HomeMy WebLinkAboutElectrical Load Calculations.pdff
Load Calc For*23&9Simba Run Per 220.83 NEC Existing Dwelling Unit 1080 Sq.Ft,
\l Lighting 1070X3 3210
Small appliance and laundry 3X1500 4500
Appliances with new microwave 3000
Range 8500
Dryer 5000
Total 24210
First 8kva 100% 8000
Remainder at 40% 6484
Electric Heat 6000
Total Load 20484/208 = 98.48 amps
Existing Service 125 amps
Tenmats will be installed above can lights