HomeMy WebLinkAboutB15-0333 Balance Report.pdf TEST, ADJUST AND BALANCE REPORT
PROJECT
LAND TITLE OFFICE VAIL
#1183
PREPARED FOR
METAL DESIGN
REPORT ISSUE DATE
10/15/2015
PREPARED BY
HVAC TAB llc
P.O. BOX 1926
VAIL, CO 81658
PHONE: 970-376-5198
E-MAIL: mrichardson@hvactab.co
HVAC TAB llc
DATE: 10/13/2015
INSTRUMENT
CALIBRATION REPORT
PROJECT : LAND TITLE OFFICE VAIL PROJECT ALTITUDE: 22.7 “HG
INSTRUMENT/ SERIAL # APPLICATION DATE OF USE CALIBRATION DATE CALIBRATION DUE DATE
SHORTRIDGE ADM-870C / #M00483 AIR FLOW READINGS 10/13/2015 06/08/2015 06/08/2016
ANEMOMETER #T57251515001 AIR FLOW READINGS NOT USED 04/6/2015 04/6/2016
SHORTRIDGE FLOW HOOD AIF FLOW READINGS 10/13/2015 * *
TH-720 HYGROMETER/ #TH7200950003 AIR TEMP / HUMIDITY NOT USED 06/03/2015 06/03/2016
PITOT TUBE 18” PRES. READINGS NOT USED N/A N/A
PITOT TUBE 24” PRES. READINGS NOT USED N/A N/A
PITOT TUBE 36” PRES. READINGS NOT USED N/A N/A
PITOT TUBE 48” PRES. READINGS NOT USED NA NA
SHIMPO TACHOMETER / #C105B0010 RPM READINGS NOT USED 06/03/2015 06/03/2016
FLUKE 375 / #21290229 VOLT / AMP NOT USED 06/03/2015 06/03/2016
SHORTRIDGE HDM-250/ #W11037 WATER PRES. READINGS NOT USED 06/08/2015 06/08/2016
ASCROFT / 0-100 PSI / #DO68332-06 WATER PRES. READINGS NOT USED * *
FLUKE 52 II THERMOMETER / 99780167 TEMP. READINGS NOT USED 06/11/2015 06/11/2016
REFRACTOMETER RHA-100 / #RHA-
100
GLYCOL % READINGS NOT USED N/A N/A
* CHECKED TO CALIBRATED METER
REMARKS: ALL READINGS WITH SHORTRIDGE INSTRUMENTS ARE CORRECTED FOR TEMPERATURE AND ALTITUDE. PAGE:
SYSTEM TERMINAL DESIGN INITIAL FINAL NOTES
NO TYPE SIZE AK VEL CFM VEL CFM VEL CFM
FC-7 1 CD 24/24 145 139 131
2 CD 24/24 145 162 127
3 CD 24/24 150 152 132
4 CD 24/24 150 136 126
5 CD 24/24 200 158 156
6 CD 24/24 200 151 155
7 CD 24/24 200 155 161
8 CD 24/24 75 107 61
9 CD 24/24 60 42 51
10 CD 24/24 180 64 91 DUCT PINCHED
11 CD 24/24 280 167 206 DUCT PINCHED
1785 1433 1397 TOTAL
78%
NOTES:
HVAC TAB llc
DATE: 10/13/2015
AIR TERMINAL
TEST REPORT
PAGE:
PROJECT: LAND TITLE OFFICE SYSTEM: FC-7