 mm) 30G28 (WTK Canada)3 inch (76 mm) 81J20 (WTK Canada) See Installation Instructions for additional information. 6 (152) Maximum If Intake and Exhaust Pipe is less than12 in. (305 mm) above snow accumulation or other obstructions,field fabricated piping must be installed. 12 (305) MAX. for 2 (51) Dia. Exhaust20 (508) MAX. for 3 (76) Dia. Exhaust 12 (305) MAX. for 2 (51) Dia. Exhaust20 (508) MAX. for 3 (76) Dia. Exhaust Note - Field provided reducer may be required to adapt larger vent pipe size to termination. 6 (152) MIN. 6 (152) MIN. EL296UHE / Page 21 EL296UH045XE36B PERFORMANCE (Less Filter) External Static Pressure in. w.g. Air Volume / Watts at Various Blower Speeds High Medium-High Medium Medium-Low Low cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts 0.00 1345 340 1255 245 1150 185 895 105 845 95 0.10 1305 345 1225 250 1105 200 855 110 810 95 0.20 1290 360 1190 260 1080 205 825 120 780 105 0.30 1275 370 1150 270 1045 215 785 125 720 110 0.40 1220 385 1120 280 1015 220 735 135 690 120 0.50 1215 390 1090 290 980 230 705 140 635 125 0.60 1190 395 1060 300 950 240 650 150 600 135 0.70 N/A N/A 1015 300 900 250 620 155 555 140 0.80 N/A N/A 1000 310 870 260 580 160 520 145 EL296UH070XE36B PERFORMANCE (Less Filter) External Static Pressure in. w.g. Air Volume / Watts at Various Blower Speeds High Medium-High Medium Medium-Low Low cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts 0.00 1380 315 1305 250 1190 200 965 105 920 100 0.10 1360 325 1270 255 1180 205 915 115 865 100 0.20 1310 335 1250 265 1130 215 880 120 815 110 0.30 1275 340 1205 275 1100 225 835 125 775 115 0.40 1250 355 1175 280 1065 230 795 135 730 125 0.50 1215 370 1145 295 1045 240 745 145 670 130 0.60 1200 380 1100 310 995 245 705 150 640 140 0.70 1145 380 1070 310 960 255 670 160 585 145 0.80 N/A N/A 1035 320 925 265 610 165 550 155 EL296UH090XE48C PERFORMANCE (Less Filter) External Static Pressure in. w.g. Air Volume / Watts at Various Blower Speeds High Medium-High Medium Medium-Low Low cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts 0.00 1740 370 1505 250 1370 195 1285 160 1135 125 0.10 1695 390 1470 265 1325 205 1240 170 1090 135 0.20 1660 405 1435 280 1290 220 1195 185 1045 145 0.30 1615 415 1390 295 1240 235 1140 200 995 160 0.40 1590 425 1350 305 1200 245 1110 210 945 165 0.50 1560 440 1310 320 1155 260 1055 225 895 175 0.60 1525 455 1255 335 1105 270 1005 230 855 190 0.70 1475 470 1220 340 1065 285 960 245 805 200 0.80 N/A N/A 1170 355 1010 295 920 255 760 210 BLOWER DATA EL296UHE / Page 22 BLOWER DATA EL296UH110XE60C PERFORMANCE (Less Filter) External Static Pressure in. w.g. Air Volume / Watts at Different Blower Speeds Bottom Return Air, Side Return Air with Optional Return Air Base, Return Air from Both Sides or Return Air from Bottom and One Side. Single Side Return Air − Air volumes in bold require field fabricated transition to accommodate 20 x 25 x 1 in. air filter in order to maintain proper air velocity. High Med-High Medium Med-Low Low High Med-High Medium Med-Low Low cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts 0.00 2220 645 1940 435 1765 335 1635 280 1435 200 2185 655 1915 440 1745 340 1620 275 1430 195 0.10 2170 660 1920 460 1715 350 1595 290 1380 205 2160 660 1880 460 1705 345 1570 285 1380 205 0.20 2130 680 1865 475 1670 370 1560 305 1345 220 2115 680 1835 470 1670 365 1535 305 1325 220 0.30 2095 700 1835 490 1640 390 1525 325 1285 230 2060 705 1795 495 1630 380 1505 320 1285 230 0.40 2065 720 1785 510 1600 405 1465 335 1250 245 2050 720 1760 510 1570 400 1455 330 1235 245 0.50 2030 740 1755 525 1560 415 1425 355 1215 260 2000 740 1720 530 1535 415 1410 345 1195 260 0.60 1995 760 1705 550 1525 435 1380 370 1150 270 1955 760 1685 550 1505 435 1380 365 1145 275 0.70 1955 770 1660 560 1475 450 1350 375 1100 290 1935 775 1650 555 1455 450 1325 375 1100 285 0.80 1930 790 1635 575 1445 460 1300 395 1050 305 1890 790 1610 575 1425 460 1285 390 1055 295 EL296UH135XE60D PERFORMANCE (Less Filter) External Static Pressure in. w.g. Air Volume / Watts at Different Blower Speeds Bottom Return Air, Side Return Air with Optional Return Air Base, Return Air from Both Sides or Return Air from Bottom and One Side. Single Side Return Air − Air volumes in bold require field fabricated transition to accommodate 20 x 25 x 1 in. air filter in order to maintain proper air velocity. High Med-High Medium Med-Low Low High Med-High Medium Med-Low Low cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts 0.00 2405 940 2235 735 2070 545 1830 390 1620 280 2395 925 2235 710 2020 550 1800 380 1610 275 0.10 2365 960 2210 745 2020 565 1770 400 1585 295 2360 935 2175 735 2005 555 1760 395 1550 295 0.20 2330 975 2180 770 1950 580 1745 420 1535 315 2350 955 2160 760 1955 565 1725 415 1510 300 0.30 2295 1000 2120 785 1925 595 1690 435 1480 325 2290 990 2095 775 1890 590 1700 435 1420 325 0.40 2275 1015 2075 805 1885 615 1640 460 1445 340 2255 995 2060 795 1850 615 1635 445 1390 340 0.50 2225 1025 2035 815 1845 630 1605 475 1395 360 2230 1010 2040 815 1845 625 1590 470 1375 360 0.60 2185 1010 2020 835 1815 645 1565 485 1330 365 2170 1025 2000 820 1795 640 1580 485 1335 370 0.70 N/A N/A 1940 850 1735 665 1520 500 1310 385 N/A N/A 1935 845 1725 660 1520 500 1295 385 0.80 N/A N/A 1890 860 1715 680 1465 510 1285 400 N/A N/A 1880 855 1705 680 1470 510 1260 405 NOTE - Due to Lennox’ ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. Installation and service must be performed by a qualified installer and servicing agency. ©2014 Lennox Industries, Inc. Visit us at www.lennox.com For the latest technical information, www.lennoxdavenet.com Contact us at 1-800-4-LENNOX REVISIONS Sections Description of Change Accessory Dimensions Updated Concentric Termination Kit (was missing “B” dimension om drawing). Venting Added Duravent® PolyPro® venting information.