HomeMy WebLinkAboutM1.1.pdfEDB (°F) LDB (°F) EWT (°F) LWT (°F) GPM PD (FT) (E)FC-6 MAGIC AIRE DHW-1000 OFFICES, 2ND FLOOR 1,200 150 0.3 0.33 22.4 80.0 61.1 45.0 54.7 6.0 7.4 200 (E)FC-7 MAGIC AIRE DHW-1000 OFFICES, 2ND FLOOR 1,185 150 0.3 0.33 22.4 80.0 61.1 45.0 54.7 6.0 7.4 200 (E)FC-8 MAGIC AIRE DHW-1000 OFFICES, 2ND FLOOR 1,100 150 0.3 0.33 22.4 80.0 61.1 45.0 54.7 6.0 7.4 200 ESP (IN) HP WATER SIDE V / PH / Hz EXISTING FAN COIL UNIT SCHEDULE - FOR REFERENCE ONLY ELECTRICAL DATA OPER. WT. (LBS) REMARKS UNIT TAG MANUFACTURER & MODEL NO. SERVICE TOTAL CFM O.A. CFM 115/1/60 FACTORY WIRED AIR PROVING SWITCH 115/1/60 FACTORY WIRED AIR PROVING SWITCH. PROVIDE CONDENSATE PUMP. COOLING COIL DATA TOTAL MBH SENSIBLE AIR SIDE 115/1/60 FACTORY WIRED AIR PROVING SWITCH. PROVIDE CONDENSATE PUMP. KW AMPS V PH HZ (E)EDH-1 WARREN TECHNOLOGIES - CBK FC-6 DUCT MOUNTED 4 1 72.0 84.6 4.0 11 208 3 60 PROVIDE DISCHARGE-AIR SENSOR (E)EDH-2 WARREN TECHNOLOGIES - CBK FC-7 DUCT MOUNTED 4 1 72.0 84.6 4.0 11.1 208 3 60 PROVIDE DISCHARGE-AIR SENSOR (E)EDH-3 WARREN TECHNOLOGIES - CBK FC-8 DUCT MOUNTED 4 1 72.0 84.6 4.0 11.1 208 3 60 PROVIDE DISCHARGE-AIR SENSOR SERVICE LOCATION # OF STAGES ELECTRICAL DATA EAT (°F) LAT (°F) EXISTING ELECTRIC DUCT HEATER SCHEDULE - FOR REFERENCE ONLY REMARKS UNIT TAG MANUFACTURER & MODEL NO. CAPACITY (KW) W (E)EF-1 COOK GC-420 EQUIP. ROOM EEF PRODUCTIONS IN-LINE 250 1,145 0.25 170 3.4 30 INTERLOCK WITH WALL-MOUNTED THERMOSTAT (E)EF-2 COOK GC-142 PANTRY EEF PRODUCTIONS IN-LINE 80 1,000 0.25 59 1.9 15 INTERLOCK WITH WALL-MOUNTED ON/OFF SWITCH 115/1/60 SERVICE REMARKS NOISE LEVEL (SONES) OPER. WT. (LBS) TYPE 115/1/60 EXISTING EXHAUST FAN SCHEDULE - FOR REFERENCE ONLY TOTAL CFM FAN RPM ESP (IN) ELECTRICAL DATA UNIT TAG MANUFACTURER & MODEL NO. V / PH / Hz LOCATION UNIT TAG MANUFACTURER & MODEL NO. SERVICE LOCATION CFM SIZE (L"xW"xT") FACE VELOCITY (FPM) PRESSURE DROP (IN SP) % FREE AREA FRAME TYPE FINISH REMARKS (E)L-1 RUSKIN - ELF6375DX FC EEF EAST SIDE WALL 300 18X12 612 0.055 0.5 STANDARD MATCH FINISH MATCH ARCHITECTURAL SOFFIT FINISH EXISTING LOUVER SCHEDULE - FOR REFERENCE ONLY UNIT TAG MANUFACTURER & MODEL NO. USE FINISH INLET SIZE (IN) STYLE FRAME TYPE MOUNTING TYPE MAX SOUND LVL (NC) REMARKS A TITUS-TMS 24X24 SUPPLY WHITE VARIES LAY IN 3 CEILING 25 FOR DIMENSIONS AND CFM SEE FLOOR PLAN, VERIFY IN FIELD WHICH DIFFUSERS CAN BE REUSED PRIOR TO ORDERING B TITUS - PAR 24X24 RETURN WHITE VARIES LAY IN 3 CEILING 25 FOR DIMENSIONS AND CFM SEE FLOOR PLAN, VERIFY IN FIELD WHICH DIFFUSERS CAN BE REUSED PRIOR TO ORDERING E TITUS-TMS 24X24 (EXISTING) SUPPLY WHITE VARIES LAY IN 3 CEILING 25 FOR DIMENSIONS AND CFM SEE FLOOR PLAN, VERIFY IN FIELD WHICH DIFFUSERS CAN BE REUSED PRIOR TO ORDERING E TITUS - PAR 24X24 (EXISTING) RETURN WHITE VARIES LAY IN 3 CEILING 25 FOR DIMENSIONS AND CFM SEE FLOOR PLAN, VERIFY IN FIELD WHICH DIFFUSERS CAN BE REUSED PRIOR TO ORDERING E TITUS - 25RL (EXISTING) XFER/RELIEF WHITE VARIES SURFACE MOUNT 3 CEILING 25 FOR DIMENSIONS AND CFM SEE FLOOR PLAN AIR DEVICE SCHEDULE 09/28/15