AIR DEVICE SCHEDULE DESIG. MFR. TYPE MODEL FRAME MATERIAL FINISH DAMPER REMARKS TYPE A TITUS CEILING SUPPLY TDV NOTE 4 STEEL WHITE NONE 1 B TITUS CEILING EXHAUST/RETURN PAR NOTE 4 STEEL/ALUMIN UM WHITE NONE 1, 2 REMARKS: 1. PROVIDE MODULE SIZE TO FIT CEILING TYPE; SEE PLANS FOR NECK SIZES. 2. PROVIDE ALUMINUM MATERIALS FOR ALL WET AREAS. 3. PROVIDE WITH HEPA FILTER. 4. COORDINATE WITH ARCHITECTURAL PLANS FOR LAY-IN VS SURFACE MOUNT FRAMES. 5. PROVIDE WITH 1.5 HR FIRE DAMPER EQUAL TO RUSKIN DFD35GA UTILIZING DAMPER ACCESS VIA GRILLE. COORDINATE WITH ARCHITECTURAL PLANS. 6. CAREFULLY COORDINATE FIRE DAMPER WITH DIFFUSER/GRILLE FOR FIT. ############ FINTUBE RADIATION SCHEDULE BTUH/LF GPM/ ELEMENT ENCLOSURE DESIG. MFR. MODEL NO. LF LF PIPE SIZE FIN SIZE FINS/ HEIGHT DEPTH DAMPER REMARKS ROWS ELEMENT ELEMENT MATERIAL MATERIAL FT (IN.) (IN.) REQUIRED FTR-1 STERLING RADIATOR JVA-S14 1 630 .063 3/4" C.U. 3-1/4" SQ 50 18 4-3/8 NO 1. HEATING CAPACITY BASED ON 170°F AWT, 65°F EAT. 2. APPROXIMATELY 10' INSTALLED LENGTH. COORIDINATE WITH FIELD CONDITIONS TO EXTEND WALL TO WALL. 3. HEATING WATER SYSTEM CONTAINS 40% PROPYLENE GLYCOL MIXTURE. SELECT AT ELEVATION OF 8150 FT. 7/1/2015 15:10 PIPING DETAIL FINTUBE RADIATION CLEANOUT DETAIL DUCT TAKE-OFF DETAIL DUCT PASSING UNDER BEAM PIPING DETAIL THERMOSTATIC MIXING VALVE TERMINAL BOX SCHEDULE (HOT WATER HEAT) INTERIOR AIR PRESSCOOLING DESIGN CFM HEATING HEATING WATER COIL DATA MODULATING DESIG OR MFR MODEL INLET DROP MAX MAXIMUM MINIMUMDESIGN CFMEAT LAT MBH GPM WATER EWT CONTROL REMARKS PERIMETER DIA. (IN WC) ELEV FT ELEV FT ELEV FT °F °F P.D. MAX °F VALVE TYPE ZONE (IN.) (SEA LEVEL) 8150 8150 8150 (FT WC) 201 PERIMETER PRICE SDV 8 8 0.64 380 380 230 55 90 7.1 0.6 3.00 180 2-WAY ALL 202 PERIMETER PRICE SDV 8 8 0.64 230 230 230 55 90 7.1 0.6 3.00 180 2-WAY ALL REQUIREMENTS APPLYING TO ALL TERMINAL BOXES: 610 610 1.2 A. PROVIDE BOX SELECTION TO MEET LAT, DESIGN CFM AND HEATING MBH. FINAL GPM SHALL BE SET DURING BALANCING TO FLOW RATES IN LISTED PRODUCT DATA SUBMITTALS. B. MAXIMUM STATIC PRESSURE IS BASED ON WIDE OPEN UNIT AT MAXIMUM FLOW FOR TERMINAL BOX WITH 2-ROW COIL. C. HEATING WATER SYSTEM CONTAINS 40% PROPYLENE GLYCOL. D. 2-ROW HEATING COIL CONDITIONS SHOWN AND PREFERED. 1-ROW COIL NOT ACCEPTABLE. E. USE OF 3- & 4-ROW COILS MUST BE SPECIFICALLY IDENTIFIED BY THE SUPPLIER & ACCEPTED BY THE ENGINEER FOR EACH LOCATION PROPOSED. F. TERMINAL BOX MAXIMUM AIR FLOW CAPABILITIES: 6"=450 CFM, 8"=800 CFM, 9"=1050 CFM, 10"=1350 CFM, 12"=2000 CFM, 14"=3000 CFM, 16"=4000 CFM & 24"x16"=8000 CFM. G. MINIMUM 2-ROW COILS REQUIRED ON ALL PERIMETER BOXES. REMARKS: 1. VAV BOXES ARE TO BE INSTALLED FOR FUTURE VARIABLE AIRFLOW CONDITION. LOCK TERMINAL BOX OPEN AND DISABLE VOLUME DAMPER AS THE SYSTEM IS CONSTANT VOLUME AT THIS TIME. INSTALL CONTROL WIRING REQUIRED FOR FUTURE VARIABLE AIR VOLUME CONTROL. 7/1/2015 P:\VVMC\2014-015 West Wing Expansion & Renovation\Cad\ICU Rooms Level 2\Cad\Mech\Mschedules\[M-2014-015.A.1B.xlsx]S933-2 Term Box HW DUCT PRESSURE CLASSIFICATION SCHEDULE DUCT TYPE PRESSURE CLASS REMARKS SUPPLY DUCT AIR SERVING CATH LAB 4" LOW PRESSURE SUPPLY AIR DUCT 2" ALL RETURN, EXHAUST, OUTSIDE AIR ETC. 2" 7/1/2015 15:10 PLUMBING FIXTURE & EQUIPMENT SCHEDULE ELECTRICAL FIXTURE FITTINGS ACCESSORY LEED CONNECTIONS SYMBOL REQUIREMENTS FIXTURE NAME MANUFACTURER MODEL TYPE SIZE MANUFACTURER MODEL SUPPLY I.R. / BATTERY GPM WASTE VENT CW HW REMARKS HP OR GPF L-1 LAVATORY AMERICAN STANDARD OVALYN 0495.221 UNDERCOUNTER, VITREOUS CHINA 17-1/8" X 14-1/8" T & S, BRASS B-0892-01 W/ B-0199-21 RE: SPEC 2" 1 1/2" 1/2" 1/2" RE: ARCH. DWGS FOR MTG. HT. & LOC. 1. REFER TO GENERAL SPECIFICATIONS FOR WATER CLOSETS, URINALS, LAVATORIES, SINKS AND MISC. FIXTURE REQUIREMENTS. 2. GRAB BARS BY ARCHITECT. 3. THIS SCHEDULE INCLUDES ITEMS THAT MAY NOT BE INCLUDED IN THE DRAWING DOCUMENTS. S440-1 181 WEST MEADOW DRIVE VAIL, CO HII-1302604 This document is the property of Heery International, Inc. and Heery International Inc. retains all rights therein, including copyrights. It may only be used in a manner consistent with Heery International Inc.'s rights while Heery International, Inc. is providing services for the specific project identified or referred to herein or extensions thereto. It may not be used for any other purpose except with the express written agreement of, and compensation to, Heery International Inc. Copyright © 2013 by Heery International, Inc. all rights reserved. WHEN PLOTTED AT FULL SIZE THIS SHEET MEASURES 30"x42" drawn by checked by consultants/construction managers owner's project number project number Heery International 555 17th Street, Suite 500 Denver, CO 80202 720.946.0276 sheet number sheet title item date date issued for seal/signature MEP: CATOR RUMA & ASSOCIATES, CO. 896 TABOR STREET LAKEWOOD, CO 80401-4700 303.232.6200 INTERIORS: GALLUN-SNOW 1920 MARKET STREET, SUITE 201 DENVER, CO 80202 303.433.9600 TEMPORARY ICU ROOMS 218 & 219 100% CONSTRUCTION DOCUMENTS 07/08/2015 M701A.1B MECHANICAL SCHEDULES AND DETAILS JDD WAT 07/31/15