225A3P
EXISTING 3000 AMP SWITCHBOARD
"DP-DA2"
208/120V., 3ɐ, 4 WIRE.
42,000 AIC
"PP-P5A"
SEC. 1
LOCATED IN 5TH FLOOR ELEC.
ROOM
(FED FROM "DP-DA2" CCT #8)
"PP-P5A"
SEC. 2
NOTES TO ELECTRICAL CONTRACTOR - PANEL:
1. INFORMATION SHOWN IN BOLD PRINT INDICATES NEW LOADS ON EXISTING UNLESS
OTHERWISE NOTED. ALL OTHER LOADS ARE EXISTING.
2. UPDATE PANEL INDEXES PRIOR TO CONCLUSION OF CONSTRUCTION PER NEC 408.4.
INDICATE LOAD INFORMATION AND ACCURATE LOCATION WITHIN TENANT SUITE.
3. VERIFY BREAKERS FOR ALL MECHANICAL REQUIREMENTS WITH MANUFACTURER'S
U.L. NAMEPLATE RATING AND CUTSHEETS PRIOR TO ROUGH-IN. CONTACT
ELECTRICAL AND MECHANICAL ENGINEERS IF ANY DISCREPANCIES OR CHANGES TO
THE SPECIFIED UNITS OCCUR.
1. BASE BUILDING SPECIFICATIONS, DRAWINGS, AND LATEST REVISION OF CONTRACT DOCUMENTS FOR
ELECTRICAL WORK SHALL APPLY TO ELECTRICAL DRAWINGS.
2. ALL WORK SHALL BE DONE IN COMPLIANCE WITH THE TENANT FINISH SPECIFICATIONS, DRAWINGS, AND
LATEST REVISIONS OF ALL NATIONAL CODES SUCH AS THE N.E.C., N.F.P.A., AND ALL APPLICABLE LOCAL
CODES AND ORDINANCES.
3. ELECTRICAL CONTRACTOR SHALL VISIT SITE AND EXAMINE DRAWINGS OF OTHER TRADES ON THIS
PROJECT, PARTICULARLY DEMOLITION, ARCHITECTURAL AND MECHANICAL, TO DETERMINE ANY
ADDITIONAL WORK THAT MAY BE REQUIRED FOR A COMPLETE AND OPERATIONAL ELECTRICAL
INSTALLATION.
4. ELECTRICAL ITEMS AFFECTED BY REMODEL WORK ARE SHOWN ON DRAWINGS. EXISTING ELECTRICAL
SHOWN IS NOT NECESSARILY INCLUSIVE. PROVIDE CONTINUITY IN ALL CIRCUITS FOR ELECTRICAL
FIXTURES, DEVICES, AND EQUIPMENT THAT IS TO REMAIN. SUCH EQUIPMENT SHALL BE RECONNECTED TO
EXISTING CIRCUITS.
5. ELECTRICAL CONTRACTOR SHALL ENSURE CIRCUIT CONTINUITY FOR ALL CIRCUITS WHICH ARE OR MAY BE
AFFECTED BY THIS REMODEL AS WELL AS TO PREVENT ANY SINGLE CIRCUIT OVER-LOADING. REMOVE ALL
EXISTING BRANCH CIRCUIT CONDUCTORS OF CIRCUITS REUSED ELSEWHERE.
6. CONTRACTOR SHALL PROVIDE NEW CONDUIT AND WIRE TO REROUTE AND RECONNECT FEEDERS THAT ARE
DAMAGED, DISTURBED OR AFFECTED BY THE DEMOLITION AND REMODEL WORK.
7. CONTRACTOR SHALL BE HELD RESPONSIBLE FOR VERIFICATION OF EXISTING JOB CONDITIONS PRIOR TO
BID. DISCREPANCIES BETWEEN ACTUAL FIELD CONDITIONS AND CONTRACT DOCUMENTS SHALL BE
BROUGHT TO THE ENGINEER'S ATTENTION FOR ALTERNATIVE METHODS OF INSTALLATION THREE (3) DAYS
MINIMUM PRIOR TO BIDDING THIS JOB TO ALLOW FOR ISSUANCE OF CLARIFICATIONS.
8. CONTRACTOR TO REMOVE ALL FIXTURES, SWITCHES, TELEPHONE AND ELECTRICAL OUTLETS SCHEDULED
FOR DEMOLITION. ALL UNUSED POWER WIRING SHALL BE REMOVED BACK TO APPROPRIATE ELECTRICAL
PANEL. ALL PHONE / DATA CABLING TO REMAIN - FOR REMOVAL PER TENANT COMMUNICATION VENDOR.
9. PROVIDE TYPEWRITTEN UPDATED PANEL DOOR DIRECTORIES FOR ALL AFFECTED PANELS REFLECTING ALL
CIRCUITS WITH THEIR ACCURATE DESTINATIONS PER N.E.C. 408.4. CLEARLY MARK J-BOXES IN CEILING
SPACE WITH REVISED CIRCUIT NUMBERS. THIS APPLIES TO BOTH SIDES OF THE TENANT DEMISING WALLS.
FLIP ALL UNUSED AND SPARE BREAKERS TO THE "OFF" POSITION AND INDICATE "SPARE" IN PANEL INDEX.
10. PREPARE AND MAINTAIN AT JOB SITE ACCURATE UPDATED "AS-BUILT" DRAWINGS OF ALL MODIFIED WORK
IN THIS CONTRACT. AT CONCLUSION OF WORK, SUBMIT ORIGINAL OR ADEQUATE LEGIBLE REPRODUCIBLE
COPY TO ARCHITECT / ENGINEER FOR PREPARATION OF RECORD DOCUMENTS.
11. ALL ELECTRICAL DEVICES, CIRCUITING, ETC. SHOWN DIAGRAMMATICALLY. ELECTRICAL CONTRACTOR
SHALL BE RESPONSIBLE FOR ACTUAL LOCATION AND WIRING AVOIDING MECHANICAL AND OTHER
EQUIPMENT.
12. ALL NEW AND RELOCATED MATERIALS INSTALLED IN CEILING PLENUM SHALL BE U.L. LISTING, CLASS 1
RATED.
13. SEE LEGEND, LIGHTING AND POWER NOTES, MECHANICAL, AND ARCHITECTURAL DRAWINGS FOR
SUPPLEMENTAL INFORMATION ON LOCATIONS, MOUNTING HEIGHTS, ETC. DIMENSIONS ON
ARCHITECTURAL DRAWINGS TAKE PRECEDENCE OVER THE ELECTRICAL DRAWINGS.
14. PROVIDE TELEPHONE OUTLETS WITH COVERPLATES AND 3
4 " CONDUIT TO ABOVE ACCESSIBLE CEILING
WITH BUSHING AND PULLWIRE. COORDINATE FURNITURE SYSTEM CONDUIT WITH MANUFACTURER /
SUPPLIER ON ALL DATA / TELEPHONE RACEWAYS. CABLING BY TENANT.
15. COORDINATE ALL POWER SHUT-DOWNS WITH BUILDING MANAGEMENT / LANDLORD.
16. CLEAN AND REPAIR ALL EXISTING LIGHTING FIXTURES, RECEPTACLES, AND ELECTRICAL DEVICES AS
NEEDED.
17. REUSE EXISTING EXIT LIGHTS. VERIFY EXISTING FIXTURE COUNT WITH ARCHITECT. PROVIDE UNIT PRICING
FOR ADDITIONAL FIXTURES AS NEEDED - BUILDING STANDARD.
18. RESUPPORT ALL NEW AND EXISTING CONDUITS, LIGHTING FIXTURES, AND CABLING PER INTERNATIONAL
BUILDING CODE (IBC 2009). REMOVE ALL UNUSED SUPPORTS AS REQUIRED.
19. ELECTRICAL CONTRACTOR TO CIRCUIT TRACE ALL POWER CIRCUITRY PRIOR TO INSTALLATION.
CONTRACTOR TO PROVIDE ELECTRICAL ENGINEER WITH AS-BUILT DRAWINGS.
20. DO NOT SCALE DRAWINGS. ELECTRICAL CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS, DISTANCES,
AND EXISTING CONDITIONS PRIOR TO PRICING AND INSTALLATIONS.
21. ELECTRICAL CONTRACTOR SHALL SUBMIT CUT-SHEETS AND SHOP DRAWINGS ON ALL ELECTRICAL AND
MECHANICAL EQUIPMENT FOR APPROVALS. SUBMIT TO GENERAL CONTRACTOR, OWNER, TENANT,
ARCHITECT, AND ENGINEERS.
22. E.C. SHALL LABEL ALL RECEPTACLE COVER PLATES WITH PANEL AND CIRCUITRY DESIGNATIONS.
DESIGN BUILD FIRE ALARM NOTE:
FIRE ALARM SHALL BE UNDER DESIGN BUILD CONTRACT. FIRE ALARM CONTRACTOR SHALL BE BUILDING
MANAGEMENT APPROVED AND WILL SUBMIT FIRE ALARM DESIGN TO THE FIRE MARSHAL OF THE LOCAL FIRE
DEPARTMENT HAVING JURISDICTION FOR APPROVAL.
ELECTRICAL GENERAL NOTES:
CONTRACTOR IS TO FIELD VERIFY ALL DIMENSIONS. WRITTEN
DIMENSIONS HAVE PRECEDENCE OVER SCALED DIMENSIONS. THE
CONTRACTOR SHALL VERIFY AND BE RESPONSIBLE FOR ALL
DIMENSIONS AND CONDITIONS ON THE JOB AND ARCHITECT MUST BE
NOTIFIED OF ANY VARIATIONS FROM THE DIMENSIONS AND CONDITIONS
SHOWN ON THESE DRAWINGS. ALL CEILING LOCATED ITEMS MUST BE
COORDINATED WITH ARCHITECT. LOCATIONS OF LIGHTING EQUIPMENT
TAKE PRECEDENCE. ELECTRICAL CONTRACTOR MUST ADHERE TO ALL
NATIONAL AND LOCAL ELECTRICAL CODES. IT IS THE RESPONSIBILITY
OF THE ELECTRICAL CONTRACTOR TO NOTIFY ARCHITECT IF ANY LOCAL
CODE CONFLICT EXISTS. ANY REVISIONS TO THIS PLAN CAUSED BY
MECHANICAL OR STRUCTURAL CONFLICTS MUST BE APPROVED IN
WRITING. FIXTURE SUBSTITUTIONS ARE NOT ALLOWED UNLESS
APPROVED IN WRITING BY ARCHITECT.
1. ALL SYMBOLS MAY NOT BE USED.
2. ALL LAMPS THAT TIE INTO THE SPECIAL DIMMED RECEPTACLES
WILL REQUIRE PLUG #RP-FDU-10(WHITE OR BROWN). THIS WORKS
IN CONJUNCTION WITH THE SPECIFIED RECEPTACLE LISTED ABOVE.
PLEASE CONTACT TAMMY WINGATE AT LUTRON, 610.282.6539,
FOR PURCHASING INFORMATION.
3. FLOOR RECEPTACLES MUST BE INSTALLED IN CARLON FLOOR BOX
#E976RFB WITH AN ACTIVATION KIT #E97AK2. INCLUDE COVER
FINISH/COLOR. ALL LAMPS THAT TIE INTO THE SPECIAL DIMMED
RECEPTACLES WILL REQUIRE PLUG #RP-FDU-10. THIS WORKS IN
CONJUNCTION WITH THE SPECIFIED RECEPTACLE LISTED ABOVE.
THIS COMBINATION IS REQUIRED TO MEET THE NATIONAL ELECTRIC
CODE (NEC). CONTACT TAMMY WINGATE AT LUTRON,
610.282.6539, FOR PURCHASING INFORMATION.
GENERAL NOTES - POWER:
NOTES TO CONTRACTOR:
ISSUE DATE
JMM
CHK BY:
SCALE:
SHEET:
JOB #:
DRW BY:
TITLE:
DATE:
COMMENT
AS NOTED
TNS
SEAL & SIGNATURE:
14-37
1
FOUR SEASONS
RESORT & RESIDENCES
VAIL, CO
FIFTH FLOOR
REMODEL
FOR PERMIT
2/16/15
CLIENT:
Four Seasons Resort & Residences
One Vail Road
VAIL, CO 81657
ARCHITECT:
Creative Design Associates
434 BROADWAY, 5TH FLOOR
NEW YORK, NY 10013
t 212-748-8900
WESTERN US
4700 E BROMLEY LN, SUITE 105
BRIGHTON, CO 80601
t 646-747-2171
c 917-756-0057
dsorenson@ralcompanies.com
INTERIOR DESIGN:
Meyer Davis Studio
180 VARICK STREET #404
NEW YORK, NY 10014
t 212-627-5574
graydavis@meyerdavis.com
ELECTRICAL ENGINEER:
C3S Incorporated
3212 WEST 45TH AVENUE
DENVER, CO 80211
t 303-480-5144
theresa@c3sengineeringinc.com
MECHANICAL ENGINEER:
MDP Engineering Group
1800 Glenarm Place, Suite 800
DENVER, CO 80202
t 303-389-0095
rloomer@mdpeg.com
LIGHTING DESIGN:
Bouyea & Associates
5 Green Hill Road
2nd & 3rd Floors
Washington Depot, CT 06794
t 860-868-4500
bbouyea@bouyea.com
FOODSERVICE CONSULTANT:
Ricca Design Studios
2 Northside Piers, Suite 8C
Brooklyn, NY 11249
t 303-221-0500
dchislett@ricca.com
2/16/215
NOTES, PANEL
SCHEDULES, & ONE
LINE DIAGRAM
E-101
5TH FLOOR LOBBY AREA KEY PLAN
1 C3S
Incorporated
EXISTING PARTIAL ONE LINE DIAGRAM
3
ALL DASHED LINES INDICATE EXISTING TO REMAIN U.O.N.
ALL SOLID LINES INDICATE NEW EQUIPMENT
ALL HIDDEN LINES INDICATE FUTURE EQUIPMENT.
ALL SHADED AREAS INDICATE EXISTING TO BE REMOVED.
1
E-201
1
E-301
1
E-501
1
E-401
5TH FLOOR LOBBY AREA DRAWING KEY PLAN
2 C3S
Incorporated
03/17/15