Loading...
HomeMy WebLinkAboutB15-0333 Balance Report.pdf TEST, ADJUST AND BALANCE REPORT PROJECT LAND TITLE OFFICE VAIL #1183 PREPARED FOR METAL DESIGN REPORT ISSUE DATE 10/15/2015 PREPARED BY HVAC TAB llc P.O. BOX 1926 VAIL, CO 81658 PHONE: 970-376-5198 E-MAIL: mrichardson@hvactab.co HVAC TAB llc DATE: 10/13/2015 INSTRUMENT CALIBRATION REPORT PROJECT : LAND TITLE OFFICE VAIL PROJECT ALTITUDE: 22.7 “HG INSTRUMENT/ SERIAL # APPLICATION DATE OF USE CALIBRATION DATE CALIBRATION DUE DATE SHORTRIDGE ADM-870C / #M00483 AIR FLOW READINGS 10/13/2015 06/08/2015 06/08/2016 ANEMOMETER #T57251515001 AIR FLOW READINGS NOT USED 04/6/2015 04/6/2016 SHORTRIDGE FLOW HOOD AIF FLOW READINGS 10/13/2015 * * TH-720 HYGROMETER/ #TH7200950003 AIR TEMP / HUMIDITY NOT USED 06/03/2015 06/03/2016 PITOT TUBE 18” PRES. READINGS NOT USED N/A N/A PITOT TUBE 24” PRES. READINGS NOT USED N/A N/A PITOT TUBE 36” PRES. READINGS NOT USED N/A N/A PITOT TUBE 48” PRES. READINGS NOT USED NA NA SHIMPO TACHOMETER / #C105B0010 RPM READINGS NOT USED 06/03/2015 06/03/2016 FLUKE 375 / #21290229 VOLT / AMP NOT USED 06/03/2015 06/03/2016 SHORTRIDGE HDM-250/ #W11037 WATER PRES. READINGS NOT USED 06/08/2015 06/08/2016 ASCROFT / 0-100 PSI / #DO68332-06 WATER PRES. READINGS NOT USED * * FLUKE 52 II THERMOMETER / 99780167 TEMP. READINGS NOT USED 06/11/2015 06/11/2016 REFRACTOMETER RHA-100 / #RHA- 100 GLYCOL % READINGS NOT USED N/A N/A * CHECKED TO CALIBRATED METER REMARKS: ALL READINGS WITH SHORTRIDGE INSTRUMENTS ARE CORRECTED FOR TEMPERATURE AND ALTITUDE. PAGE: SYSTEM TERMINAL DESIGN INITIAL FINAL NOTES NO TYPE SIZE AK VEL CFM VEL CFM VEL CFM FC-7 1 CD 24/24 145 139 131 2 CD 24/24 145 162 127 3 CD 24/24 150 152 132 4 CD 24/24 150 136 126 5 CD 24/24 200 158 156 6 CD 24/24 200 151 155 7 CD 24/24 200 155 161 8 CD 24/24 75 107 61 9 CD 24/24 60 42 51 10 CD 24/24 180 64 91 DUCT PINCHED 11 CD 24/24 280 167 206 DUCT PINCHED 1785 1433 1397 TOTAL 78% NOTES: HVAC TAB llc DATE: 10/13/2015 AIR TERMINAL TEST REPORT PAGE: PROJECT: LAND TITLE OFFICE SYSTEM: FC-7