HomeMy WebLinkAboutE603A.1B.pdfT R A N S F O R M E R S C H E D U L E KEY (6) HV FLA LV FLA HV PROT (1) HIGH VOLTAGE FEEDER (3) LV PROT (2) LOW VOLTAGE FEEDER (3) GROUNDING (4) DIMENSIONS (5) WEIGHT BTUH NOTE 480 V 208 V CCT BRKR CONDUCTORS "C CCT BRKR CONDUCTORS "C CNDTRS "C HIGH WIDE DEEP (5) OTPT (5) T30 36.1 83.3 45 A 3 P 3 # 6 , 1 # 10 G 1 100 A 3 P 4 # 1 , 1 # 8 G 1-1/2 1 # 6 3/4 30.00 20.13 16.00 370 5753 NOTES: 1.) PRIMARY O.C. PROTECTION PER NEC 450.3. 2.) SECONDARY O.C. PROTECTION PER NEC 450.3. 3.) ALL CONDUCTORS ARE COPPER. SEE PLANS FOR INCREASED CONDUCTOR SIZES DUE TO VOLTAGE DROP ETC. 4.) BONDING AND GROUNDING CONDUCTOR PER NEC 250.66. 5.) DIMENSIONS, WEIGHTS & BTUH OUTPUT SHOWN ARE FOR REFERENCE ONLY. ACTUAL DIMENSIONS MAY VARY FROM MANUFACTURER TO MANUFACTURER. 6.) BRANCH CIRCUITS TO HAVE A DEDICATED NEUTRAL FOR EACH CIRCUIT ON K-RATED TRANSFORMERS. 7.) FOR K-RATED TRANSFORMERS, PROVIDE PARALLEL NEUTRAL CONDUCTORS LUGS AT TRANSFORMERS, LOW VOLTAGE PANELBOARD, DISCONNECTS AND/OR LOAD . 8.) CONDUIT 40% FILL RATIO BASED ON EMT. 181 WEST MEADOW DRIVE VAIL, CO HII-1302604 This document is the property of Heery International, Inc. and Heery International Inc. retains all rights therein, including copyrights. It may only be used in a manner consistent with Heery International Inc.'s rights while Heery International, Inc. is providing services for the specific project identified or referred to herein or extensions thereto. It may not be used for any other purpose except with the express written agreement of, and compensation to, Heery International Inc. Copyright © 2013 by Heery International, Inc. all rights reserved. WHEN PLOTTED AT FULL SIZE THIS SHEET MEASURES 30"x42" drawn by checked by consultants/construction managers owner's project number project number Heery International 555 17th Street, Suite 500 Denver, CO 80202 720.946.0276 sheet number sheet title item date date issued for seal/signature MEP: CATOR RUMA & ASSOCIATES, CO. 896 TABOR STREET LAKEWOOD, CO 80401-4700 303.232.6200 INTERIORS: GALLUN-SNOW 1920 MARKET STREET, SUITE 201 DENVER, CO 80202 303.433.9600 TEMPORARY ICU ROOMS 218 & 219 100% CONSTRUCTION DOCUMENTS 07/08/2015 E603A.1B ELECTRICAL EMERGENCY ONE-LINE DIAGRAM NCW NCW 07/31/15