HomeMy WebLinkAboutE300 DIAGRAMS.pdfSCALE:ELECTRICAL ONE-LINE DIAGRAMNONE800A120/240V, 1PHP2AL1A800A (3W)UTILITY METER ANDCT CABINET.TO UTILITY.UTILITY TRANSFORMER240/120V SECONDARY.(BY HOLY CROSS ENERGY)M1ANEMA 3R SERVICE800A DISCONNECT.100' MAX.PROVIDE PROVISIONS FOR FUTURESPD800A (3WG)200A (3WG)200A (3WG)200/2200/2100/2200/2200A (3WG)MGNNEMA 3RSPARE200/2200/2200/2PER NEC 250.52.GROUNDING ELECTRODECONDUCTORS SIZED PERN.E.C. TABLE 250.66.M2AP3A100A (3WG)T1A800A120/240V, 1PHMAIN FLOORP2BL1BM1BPROVIDE PROVISIONS FOR FUTURESPD200A (3WG)200A (3WG)200/2200/2100/2200/2200A (3WG)SECOND FLOORSPARE200/2200/2200/2M2BBASEMENTP3B100A (3WG)T1BUTILITY METER ANDCT CABINET.NEMA 3R SERVICE800A DISCONNECT.800A (3WG)MGNNEMA 3RPER NEC 250.52.GROUNDING ELECTRODECONDUCTORS SIZED PERN.E.C. TABLE 250.66.800A (3W)200/2200/2200A (3WG)200A (3WG)MAIN FLOORSECOND FLOORBASEMENTP1B200A (3WG)SPAREP1ASPAREN.E.C. LOAD CALCULATION - RESIDENTIAL**Calculation typical for Unit A and Unit BLIGHTING & GENERAL RECEPTACLESAREA(ft²)VA / ft² LOAD6200 5=31000VASMALL APPLIANCES21500=3000VALAUNDRY CIRCUITS:11500=1500VASubtotal=35500VAFirst 3000VA @ 100%=3000VAFrom 3001 to 120,000VA=11375VAOver 120,000VA=0VATotal Lighting/Receptacle Load=14375VA X100%=14375VAAPPLIANCES:VENT HOOD1300VA =300VADISHWASHER11200VA =1200VAGARBAGE DISPOSAL11200VA =1200VAFREEZER 11200VA =1200VAREFRIGERATOR11200VA =1200VAMICROWAVE11500VA =1500VAWASHER11200VA =1200VAJACUZZI/WHIRLPOOL TUB21200VA =2400VA10200VA X100%=10200VACOOKING EQUIPMENT:Oven/Range18000VA =8000VA00VA =0VA00VA =0VA00VA =0VA00VA =0VA8000VA X100%=8000VADRYERS:Electric Dryer25000VA =10000VA X100%=10000VAMECHANICAL EQUIPMENT:FC-1A/B1528VA =528VAFC-2A/B1528VA =528VAFC-3A/B12880VA =2880VAFC-4A/B1528VA =528VAFC-5A/B11656VA =1656VAFC-6A/B1528VA =528VAFC-7A/B1528VA =528VAFC-8A/B12400VA =2400VACU-111284VA =1284VAGF-1150VA =50VAGF-2150VA =50VAH-13 3800VA =11400VAEF-1 4 12 VA =48VAEF-2 7 42 VA =294VAEF-3197VA =97VAEF-4 184VA =84VACH-121284VA =2568VAB-13 500VA =1500VAP-13 1656VA =4968VAP-2 21656VA =3312VAP-32200VA =400VAP-4 11656VA =1656VAP-511656VA =1656VAP-611656VA =1656VAP-7 11176VA =1176VAP-821656VA =3312VAP-921656VA =3312VASP-111176VA =1176VASP-211176VA =1176VA0VA =0VA50751VAX100%=50751VAMISCELLANEOUS EQUIPMENT:STEAM SHOWER 3 15000VA =45000VAHEAT TRACE 10 1000VA =10000VA55000VAX100%=55000VA25% OF LARGEST MOTOR:3800VAX25%=950VATOTAL ELECTRICAL LOAD:149276VA240/120v 1Ø, 3W Service149276VA/ 240=622.0A+20%=746.4A200/2200/2200A (3WG)SERVICE WIRING SCHEDULEAMPSCOPPER(3W)GROUNDING ELECTRODE CONDUCTOR1Ø, 3 WIREW.P. M.F. C.E.C. G.RING G. ROD8003[(3-300 KCMIL) 2 1/2"C]#2/0 CU #2/0 CU #2/0 CU #2/0 CU #6 CUCONDUIT SIZES ARE BASED ON NEC TABLE 4 (RNC) AND TABLE 5 (THHN INSULATION).ABBREVIATIONS: W.P. - WATER PIPE; M.F. - METAL FRAME OR STRUCTURE; C.E.C. - CONCRETE ENCASED ELECTRODE;G.RING. - GROUND RING; G.ROD - GROUND ROD, PIPE OR PLATE ELECTRODE.MECHANICAL EQUIPMENT SCHEDULEMARK DESCRIPTIONQUANTITYVOLT /PHASEHP WATTS FLA MCA MOCPDISCONNECT/ FUSESIZEFEEDER SPECIFIC NOTES MARK DESCRIPTIONQUANTITYVOLT /PHASEHP WATTS FLA MCA MOCPDISCONNECT/ FUSESIZEFEEDER SPECIFIC NOTESFC-1A FAN COIL 1 120/1 1/61P MOTORRATED SWITCH2#12,#12GRDSG-1 STEAM GENERATOR 2 240/124,000 200A, 2P, NF3#1,#6GRDFC-2A FAN COIL 1 120/1 1/61P MOTORRATED SWITCH2#12,#12GRDSG-2 STEAM GENERATOR 2 240/112,000 100A, 2P, NF3#4,#8GRDFC-3A FAN COIL 1 240/1 22P MOTORRATED SWITCH2#10,#10GRDSG-3 STEAM GENERATOR 2 240/115,000 100A, 2P, NF3#2,#8GRDFC-4A FAN COIL 1 120/1(2) 1/121P MOTORRATED SWITCH2#12,#12GRDEF-1 EXHAUST FAN 120/1 121P MOTORRATED SWITCH2#12,#12GRDFC-5A FAN COIL 1 120/1 3/41P MOTORRATED SWITCH2#12,#12GRDEF-2 EXHAUST FAN 120/1 421P MOTORRATED SWITCH2#12,#12GRDFC-6A FAN COIL 1 120/1(2) 1/121P MOTORRATED SWITCH2#12,#12GRDEF-3 EXHAUST FAN 120/1 971P MOTORRATED SWITCH2#12,#12GRDFC-7A FAN COIL 1 120/1 1/61P MOTORRATED SWITCH2#12,#12GRDEF-4 EXHAUST FAN 120/1 641P MOTORRATED SWITCH2#12,#12GRDFC-8A FAN COIL 1 120/1 1/61P MOTORRATED SWITCH2#12,#12GRDCH-1 CHILLER 4 240/1 66.25 100100A, 2P, NF2#1,#8GRDFC-1B FAN COIL 1 120/1 1/61P MOTORRATED SWITCH2#12,#12GRDB-1 BOILER 6 120/11P MOTORRATED SWITCH2#12,#12GRDFC-2B FAN COIL 1 120/1 1/61P MOTORRATED SWITCH2#12,#12GRDP-1 BOILER INJECTION PUMP 6 120/1 3/430A, 1P, NF2#10,#10GRDFC-3B FAN COIL 1 240/1 22P MOTORRATED SWITCH2#10,#10GRDP-2 HEATING WATER CIRC PUMP 4 120/1 3/430A, 1P, NF2#10,#10GRDFC-4B FAN COIL 1 120/1 1/61P MOTORRATED SWITCH2#12,#12GRDP-3 DWH INJECTION 4 120/1 3/430A, 1P, NF2#10,#10GRDFC-5B FAN COIL 1 120/1 1/61P MOTORRATED SWITCH2#12,#12GRDP-4 DHW RECIRC PUMP 2 120/1 1/2530A, 1P, NF2#12,#12GRDFC-6B FAN COIL 1 120/1 1/61P MOTORRATED SWITCH2#12,#12GRDP-5SNOWMELT INJECTION PUMP 2 120/1 3/430A, 1P, NF2#10,#10GRDFC-7B FAN COIL 1 120/1 1/61P MOTORRATED SWITCH2#12,#12GRDP-6 SNOWMELT CIRC PUMP 2 120/1 3/430A, 1P, NF2#10,#10GRDFC-8B FAN COIL 1 120/1 20 151P MOTORRATED SWITCH2#12,#12GRDP-7 SPA HX INJECTION PUMP 2 120/1 1/230A, 1P, NF2#12,#12GRDCU-1 CONDENSING UNIT 2 120/1 10.7 1530A, 1P, NF2#12,#12GRDP-8 CHILLER INJECTION PUMP 2 120/1 3/430A, 1P, NF2#10,#10GRDGF-1 GLYCOL FEEDER 2 120/1 50 CORD AND PLUG2#12,#12GRDP-9 CHILLED WATER CIRC PUMP 4 120/1 3/430A, 1P, NF2#10,#10GRDGF-2 GLYCOL FEEDER 2 120/1 50 CORD AND PLUG2#12,#12GRDSP-1 SEWAGE EJECTOR 2 120/1 1/230A, 1P, NF2#12,#12GRDH-1HUMIDIFIER6 240/13,8002P MOTORRATED SWITCH2#12,#12GRDSP-2 SEWAGE EJECTOR 2 120/1 1/230A, 1P, NF2#12,#12GRDGENERAL NOTES:GENERAL NOTES:A. SEE SPECIFICATIONS FOR ELECTRICAL DIVISION AND MECHANICAL DIVISION MOTOR STARTER COORDINATION.A. SEE SPECIFICATIONS FOR ELECTRICAL DIVISION AND MECHANICAL DIVISION MOTOR STARTER COORDINATION.B. PROVIDE PHASE PROTECTION FOR ALL THREE PHASE MOTORS ABOVE 7-1/2 HP.B. PROVIDE PHASE PROTECTION FOR ALL THREE PHASE MOTORS ABOVE 7-1/2 HP.C. PROVIDE ALL EXTERIOR DISCONNECTS WITH NEMA 3R RATING.C. PROVIDE ALL EXTERIOR DISCONNECTS WITH NEMA 3R RATING.D.WHEN EQUIPMENT IS LISTED WITH ONLY A HORSEPOWER RATING THE DISCONNECT AND FEEDER ARE SIZED PER THE N.E.C.D.WHEN EQUIPMENT IS LISTED WITH ONLY A HORSEPOWER RATING THE DISCONNECT AND FEEDER ARE SIZED PER THE N.E.C.SPECIFIC NOTES:SPECIFIC NOTES:(1)(1)(2)(2)(3)(3)(4)(4)WIRING SCHEDULE - COPPERAMPS(2WG) (3WG)IG1Ø, 2 WIRE, GROUND 1Ø, 3 WIRE, GROUNDISOLATED GROUND20(2#12 & 1#12 G) 3/4"C (3#12 & 1#12 G) 3/4"C1#12 IG30(2#10 & 1#10 G) 3/4"C (3#10 & 1#10 G) 3/4"C1#10 IG40(2#8 & 1#10 G) 3/4"C (3#8 & 1#10 G) 3/4"C1#10 IG50(2#6 & 1#10 G) 3/4"C (3#6 & 1#10 G) 1"C1#10 IG60(2#4 & 1#10 G) 1"C (3#4 & 1#10 G) 1"C1#10 IG70(2#4 & 1#8 G) 1"C (3#4 & 1#8 G) 1 1/4"C1#8 IG80(2#2 & 1#8 G) 1"C (3#2 & 1#8 G) 1 1/4"C1#8 IG90(2#2 & 1#8 G) 1"C (3#2 & 1#8 G) 1 1/4"C1#8 IG100(2#1 & 1#8 G) 1 1/4"C (3#1 & 1#8 G) 1 1/2"C1#8 IG110(2#1 & 1#6 G) 1 1/4"C (3#1 & 1#6 G) 1 1/2"C1#6 IG125(2#1 & 1#6 G) 1 1/4"C (3#1 & 1#6 G) 1 1/2"C1#6 IG150(2#1/0 & 1#6 G) 1 1/4"C (3#1/0 & 1#6 G) 1 1/2"C1#6 IG175(2#2/0 & 1#6 G) 1 1/2"C (3#2/0 & 1#6 G) 2"C1#6 IG200(2#3/0 & 1#6 G) 1 1/2"C (3#3/0 & 1#6 G) 2"C1#6 IG225(2#4/0 & 1#4 G) 2"C (3#4/0 & 1#4 G) 2"C1#4 IG250(2-250 KCMIL & 1#4 G) 2"C (3-250 KCMIL & 1#4 G) 2 1/2"C1#4 IG300(2-350 KCMIL & 1#4 G) 2"C (3-350 KCMIL & 1#4 G) 3"C1#4 IG380(2-500 KCMIL & 1#3 G) 2 1/2"C (3-500 KCMIL & 1#3 G) 3"C1#3 IG4002[(2#3/0 & 1#3 G) 1 1/2"C] 2[(3#3/0 & 1#3 G) 2"C]1#3 IG4502[(2#4/0 & 1#2 G) 2"C] 2[(3#4/0 & 1#2 G) 2"C]1#2 IG5002[(2-250 KCMIL & 1#2 G) 2"C] 2[(3-250 KCMIL & 1#2 G) 2 1/2"C]1#2 IG6002[(2-350 KCMIL & 1#1 G) 2 1/2"C] 2[(3-350 KCMIL & 1#1 G) 3"C]1#1 IG7002[(2-500 KCMIL & 1#1/0 G) 2 1/2"C] 2[(3-500 KCMIL & 1#1/0 G) 3"C]1#1/0 IG7602[(2-500 KCMIL & 1#1/0 G) 2 1/2"C] 2[(3-500 KCMIL & 1#1/0 G) 3"C]1#1/0 IG8003[(2-300 KCMIL & 1#1/0 G) 2"C] 3[(3-300 KCMIL & 1#1/0 G) 2 1/2"C]1#1/0 IGCONDUCTOR SIZES ARE BASED ON 60° TERMINATIONS LESS THAN 100A AND 75° TERMINATIONSGREATER THAN 100A.CONDUIT SIZES ARE BASED ON NEC TABLE 4 (RNC) AND TABLE 5 (THHN INSULATION).182 WEST MEADOW DRIVEVAIL, CO 81657PIETRINI RESIDENCEProject Number - 142807/30/14DESIGN REVIEWCOPYRIGHT 2014BANZEGEAUDIN(970) 949-6108(303) 278-3820(970) 221-5691(505) 323-9070(307) 739-3944Vail:Denver:Fort Collins:Albuquerque:Jackson:www.bgce.com09/05/14PERMIT SETE3.00ELECTRICALDIAGRAMSSHEET