Loading...
HomeMy WebLinkAboutcut sheets.pdfPlease read thoroughly before installing and servicing 7215 0200 – 10/2007 US/CA (en) For registered installers Installation instructions Condensing gas boiler Logamax plus GB142-24/30/45/60 CAUTION! Before putting the boiler into operation read this manual carefully. WARNING! Improper installation, adjustment, alteration, service or maintenance can cause injury, loss of life or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency or the gas supplier. CAUTION! The operating manual is part of the documentation that is delivered to the installation's operator. Go through the information in this manual with the owner/operator and make sure that he or she is familiar with all the necessary operating instructions. NOTICE! In the Commonwealth of Massachusetts this boiler must be installed by a licensed Plumber or Gas Fitter. –Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other boiler. – What to do if you smell gas •Do not try to light any boiler. •Do not touch any electrical switch; do not use any phone in your building. •Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions. •If you cannot reach your gas supplier, call the fire department. – Installation and service must be performed by a qualified installer, service agency or the gas supplier. Warning: If the information in these instructions is not followed exactly, a fire or explosion may result caus- ing property damage, personal injury or loss of life. Preface 2 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 Buderus • http://www.buderus.net We reserve the right to make any changes due to technical modifications! About these instructions These Installation Instructions contain important informa- tion for the safe and professional installation, start-up and maintenance of the boiler with boiler capacities 24, 30, 45 and 60 kW. These Installation Instructions are intended for profes- sional installers, who have the necessary training and experience for working on heating and gas systems. Subject to technical changes! Slight changes may be made to the illustrations, process steps and technical data as a result of our policy of continuous improvement. Updating of documentation Please contact us if you have any suggestions for improvements or corrections. Contents Installation Instructions Logamax plus GB142-24/30/45/60 • version 10/2007 3 We reserve the right to make any changes due to technical modifications! Buderus • http://www.buderus.net 1 Safety and general instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1.1 Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 1.2 Hazard definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 1.3 The following instructions must be observed. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 1.4 Observe these instructions for space heating water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 1.5 Tools, materials and additional equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 1.6 Disposal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 2 Regulations and guidelines. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 3 Product description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 4 Dimensions and connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 5 Packaging and transportation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 5.1 Scope of delivery. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11 5.2 Transporting the boiler. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11 6 Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 6.1 Requirements for the installation room . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12 6.2 Fitting the boiler. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12 6.3 Making the gas connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13 6.4 Fitting the heating circuit supply and return pipes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14 6.5 Combustion Air and Ventilation Openings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17 6.6 Installation of the flue gas adapter (included in the scope of delivery) . . . . . . . . . . . . . . . . . . . . . . . . . . . .19 6.7 Installation of the Exhaust and Air Intake system.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20 7 Connecting the condensate drain. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 8 Electrical connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 8.1 External connection board connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27 9 Start-up procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 9.1 Testing for gas leaks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31 9.2 Filling the boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31 9.3 Filling the condensate trap. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32 9.4 Bleeding the gas supply valve. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32 9.5 Checking the combustion air/flue gas connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32 9.6 Checking the orifices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33 9.7 Inlet gas pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33 9.8 Checking and adjusting the gas/air ratio . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34 9.9 Carrying out a leak test in operating conditions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36 9.10 Measuring the carbon monoxide content (CO) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36 9.11 Function testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36 9.12 Measuring the ionization current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37 9.13 Testing the Ignition Safety shut off device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38 9.14 Installing the casing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38 9.15 Informing the owner, handing over the technical documents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38 10 BC10 basic controller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 10.1 Operating the BC10 basic controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39 10.1.1 Switching the heating system on and off. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 10.1.2 Displaying the operating conditions of the burner and resetting the burner or resetting burner faults . . . . . . 39 10.1.3 Displaying the heating system status and/or faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 10.2 Carrying out additional tasks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42 10.2.1 Carrying out a flue gas test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 10.2.2 Selecting partial load operation (e. g. during flue gas testing). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 10.2.3 Switching the heating system to manual mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Contents 4 Installation Instructions Logamax plus GB142-24/30/45/60 • version 10/2007 Buderus • http://www.buderus.net We reserve the right to make any changes due to technical modifications! 10.3 Configuring the boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 10.3.1 Adjusting the heating capacity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 10.3.2 Setting the DHW temperature value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 10.3.3 Entering the space heating water temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 10.3.4 Setting the pump post-purge period . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 11 Shutting down the system. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 11.1 Shut down the heating system using the control unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 11.2 Shutting down the heating system in the event of an emergency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 12 Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 12.1 Preparing the boiler for inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 12.2 Visual inspection for general signs of corrosion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 12.3 Internal leak testing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 12.4 Measuring the ionization current. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 12.5 Measuring the inlet gas pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 12.6 Checking and adjusting the gas/air ratio. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 12.7 Carrying out a gas leak test in operating conditions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 12.8 Measuring the carbon monoxide content (CO). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 12.9 Carrying out a pressure test of the heating system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 12.10 Checking the functioning and the safety of the air intake and flue gas conduit . . . . . . . . . . . . . . . . . . . . . 48 12.11 Checking venting systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 13 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 13.1 Cleaning the heat exchanger, burner and condensate trap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 13.2 Checking and adjusting the gas/air-ratio . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 14 Converting the boiler to propane . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 15 Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 15.1 Operating messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 15.2 Error messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 15.3 Technical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 16 Reports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 16.1 Start-up report. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 16.2 Inspection report. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 16.3 Maintenance report. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 17 Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 18 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 Safety and general instructions 1 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 5 We reserve the right to make any changes due to technical modifications! Buderus • http://www.buderus.net 1 Safety and general instructions Please observe these instructions in the interest of your own safety. 1.1 Designated use The boiler was designed for heating water for a central heating system and generating domestic hot water. The boiler is delivered with a BC10 basic controller and the "Universal Automatic Burner Control Unit 3" (UBA 3) pre-installed. The boiler can be fitted with a modulating outdoor reset control AM10 (scope of delivery), a room controller RC10 (optional), or an On/Off thermostat or relay panel end switch (accessories). 1.2 Hazard definitions The following defined terms are used throughout the docu- mentation to bring attention to the presence of hazards of various risk levels. Notices give important information concerning the operation of the product. 1.3 The following instructions must be observed – The boiler must only be used for its designated purpose, observing the Installation Instructions. – Only use the boiler in the combinations and with the accessories and spares listed. – Other combinations, accessories and consumables must only be used if they are specifically designed for the intended application and do not affect the system performance and the safety requirements. – Maintenance and repairs must only be carried out by trained professionals. – You must report the installation of a condensing gas boiler to the relevant gas utility company and have it approved. – You are only allowed to operate the condensing gas boiler with the combustion air/flue gas system that has been specifically designed and approved for this type of boiler. – Please note that local permission for the flue system and the condensate water connection to the public sewer system may be required. You must also observe: – the local building regulations stipulating the installation rules. – the local building regulations concerning the air intake and outlet systems and the chimney connection. – the regulations for the power supply connection. – the technical rules laid down by the gas utility company concerning the connection of the gas burner fitting to the local gas main. – the instructions and standards concerning the safety equipment for the water/space heating system. – the Installation Instructions for building heating systems. – The boiler must be located in an area where leakage of the tank or connections will not result in damage to the area adjacent to the boiler or to lower floors of the structure. When such locations cannot be avoided, it is recommended that a suitable drain pan, adequately drained, be installed under the boiler. The pan must not restrict combustion air flow. – The boiler must be installed such that the gas ignition system components are protected from water (dripping, spraying, rain etc.) during boiler operation and service. – The boiler must not be installed on carpeting. – Do not restrict or seal any air intake or outlet openings. DANGER: Indicates the presence of hazards that will cause severe personal injury, death or substantial property damage. WARNING: Indicates the presence of hazards that can cause severe personal injury, death or substantial property damage. CAUTION: Indicates presence of hazards that will or cause minor personal injury or property damage. CAUTION: Risk of electric shock. Indicates presence of hazards due to electric shock. NOTICE: Indicates special instructions on installation, operation or maintenance that are important but not related to personal injury or property damage. Safety and general instructions1 6 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 Buderus • http://www.buderus.net We reserve the right to make any changes due to technical modifications! – If you find any defects, you must inform the owner of the system of the defect and the associated hazard in writing. 1.4 Observe these instructions for space heating water Unsuitable heating system water can promote the forma- tion of scale or sludge, which affects system efficiency. It can also cause corrosion and reduce life of the heat exchanger. – You must follow Buderus guidelines for boiler water quality. – Thoroughly flush the system prior to filling. – Use of a Buderus approved boiler cleaner is recommended. – Never use salt bedding exchangers to soften the water. – Do not use inhibitors or other additives unless approved by Buderus for that purpose! – When frost protection of the heating system is desired, only use Buderus-approved Aluminum-safe antifreeze. – When using oxygen-permeable pipes, e. g. for floor heating systems, you must separate the system using heat exchangers. – The maximum permissible flow rate of the GB142-24/30 this is 11 GPM (gal./min.)(= 42 l/min.), for the GB142-45 is 15 GPM (= 57 l/min.) and for the GB142-60 is 20 GPM (= 76 l/min.). 1.5 Tools, materials and additional equipment For the installation and maintenance of the boiler you will need the standard tools for space heating, gas and water fitting. In addition, a handtruck with a fastening belt is useful. 1.6 Disposal – Dispose of the boiler packaging in an environmentally sound manner. – Dispose of components of the heating system (e. g. boiler or control device), that must be replaced in an environmentally responsible manner. DANGER if flammable gas explodes. Beware if you smell gas: there may be an explosion hazard! Warning: If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury or death. z Do not store or use gasoline or other flam- mable vapors and liquids in the vicinity of this or any other boiler. What to do if you smell gas z Do not try to light any boiler. z Do not touch any electrical switch; do not use any phone in your building. z Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions. z If you cannot reach your gas supplier, call the fire department. Installation and service must be performed by a qualified installer, service agency or the gas supplier. Regulations and guidelines 2 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 7 We reserve the right to make any changes due to technical modifications! Buderus • http://www.buderus.net 2 Regulations and guidelines The installation must conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the latest edition of the National Fuel Gas Code, ANSI Z223.1. In Canada, installation must be in accordance with the requirements of CAN/CSA B149.1, Natural Gas and Propane Installation Code. Where required by the authority having jurisdiction, the installation must conform to the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ ASME CSD-1. Install CO detectors per local regulations. Boiler requires yearly maintenance, see maintenance section see chapter 13 "Maintenance", page 49. Operating Limits of the boiler: Max. boiler temperature: 230 °F (110 °C) Max. operating pressure: 44 psi (3 bar) The hot water distribution system must comply with all applicable codes and regulations. When replacing an existing boiler, it is important to check the condition of the entire hot water distribution system to ensure safe opera- tion. Massachusetts Installations Only: For direct- vent boilers, mechanical-vent heating boilers or domestic hot water equipment, where the bottom of the vent terminal and the intake is installed below four feet above grade the following requirements must be satisfied: 1) If there is not one already present, a carbon monoxide detector and alarm shall be placed in a living area outside the bedrooms. The carbon monoxide detector and alarm shall comply with NFPA 720 (2005 Edition). 2) A carbon Monoxide detector and alarm shall be located in the room that houses the boiler or equipment and shall: a) Be powered by in series on the same electrical circuit as the boiler or equipment: b) Have battery back-up power: c) Meet ANSI/UL 2034 Standards and comply with NFPA 720 (2005 Edition): d) Have been approved and listed by a Nationally Recognized Testing Lab: 3) A product-approved vent terminal must be used, and if applicable, a Product approved air intake must be used. Installation shall be in strict compliance with the manufacturer's instructions. A copy of the installation. 4) A metal or plastic identification plate shall be mounted at the exterior of the building, four feet directly above the location of vent terminal. The plate shall be of sufficient size to be easily read from a distance of eight feet away, and read "Gas Vent Directly Below". b) For direct-vent boilers mechanical-vent heating boilers or domestic hot water equipment where the bottom of the vent terminal and the intake is installed four feet or above grade the following requirements must be satisfied: 1) If there is not one already present, a carbon monoxide detector and alarm shall be placed in the living area outside the bedrooms, The carbon monoxide detector and alarm shall comply with NFPA 720 (2005 Edition). 2) A carbon monoxide detector shall: a) Be located inn the area where the boiler or equipment is located: b) Have battery back-up power: c) Be a minimum comply with NFPA 720 (2005 Edition). 3) A product-approved vent terminal must be used, and if applicable, a product-approved air intake must be used. Installation shall be in strict compliance with the manufacturer's instructions. A copy of the installation instructions shall remain with the boiler or equipment at the completion of the installation. Product description3 8 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 Buderus • http://www.buderus.net We reserve the right to make any changes due to technical modifications! 3 Product description Fig. 1 Logamax plus GB142-24/30 (left) and GB142-45/60 (right) pos. 1: Drawer with control unit pos. 2: Universal Burner Automat (UBA3) pos. 3: Control unit BC10 pos. 4: Gas valve pos. 5: Cover pos. 6: Flue measuring points pos. 7: Parallel flue pos. 8: Burner pos. 9: Latches of which two have locks pos. 10: Sighting glass pos. 11: Heat exchanger pos. 12: Back cover pos. 13: Air intake for the fan pos. 14: Fan pos. 15: Condensate trap pos. 16: External Connection Board (under the cover) pos. 17: Pressure sensor 1 2 3 9 11 1314 9 1615 5 8 1 4 10 12 13 14 2 3 5 4 6 7 9 11 9 8 10 12 1615 17 76 Fig. 2 Basic Controller Logamatic BC10 pos. 1: Main switch pos. 2: DHW temperature knob 1) pos. 3: LED "DHW status" pos. 4: Display pos. 5: Space heating water temperature knob pos. 6: LED "Heating system status" pos. 7: Under the cover a RC system controller can be installed pos. 8: LED "Burner Operation" pos. 9: Service Tool connector pos. 10: "Service" e button pos. 11: "Chimney sweep" d button pos. 12: "Reset" c button 1) ECO mode means that the temperature inside the hot water tank is 140 °F (60 °C), with a hysteresis (ΔT) of 18 °F (10 °C) instead of 9 °F (5 °C) 190 170 150 130 90 110 140 130 120 90 100 110 4 7 2 1 5 8121011 3 6 9 Dimensions and connections 4 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 9 We reserve the right to make any changes due to technical modifications! Buderus • http://www.buderus.net 4 Dimensions and connections Fig. 3 Dimensions and connections for boiler GB142-24/30 (dimensions in inches) AA (A) AKO (E) GAS (D) = = = Flue gas connection (inside diameter 3'') Condensate water outlet, Ø 1.3” (Ø 32 mm) outside diameter Gas connection, ¾” NPT LA (B) RK (G) VK (F) WB (C) = = = = Air intake (inside diameter 3'') Return, Ø 1.0” 1 (Ø 25.4 mm) Supply, Ø 1.0” 1 (Ø 25.4 mm) Wall bracket 1 One Ø 1.0” (Ø 25.4 mm) inside x 1'' NPT threaded compression fitting is delivered enclosed with boiler packaging4" (100 mm)12" (300 mm) 20" (500 mm) 6.2" (158 mm) 0.25" (6 mm) 1.8" (46 mm) 18.7" (475 mm) > 6" (150 mm)2.2" (55 mm)3" (75 mm)3" (75 mm)6" (150 mm)1.2" (30 mm)16" (420 mm)7.5" (190 mm)28" (712 mm)4.7" (119 mm) 4.3" (110 mm)13.2" (335 mm) 22" (560 mm) 3" (75 mm) > 4" (100 mm)6" (150 mm)DE FG AB C NOTICE Observe the lateral minimum distances of the boiler (12” = 300 mm) and the necessary distances (24” (600 mm) at the front and 4” (100 mm) at the top) for removing the casing and for servicing. Closet clearances are: 4” (100 mm) to the right, 4” (100 mm) at the top and 6” (150 mm) to the left. Dimensions and connections4 10 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 Buderus • http://www.buderus.net We reserve the right to make any changes due to technical modifications! Fig. 4 Dimensions and connections for boiler GB142-45/60 (dimensions in inches) AA (A) AKO (E) GAS (D) = = = Combustion air Condensate water outlet, Ø 1.3” (Ø 32 mm) Gas connection, ¾” NPT LA (B) RK (G) VK (F) WB (C) = = = = Air intake Return, Ø 1.0” 1 (Ø 25.4 mm) Supply, Ø 1.0” 1 (Ø 25.4 mm) Wall bracket 1 One Ø 1.0” (Ø 25.4 mm) inside x 1'' NPT threaded compression fitting is delivered enclosed. 20.7" (526 mm)1.2" (30 mm)16" (420 mm)7.5" (190 mm)28" (712 mm)4.7" (119 mm) 4.3" (110 mm)13.2" (335 mm) 35.4" (900 mm) 9.7" (246 mm) 6.2" (158 mm) 0.25" (6 mm) 1.8" (46 mm) 18.7" (475 mm) > 6" (150 mm) > 4" (100 mm)2.2" (55 mm)3" (75 mm)3" (75 mm)DE FG AB C4" (100 mm)12" (300 mm) 20" (500 mm) NOTICE Observe the lateral minimum distances of the boiler (12” = 300 mm) and the necessary distances (24” (600 mm) at the front and 4” (100 mm) at the top) for removing the casing and for servicing. Closet clearances are: 4” (100 mm) to the right, 4” (100 mm) at the top and 6” (150 mm) to the left. Packaging and transportation 5 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 11 We reserve the right to make any changes due to technical modifications! Buderus • http://www.buderus.net 5 Packaging and transportation 5.1 Scope of delivery The boiler is delivered fully assembled. z When receiving the delivery, check if the packaging is intact. z Check that all the items listed in see table 1 are included in the delivery. 5.2 Transporting the boiler z Packaged boilers must always be lifted and carried to their destination by two people, or you must use a handtruck or special equipment to transport them to their destination. z Transport the boiler to the room where it is to be installed. Fig. 5 Items supplied with unit Pos.Parts Quantity Packaging 1 Boiler with casing 1 1 box 2 Wall bracket 1 3 Technical documents 1 including: - User's Instructions - Installation Instructions - wall mounting template - Servicing Instructions 3 4 Compression fittings 2 5 AM10 with outdoor sensor 1 6 Flue gas adapter 1 7 Propane conversion kit 1 8 Boiler connection kit, including the DHW sensor 1 9 GB142 Boiler manifold including: - low loss header - pressure relief valve - tridicator - DHW connections - Grundfoss 15-58 3-speed boiler circulator - supply and return shutoff ball valves 1 Table 1 Items supplied with unit 1 The user’s instructions (in a special format) is located in the boiler drawer 1 2 6 8 4 3 7 9 5 CAUTION The boiler may be damaged when it is improp- erly secured. – Only transport the boiler using the right transportation equipment, such as a handtruck with a fastening belt or special equipment for manoeuvering steps. – During transportation the boiler must be secured on the transportation equipment to prevent it from falling off. – Protect all parts against impacts if they are to be transported. – Observe the transportation markings on the packaging. Installation6 12 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 Buderus • http://www.buderus.net We reserve the right to make any changes due to technical modifications! 6 Installation 6.1 Requirements for the installation room 6.2 Fitting the boiler Observe the installation clearances of the combustion air/ flue gas system. z Remove the packaging materials and dispose of them. z Use the mounting template to mark the drill holes. z Install the wall bracket taking into account the necessary service clearances. z Remove the transport safety clamps (fig. 6). DANGER – Install the heating system in a frost-free room. – Do not store any flammable materials or liquids in the immediate vicinity of the boiler. – Never use any chlorinated detergents or halogenated hydrocarbons (e. g. in spraycans, solvents and detergents, paints, adhesives). – Do not allow too much dust to collect on the boiler. NOTICE – To protect the connection orifice you must not remove the styrofoam bottom panel. – Do not lift the boiler by the drawer. – Do not remove the transport safety clamps (see fig. 6) from the drawer at this time. – Protect the boiler and the combustion air/flue gas orifice against pollution during installation. Fig. 6 Removing the transport safety clamps Installation 6 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 13 We reserve the right to make any changes due to technical modifications! Buderus • http://www.buderus.net z Use the radiator key to unlock the two latches a quarter turn (fig. 7, pos. 1). z Open the latches (fig. 7, pos. 2). z Remove the casing by lifting it upwards and then pulling it forwards (fig. 7, pos. 3); do not hold the casing by the latches. z Hold the boiler by the rear boiler casing and place it on the wall bracket. z Level out the boiler. 6.3 Making the gas connection z Determine proper size gas pipe for the installation using see table 2 and see table 3. Do not forget the pipe fitting losses and observe proper size of the fittings. z Install the furnished ¾” gas cock on the gas connection. z Connect the gas pipe to the gas cock (fig. 8, pos. 1) so that it is free from any strain. A sediment trap must be provided upstream of the gas controls. Fig. 7 Removing the casing 1 2 2 2 2 3 Fig. 8 Making the gas connection 1 DANGER Only carry out work on gas lines if you are licensed for such work. Length of pipe (feet) Gas Volume Capacity (ft3 / hr) 1 ¾"1"1 ¼"1 ½" 10 278 520 1,060 1,600 20 190 350 730 1,100 30 152 285 590 890 40 130 245 500 760 50 115 215 440 670 75 93 175 360 545 100 79 160 305 480 150 64 120 250 380 Table 2 Gas Pipe Capacity for different pipe sizes 1 Maximum pipe capacity in ft 3/hr, based on a specific gravity of .60 (42 mbar) and a inlet gas pressure of 14 inches W.C. (35 mbar) or less and a pressure drop of .3 inches W.C. (20 mbar) NOTICE When installing the gas supply connection, it must comply with local regulations or, if such regulations do not exist, with the National Fuel Gas Code, ANSI Z 223.1. In Canada, the gas supply connection must comply with local regulations or, if such regula- tions do not exist, with CAN/CSA B149.1, Natural Gas and Propane Installation Code. Installation6 14 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 Buderus • http://www.buderus.net We reserve the right to make any changes due to technical modifications! 6.4 Fitting the heating circuit supply and return pipes z Fit a filling and drain cock in the heating system supply pipe if required. z Also fit an adequately sized safety valve in the system that meets all applicable codes and regulations. z Thoroughly flush all pipes and radiators. Use of a Buderus approved boiler cleaner is recommended. z Refer to the installation template for the pipe connection dimensions. z Fit the compression fittings (fig. 9, pos. 1 and 2) first to the Hydronic set (see fig. 10, 11 and 12) and then to the boiler. z Connect the expansion tank to the system. z Connect the pipes so that they are free from strain. Connecting boiler with DHW tank z Connect the external hot-water tank according to the Installation instructions of the hot-water tank and fittings concerned. Steel pipe diameter in inches Equivalent length for Pipe Fittings in feet Type of pipe fitting 90°-Elbow Tee (flow thru branch) Gate valve Gas cocks Equivalent length in feet ¾2.1 4.1 0.5 1.25 1 2.6 5.2 0.6 1.60 1 ¼3.5 6.9 0.8 2.15 1 ½ 4.0 8.0 0.9 2.50 Table 3 Equivalent length for pipe fittings in feet Fig. 9 Pump manifold installation pos. 1: Compression fitting (heating system supply pipe) pos. 2: Compression fitting (heating system return pipe) pos. 3: DHW supply pos. 4: DHW return pos. 5: Relief valve 21 3 4 5 NOTICE – To protect the entire heating system we recommend installing a dirt particle filter in the return circuit. When retrofitting the boiler to an existing heating system this filter is required. – Install shut-off valves immediately before and after the dirt particle filter to allow the filter to be cleaned. NOTICE When using oxygen-permeable pipes, e. g. for radiant floor heating systems, you must sepa- rate the system using heat exchangers. Buderus recommends hydraulically isolating snowmelt systems using heat exchangers. Installation 6 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 15 We reserve the right to make any changes due to technical modifications! Buderus • http://www.buderus.net Piping examples The following illustrations are two Installation examples. Piping and field components must be field verified. z A hot water boiler installed above radiation level or as required by the Authority having jurisdiction, must be provided with a low water cutoff device either as a part of the boiler or at the time of boiler installation. Fig. 10 is a schematic representation of fig. 9. Fig. 10 Schematic representation of the boiler with the hydronic set pos. 1: DHW supply pos. 2: drain valve pos. 3: pump manifold shut-off valves pos. 4: secondary supply pos. 5: DHW return pos. 6: secondary return GB142GB142GB142 FLUE GAS PT AIR INTAKE pump manifold 1 4 5 6 2 3 NOTICE The following illustrations are simplified concep- tual illustrations only. NOTICE If this boiler is installed in a closed water supply system with an external indirect DHW tank, such as one having a backflow preventer in the cold water supply line, means shall be provided to control thermal expansion. Contact the water supplier or local plumbing inspector on how to control this situation. Relief valve The indirect DHW tank must have a tempera- ture and pressure relief valve installed. The relief valve shall comply with the Standard for Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems, ANSI Z21.22-CSA 4.4. z Install the relief valve according fig. 10. The relief valve must comply with following specifications: – dimensions: height 2¼ inch (57.15 mm), width 2 inch (50.8 mm). – 30 Psi (2 bar) discharge pressure. – discharge is ¾ inch (19.1 mm) female in diameter. Installation6 16 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 Buderus • http://www.buderus.net We reserve the right to make any changes due to technical modifications! Fig. 11 Schematic representation of the boiler with the hydraulic set connected to an optional hot water tank with one or multiple zones including one pump and zone valves pos. 1: pressure relief valve pos. 2: PT meter (pressure and temperature meter) pos. 3: drain valve pos. 4: DHW pump pos. 5: secondary pump pos. 6: shut-off valve pos. 7: shut-off valve pos. 8: zone valve pos. 9: primary pump GB142GB142GB142 AdditionalAdditional DHWDHW TankTank Optional DHW Tank Aditional zones zones Radiant FLUE GAS PT AIR INTAKE 9 1 2 4 5 6 3 7 8 WARNING No valve is to be placed between the relief valve and the tank. Discharge of the relief valve must be conducted to a suitable place for disposal when relief occurs and no reducing coupling or other restriction may be installed in the discharge line. Fig. 12 Schematic representation of the boiler with the Hydronic set connected to an optional hot water tank with one or multiple zones and zone pumps pos. 1: pressure relief valve pos. 2: PT meter (pressure and temperature meter) pos. 3: drain valve pos. 4: DHW pump pos. 5: shut-off valve pos. 6: shut-off valve pos. 7: zone pump pos. 8: primary pump GB142GB142GB142 AdditionalAdditional DHWDHW TankTank Optional DHW Tank Aditional zones zones Radiant FLUE GAS PT AIR INTAKE 8 1 2 3 6 7 5 4 NOTICE Primary boiler pump must have an internal check valve. Installation 6 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 17 We reserve the right to make any changes due to technical modifications! Buderus • http://www.buderus.net 6.5 Combustion Air and Ventilation Openings Provisions for combustion and ventilation air must be made in accordance with section 5.3, Air for Combustion and Ventilation, of the National Flue Gas Code, ANSI Z223.1, or Sections 7.2, 7.3 or 7.4 of CAN/CGA B149, Installation Codes, or applicable provisions of the local building codes. CAUTION: BOILER DAMAGE AND OPERATIONAL FAILURES ! Due to insufficient or lacking openings for combustion air and/or ventilation of the boiler room. Provisions for combustion air and ventilation are always required, regardless whether the combustion air is taken from the outside (sealed combustion) or inside (room air for combustion). Insufficient ventilation of the boiler room can lead to high air temperatures. This can result in boiler damage. – Make sure that intake and exhaust openings are sufficiently sized and no reduction or closure of openings takes place. – When the problem is not resolved, do not operate the boiler. – Please note these restrictions and its dangers to the operator of the boiler. WARNING: BOILER DAMAGE ! due to contaminated air. – Boiler must be clear and free from combustible materials, gasoline and other flammable vapors and liquids, and corrosive liquids and vapors. Never use chlorine and hydrocarbon containing chemicals (such as spray chemicals, solution and cleaning agents, paints, glues etc) in the vicinity of the boiler. – Do not store and use these chemicals in the boiler room. – Avoid excessive dust formation and build-up. NOTICE When one expects contaminated combustion air (near swimming pools, chemical cleaning operations and hair salons), sealed combustion operation is recommended. Installation6 18 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 Buderus • http://www.buderus.net We reserve the right to make any changes due to technical modifications! All Air from Inside the Building (room air) The closet shall be provided with two permanent openings communicating directly with an additional room(s). The total input of all gas utilization equipment installed in the combined space shall be considered in making this determi- nation. Each opening shall have a minimum free area of 1 square inch per 1,000 Btu per hour of total input rating of all gas utilization equipment in the confined space, but no less than 100 square inches. One opening shall commence within 12 inches (305 mm) of the top, and one opening shall commence within 12 inches (305 mm) of the bottom of the enclosure. The minimum dimension of air openings shall be not less than 3 inches (75 mm). All Air from Outdoor (sealed combustion) The closet shall be provided with two permanent openings, one commencing within 12 inches (305 mm) from the top, and one commencing within 12 inches (305 mm) from the bottom of the enclosure. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors. The minimum dimension of air openings shall be no less than 3 inches (75 mm). 1. Where directly communicating with the outdoors, each opening shall have a minimum free area of 1 square inch per 4,000 Btu/hr of total input rating of all equipment in the enclosure. 2. Where communicating with the outdoors through vertical ducts, each opening shall have a minimum free area of 1 square inch per 4,000 Btu/hr of total input rating of all equipment in the enclosure. 3. Where communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch per 2,000 Btu/hr of total input rating of all equipment in the enclosure. 4. Where ducts are used, they shall be of the same cross- sectional area as the free area of the opening to which they connect. DANGER: FIRE DANGER ! due to flammable materials or liquids. – Do not store flammable materials and liquids in the immediate vicinity of the boiler. Installation 6 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 19 We reserve the right to make any changes due to technical modifications! Buderus • http://www.buderus.net 6.6 Installation of the flue gas adapter (included in the scope of delivery) Before installing the exhaust and air intake system, it is necessary to remove the transport safety device and to install the flue gas adapter. z Remove the transport safety device with the two screws (see fig. 13). z Screw on the flue gas adapter using six screws (see fig. 14). Fig. 13 Removing the transport safety device NOTICE The transport safety device has been installed to prevent unwanted movement of the heat exchanger during transport. Fig. 14 Connecting the flue gas adapter Installation6 20 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 Buderus • http://www.buderus.net We reserve the right to make any changes due to technical modifications! 6.7 Installation of the Exhaust and Air Intake system. An optional concentric vent/air intake body (see fig. 18 and 26) can be used for the installation of a vertical venting system as well as for a horizontal venting system. The concentric vent/air intake body can be ordered by Buderus Hydronic Systems, part no. BRYKGAVTO601CV. Other optional vent kits are: 383-500-397 Plastic Vent Kit PAZ1900019 V1000 Aluminum Vent Kit. The boiler can also be operated with separate air intake and exhaust piping (see fig. 19 and fig. 26). The termination shall be at least 4 ft (1,220 mm) for the U.S. and 6ft. (1,830 mm) for Canada away from a gas utility meter, service regulator or the like (for room air applications only). The termination shall terminate at least 4 ft (1,220 mm) below, 4 ft (1,220 mm) horizontally from, or 1 ft (305 mm) above any door, window, or gravity air inlet into any building. Vent must be at least 12 inches (305 mm) above grade, anticipated snow line or roof surface (Canada 18” (457 mm) minimum) (see fig. 16). Vent termination must be at least 7 ft (2,135 mm) above a public walkway (see fig. 17). Vent must be 3 ft (915 mm)above any forced air intake within 10 ft (3,050 mm) (see fig. 17). Do not extend exposed vent pipe outside the building beyond recommended distance. Condensate could freeze and block vent pipe. Vent should terminate at least 3 ft (915 mm) away from adja- cent walls, inside corners and 5ft (1525 mm) below roof overhang (see fig. 17). It is not recommended to terminate vent above any door or window, condensate can freeze causing ice formations. Do not use chimney as a raceway if another boiler or fire- place is vented into or through chimney. NOTICE: Consult local and state codes pertaining to special building code and fire department requirements. Adhere to national code require- ments. NOTICE: Observe the listed maximum lengths of vent system, which are boiler model dependent. The maximum permissible lengths are listed in see table 4, page 25. Fig. 15 Vent pipes 1 2 Installation 6 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 21 We reserve the right to make any changes due to technical modifications! Buderus • http://www.buderus.net All vent pipes must be glued, except for the flue gas adapter (fig. 15, pos. 1) which is screwed into place and the first connection to the flue gas adapter (fig. 15, pos. 2). Installed you can slide the pipe onto the adapter, properly supported and the exhaust pipe must be pitched a minimum of a ¼ inch per foot back to the boiler. This allows the condensate to drain away. All combustion air and vent pipe materials and fittings must comply with the following: * Components of the certified vent systems must not be interchanged with other vent systems or unlisted pipe fittings Plastic components, and specified primers and glues of the certified vent system must be from a single system manufacturer and not intermixed with other system manufacturer's vent system parts. Item Material United states Canada Vent or air pipe and fitting PVC schedule 40 ANSI/ASTM D1785 CSA or BH Gas venting systems, ULC S636 * certified only PVC-DWV ANSI/ASTM D2665 CPVC schedule 40 ANSI/ASTM F441 ABS-DWV schedule 40 ANSI/ASTM D2661 Pipe cement/primer PVC ANSI/ASTM D2564 CPVC ANSI/ASTM F493 ABS ANSI/ASTM D2235 Fig. 16 Vent and air pipe position (1) of a sealed combustion system 12" (300 mm) minimum 12" (300 mm) minimum 12" (300 mm) minimum INTAKE EXHAUST 12" (300 mm) minimum 12" (300 mm) minimum NOTICE Do not use cellular core pipe. NOTICE Ensure that a condensate drain is always installed at the exhaust connection see chapter "7 Connecting the condensate drain" on page 26 NOTICE A minimum clearance of 4 feet horizontally from and in no case above and below, unless a 4-foot horizontal distance is maintained, from electric meters, gas meters, regulators and relief equip- ment Installation6 22 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 Buderus • http://www.buderus.net We reserve the right to make any changes due to technical modifications! Below are approved examples of vertical and horizontal venting installation Fig. 17 Vent and air pipe position (2) of a system with combustion air supply from the room (non-room sealed) 1' Gravity Air Inlet 3' 3' 1' at least 1 ft (305 mm) above grade and snow line 4' 4' Forced Air Inlet 7' 4' 1' Exhaust terminal must be at least 3 ft (915 mm) above forced air inlet within 10 ft (3050 mm) 3' 5'(2135 mm)(305 mm)(1220 mm) (1525 mm) (1220 mm) (915 mm) (915 mm)(305 mm)(305 mm)(1220 mm) (1220 mm) Fig. 18 Vertical venting system (sealed combustion) INTAKE EXHAUST 10"- 0" MIN (250 mm - 0 mm MIN) 12" (300 mm) OVER MAXIMUM SNOW LEVEL OR 24" (600 mm) WHICHEVER IS GREATER 3" (80 mm) 3" (80 mm) 1 NOTICE Place pipe supports every 5 feet (1525 mm) of horizontal run, beginning with support near boiler. NOTICE The condensate water must be drained in accordance with the applicable rules. See chapter 7 „Connecting the condensate drain“. NOTICE Periodic cleaning of the vent terminal and air-intake screens is mandatory. Installation 6 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 23 We reserve the right to make any changes due to technical modifications! Buderus • http://www.buderus.net Fig. 19 Horizontal venting system (room air only) - Situation 1 INTAKEEXHAUST 3" (80 mm) Fig. 20 Vertical parallel venting system (sealed combustion) - Situation 1 INTAKE EXHAUST 10"- 0" MIN (250 mm - 0 mm MIN) 12" (300 mm) OVER MAXIMUM SNOW LEVEL OR 24" (600 mm) WHICHEVER IS GREATER 3" (80 mm) 3" (80 mm) Fig. 21 Horizontal venting system (sealed combustion) - Situation 2 INTAKE EXHAUST 3" (80 mm) Fig. 22 Vertical parallel venting system (sealed combustion) - Situation 2 INTAKE EXHAUST 10"- 0" MIN(250 mm - 0 mm MIN) 12" (300 mm) OVER MAXIMUM SNOW LEVELOR 24" (600 mm)WHICHEVER IS GREATER 3" (80 mm) 3" (80 mm) Installation6 24 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 Buderus • http://www.buderus.net We reserve the right to make any changes due to technical modifications! Fig. 23 Horizontal parallel venting system (sealed combustion) EXHAUST 3" (80 mm) min. 12" INTAKE 3" (80 mm) 12" (300 mm) minimum12" (300 mm)minimum 12"(300 mm) minimum 12"(300 mm) minimum 12"(300 mm) minimum Fig. 24 Vertical venting system (room air only) INTAKE EXHAUST 10"- 0" MIN (250 mm - 0 mm MIN) 12" (300 mm) OVER MAXIMUM SNOW LEVEL OR 24" (600 mm)WHICHEVER IS GREATER 3" (80 mm) Fig. 25 Vertical exhaust and horizontal intake venting system (sealed combustion) INTAKE 3" (80 mm) EXHAUST 3" (80 mm) 10"- 0" MIN (250 mm - 0 mm MIN) 12" (300 mm) OVER MAXIMUMSNOW LEVEL OR 24" (600 mm)WHICHEVER IS GREATER Fig. 26 Horizontal venting system (sealed combustion) INTAKE EXHAUST 3" (80 mm) 3" (80 mm) Installation 6 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 25 We reserve the right to make any changes due to technical modifications! Buderus • http://www.buderus.net Do not exceed the total equivalent venting length of 100 feet (30,480 mm) (GB142-24/30/45) and 60 feet (18,288 mm) (GB142-60) maximum requirement each for the intake and exhaust piping. See table 4 for the Friction Loss Equivalent in piping and fittings. Example: When you end up using 3 x 45°-elbows and the concentric vent kit, then the total venting length may not exceed 88 feet (26.82 m) (GB142-24/30/45) or 48 feet (14.63 m) (GB142-60). 3 x 45°-elbow = 3 x 3 ft (0.91 m) = 9 ft (2.73 m) concentric vent kit = 3 ft (0.91 m) Total friction loss equivalent = 12 ft (3.66 m) Total venting length for this example is: GB142-24/30/45 = 100 ft (30.48 m) - 12 ft (3.66 m) = 88 feet (26.82 m) GB142-60 = 60 ft (18.29 m) - 12 ft (3.66 m) = 48 feet (14.63 m). Fittings or Piping Equivalent feet m 45 degree elbow 3 0.91 90 degree elbow 5 1.52 plastic pipe per foot 1 0.30 concentric vent kit 3 0.91 Table 4 Friction Loss Equivalent in piping and fittings NOTICE The minimum covering wall thickness is 1" (25 mm). The maximum covering wall thickness is 16" (406 mm). CAUTION ! Vent connectors serving appliances vented by natural draft shall not be connected into any portion of mechanical draft systems operating under positive pressure. NOTICE For Direct venting properly reassemble and reseal the vent and air-intake systems. Connecting the condensate drain7 26 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 Buderus • http://www.buderus.net We reserve the right to make any changes due to technical modifications! 7 Connecting the condensate drain No condensate drain is integrated into the boiler. It is required to install the furnished 3” x ¾” drain tee as an external condensate drain. See fig. 27. Install this drain tee as close as possible to the boiler exhaust connection. If the condensate outlet of the boiler is lower than the drain, a condensate pump must be used. The condensate produced by the boiler has a pH value between 3 and 4. Install a neutralization unit if required by the local code. NOTICE The condensate must be drained from the boiler and from the flue in accordance with the appli- cable rules and regulations. Fig. 27 Condensate drain INTAKEEXHAUST 3" (80 mm) NOTICE Use materials approved by the authority having jurisdiction. In the absence of such authority, PVC and CPVC pipe must comply with ASTM D1785, F441 or D2665. Cement and primer must comply with ASTM D2564 or F493. For Canada, use CSA or ULC certified PVC or CPVC pipe, fittings and cement. Electrical connections 8 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 27 We reserve the right to make any changes due to technical modifications! Buderus • http://www.buderus.net 8 Electrical connections Devices such as pumps, outdoor sensor and 3-way valve are all connected to the external connection board. The electrical connections to the boiler must be made in accordance with all applicable local codes and the latest revision of the National Electrical Code, ANSI/NFPA-70 Installations should also conform with CSA C22. 1 Canadian Electrical Code Part 1 if installed in Canada. 8.1 External connection board connections Make all electrical connections inside the external connec- tion box. z Remove the cover of the external connection box (fig. 28). z Install a 120V cable to the boiler (see fig. 29, pos. 1). z Lead the cable through the cable guide (see fig. 29, pos. 2). Terminals 1 – 6 (fig. 30) are low-voltage connections and terminals 7 – 10 (fig. 30) are 120 Volt connections. RC terminal Connector for installation of an RC controller for indoor reset operation or a module like the AM10. FA terminal This is the terminal where you connect the outdoor temper- ature sensor. Only necessary for outdoor weather respon- sive operation. WA terminal For connection of a potential free thermostat or relay panel end switch. FW Connection for an external DHW tank sensor Fig. 28 Removing the cover from the external connection box Fig. 29 external connection board Fig. 30 Connections to external connection board 12 RC FA WA FW EV PK PS PZ NetzDWV 1234 5 6 7 8 9 10 Abbr.Color Component RC orange RC room controller connection or for an AM10 or other module FA blue Outdoor-temperature sensor WA green Potential-free On/Off thermostat FW gray DHW temperature sensor EV red External switching contact, potential-free for floor heating safety etc. DWV green Connection for external 3-way valve PK green Primary loop pump 120V 60Hz PS gray DHW tank pump 120V 60Hz PZ lilac DHW recirculating pump 120V 60Hz Netz white Main power connection 120V 60Hz Connecting incoming power The boiler must be electrically grounded in accordance with local codes, or in absence of local codes, with the National Electrical Code, ANSI/INFPA 70 and/or the CSA C22.1, Elec- trical Code. CAUTION RISK OF ELECTRIC SHOCK. Once the main power supply is on then there is 120V on terminals 7 – 10 (can only be used with the correct configuration of the control unit and specific system hydraulics), if the main switch of the BC10 basic controller is switched on. Electrical connections8 28 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 Buderus • http://www.buderus.net We reserve the right to make any changes due to technical modifications! EV terminal (external switching contact) This terminal can be used for example for the safety switch of floor heating. This protects the floor heating against too high boiler water temperatures (external manual reset high limit). The boiler is shut down when the external switching contact is opened. The normally closed contacts of a LWCO will shut down burner operation but allow the pump to continue to operate in case of a low water condition. DWV Terminal for connection of an external 3-way valve. PK Connector for the primary loop pump 120V 60Hz. PS Connector for the DHW tank pump 120V 60Hz. PZ Connector for the DHW recirculating pump 120V 60Hz. Netz Main power connector 120V 60Hz. 120-volt connections CAUTION Make sure that the power consumption of each of the terminals 7 – 9 (see circuit diagram) does not exceed 250 W or 5 Amp. Electrical connections 8 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 29 We reserve the right to make any changes due to technical modifications! Buderus • http://www.buderus.net Fig. 31 Electric circuit diagram 4321123123P6754123123LNPELN5M120VAC14512432154321171615141312111098765432132143215715451461977266364757436375857336035843341615811516131Pin 12855Pin 81Pin 16Pin 1KIM24 VRAC 78 65 1234 582PZGrid 14 13NL PENL 537923Fan unitGas burnerfittingTransformerHotsurfaceignitor16-pole connector(120 VAC)81-pole connector(AC 0, 10, 24 and 120 V)81-pole connector16-pole connectorConnection box UBA 3.0Ionization EarthPressuresensorReturn sensor Safety-temperature sensor Supply sensorOperating switchEarth120 VACFunction moduleMains supply120 VAC 60 HzCirculating pump120 VAC, max. 250 VADHW circulator120 VAC, max. 250 VABoiler circulator120 VAC, max. 250 VAExternal connection for specialist servicing companyExternal switch contactPotential-free e.g.for floor heatingDHW sensorOn/Off temperature control, potential-freeOutdoor-temperaturesensorModulating room controllerBC10 connectorBusFunction moduleExternal 3-way valvewhite greengreylilac 120 VACFunction module21 DWV High Voltage 0 VAC 24 VAC 10 VAC 10 VAC 230 VAC 230 VAC 24 VRAC 120 VAC 120 VAC 120 VAC 120 VAC white red grey blue orangegreen PS PK PENLPENLPENL 25 24 63 61 EV FW WA FA RC 21213212121 65 65 1234 1234 14 13 24 22 39 38 12 11 70 61 62 2 55 1 28 9081 25 52 27 23 79 53 76 49 16 44 17 45 69 68 67 14 12 13 PE N L L PE N 10 11 9 L N 3 7 4 6 5 CAUTION Label all wires prior to disconnection when servicing. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing. Start-up procedure9 30 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 Buderus • http://www.buderus.net We reserve the right to make any changes due to technical modifications! 9 Start-up procedure There are several steps involved in starting up the boiler. A. B. C. D. FOR YOUR SAFETY READ BEFORE OPERATING WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life. This appliance does not have a pilot. It is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand, BEFORE OPERATING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. WHAT TO DO IF YOU SMELL GAS • Do not try to light any appliance. • Do not touch any electric switch; do not use any phone in your building. • Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instruction. • If you cannot reach your gas supplier, call the fire department. OPERATING INSTRUCTION TO TURN OFF GAS TO APPLIANCE Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or turn by hand, don't try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion. Do not use this appliance if any parts have been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water. 1. STOP! read the safety information above on this label. 2. Turn off all electric power to the appliance. 3. Set the thermostat or other operating control to lowest setting. 4. This appliance is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand. 5. Close main gas shut off valve. 6. Wait (5) minutes to clear out any gas. Then smell for gas. Including near the floor. If you smell gas, STOP! Follow "B" in the safety information above on this label. If you don't smell gas, go to the next step. 7. Open main shut off valve. 8. Set the thermostat or other operation control to desired setting. 9. Turn on all electric power to the appliance. 10. If the appliance will not operate, follow the instruction "To Turn Off Gas To Appliance" and call your service technician or gas supplier. 1. Turn off all electric power to the appliance if service is to be performed. 2. Set the thermostat or other operating control to lowest setting. 3. Close main gas shut off valve.708.375A - 2172B Start-up procedure 9 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 31 We reserve the right to make any changes due to technical modifications! Buderus • http://www.buderus.net 9.1 Testing for gas leaks Prior to start-up of the boiler you must check the external tightness of the gas supply valve and confirm this in the start-up report. z Disconnect the heating system from the power supply. z Check the exterior tightness of new conduit sections up to and including the direct sealing point on the gas burner fitting. The maximum test pressure allowed on the input of the gas burner fitting is 14 inch W.C. (35 mbar). 9.2 Filling the boiler Set the main switch to "1". P0.0 appears in the display of the BC10 telling you that there is no system pressure. z Fill the heating system to a pressure of around 20 psi (1.5 bar). z Observe the pressure on the BC10 or the P/T gauge in the pump manifold for the heating circuit. The fill pres- sure of the system should be at least the required inlet pressure for the expansion tank plus 7.2 psi (0.5 bar). The minimum pressure is 15 psi (1.0 bar) (on a cold system). The maximum pressure is 44 psi (3.0 bar) (if the heating medium temperature is at its highest possible level). If this pressure is exceeded, the pressure relief valve will open. WARNING – Cover endangered positions before leak testing. – Do not spray the leak testing agent onto cables, plugs or electrical connection lines. Do not allow it to drip onto them either. DANGER Leaks may be caused to pipes and screw connections during commissioning and mainte- nance activities. – Carry out a proper leak test. – Only use approved leak detection agents for leak detection. NOTICE Observe the space heating water requirements as described in paragraph 1.4 on page 6. NOTICE If a relief valve discharges periodically, this may be due to thermal expansion in a closed water supply system. Contact the water supplier or local plumbing inspector on how to correct the situation. Never plug the relief valve. Start-up procedure9 32 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 Buderus • http://www.buderus.net We reserve the right to make any changes due to technical modifications! For first time start up it is necessary to set the DHW temper- ature knob and the space heating water temperature knob to the desired setting (see subsection 10.3.2 and 10.3.3). Factory setting is "0". 9.3 Filling the condensate trap z Make sure that you fill the condensate trap with water. This is to prevent exhaust gases from entering the room. z Remove the condensate trap (see fig. 32). z Fill with water and refit the condensate trap in reverse order. 9.4 Bleeding the gas supply valve z Loosen the screw plug on the testing nipple for the gas connection and venting (fig. 33, pos. 1) by two turns and fit a hose. z Slowly open the gas shut-off valve. z Run the gas that is discharged through a water bath. z Close the gas shut-off valve when no more air is released. z Remove the hose and tighten the screw plug again. 9.5 Checking the combustion air/flue gas connection Check the following points: – Is the prescribed combustion air/flue system used? – Have the instructions for configuring the flue system as specified in the relevant Installation instruction for the flue gas system been observed? 190 170 150 130 90 110 140 130 120 90 100 110 WARNING There is a hot water scald potential if the BC10 is set too high. Fig. 32 Filling water into the condensate trap Fig. 33 Bleeding the gas supply conduit 1 Start-up procedure 9 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 33 We reserve the right to make any changes due to technical modifications! Buderus • http://www.buderus.net 9.6 Checking the orifices 9.7 Inlet gas pressure z Open at least one thermostatic radiator valve if present to allow water to flow through the boiler. Do not switch on the boiler. z Close the gas shut-off valve. Loosen the screw plug on the inlet gas pressure testing nipple by two turns (fig. 34, pos. 1). z Connect the pressure gauge connection hose to the testing nipple (fig. 34, pos. 2). z Slowly open the gas shut-off valve. The boiler and its individual shutoff valve must be discon- nected from the gas supply piping system during any pres- sure testing of that system at test pressures in excess of ½ psi (3.5 kPa). The boiler must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than ½ psi (3.5 kPa). z Briefly press on the control panel cover to open it. z Switch on the heating system by setting the main switch to position "1" (see chapter 10 "BC10 basic controller", page 39). z Press the "Chimney Sweep" d button and hold it (for approx. two seconds) until the display shows a decimal point. CAUTION The burner must only be commissioned if the correct orifices are fitted (see table 6). z Convert the burner fitting to another gas type if required (see chapter 14 "Converting the boiler to propane", page 52). Boiler capacity Type of gas supply Gas orifice diameter in mm (inch) 24 kW Natural gas 4.45 (0.174) LPG P 3.35 (0.131) 30 kW Natural gas 4.45 (0.174) LPG P 3.35 (0.131) 45 kW Natural gas 5.40 (0.213) LPG P 4.05 (0.158) 60 kW Natural gas 7.50 (0.293) LPG P 5.40 (0.213) Table 6 Gas orifice diameter Fig. 34 Measuring the inlet gas pressure Fig. 35 Opening the control panel Start-up procedure9 34 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 Buderus • http://www.buderus.net We reserve the right to make any changes due to technical modifications! z Measure the gas connection pressure as soon as the "Burner" LED lights and enter this value in the start-up report. The inlet gas pressure must be: – for natural gas - min. 3.5 to 10.5 inch W.C (8.7 to 26.1 mbar), nominal supply pressure 7.0 inch W.C. (17,4 mbar) – for LPG - min. 8.0 to 13.0 inch W.C. (19.9 to 32.3 mbar), nominal supply pressure 11.0 inch W.C. (27.4 mbar). z Repeatedly press the "Service" e button until the temperature indication is displayed. z Press the "Chimney Sweep" d button to end the measurement procedure. z Close the gas shut-off valve. z Remove the connection hose again and tighten the screw plug on the testing nipple. z Open the gas shut-off valve again. 9.8 Checking and adjusting the gas/air ratio z Switch off the heating system using the main switch. z Loosen the screw plug on the measuring nipple for the burner pressure by two rotations (fig. 36, pos. 1). z Set the pressure gauge to zero. z Use a hose to connect the plus terminal of the pressure gauge to the burner pressure measuring nipple (fig. 36, pos. 2). z Switch on the heating system using the main switch. CAUTION – Contact the relevant gas utility company if the required inlet gas pressure is not available. – Install a gas pressure regulator before the gas burner fitting if the supply pressure is too high. Fig. 36 Checking the gas/air ratio 1 2 Start-up procedure 9 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 35 We reserve the right to make any changes due to technical modifications! Buderus • http://www.buderus.net z Press the "Chimney Sweep" d button and hold it (for approx. two seconds) until the display shows the decimal point. z Press and hold the "Chimney Sweep" d and "Service" e buttons (for approx. five seconds) until the display shows "Lxx" (e. g. L80). z Set the boiler to partial load "L30" by pressing the "Chimney Sweep" d button (higher values) or the "Reset" c button (lower values). z Read out the differential pressure. The differential pressure (pGas – pAir) must be -0.02 inch W.C. (- 5 Pa) (±0.02 inch W.C. = ± 5 Pa) (read-out on pressure gauge: -0.04 – 0 inch W.C. = -10 – 0 Pa). z Enter the value measured in the start-up report. z If the gas/air ratio is not correct it can be adjusted using the adjustment screw (fig. 37, pos. 1). The adjustment screw is located behind the cover screw. z Repeatedly press the "Service" e button until the temperature indication is displayed. z Press the "Chimney Sweep" d button until the decimal point is cleared from the display. z Switch off the heating system using the main switch. z Remove the measurement set-up, tighten the screw in the burner pressure measuring nipple. z Switch on the heating system using the main switch. + = higher values = lower values Fig. 37 Setting the gas/air ratio Start-up procedure9 36 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 Buderus • http://www.buderus.net We reserve the right to make any changes due to technical modifications! 9.9 Carrying out a leak test in operating conditions z Check all gaskets and joints in the burner gas circuit for leaks while the burner is operational, using a foaming agent. 9.10 Measuring the carbon monoxide content (CO) z Measure the carbon monoxide content on the flue gas sampling point (fig. 38). The CO values in an air-free condition must be below 400 ppm or 0.04 vol. %. Values of 400 ppm and up indicate that the burner adjust- ment may be wrong, the gas burner fitting or the heat exchanger are dirty or that there may be burner faults. z You must establish and resolve the cause. The boiler must be operational when you do this. 9.11 Function testing z You must check the functioning and, if readjustment is possible, the adjustment of all control, regulating and safety devices when carrying out start-up tests, annual inspections or maintenance as required. z You must also test the gas and water lines for leaks. DANGER Leaks may be caused to pipes and screw connections during start-up activities if flam- mable gas explodes. – Only use approved leak detection agents for leak detection such as a soapy water solution. CAUTION due to a short circuit. – Cover damageable parts before leak testing. – Do not spray the leak testing agent onto cables, plugs or electrical connection lines. Do not allow it to drip onto them either. Fig. 38 Flue gas sampling point Start-up procedure 9 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 37 We reserve the right to make any changes due to technical modifications! Buderus • http://www.buderus.net 9.12 Measuring the ionization current z Switch off the heating system using the main switch. z Disconnect the plug and socket connection of the moni- toring cable and connect the measuring device in series (fig. 39). Select the µA direct current range on the measuring device. The measuring device must have a resolution of at least 1 µA. z Switch on the heating system using the main switch. z Press the "Chimney Sweep" d button and hold it (for approx. two seconds), until the display shows the decimal point. z Press and hold the "Chimney Sweep" d and "Service" e buttons, until the display shows "Lxx" (e. g. L80). z Set the boiler to partial load "L30" by pressing the "Chimney Sweep" d button (higher values) or the "Reset" c button (lower values). z Measure the ionization current. When the boiler is in partial load mode the ionization current must be > 5 µA DC. z Enter the value measured in the start-up report. z Repeatedly press the "Service" e button, until the temperature indication is displayed. z Press the "Chimney Sweep" d button to end the measurement procedure. z Switch off the heating system using the main switch. z Remove the measuring device and restore the plug and socket connection. z Switch on the heating system again using the main switch. Fig. 39 Measuring the ionization current + = higher values = lower values Start-up procedure9 38 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 Buderus • http://www.buderus.net We reserve the right to make any changes due to technical modifications! z Push against the drawer (fig. 40) to close the control panel. 9.13 Testing the Ignition Safety shut off device z Switch off the heating system using the main switch. z Disconnect the plug and socket connection of the moni- toring cable. z Switch on the heating system using the main switch. z Press the "Chimney Sweep" d button and hold it (for approx. two seconds), until the display shows the decimal point. z Check if the boiler does one start-up attempt and three restart attampts. After each start-up attempt the boiler will signal a start-up failure. A "6A" code can be seen in the display. After the last start-up attempt, the boiler will lock out. The "6A" code is blinking in the display. z Connect the plug and socket connection of the moni- toring cable. z Press the reset button. z Check if the boiler starts-up. z Press the "Chimney Sweep" button return to normal operating conditions. 9.14 Installing the casing z Install the casing and close the latches (fig. 41). Do not lift the casing by the latches! z Lock the latches using the radiator key. 9.15 Informing the owner, handing over the technical documents z Show the owner how the heating system works and how the boiler can be operated. Hand over the technical documents. Fig. 40 Closing the control panel Fig. 41 Installing the casing BC10 basic controller 10 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 39 We reserve the right to make any changes due to technical modifications! Buderus • http://www.buderus.net 10 BC10 basic controller 10.1 Operating the BC10 basic controller 10.1.1 Switching the heating system on and off Switching on the heating system z Set the main switch on the BC10 basic controller to position "1" (On). Switching off the heating system z Set the main switch on the BC10 basic controller to position "0" (Off). 10.1.2 Displaying the operating conditions of the burner and resetting the burner or resetting burner faults Displaying the operating conditions of the burner The LED indicates the operating condition of the burner. Fig. 42 BC10 basic controller – Controls pos. 1: Main switch pos. 2: DHW temperature knob pos. 3: LED "DHW status" pos. 4: Display pos. 5: Space heating water temperature knob pos. 6: LED "Heating system status" pos. 7: Under the cover a RC system controller can be installed (not available). pos. 8: LED "Burner Operation" pos. 9: Service Tool connector pos. 10: "Service" e button pos. 11: "Chimney sweep" d button pos. 12: "Reset" c button 190 170 150 130 90 110 140 130 120 90 100 110 4 7 2 1 5 8121011 3 6 9 LED Condition Explanation On Burner operational The water in the boiler is being heated. Off Burner off The water in the boiler has reached the required temperature or there is no heat request. Table 7 LED indication BC10 basic controller10 40 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 Buderus • http://www.buderus.net We reserve the right to make any changes due to technical modifications! Resetting the boiler or resetting faults If the boiler is down due to a fault, you can reset the boiler by pressing the "Reset" c button. This is only possible for so-called lock-out faults. There is another type of fault, so- called blocking faults, that reset themselves when the cause has been remedied. z Press the "Reset" c button to reset the boiler. The display shows "rE" while resetting. It is only possible to reset the boiler when a lock-out code (blinking fault code) is visible in the display. 10.1.3 Displaying the heating system status and/or faults The display of the BC10 basic controller shows the status of the heating system. In the event of a fault the display immediately shows the fault or the warning in the form of an error code (see subsection 15.2). The status display will flash if the fault is a lock-out fault. z Press the "Service" e button to switch between status displays or to read out the service and error codes. z Resolve the fault see subsection 15.3. The following status displays can be seen depending on the operating conditions: rE NOTICE If the burner returns to fault mode after resetting the boiler, you must resolve the fault using the servicing section in this document. Contact your supplier if necessary. Displays (examples) Values Meaning Operating condition/Remedy 1)number 0 ... 199 2)Current boiler water temperature (in °F) > P15 Current system pressure (in psi)Normal operating conditions Table 8 Possible status displays 1)Standard display for this operating condition. This display appears after 5 minutes if no button is pressed. 2)The temperature is higher as 199° when 199 is blinking in the display. 140 P21 -H BC10 basic controller 10 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 41 We reserve the right to make any changes due to technical modifications! Buderus • http://www.buderus.net 1) (changing) P3 ... P12 Warning: System pressure is too low (between 3 and 12 psi = 0.2 and 0.8 bar) Warning Heating system remains operational between 12 psi and 3 psi (0.8 and 0.2 bar). Fill the heating system and restore the minimum filling pressure (≥14.5 psi = ≥1.0 bar). The system pressure is shown for 10 minutes after which the standard display returns. number 0 ... 199 2)Current boiler water temperature (in °F) P3 ... P12 Current system pressure (in psi) 1) (flashing) < P3 Fault: system pressure is far too low (< 3 psi = < 0.2 bar) Fault Burner and boiler circuit pump are not operational. Frost protection is active up to 2 psi (0.1 bar). The heating system will only become operational again if the pressure is back to 14.5 psi (1.0 bar). Fill the heating system and restore the minimum filling pressure (≥14.5 psi = ≥1.0 bar). The system pressure is shown for 10 minutes after which the standard display returns. number > 200 Error code Remedy the error see servicing section number 0 ... 199 2)Current boiler water temperature (in °F) < P3 Current system pressure (in psi) 1) (partially flashing) Combination of letters and digits Service code Fault Lock-out faults (flashing display) must be reset by pressing the "Reset" c button. Blocking faults reset automatically as soon as the cause has been removed. Remedy any blocking faults that remain active for a long time using the service section in this manual. number > 199 Error code Remedy the error using the servicing section in this manual number 0 ... 199 2)Current boiler water temperature (in °F) > P15 Current system pressure (in psi) 1) A00 ... A99 Service code System faults System faults are faults in the heating system that do not affect the burner operation.number > 800 Error code Remedy the error using the service section in this manual number 0 ... 199 Current boiler water temperature (in °F) > P15 Current system pressure (in psi) (flashing)Fault No communication between BC10 and automatic gas burner. Fault Remedy the error using the service section in this manual. Check the connections to both devices. Check the communication lines. Displays (examples) Values Meaning Operating condition/Remedy Table 8 Possible status displays 1)Standard display for this operating condition. This display appears after 5 minutes if no button is pressed. 2)The temperature is higher as 199° when 199 is blinking in the display. P12 H7 -H 140 P12 P3 207 140 P3 3A 207 140 P21 A12 816 -H 140 P21 - BC10 basic controller10 42 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 Buderus • http://www.buderus.net We reserve the right to make any changes due to technical modifications! 10.2 Carrying out additional tasks 10.2.1 Carrying out a flue gas test The "Chimney Sweep" d button is used for the flue gas test. The heating control system works at the maximum flow temperature for 30 minutes. This is set on the BC10 basic controller using the "maximum heater temperature" knob. During flue gas testing the decimal point lights up in the display. z Press and hold the "Chimney Sweep" d button (< 5 seconds) until the decimal point is displayed. z Carry out the flue gas test. z Press the "Chimney Sweep" d button to interrupt the flue gas test. 10.2.2 Selecting partial load operation (e. g. during flue gas testing) You can operate the boiler at a reduced boiler capacity during flue gas testing. This reduction is only effective for the duration of the flue gas test. z Press the "Chimney Sweep" d button (max. 2 seconds) until the decimal point shows in the status display. This will switch on the flue gas test. z Press and hold the "Chimney Sweep" d and "Service" e buttons (for approx. 5 seconds) to enter the partial load mode. z Press the "Reset" c button to reduce the boiler capacity percentage. Example: boiler capacity reduced to 50 % of the rated boiler capacity. z Press the "Chimney Sweep" d button to increase the boiler capacity percentage. z When test is completed, press the "Service" e button until the temperature indication is displayed. z Press the "Chimney Sweep" d button until the decimal point is cleared from the display. 10.2.3 Switching the heating system to manual mode In manual mode the heating system can be operated inde- pendently of an external control unit. The boiler is operated with the heating system temperature set on the right knob serving as the target value. A blinking decimal point is displayed while manual mode is active. z Press the "Chimney Sweep" d button (for more than 5 seconds) until the decimal point in the status display flashes. + L50. BC10 basic controller 10 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 43 We reserve the right to make any changes due to technical modifications! Buderus • http://www.buderus.net z Turn the knob to set the maximum space heating system temperature. z Press the "Chimney Sweep" d button to exit manual mode. 10.3 Configuring the boiler 10.3.1 Adjusting the heating capacity Setting the heating capacity depending on the maximum heat requirement (see table 9). z Press and hold the "Chimney Sweep" d and "Service" e buttons until an "L" with a double-digit value (e. g. L80) or an "L" followed by two dashes (L--) is displayed. Factory setting "L--". z Set the heating capacity by pressing the "Chimney Sweep" d button (higher values) or the "Reset" c button (lower values). z Press the "Service" e button to confirm the setting. 190 170 150 130 90 110 Regu- lator setting in % Heating capacity (±5 %) boiler cap. 24 kW boiler cap. 30 kW boiler cap. 45 kW boiler cap. 60 kW kW btu kW btu kW btu kW btu L30 7.2 24,566 8.7 29,684 13.5 46,062 18.0 61,542 L40 9.6 32,755 11.7 39,920 18.0 61,416 24.0 82,080 L50 12.0 40,944 14.8 50,498 24.5 83,619 30.0 102,630 L60 14.4 49,133 17.8 60,734 27.0 92,178 36.0 123,192 L70 16.8 57,322 20.9 71,311 31.5 107,573 42.0 143,766 L80 19.2 65,510 23.9 81,547 36.0 122,976 48.0 164,352 L90 21.6 73,699 27.0 92,124 40.5 138,389 54.0 184,950 L--24.0 81,888 30.0 102,360 45.0 153,810 60.0 205,560 Table 9 Heating capacity WARNING – Turn the "space heating system temperature" knob to limit the heating system temperature to the permissible flow temperature for the floor heating circuit (e. g. 86 – 104 °F = 30 – 40 °C), so pipes will not overheat. DANGER The heating system can freeze up if a power failure occurs or after switching off the power supply, because manual operation then is no longer active. – You must re-activate manual operation after switching on the system to keep the heating system operational (especially if there is a risk of frost). + L-- / BC10 basic controller10 44 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 Buderus • http://www.buderus.net We reserve the right to make any changes due to technical modifications! 10.3.2 Setting the DHW temperature value z Turn the "DHW temperature" rotary knob to set the desired temperature of the hot water in the hot-water tank. 10.3.3 Entering the space heating water temperature z Turn the "space heating water temperature" knob to set the upper limit value of the heater water for the heating operation. This limitation does not apply to DHW prepa- ration. 140 130 120 90 100 110 Condition Explanation LED 0 Off No hot water supply (only heating mode). Off Eco 1 Economy mode, Hot water temperature 140 °F (60 °C) The DHW will only be reheated to 140 °F (60 °C), if the temperature has signifcantly fallen. This reduces the number of burner starts and saves energy. As a result the water may be a bit colder initially. On 2 86 – 140 Direct setting on BC10 in °F The temperature set on the BC10 is a temperature that cannot be changed using a RC thermostat. On 2 Aut Entry via thermostat (presetting) The temperature is set on the thermostat (e. g. RC30). If no thermostat is connected, the maximum DHW temperature is 140 °F (60 °C). On 2 Table 10 Settings of "DHW temperature" knob 1 This function has been optimized for boilers with combined DHW heating (combi-units). 2 The heating program (timer) of the room control unit remains active, as a result of which no hot water is heated during night-time operation. 3 The LED under the rotary knob lights up if the DHW temperature is below the target value (heat request for DHW). 190 170 150 130 90 110 Condition Explanation LED 0 Off No supply to heating system (only DHW heating operation).Off 86 – 190 Direct setting on BC10 in °F (86 – 190 °F = 30 – 90 °C) The temperature set on the BC10 is a temperature that cannot be changed using a RC thermostat. Supply temperature does not rise above the set temperature. On 1 Aut Entry via thermostat (presetting) The temperature is automatically determined on the basis of the heating characteristic. If no thermostat is connected, the maximum heater temperature is 190 °F (90 °C). On 1 Table 11 Settings of "space heating water temperature" rotary knob 1 The LED under the rotary knob lights up when the heating system is switched on and heat is requested. In summer mode the heating system is switched off (LED off). BC10 basic controller 10 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 45 We reserve the right to make any changes due to technical modifications! Buderus • http://www.buderus.net 10.3.4 Setting the pump post-purge period A pump must be connected to PK (see fig. 29, pos. 7) of the external connection board in order to be able to set the pump run over time. z Press and hold the "Chimney Sweep" d and "Service" e buttons until the display shows "L--". z Press the "Service" e button. The display shows "F05". The heating system has been factory-set to a pump post- purge period of 5 minutes. z Press the "Chimney Sweep" d or "Reset" c buttons to set the pump post-purge period. The pump post-purge period can be set from 5 – 60 minutes (F5 - F60) or to 24 hours (F1d). z Press the "Service" e button to confirm the setting. CAUTION – Set the boiler primary pump post-purge period to 24 hours if the heating system is controlled by room temperature sensor and there is a risk of parts of the heating system that are outside the coverage of the room thermostat freezing (e. g. radiators in a garage; constant circulation). + / NOTICE On thermostat only systems a 5 to 10 minute post-purge setting is recommended to purge heat from the boiler. Shutting down the system11 46 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 Buderus • http://www.buderus.net We reserve the right to make any changes due to technical modifications! 11 Shutting down the system 11.1 Shut down the heating system using the control unit Shut down your heating system using the BC10 basic controller. When the BC10 basic controller is shut down, the burner is also switched off automatically. Further information on how to operate the BC10 basic controller can be found in chapter 10 "BC10 basic controller", page 39. z Switch off the heating system using the main switch. z Close the main shut-off valve or the gas shut-off valve. 11.2 Shutting down the heating system in the event of an emergency You must immediately close the main shut-off valve or gas shut-off valve and disconnect the power from the heating system. z Close the main shut-off valve. DANGER The heating system may freeze if it is not operational in times of frost. Protect the heating system against freezing if there is a danger of frost affecting the system. Drain the heating system water from the lowest point of the heating system. The vent screw at the highest point of the heating system must then be open. DANGER Should overheating occur or gas supply fail to shut off, turn off the manual gas control valve to the boiler. Inspection 12 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 47 We reserve the right to make any changes due to technical modifications! Buderus • http://www.buderus.net 12 Inspection We advise you to offer your customer an annual inspection and maintenance contract (for the contents of this contract, see page 59 and page 60). If inspection reveals that maintenance work is necessary you can carry this out as required (see chapter 13 "Mainte- nance", page 49). z Periodically examine the venting systems and cleaning of the screens in the vent terminal. z Also periodically inspect the low water cutoffs, including flushing of float types and clean the condensate collec- tions and disposal system. 12.1 Preparing the boiler for inspection z Switch off the heating system using the main switch. z Remove the cover from the boiler (fig. 7, page 13). 12.2 Visual inspection for general signs of corrosion z Check all gas and water pipes for signs of corrosion. z Replace any pipes that are corroded. CAUTION – Check and clean the heating system once a year. – Carry out a maintenance overhaul if necessary. Immediately repair defects to avoid damage to the heating system! WARNING Do not use this boiler if any part has been under water. Immediately call a qualified service tech- nician to inspect the boiler and to replace any part of the control system and any gas control which has been under water. CAUTION Risk of electric shock. – Before opening the system: disconnect the heating system from the power supply using the heating system emergency OFF button or disconnect the relevant circuit breaker of the house from the power grid. – Secure the heating system against accidental restarting. INSTRUCTION FOR THE INSTALLER – If gas pipes have to be disconnected from the gas burner fitting, the burner cover must only be opened by a specialized professional. Inspection12 48 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 Buderus • http://www.buderus.net We reserve the right to make any changes due to technical modifications! 12.3 Internal leak testing z Switch off the heating system using the main switch. z Test for internal leaks of the gas burner fitting on the inlet side, applying a test pressure of 7.0 inch W.C. (17.4 mbar) in case of natural gas and 11.0 mbar (27.4 mbar) in case of LPG. After one minute the pressure must not have dropped by more than 3.8 inch W.C. (10 mbar). z If the pressure has dropped more, you must check all gaskets and joints upstream of the gas burner fitting for leaks using a foaming agent. Repeat the pressure test if no leaks are found. If the pressure has again dropped by more than 3.8 inch W.C. (10 mbar) per minute you will have to replace the gas burner fitting. 12.4 Measuring the ionization current See subsection 9.12 "Measuring the ionization current", page 37. 12.5 Measuring the inlet gas pressure See subsection 9.7 "Inlet gas pressure", page 33. 12.6 Checking and adjusting the gas/air ratio See subsection 9.8 "Checking and adjusting the gas/air ratio", page 34. 12.7 Carrying out a gas leak test in operating conditions See subsection 9.9 "Carrying out a leak test in operating conditions", page 36. 12.8 Measuring the carbon monoxide content (CO) See subsection 9.10 "Measuring the carbon monoxide content (CO)", page 36. 12.9 Carrying out a pressure test of the heating system See chapter 9 "Start-up procedure", page 30. 12.10 Checking the functioning and the safety of the air intake and flue gas conduit See subsection 9.5 "Checking the combustion air/flue gas connection", page 32. 12.11 Checking venting systems Check air intake and flue gas for obstruction or damage. Maintenance 13 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 49 We reserve the right to make any changes due to technical modifications! Buderus • http://www.buderus.net 13 Maintenance z Switch off the heating system using the main switch. z Close the gas shut-off valve. z Remove the casing. 13.1 Cleaning the heat exchanger, burner and condensate trap z Dismantle the hot surface ignitor and the ionization elec- trode. z Loosen the fastening nuts (fig. 43, pos. 1). z Remove the earth cable (fig. 43, pos. 2). z Remove the retaining plate. z Pull the hot surface ignitor (fig. 43, pos. 3) and the ioniza- tion electrode (fig. 43, pos. 4) out of the heat exchanger. z Loosen the threaded connection to the gas control valve (fig. 44, pos. 1) and pull the plug (fig. 44, pos. 2) from the gas valve terminal block. z Pull the plug from the fan unit (fig. 44, pos. 3). CAUTION There is no need to lubricate the combustion motor as it is permanently lubricated. Fig. 43 Removing the hot surface ignitor and the ionization electrode CAUTION To avoid a short circuit. – Do not spray the cleaning agent onto the burner, the hot surface ignitor, the ionization electrode or other electric components. Fig. 44 Removing the connections 4 1 4 3 2 55 Maintenance13 50 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 Buderus • http://www.buderus.net We reserve the right to make any changes due to technical modifications! z Loosen both sets of retaining clips (fig. 44, pos. 4 and 5) of the burner cover and remove the burner cover with the fan unit and the gas burner fitting (fig. 45, pos. 1). z Remove the gas/air distributor plate (fig. 45, pos. 2), the orifice plate (GB142-24, GB142-30 and GB142-60 only, fig. 45, pos. 3) and the burner (fig. 45, pos. 4). Note that the orifice plate of the GB142-60 has a different shape. z Clean the gas/air distributor plate, the orifice plate (GB142-24, GB142-30 and GB142-60 only) and the burner using compressed air. z Remove the baffle plate and clean it using compressed air (fig. 46). z Flush the heat exchanger with water. z Re-assemble all parts in reverse order of disassembly. z Switch on the heating system using the main switch. z Press the "Chimney Sweep" d button until the decimal point is displayed. Leave the boiler on for approx. 10 minutes. Fig. 45 Cleaning the burner cover, gas/air distributor plate, orifice plate and burner 1 2 3 4 Fig. 46 Baffle plate Fig. 47 Cleaning the heat exchanger 1NOTICE It is important to inspect and properly replace the rubber gaskets. Maintenance 13 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 51 We reserve the right to make any changes due to technical modifications! Buderus • http://www.buderus.net z Switch off the heating system using the main switch. z Dismantle the boiler again and flush the heat exchanger with water. z Pull the condensate trap from the condensate plate (fig. 48, pos. 1). z Loosen the condensate trap from the connection (fig. 48, pos. 2) and remove it. z Use a bristle brush to clean the condensate trap. z Flush the condensate trap. z Fill the condensate trap with water before re-installing it. z Check the condensate trap gasket for damage and replace it if necessary. z Re-assemble all parts in reverse order of disassembly. 13.2 Checking and adjusting the gas/air-ratio See chapter 9.8 "Checking and adjusting the gas/air ratio", page 34. Fig. 48 Condensate trap 1 2 Converting the boiler to propane14 52 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 Buderus • http://www.buderus.net We reserve the right to make any changes due to technical modifications! 14 Converting the boiler to propane To convert the boiler to propane, the following instructions must be adhered to: z Turn off the gas supply. z Switch off the heating system using the main switch. z Disconnect the electrical power to the boiler. z Set the thermostat or other operating control to lowest setting. z Remove the casing (fig. 49). z Loosen the screw connection on the gas valve (fig. 44, pos. 1, page 49) and pull the plug (fig. 44, pos. 2, page 49) from the gas valve. z Pull both plugs from the fan unit (fig. 44, pos. 3, page 49). z Loosen both retaining clips (fig. 44, pos. 4, page 49) on the burner cover and remove the burner cover together with the fan unit and the gas valve. z Loosen the three crosshead screws and remove the gas valve from the fan unit (fig. 50, pos. 1). z Remove the gas orifice (fig. 50, pos. 2). DANGER if flammable gas explodes. Only carry out work on gas conduits and fittings if you are licensed for such work. Fig. 49 Remove the casing GB142-24/30 GB142-45/60 Fig. 50 Replacing the gas orifice 1 2 Converting the boiler to propane 14 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 53 We reserve the right to make any changes due to technical modifications! Buderus • http://www.buderus.net z Fit the right orifice for the new type of gas supply (see table 12). Make sure not to damage the O-rings. z Re-assemble all parts in reverse order of disassembly. z Carry out the start-up activities and complete a new start- up report. z Also check all joints and gaskets affected by the installa- tion activities while carrying out the tightness test in oper- ating conditions. z Place a new sticker underneath the existing rating plate sticker indicating the type of gas supply installed. Fill out the required information on the conversion label. z Fit the casing again. Boiler capacity Type of gas supply Gas orifice diameter in mm (inch) 24 kW Natural gas 4.45 (0.174) LPG P 3.35 (0.131) 30 kW Natural gas 4.45 (0.174) LPG P 3.35 (0.131) 45 kW Natural gas 5.40 (0.213) LPG P 4.05 (0.158) 60 kW Natural gas 7.50 (0.293) LPG P 5.40 (0.213) Table 12 Gas orifice diameter Appendix15 54 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 Buderus • http://www.buderus.net We reserve the right to make any changes due to technical modifications! 15 Appendix 15.1 Operating messages z Press the "Service" e button a number of times to switch between the various status displays. * “- H” May also appear when the boiler is in frost protection mode. There has been a continuous DHW demand and CH request for more then one hour. The boiler then switches to CH mode. The operating code flashing in the display after the service button is pressed is A01/ 818. To enable the DHW, restart the boiler. Display Meaning Normal mode [-/h/\|Boiler in space heating mode * [=/h/\|Boiler in DHW heating mode Normal mode [0/a/\|Burner interval circuit, burner will start automatically after 10 minutes [0/c/\|Burner is started [0/e/\|More capacity was delivered than required [0/h.\|Standby [0/l/\|Gas burner fitting is opened [0/u/\|Initializing/ pre purge [0/y/\|Flow temperature higher than set Test mode Boiler in flue gas test Manual mode Boiler in manual mode Reset [r/e/\|Reset (after holding the "Reset" c button for 5 seconds, the heating system is returned to its switch-on condition) Table 13 Normal operating messages =/- 0 - Dot displayed in right- hand bottom corner [-/a.\| - Blinking dot in right- hand bottom corner [-/h.} Appendix 15 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 55 We reserve the right to make any changes due to technical modifications! Buderus • http://www.buderus.net 15.2 Error messages z Press the "Service" e button to display the service code (e. g. "3A"). z Press the "Service" e button to display the error code (e. g. "207"). The error message is a combination of the service code (e. g. "3A") and the error code (e. g. "207"). You can only resolve the error message using the Service chapter in this manual. INSTRUCTION FOR INSTALLERS The display may also show system faults (e. g. "A11"). In principle, they are identified by the initial letter "A" and they refer to faults between the boiler and the additionally available elec- tronic components. Display Meaning 6 Flame monitoring A 227 No ionization message after ignition. C 228 306 Ionization measured before burner start. L306The flame went out during the heating phase. P 229 Hot-surface ignitor on for too long. 7 Grid voltage C 231 The grid power was interrupted after an error. L261 280 UBA fault. 8 External switching contact Y External switching contact, e. g. temperature safety switch for floor heating, has taken place. 9 System faults A235Communication fault between UBA and KIM. H 237 267 272 UBA fault. P 239 UBA fault. L 234 238 239 Faulty gas burner fitting cable connection. U233KIM out of order. Y Communication fault between BC10 basic controller and UBA. E System faults 1, A, C, F, H, L, Y Internal UBA fault. Display Meaning 2 Water flow / water pressure E207System pressure too low < 3 psi (0.2 bar). F271Temperature difference between safety and supply sensors too much or no temperature increase after starting the burner. L266Test of pump operation via a pressure increase in the heating system (during pump start). P Temperature increase of safety sensor or supply sensor too high. U Temperature difference between supply and return sensor too much. Y Pump feedback fault. 3 Fan speed A264Fan unit failed during operation. F273Continuous 24 hour operation. L214Fan shut down during security test. P216Fan unit is running too slowly. Y215Fan unit is running too fast. 4 Temperatures A218Supply sensor over 220 °F (105 °C). E278Sensor test failed L220Safety sensor affected by short circuit or higher than 266 °F (130 °C). P 221 Loose contact or defective safety sensor. U 222 Supply sensor affected by short circuit. Y 223 Loose contact or faulty supply sensor. Appendix15 56 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 Buderus • http://www.buderus.net We reserve the right to make any changes due to technical modifications! 15.3 Technical specifications General specifications Unit boiler cap. 24 kW boiler cap. 30 kW boiler cap. 45 kW boiler cap. 60 kW Gas category Natural gas Natural gas Natural gas Natural gas Rated thermal load for Natural gas btu/hr 25,700 – 84,800 31,800 – 106,000 46,000 – 149,000 66,000 – 214,800 Rated heating capacity for heating curve 176/140 °F (80 – 60 °C) btu/hr 22,700 – 75,200 28,100 – 91,500 40,600 – 131,500 58,200 – 189,800 Rated heating capacity for heating curve 122/86 °F btu/hr 25,300 – 83,300 30,700 – 102,400 45,100 – 146,300 64.800 – 211,600 Boiler efficiency rating max. capacity for heating curve 176/140 °F (80 – 60 °C) %88888888 Boiler efficiency rating max. capacity for heating curve 122/86 °F (50 – 30 °C) %97979797 CSA output btu/hr 76,300 95,400 144,800 178,900 Heating Max. flow temperature °F (°C) 194 (90) 194 (90) 194 (90) 194 (90) Heater water temperature °F (°C) 86 – 190 (30 – 90), can be set on BC10 basic controller 86 – 190 (30 – 90), can be set on BC10 basic con- troller 86 – 190 (30 – 90), can be set on BC10 basic controller 86 – 190 (30 – 90), can be set on BC10 basic controller Max. operating overpressure of boiler psi (bar) 43.5 (3) 43.5 (3) 58 (4) 58 (4) Heat exchanger heating circuit volume gallons (l) 0.7 (2.5) 0.7 (2.5) 1.0 (3.6) 1.3 (4.7) Pipe connections Gas connection inch ¾” NPT ¾” NPT ¾” NPT ¾” NPT Heating system water connection inch (mm) 1.0” NPT (25.4) 1.0” NPT (25.4) 1.0” NPT (25.4) 1.0” NPT (25.4) Condensate water connection inch (mm) Ø 1.3” (Ø 32) Ø 1.3” (Ø 32) Ø 1.3” (Ø 32) Ø 1.3” (Ø 32) Flue gas values Condensate water quantity for natural gas G20, 104/86 °F (40/30 °C) gallons per hour 2.6 3.3 4.7 7.1 pH value condensate water pH approx. 4.1 approx. 4.1 approx. 4.1 approx. 4.1 Flue gas mass flow rate at full load g/s 10.0 12.6 19.4 25.9 Flue gas temperature 176/140 °F (80/60 °C), full load °F (°C) 150 (66) 167 (75) 150 (66) 150 (66) Flue gas temperature 176/140 °F (80/60 °C), partial load °F (°C) 135 (57) 137 (58) 135 (57) 135 (57) Flue gas temperature 122/86 °F (50/30 °C), full load °F (°C) 113 (45) 118 (48) 96 (36) 96 (36) Flue gas temperature 122/86 °F (50/30 °C), partial load °F (°C) 91 (33) 91 (33) 91 (33) 91 (33) CO2 content, full load, natural gas G20 % 9.2 9.2 9.3 9.3 CO2 content, full load, LPG G31, propane % 10.0 10.0 10.0 10.0 Standard emission factor CO mg/kWh ≤15 ≤15 1 ≤15 ≤15 Standard emissions factor NOx mg/kWh ≤20 ≤20 1 ≤20 ≤20 Free fan unit feed pressure inch W.C. (Pa) up to 0.023 (up to 60) up to 0.039 (up to 100) up to 0.054 (up to 140) up to 0.054 (up to 140) Flue gas connection Ø Flue system, dependent on the air in the room inch (mm) 3 (80) 3 (80) 3 (80) 3 (80) Ø Flue system, independent of the air in the room inch (mm) 3/3 (80/80) parallel 3/3 (80/80) parallel 3/3 (80/80) parallel 3/3 (80/80) parallel Electric data main voltage V, Hz 120, 60 120, 60 120, 60 120, 60 Fuses amps 5 amps 120V slow blow 5 amps 120V slow blow 5 amps 120V slow blow 5 amps 120V slow blow Electrical protection rating IP X4D IP X4D IP X4D IP X4D Electrical power consumption, at full load W 96 117 64 82 Electrical power consumption, at partial load W 22 22 20 22 Table 14 Technical specifications 1 If the heating capacity is limited to max. 80% (L80). (50 – 30 °C) Appendix 15 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 57 We reserve the right to make any changes due to technical modifications! Buderus • http://www.buderus.net z The gas orifice diameter is marked on the gas orifice (in mm). z The venturi article number is marked on both clips of the venturi (see fig. 51, pos. 1 and 2). Boiler dimensions and weight Height × Width × Depth inch (mm) 28 × 22 × 18.7 (712 x 560 x 475) 28 × 22 × 18.7 (712 x 560 x 475) 28 × 35.4 × 18.7 (712 x 900 x 475) 28 × 35.4 × 18.7 (712 x 900 x 475) Weight lbs (kg) 110 (50)110 (50) 143 (65) 158 (72) General specifications Unit boiler cap. 24 kW boiler cap. 30 kW boiler cap. 45 kW boiler cap. 60 kW Table 14 Technical specifications 1 If the heating capacity is limited to max. 80% (L80). Type of gas supply Factory pre-setting of the gas control valve Natural gas Delivered factory-set: Natural Gas LPG P Suitable for propane after conversion (also see the chapter "Conversion to another type of gas supply"). Information on gas type instruction plate: Set to gas category: Propane. Table 15 Factory setting of the gas control valve Fig. 51 Venturi article number 1 2 Thermal power gas boiler Type of gas supply Gas orifice diameter in mm (inch) Venturi article number GB142-24 Natural gas 4.45 (0.174)423.072A LPG P 3.35 (0.131)423.072A GB142-30 Natural gas 4.45 (0.174) 423.072A LPG P 3.35 (0.131) 423.072A GB142-45 Natural gas 5.40 (0.213)423.170A LPG P 4.05 (0.158)423.170A GB142-60 Natural gas 7.50 (0.293) 423.173A LPG P 5.40 (0.213) 423.173A Table 16 Gas orifice diameter Reports16 58 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 Buderus • http://www.buderus.net We reserve the right to make any changes due to technical modifications! 16 Reports 16.1 Start-up report Put your signature and the date at the bottom of the start-up report. Start-up activities Page Measured values Remarks 1. Fill the heating system and check that all connections are tight – Inlet pressure of expansion tank (observe the Installation Instructions for the expansion tank) – Pressurize the system – Fill the condensate trap 30 30 30 30 __________ psi __________ psi 2.Carry out a gas tightness test 30 3. Note down the gas characteristics: Wobbe index Operating heat value 30 __________ kWh/m³ __________ kWh/m³ 4.Convert the boiler to another type of gas supply (only if allowed)52 5. Vent the gas supply conduit 32 6.Check the combustion air/flue gas connection 32 7. Measure the gas connection pressure (flow pressure) 33 ________ inch W.C. 8.Check and adjust the gas/air ratio 34 ________ inch W.C. 9. Measure the carbon monoxide content (CO) 36 __________ ppm 10.Check and if necessary adjust the carbon monoxide content (CO2)__________ % 11. Measuring the ionization current 37 __________ µA 12.Make the necessary settings on the thermostat 39 13. Carry out function testing 36 14.Fitting the casing 38 15. Inform the owner; hand over the technical documents 38 Confirm proper start-up Company stamp/signature/date Reports 16 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 59 We reserve the right to make any changes due to technical modifications! Buderus • http://www.buderus.net 16.2 Inspection report z Please indicate the inspection activities that you have carried out and enter the values measured. Inspection activities page Date: ______Date: ______Date: ______ 1. Test the general condition of the heating system 2.Carry out a visual inspection and test the functions of the heating system 3. Test all gas and water conduits and fittings for: – their tightness during operation – visible corrosion – signs of aging – fill the condensate trap 48 47 32 4.Check the burner, the heat exchanger and the condensate trap for pollution. First shut down the heating system 49 5. Check the burner and the ignition and ionization electrodes. First shut down the heating system 49 6.Measure the ionization current 37 _______ µA _______ µA _______ µA 7. Measure the gas connection pressure (flow pressure) 33 _______ psi _______ psi _______ psi 8.Check the gas/air ratio 34 _____ inch W.C._____ inch W.C._____ inch W.C. 9. Carry out a gas tightness test in operating conditions 48 10.Measure the carbon monoxide content (CO)48 _______ ppm _______ ppm _______ ppm 11. Check the water pressure of the heating system – Inlet pressure of expansion tank (also see the Installation Instructions for the expansion tank) – Filling pressure 30 30 _______ _______ psi _______ psi 12.Check the operation and safety of the air intake and flue pipe 32 13. Check that the thermostat is set in line with the needs (see documents with thermostat) 39 14.Final check of inspection activities, note down the measurement and test results 15. Confirm proper inspection Company stamp/signature Company stamp/signature Company stamp/signature Reports16 60 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 Buderus • http://www.buderus.net We reserve the right to make any changes due to technical modifications! 16.3 Maintenance report z Sign for the maintenance activities that you have carried out and enter the date. Needs-dependent maintenance activities Page Date: _____________Date: _____________ 1. Clean the burner, the heat exchanger and the condensate trap. First shut down the heating system 49 2.Check and adjust the gas/air ratio CO2 content with full load CO2 content with partial load 34 _____________ inch W.C. _______________ % _______________ % _____________ inch W.C. _______________ % _______________ % 3. Confirm proper maintenance Company stamp/ Signature Company stamp/ Signature Spare parts 17 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 61 We reserve the right to make any changes due to technical modifications! Buderus • http://www.buderus.net 17 Spare parts Below is a list of the spare parts for this boiler. Look up the position number in the exploded view drawing on the next two pages for the illustration. Spare parts may be ordered from Buderus. Pos.Description Product No. 34 Air inlet pipe; 24/30 kW 7099024 Air inlet pipe; 45/60 kW 7099023 35 Seal Ø50 mm (5 pc) 7099058 36 Venturi 24/30 kW 7099020 Venturi 45 kW 7099925 Venturi 60 kW 7099931 37 Seal set (4 pc) 7099021 38 Fan 78184 39 Gas control valve 7099025 40 Gas supply pipe GB142 USA 76685 41 Spring (5 pc) 7100549 42 Seal 2x16x22 (5 pc) 7098778 43 Orifice Ø 4.45 24/30 kW 7099016 Orifice Ø 5.40 45 kW 76690 Orifice Ø 7.50 60 kW 76686 44 Condensate trap 75978 45 Seal condensate trap (5 pc) 7100742 47 Supply pipe CH; 24/30/45 kW 75990 Supply pipe CH; 60 kW 75991 48 Return pipe 24/30/45 kW 709965 Return pipe 60 kW 709945 49 Pressure sensor ** 7101436 50 Bottom plate 7099049 51 Transformer 120V 78191 52 Grommet 7099050 53 External connection board 7099042 54 External connection board cover 7099046 55 Fuse 5 AF slow blow 73904s 56 UBA cover 7099047 57 UBA3 - 120V 7099707 58 Drawer 7099043 59 Drawer front 7099037 60 Controller connection plate 78186 61 On/off switch 7099041 62 Controller cover 73698 63 Boiler ident. module 24 kW 78223 Boiler ident. module 30 kW 78224 Boiler ident. module 45 kW 78225 Boiler ident. module 60 kW 78226 64 Cable harness low voltage 78193 65 Cable harness high voltage 7099957 66 O-ring (10 pc) 38434s 67 Sealing bush (set) 7099002 68 Cable harness of on/off switch 7099072 69 Cable harness BX holder 7099070 70 Fuse holder 38345 71 Seal Ø60 mm (5 pc) 7098878 72 O-ring set orifice 7099018 73 Seal (5 pc) 7099059 74 Set screw M5x20 (5 pc) 7099065 ** not shown in exploded views Pos.Description Product No. 1 Casing 24/30 kW 7099988 Casing 45/60 kW 7099901 2 Casing latches left (2 pc) 7099039 3 Casing latches right (2 pc) 7099038 4 Casing seal 24/30 kW 7098752 Casing seal 45/60 kW 7098798 5 Wall mounting bracket 7098364 6 Back panel 24/30 kW 7099001 Back panel 45/60 kW 7099903 7 Cap air vent 7100250 8 Exhaust adapter 3” – 3” 28268 9 Seal ring Ø 3” 77470s 10 Seal ring Ø 80 mm 7096475 11 Flue gas collector 7098857 12 Oval seal 7098858 13 Heat exchanger 24/30 kW 7746900159 Heat exchanger 45 kW 7746900160 Heat exchanger 60 kW 7746900161 14 Heat exchanger baffle 24/30 kW 7098828 15 Seal condensate collector 24/30 kW 7098834 Seal condensate collector 45 kW 7098838 Seal condensate collector 60 kW 67900522 16 Condensate collector + sealing 24/30 kW 7098840 Condensate collector + sealing 45 kW 7098844 Condensate collector + sealing 60 kW 67900521 17 Clamp 7098848 18 Sensor NTC 7100136 19 Revision set air vent ** 7098822 20 Sight glass 7098575 21 Burner box 24/30 kW 7099057 Burner box 45 kW 7098875 Burner box 60 kW 67900525 22 Safety sensor 78194 23 Seal burner 24/30 kW 7098916 Seal burner 45 kW 7098920 Seal burner 60 kW 67900526 24 Gas/air distribution plate 24/30 kW 7100922 Gas/air distribution plate 45 kW 7098926 Gas/air distribution plate 60 kW 67900527 25 Orifice plate 24/30 kW 7100920 Orifice plate 60 kW 7746700120 26 Burner 24/30 kW 7099003 Burner 45 kW 7098932 Burner 60 kW 67900528 27 Gas-air inlet 7099004 28 Seal fan 7099023 29 Ionization electrode 78195 30 Hot surface ignitor 7099006 31 Shield hot surface ignitor 7100229 32 Mounting plate 7098852 33 Seal mounting plate (5 pc) 7098850 Spare parts17 62 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 Buderus • http://www.buderus.net We reserve the right to make any changes due to technical modifications! Pos.Description Product No. 75 Cap 24/30 kW 79105 76 Double nipple THR x COMPR 75977 77 Cabel saddle (10 pc) 7098810 78 Bolt M6x16 (2 pc) 7099078 79 Clip pressure sensor 7101370 80 Drainplug 7099364 81 Cap connection piece 38498 82 Clip (5 pc) 73651s 83 Centering ring (5 pc) 73480s 84 Coupling nut pump 73481s 85 Seal pump (10 pc) 15022s 86 Coupling nut pump 15020 87 Conversion set pump 73149 *** Conversion kit propane 24/30 kW 76687 *** Conversion kit propane 45 kW 76688 *** Conversion kit propane 60 kW 7746900156 Spare parts 17 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 63 We reserve the right to make any changes due to technical modifications! Buderus • http://www.buderus.net Exploded view Logamax plus GB142-24/30 1 2 3 4 3332 34 27 31 30 29 28 74 74 23 17 17 19 10 11 12 9 8 7 48 20 44 45 16 14 15 47 18 5 6 67 35 36 37 72 43 3973 40 41 42 58 50 5153 65 64 54 52 5662 57 60 61 59 63 1322 38 26 25 24 21 68 74 71 69 75 76 76 49 70 55 66 66 84 85 85 83 86 87 77 78 8281 79 80 Spare parts17 64 Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007 Buderus • http://www.buderus.net We reserve the right to make any changes due to technical modifications! Exploded view Logamax plus GB142-45/60 1 2 3 4 3332 34 27 31 30 29 28 74 74 23 24 25 26 17 17 19 10 11 12 9 8 7 48 20 44 45 16 14 15 47 18 5 6 67 67 35 36 37 72 43 39 73 40 41 42 58 50 57 63 60 61 59 56 54 51 64 52 53 65 13 22 38 69 62 68 74 2171 49 55 70 66 83 66 84 85 85 86 87 82 80 81 79 78 77 Installation Instructions Logamax plus GB142-24/30/45/60 • version 10/2007 65 We reserve the right to make any changes due to technical modifications! Buderus • http://www.buderus.net Index 18 18 Index B Baffle plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50 BC10 basic controller . . . . . . . . . . . . . . . . . . . . . .8, 39 Burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49 C Carbon monoxide content . . . . . . . . . . . . . . . . . . . . .36 Casing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13 CO values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36 Combustion air/flue gas connection . . . . . . . . . . . . .32 Condensate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26 Condensate trap . . . . . . . . . . . . . . . . . . . . . . . . .49, 51 Condensate water drain . . . . . . . . . . . . . . . . . . . . . .26 Connection 120 volts . . . . . . . . . . . . . . . . . . . . . . . .28 Connections (for gas, flue gas and water) . . . . . .9, 10 D DHW recirculating pump . . . . . . . . . . . . . . . . . . . . . .27 DHW tank pump . . . . . . . . . . . . . . . . . . . . . . . . . . . .27 DHW temperature . . . . . . . . . . . . . . . . . . . . . . . . . . .27 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9, 10 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 E Emergency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46 Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55 F Fan unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55 Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40 Flue gas test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42 Frost . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12, 46 Function testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36 G Gas leak tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31 Gas nozzles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33 Gas supply conduit . . . . . . . . . . . . . . . . . . . . . . . . . .32 Gas supply pressure . . . . . . . . . . . . . . . . . . . . . . . . .33 Gas/air distributor plate . . . . . . . . . . . . . . . . . . . . . . .50 Gas/air ratio . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34 H Heat exchanger . . . . . . . . . . . . . . . . . . . . . . . . . .49, 56 Heating system water . . . . . . . . . . . . . . . . . . . . . . . .46 Hot-water target value . . . . . . . . . . . . . . . . . . . . . . . .44 I Inspection report . . . . . . . . . . . . . . . . . . . . . . . . . . . .59 Installation room . . . . . . . . . . . . . . . . . . . . . . . . . . . .12 Internal leak testing . . . . . . . . . . . . . . . . . . . . . . . . . .48 Ionization current . . . . . . . . . . . . . . . . . . . . . . . . . . . .37 Items supplied with unit . . . . . . . . . . . . . . . . . . . . . . .11 M Mains connection . . . . . . . . . . . . . . . . . . . . . . . . . . . .27 Maintenance report . . . . . . . . . . . . . . . . . . . . . . . . . .60 Manual mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42 O Operating messages . . . . . . . . . . . . . . . . . . . . . . . . .54 Orifice plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50 Outdoor-temperature sensor . . . . . . . . . . . . . . . . . . .27 P Part-load operation . . . . . . . . . . . . . . . . . . . . . . . . . .42 Primary loop pump . . . . . . . . . . . . . . . . . . . . . . . . . .27 Pump slowing-down period . . . . . . . . . . . . . . . . . . . .45 R Resetting the burner . . . . . . . . . . . . . . . . . . . . . 39, 40 S Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 Service codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55 Signs of corrosion . . . . . . . . . . . . . . . . . . . . . . . . . . .47 Space heating water temperature . . . . . . . . . . . . . . .44 Start-up report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58 Switching contact, external . . . . . . . . . . . . . . . . . . . .27 Switching on the heating system . . . . . . . . . . . . . . . .39 T Technical specifications . . . . . . . . . . . . . . . . . . . . . . .56 Tightness test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36 Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 Transportation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11 V Venturi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57 Notes 66 Installation Instructions Logamax plus GB142-24/30/45/60 • version 10/2007 Buderus • http://www.buderus.net We reserve the right to make any changes due to technical modifications! Notes Installation Instructions Logamax plus GB142-24/30/45/60 • version 10/2007 67 We reserve the right to make any changes due to technical modifications! Buderus • http://www.buderus.net 50 Wentworth Avenue Londonderry, NH 03053 Tel: 603-552-1Ɣ)D[ www.buderus.net Bosch Thermotechnology Corporation reserves the right to make changes without notice due to continuing engineering and technological advances. Heating Contractor: PRODUCTS MANU)ACTURED BY BBT Thermotechnik GmbH 35573 WHW]ODU www.buderus.de Bosch Thermotechnology Corp.721.502A – 4848 – 10/2007