HomeMy WebLinkAboutload calc.pdf9/2/2015 Unit 504 load calc.htm
file:///H:/2015%20Fall%20Remodels/Unit%20504%20remodel/Town%20of%20Vail/Unit%20504%20load%20calc.htm 1/2
From: Nick Lunn [nicklunncec@yahoo.com]
Sent: Tuesday, September 01, 2015 4:16 PM
To: Dave Collins
Subject: Unit 504 load calc
Load calc for Antlers Unit 504
Optional Residential Load Calculation Results:
Multifamily Dwelling:
Dwelling Units:
Demand Factor: 100%
Step 1: General Lighting and Recepticles:
Total General Load @ 3VA: 7500 VA
Step 1 Total: 7500 VA
Step 2: AC System:
220.82(C)1 Total: 0
220.82(C)2 Total: 0
220.82(C)3 Total: 0
220.82(C)4 Total: 4680
220.82(C)5 Total: 0
220.82(C)6 Total: 0
Largest Load Per 220.82(C)
Step 2 Total: 4680 VA
Step 3: Fixed in Place Appliances:
Step 3 Total: 6200VA
Step 4: Dryers:
Step 4 Total: 3000 kW
Step 5: Cooking Appliances:
Step 5 Total: 5000 kW
General Load:
First 10k @ 100%: 10000
Remainder over 10k @ 40%: 4680
Total General Load: 14680
Final Totals:
Feeder Load: 19360 VA
Feeder Amperage: 80.666666666667 Amps
Neutral Load: 16300 VA
Neutral Amperage: 67.916666666667 Amps
Service Size:
9/2/2015 Unit 504 load calc.htm
file:///H:/2015%20Fall%20Remodels/Unit%20504%20remodel/Town%20of%20Vail/Unit%20504%20load%20calc.htm 2/2
100 Amps
Conductor Size:
Feeders per Table 310.15(B)7:
Copper: 4 AWG
Aluminum: 2 AWG
Neutral per Table 310.15(B)7:
Copper: 4 AWG
Aluminum: 2 AWG
Ground per Table 250.66:
Copper: 8 AWG
Aluminum: 6 AWG
It is highly recommended to double check the calculations before submitting them on any professional
level.
This calculation was generated with the ReiWare, LLC Service Load Calculation Tool Available on the
Apple App Store, Google Play and Amazon App Store.
Sent from my iPhone