Loading...
HomeMy WebLinkAboutCrespelle_Response_TownOfVail.pdf Response to comments: project: Crespelle Pop Up at Gorsuch regarding: 263 E Gore Creek Food Service Plan Review date: 01.09.14 Comments by Town of Vail Plans Examiner J Mondragon received via project dox 01.07.12 J Mondragon Comments & Responses Building Sheet A100 Architect to submit separated use calculations to determine verify building construction type Response SBD: See revised Code Analysis sheet A000 classifying building as Type V B non-separated per 508.3.2, A-2 governing Sheet A101 Provide details for all fire walls/ceilings UL listed assemblies Response SBD: Non-separated per 508.3.2 FS000 Architect of Record to review and stamp these drawings as part of submittal record Response SBD: See Attached FS sheet M100 Address requirement of Type II hood 2012 IMC 507.2 and listing griddles as commercial cooking appliances Response Rader Engineering: See revised sheet M100 for addition of exhaust Note: electrical service size and location revised