Optional Residential Load Calculation Results:
Multifamily Dwelling:
Dwelling Units:
Demand Factor: 100%
Step 1: General Lighting and Recepticles:
Total General Load @ 3VA: 8760 VA
Step 1 Total: 8760 VA
Step 2: AC System:
220.82(C)1 Total: 0
220.82(C)2 Total: 0
220.82(C)3 Total: 0
220.82(C)4 Total: 0
220.82(C)5 Total: 1600
220.82(C)6 Total: 0
Largest Load Per 220.82(C)
Step 2 Total: 1600 VA
Step 3: Fixed in Place Appliances:
Step 3 Total: 3200VA
Step 4: Dryers:
Step 4 Total: 3500 kW
Step 5: Cooking Appliances:
Step 5 Total: 7000 kW
General Load:
First 10k @ 100%: 10000
Remainder over 10k @ 40%: 4984
Total General Load: 14984
Final Totals:
Feeder Load: 16584 VA
Feeder Amperage: 69.1 Amps
Neutral Load: 19310 VA
Neutral Amperage: 80.458333333333 Amps
Service Size:
z
100 Amps
Conductor Size:
Feeders per Table 310.15(B)7:
Copper: 4 AWG
Aluminum: 2 AWG
Neutral per Table 310.15(B)7:
Copper: 4 AWG
Aluminum: 2 AWG
Ground per Table 250.66:
Copper: 8 AWG
Aluminum: 6 AWG