GENERAL NOTES:
1. OFFSET PIPING AS REQUIRED TO AVOID ALL LIGHTS AND STRUCTURE.
COORDINATE ALL STRUCTURAL PENETRATIONS WITH THE STRUCTURAL
ENGINEER.
2. ALL PIPING PASSING THROUGH FIRE-RATED ASSEMBLIES SHALL INCLUDE
A FIRE-RATED PIPE SEALANT RATED TO MATCH THAT OF THE ASSEMBLY.
3. INSTALL CLEAN OUTS PER CODE (2012 IPC SECTION 708).
4. ALL ROUND DUCT CONNECTIONS TO ROUND DUCTWORK SHALL BE
CONICAL TEES.
5. THESE RESTROOMS ARE UNHEATED SPACE AND WHENEVER THE
287'2257(03(5$785('5236%(/2:)7+(&2/'ߙ+27:$7(5
PIPING MUST BE DRAINED, D.F.U SUCH AS WATER CLOSETS MUST BE
WINTERIZED BY POURING PROPYLENE GLYCOL OR ANY SIMILAR
ANTI-FREEZE SOLUTION INTO THE BOWLS AND FLOOR DRAINS.
WOMENS RESTROOM
COVERED PICNIC AREA
MENS RESTROOM
JANITOR
COVERED ENTRY
E
F
D
C
B
A
1 2 3 4
LV 1
LV 1
WC 2
WC 2
WC 2
WC 2
LV 1 LV 1
WC 2
WC 2
UR 3
UR 3
MS 4
FD 5
FD 5
CONNECT 1
2" CW, 1
2" HW, 1 1
2" W & 1 1
2" V TO LV.
CONNECT 1" CW, 3" W TO WC.
CONNECT 1" CW, 2" W & 1 1
2" V TO UR.
CONNECT 3
4" CW, 3
4" HW, 2" W & 1 1
2" V TO MS.
CONNECT 2" W TO FD.
CONNECT 1
2" CW, 11
4" W & 1 1
2" V TO DF.
21
2" CIRCUIT VENT SERVING ALL WC AND FD FIXTURES. HORIZONTAL
%5$1&+'5$,1$&76$6:(79(17$1'0867%()25$//
BATHROOM FIXTURES.
3" STORM DRAINAGE LINE TO RUN UNDER SLAB. SEE CIVIL PLANS FOR
CONTINUATION.
WATER ENTRY. REFERENCE DETAIL ON SHEET MP1.1.
ROUTE STORM DRAINAGE LINE HORIZONTALLY THROUGH ROOF AND
DOWN THE EXTERIOR SIDE OF THE BUILDING VIA DOWNSPOUT.
CONFIRM LOCATION WITH ARCHITECT.
CONNECT TO EXISTING SEWER LINE. VERIFY LOCATION IN FIELD.
PROVIDE CLEAN OUT TO GRADE.
CONNECT 3
4" CW TO FPHB.
CONNECT 3
4" CW TO HB.
EXPOSED DUCTWORK IN THIS AREA. PAINT AS PER ARCHITECT OR
OWNER.
MIN. FREE AREA FOR THE LOUVER DOOR OPENING SHALL BE 216
SQUARE INCHES OR LARGER.
WH-1 SHOWN OFFSET FOR CLARITY. SUSPEND FROM CEILING.
CONNECT 3
4" HW AND 3
4" CW TO WH-1. ROUTE PRESSURE RELIEF
VALVE TO MOP SINK .
ROUTE WATER LINE TO WATER ENTRY. SEE WATER ENTRY DETAIL ON
MP1.1.
WATER METER IS LOCATED IN VAULT. SEE CIVIL PLANS FOR LOCATION.
PIPES WILL BE WINTERIZED VIA COMPRESSOR CONNECTION VALVE IN
VAULT.
CONNECT 3" SD TO RD.
IRRIGATION LINE TO RUN UNDER SLAB.
INSTALLED BY OWNER. REFERENCE ELECTRICAL DRAWINGS.
PROVIDE REMOTE THERMOSTAT, RAYWALL MODEL ET5DS FOR EH-1.
PROVIDE TAMPER PROOF LOCK BOX FOR THERMOSTAT, RAYWALL
MODEL TG3.
SHEET DETAIL NOTES:
1
2
3
4
5
6
7
8
9
10
11
DF 6
4" CIRCUIT VENT
8
8
1 1
4" CW
11
2" CW
2" CW
2" CW
1
2" CW
1
2" CW
2" CW
2" CW
3
4" HW
3
4" HW
3
4" HW
21
2" V & 4" W
BELOW
21
2" V & 4" W BELOW
21
2" V & 4" W BELOW
11
4" W 4" W
11
2" W
4" W
11
2" V
11
2" V
11
2" V
4" V.U.T.R.
7
7
WH
1
9
11
12
FPHB 12
13
HB 13
3
4" CW
2" CW
14
L
1
EF
1-A
EF
1-B
15
LOUVERED
DOOR
LOUVERED
DOOR
16
15
15
17
16
WATER ENTRY
18
17
19
18
EXISTING 2" PIPE TO
WATER METER IN VAULT
14 14
19
19
19
10
10
10
IRRIGATION LINE.
REF. WATER ENTRY DETAIL ON SHEET MP1.1
8
8
8
8
8
20
20
IRRIGATION DESIGN.
SEE CIVIL PLANS FOR CONTINUATION.
2" COPPER IRRIGATION
LINE UNDER SLAB.
SLOPE TO DRAIN.
EH
1
EH
1
EH
2
21
21
21
21
T T
22
22
22
TO EH-1
TO EH-1
2
2
2
2
2
2
3
3
225 MAIN STREET, UNIT C 101, EDWARDS, COLORADO 81632
MAIN 970.926.6007 MARTINMARTIN.COM
FORD PARK IMPROVEMENTS
LOWER BENCH
C
Mechanical, Electrical & Lighting Design Services
Architectural Engineering
Consultants
Telephone: 970-748-8520 Fax: 970-748-8521
EG
$Q2IILFHZLWK/(('$FFUHGLWHG3URIHVVLRQDOV
NORTH
PLAYGROUND RESTROOM PLUMBING PLAN
SCALE: 1/4" = 1'0"
/2
PLUMBING & MECHANICAL
PLAN
PLAYGROUND RESTROOM MECHANICAL PLAN
SCALE: 1/4" = 1'0"
04/10/15