HomeMy WebLinkAboutE002.pdf1
1
1 1
LIGHTING FIXTURE SCHEDULE
PREPARED BY KAZIN & ASSOCIATES
DESCRIPTION OF LUMINAIRE LUMINAIRE SPECIFICATION
ID DESCRIPTION FINISH MOUNTING
INFO
MANUFACTURER CATALOG NUMBER LAMP(S) VOLTAGE
A LED LINEAR PROFILE PER TENANT RECESSED ON-LIGHT KOOLED-UH #17-30-90-FL-1-AN LED: 7.5W/FOOT 120
B LED TRACK HEAD PER TENANT TRACK ON-LIGHT MICRO ON GLOBAL TRAC
MICRO--26-30-84-NFL-GLO-1-3
33W LED 120
T 3-CIRCUIT TRACK PER TENANT SURFACE GLOBAL TRAC GLOBAL TRAC N/A 120
C 4' FLUORESCENT STRIP WHITE SURFACE COLUMBIA OR
EQUAL
CS4-128T5-EBU-CSWG4 (1) F28T5 120
E1
SURFACE MOUNTED OR
SUSPENDED WET LOCATION
DIFFUSER LUMINAIRE
PER TENANT SURFACE OR
PENDANT
ON-LIGHT TUBIS LED 144L-4-PO-1-WB-SSC 44W LED 120
E2
SURFACE MOUNTED OR
SUSPENDED WET LOCATION
DIFFUSER LUMINAIRE
PER TENANT SURFACE OR
PENDANT
ON-LIGHT TUBIS LED 155L-5-PO-1-WB-SSC 55W LED 120
NOTES:
1. PROVIDED HANGERS, ADAPTERS, INSTALLATION KITS, PARTS AND PIECES TO INSTALL THE SPECIFIED FIXTURE IN THE LOCATIONS SHOWN ON THE PLAN.
1
LIGHTING RELAY PANEL (LRP1)
RELAY FED
FROM
CIRCUIT
NUMBER
LOAD
(VA)
LOCATION LOCAL
CONTROL
CONTROL DESCRIPTION
1 NE8 2 600
RETAIL - LED LINEAR
PROFILE
PUSHBUTTON
MANUAL SWITCH ON, TIME SWITCH OFF,
MANUAL SWITCH OVERRIDE
2 NE8 4 1683 RETAIL - TRACK
PUSHBUTTON
MANUAL SWITCH ON, TIME SWITCH OFF,
MANUAL SWITCH OVERRIDE
3 NE8 6 1200 SIGN
4
1
LIGHTING CONTROL PANEL WITH INTEGRAL
CLOCK. REFERENCE ELECTRICAL
SPECIFICATIONS AND RELAY SCHEDULE
FOR ADDITIONAL REQUIREMENTS.
DIGITAL SWITCH - REFERENCE
LIGHTING PLAN FOR QUANTITY,
LOCATIONS AND NUMBER OF
BUTTONS PER SWITCH.
INCOMING CIRCUIT
PER RELAY SCHEDULE
SWITCHED CIRCUIT
OUT TO LOAD PER
RELAY SCHEDULE
REFERENCE RELAY
SCHEDULE FOR
QUANTITY OF RELAYS
2
LIGHTING RELAY PANEL CONCEPTUAL ONE-LINE DIAGRAM
NOT TO SCALE
1
PANEL
NE8
MDC-L1
3,000A
<9 :
35,000AIC
MBE4
METER CENTER
800A
<9 :
35,000AIC MIN
7[4-500kcmil CU] (2500A)
2[4-500kcmil CU, 1 #1/0 CU G] (760A)
(4 #1/0, 1 #6G)2"C (150A)
1
PARTIAL ONE-LINE DIAGRAM
NOT TO SCALE
NOTES:
1. EQUIPMENT, WIRING, AND DEVICES SHOWN LIGHT ARE EXISTING
AND SHOWN DARK ARE NEW UNLESS OTHERWISE NOTED.
2. NEW WIRING SHALL BE THHN/THWN-2 INSULATED COPPER
UNLESS OTHERWISE NOTED.
FAULT CURRENT CALCULATIONS (END OF CONDUCTOR)
LOCATION DESCRIPTION
(@ ISC END)
STARTING ISC
MINIMUM
CONDUCTOR
LENGTH
PHASE
MULTIPLIER
VOLTAGE
# OF
CONDUCTOR
SETS
C VALUE ISC END
@ PANEL NE8 37,664 125 1.73 208 1 8,295 6,584
ISC = 37,664 PER ORIGINAL
ELECTRICAL DRAWINGS
800A METER CENTER LOAD
SUMMARY
LOAD DESCRIPTION LOAD
72.9kVA
PANEL NE6 19.9kVA
PANEL NE8 22.9kVA
TOTAL LOAD 115.7kVA
TOTAL AMPERAGE @ 321A
VOLTAGE 208 PHASE 3
UTILITY COMPANY PAD
MOUNTED TRANSFORMER
<9 : 6(&21'$5<
1
NOT ISSUED FOR CONSTRUCTION UNLESS
SIGNED THROUGH THE SEAL IN BLUE INK OR
DIGITALLY SIGNED BY BRYAN KAZIN.
LIMITED TO ELECTRICAL.
36628
Scale
Project Number
Date
Drawn by
Checked by
The Arrabelle at Vail Square
Building "D" Level
Two
Retail
Vail, CO 81657
THIS BOX FOR TOV APPROVALS ONLY
AS NOTED
24515
Arrabelle Tenant Finish
Vail Resorts Retail
17 Sep 2015
BEK
BEK
No. Description Date
E002
10/21/15
1 Revisions
ONE-LINE &
SCHEDULES
1