HomeMy WebLinkAboutB15-0095 Electrical Calcs.pdfr
Load Calc For XMcSimba Run Per 220.83 NEC Existing Dwelling Unit 1080 Sq.Ft
*NV
General Lighting 1070X3" 3210
Small appliance and laundry 3X1500 4500
Appliances with new microwave 3000
Range 8500
Dryer 5000
Total 24210
First 8kva 100% 8000
Remainder at 40% 6484
Electric Heat 6000
Total Load 20484/208 = 98.48 amps
Existing Service 125 amps
Tenmats will be installed above can lights