Loading...
HomeMy WebLinkAboutmountainbridge electrical load calcs.pdf Tim Barany From: Nick Lunn <nicklunncec@yahoo.com> Sent: Friday, March 27, 2015 2:07 PM To: Tim Barany Subject: Load caic for manor vail 209 Optional Residential Load Calculation Results: Multifamily Dwelling: Dwelling Units: Demand Factor: 100% Step 1: General Lighting and Recepticles: Total General Load @ 3VA: 8760 VA Step 1 Total: 8760 VA Step 2: AC System: 220.82(C)1 Total: 0 220.82(C)2 Total: 0 220.82(C)3 Total: 0 220.82(C)4 Total: 0 220.82(C)5 Total: 1600 220.82(C)6 Total: 0 Largest Load Per 220.82(C) Step 2 Total: 1600 VA Step 3: Fixed in Place Appliances: Step 3 Total: 3200VA Step 4: Dryers: Step 4 Total: 3500 kW Step 5: Cooking Appliances: Step 5 Total: 7000 kW General Load: First 10k @ 100%: 10000 Remainder over 10k @ 40%: 4984 Total General Load: 14984 Final Totals: Feeder Load: 16584 VA Feeder Amperage: 69.1 Amps Neutral Load: 19310 VA Neutral Amperage: 80.458333333333 Amps Service Size: z 100 Amps Conductor Size: Feeders per Table 310.15(B)7: Copper: 4 AWG Aluminum: 2 AWG Neutral per Table 310.15(B)7: Copper: 4 AWG Aluminum: 2 AWG Ground per Table 250.66: Copper: 8 AWG Aluminum: 6 AWG It is highly recommended to double check the calculations before submitting them on any professional level. This calculation was generated with the ReiWare, LLC Service Load Calculation Tool Available on the Apple App Store, Google Play and Amazon App Store. Sent from my iPhone 2