HomeMy WebLinkAboutMPB TI Comcheck - Lighting and Power.pdfProject Title: Medical Professions Building Report date: 12/15/14
Data filename: P:\VVMC\2014-369 MPB TF\MPB TI Comcheck.cck Page 1 of 2
COMcheck Software Version 3.9.4
Interior Lighting and Power
Compliance Certificate
2012 IECC
Section 1: Project Information
Project Type: New Construction
Project Title : Medical Professions Building
Construction Site:Owner/Agent:Designer/Contractor:
108 S Frontage Road
Vail, CO 81657
VVMC Neal Wondel
Cator, Ruma & Associates
896 Tabor St.
Lakewood, CO 80401
303-232-6200
nwondel@catorruma.com
Additional Efficiency Package: Reduced interior lighting power. Requirements are implicitly enforced within interior lighting
allowance calculations.
Section 2: Interior Lighting and Power Calculation
A B
Floor Area
C
Allowed
Watts / ft2
D
Allowed Watts
Tenant Spaces (Health care clinic)9731 0.87 8466
Total Allowed Watts =8466
Section 3: Interior Lighting Fixture Schedule
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
D
Fixture
Watt.
E
(C X D)
Tenant Spaces ( Health care clinic 9731 sq.ft.)
T1,T1E: T1,T1E: 2x4 Troffer: Other:1 97 54 5238
T2,T2E: T2,T2E: 2x2 Troffer: Other:1 41 42 1722
P1: P1: Pendant: Other:1 3 35 105
D1,D1D,D2: D1,D1D,D2: Downlight: Other:1 18 21 378
W1: W1: Sconce: Other:1 2 20 40
W2: W2: Vanity Light: Other:1 3 19 57
ExPen: Ex Pendant: Existing Linear Pendant: 48" T8 32W (Super T8): Electronic:2 5 64 320
S1: S1: Striplight: 48" T8 32W (Super T8): Electronic:2 2 64 128
Total Proposed Watts =7988
Interior Lighting PASSES: Design 6% better than code.
Section 4: Compliance Statement
Compliance Statement: The proposed lighting design represented in this document is consistent with the building plans, specifications
and other calculations submitted with this permit application. The proposed lighting system has been designed to meet the 2012 IECC
requirements in COMcheck Version 3.9.4 and to comply with the mandatory requirements in the Requirements Checklist.
Neal Wondel, P.E.
Name - Title Signature Date
Section 5: Post Construction Compliance Statement
12/15/14