HomeMy WebLinkAboutA100.1.pdfUP DN 1 2 3 4 A B C D E F G H DEMO EXISTING CEILING, PREP TO RECEIVE CEILING PER SCHEDULE 5. 5. 5. 5. 5. 5. 5. 5. 5. 5. 5. 5. 5. 5. 5. DEMO DOOR, INFILL OPENING MATCH EXISTING EXTERIOR FINISH REMOVE CROWN MOULDING, SAVE FOR RE-INSTALLATION EXTENT OF PROJECT 13. 13. 13. 13. 13. 13. DEMO EXISTING FLOORING AND WALL BASE, PREP TO RECEIVE FLOORING PER SCHEDULE 14. 14. 14. 14. 14. 3 3 A403.3 E GENERAL DEMOLITION NOTES: LEGEND: DOOR, FRAME, AND HARDWARE TO BE REMOVED PARTITION TO BE REMOVED PARTITION AND BORROWED LIGHT WINDOWS TO BE REMOVED SHOWER OR MOP SINK TO BE REMOVED (PATCH FLOOR AS REQUIRED, REFER TO PLUMBING DEMOLITION PLANS) LAVATORIES AND SINKS TO BE REMOVED (PATCH FLOOR AS REQUIRED, REFER TO PLUMBING DEMOLITION PLANS) EXISTING TOILET TO BE REMOVED (PATCH FLOOR AS REQUIRED, REFER TO PLUMBING DEMOLITION PLANS) EQUIPMENT TO BE REMOVED/RELOCATED CASEWORK TO BE REMOVED LOCKERS TO BE REMOVED 1. DASHED LINES INDICATE ITEMS TO BE REMOVED. DEMOLITION OF WALLS INCLUDES ALL DOORS, WINDOWS AND OTHER ITEMS LOCATED WITHIN THE WALL TO BE REMOVED UNLESS NOTED OTHERWISE. RE: STRUCTURAL, MECHANICAL, PLUMBING AND ELECTRICAL FOR EXISTING UTILITIES 2. FADED LINES INDICATE ITEMS TO REMAIN. 3. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONSTRUCTION RELATED CONDITIONS PRIOR TO COMMENCEMENT OF DEMOLITION. 4. ALL EXISTING SERVICES AND UTILITIES SHALL BE MAINTAINED TO DEPARTMENTS OR AREAS THAT ARE IN OPERATION AND SERVED BY SUCH SERVICES. COORDINATE ALL DISRUPTIONS OR DISCONTINUATIONS OF UTILITIES AND SERVICES WITH OWNER. 5. ALL FURNISHINGS AND MOVABLE EQUIPMENT IN DEMOLITION/CONSTRUCTION AREA SHALL BE REMOVED/RELOCATED BY OWNER PRIOR TO START OF DEMOLITION. 6. PATCH CORRIDOR WALLS AND RAILINGS TO MATCH EXISTING ADJACENT CONSTRUCTION, PATCH ALL EXISTING WALLS, CEILINGS AND FLOOR TO REMAIN AFTER DEMOLITION IS COMPLETE. COORDINATE EXTENT OF SELECTIVE DEMOLITION WITH PROJECT SEQUENCING PLANS AND WITH OTHER TRADES. PATCH WALL BOXES AND OTHER WALL/CEILING OPENINGS WHEREVER FIXTURES/OUTLETS ARE BEING REMOVED AND WALLS ARE TO REMAIN. 7. PROVIDE METAL STUD AND GYPSUM BOARD DUST/PRIVACY ENCLOSURES FOR DEMOLITION WORK TO MAINTAIN SEPARATION OF CONSTRUCTION AND IN-USE SPACES. REFER TO SHEET G003 FOR ADDITIONAL INFORMATION. 8. REVIEW DEMOLITION AND PENETRATIONS THROUGH EXISTING STRUCTURE WITH AS-BUILT STRUCTURAL DRAWINGS WHERE POTENTIAL OF ENCOUNTERING LOADED/STRUCTURAL BEAMS/JOISTS/COLUMNS EXIST. 9. CORE-DRILL EXISTING FLOOR AND/OR ROOF AS REQUIRED FOR NEW PLUMBING OR ELECTRICAL SYSTEMS. SAWCUT FLOOR SLABS TO SLAB DEPTH ONLY, TO PREVENT DAMAGE TO UNDER SLAB UTILITIES. 10. CONTRACTOR TO COORDINATE I.C.R.A. (INFECTION CONTROL RISK ASSESSMENT) PLAN WITH OWNER PRIOR TO COMMENCEMENT OF EACH PHASE/SUB-PHASE. 11. DEMOLITION WORK SHALL NOT REDUCE INTEGRITY OF STRUCTURE TO REMAIN NOR OF FIRE- PROOFING/SEPARATION. MAINTAIN STRUCTURAL AND LIFE SAFETY INTEGRITY IN AREAS OF WORK AT ALL TIMES. 12. VERIFY ALL ELECTRICAL AND PLUMBING REQUIREMENTS PRIOR TO REMOVING ANY EQUIPMENT. 13. PROVIDE SIGNAGE FOR TEMPORARY CIRCULATION AND EGRESS PATHS DURING DEMOLITION. 14. REFER TO MECHANICAL, PLUMBING & ELECTRICAL DRAWINGS FOR OTHER DEMOLITION WORK AND WORK TO REMAIN IN PLACE, REQUIRED FOR EACH CONSTRUCTION SEQUENCE. 15. NOTIFY OWNER AND ARCHITECT IMMEDIATELY IF HAZARDOUS MATERIALS ARE ENCOUNTERED. ASBESTOS ABATEMENT (OR REMOVAL) TO BE PROVIDED BY OWNER UNDER SEPARATE CONTRACT. COORDINATE WITH GENERAL CONTRACTOR FOR TIMING OF DEMOLITION IN RELATION TO ABATEMENT TO WORK AT EACH CONSTRUCTION SEQUENCE AREA. 16. PATCH UNDER SLAB SYSTEMS AND FLOOR SLABS TO MATCH ADJACENT CONSTRUCTION AFTER THE UNDER FLOOR PLUMBING WORK IS COMPLETED AND INSPECTED. REFER TO PLUMBING DOCUMENTS. 17. NOTE THAT SOME SYSTEMS WILL REQUIRE WORK BEYOND CONSTRUCTION SEQUENCE ZONES IN ORDER TO SUPPORT SPACES WITHIN EACH CONSTRUCTION SEQUENCE. COORDINATE THIS WORK WITH GENERAL CONTRACTOR AND OWNER PRIOR TO STARTING WORK OUTSIDE OF CONSTRUCTION SEQUENCE AREA. COORDINATE DEMOLITION/ CONSTRUCTION WORK HOURS, CONSTRUCTION SEQUENCE AND CONSTRUCTION ACCESS WITH OWNER TO MINIMIZE DISRUPTION OF NORMAL DAILY FUNCTION OF OWNER OCCUPIED AREAS. 18. NOTIFY OWNER AND ARCHITECT IF UNDER SLAB TEMPORARY DEWATERING IS REQUIRED. 19. REVIEW DEMOLITION DOCUMENTS WITH OWNER TO VERIFY ANY ITEMS TO BE SALVAGED AND TURNED OVER TO THE OWNER. 20. NOISE DURING DEMOLITION TO BE KEPT TO A MINIMUM. COORDINATE WITH OWNER 72 HOURS PRIOR TO COMMENCEMENT OF PARTICULARLY NOISY WORK SUCH AS CORE-DRILLING. 21. CONTRACTOR TO PROVIDE M.O.P. (METHOD OF PROCEDURE) PRIOR TO COMMENCEMENT OF WORK IN ANY PHASE/SUB-PHASE WHICH AFFECTS HOSPITAL OPERATION. M.O.P.'S TO BE APPROVED BY OWNER AT LEAST 72 HOURS PRIOR TO START OF WORK. DEMOLITION KEY NOTES: 1. DEMO EXISTING DOOR AND HARDWARE, RE-USE EXISTING FRAME, PREP FOR NEW HARDWARE AND PAINT. 2. REMOVE EXISTING CUSTOM CASEWORK (UPPER CABINETS) AND SAVE FOR REINSTALLATION, RE: ELEVATIONS 3. PARTITIONS/ITEMS TO REMAIN 4. 5. EXISTING FIRE EXTINGUISHER CABINET TO REMAIN. REMOVE EXISTING CEILING AS REQUIRED FOR WORK AND REPLACE TO MATCH EXISTING ADJACENT CEILING UPON COMPLETION OF WORK. 22. CONTRACTOR TO COORDINATE EXISTING EQUIPMENT TO BE RELOCATED WITH OWNER. DEMO ALL EXISTING CUSTOM CASEWORK IN THIS ROOM. EXISTING CEILING TO REMAIN 6. DEMO EXIST. INTERIOR GLASS INFILL PANEL BETWEEN WINDOW AND END OF WALL. 7. REMOVE WINDOW ASSEMBLY AND SAVE/PREP FOR RE-INSTALLATION. PROVIDE NEW THROUGH WALL FLASHING, DRIP EDGE, SEALANTS, ETC. FOR A COMPLETE INSTALLATION. 8. DEMO EXISTING SIDING DOOR, INFILL OPENING TO MATCH EXISTING ADJACENT WALL ASSEMBLY. PROVIDE FRAMING, INSULATION, GUPSUM WALL BOARD, AND FINISH FLUSH WITH EXISTING INTERIOR WALL. PREP OPENING FOR RE-INSTALLATION OF SAVED WINDOW. MATCH EXISTING EXTERIOR FINISH. 9. REMOVE WINDOW AND RETURN TO OWNER. 10. DEMO EXISTING COUNTERTOP AND BASE CABINET ONLY AT THIS LOCATION. 12. REMOVE EXISTING CROWN MOULDING, SAVE AND MODIFY/PREP FOR RE-INSTALLATION. 11. REMOVE EXISTING RECESSED VIEW BOX, SAVE FOR RE-INSTALLATION, COORDINATE WITH OWNER. 13. REMOVE EXTERIOR GLASS PANEL, PREP FRAME FOR SPANDREL GLASS. DEMO INTERIOR WINDOW SILL IF APPLICABLE. 23. REFER TO SHEET G003 FOR SEQUENCING OF WORK, INCLUDING DEMOLITION. 14. EXISTING WINDOW COVERINGS: REMOVE AND SAVE FOR RE-INSTALLATION 15. REPLACE BASEBOARD HEATER COVER; COLOR TBD BY ARCHITECT. 000 4' 8' 16' SCALE: 000 2' 4' 8' SCALE: N This document is the property of Heery International, Inc. and Heery International Inc. retains all rights therein, including copyrights. It may only be used in a manner consistent with Heery International Inc.'s rights while Heery International, Inc. is providing services for the specific project identified or referred to herein or extensions thereto. It may not be used for any other purpose except with the express written agreement of, and compensation to, Heery International Inc. Copyright © 2013 by Heery International, Inc. all rights reserved. WHEN PLOTTED AT FULL SIZE THIS SHEET MEASURES 30"x42" drawn by checked by sheet number sheet title item date date issued for seal/signature consultants/construction managers owner's project number project number 1/4" = 1'-0" 1/8" = 1'-0" 3/13/2015 6:36:28 PM A100.1 Checker Author ARCHITECTURAL DEMOLITION PLAN- LEVEL 1 DECEMBER 15, 2014 CONSTRUCTION DOCUMENTS VVMC MEDICAL PROFESSIONAL BUILDING COMMERCIAL TENANT IMPROVEMENT, INTERIOR REMODEL 108 SOUTH FRONTAGE ROAD VAIL, CO 81657 13026.07 CATOR RUMA & ASSOCIATES, CO 896 TABOR STREET LAKEWOOD, CO 80401-4700 303.232.6200 MARTIN/MARTIN, INC. 225 MAIN ST., SUITE C 101, EDWARDS, COLORADO 81632 970.926.6007 1/4" = 1'-0" 1 DEMOLITION PLAN - LEVEL ONE 2 Addendum 2 1/20/15 3 Addendum 4 3/13/15 2 2 2 2 2 2 3 04/15/15