HomeMy WebLinkAboutM400 DIAGRAMS.pdfWALL CLEANOUTDIAGRAMNO SCALE1'-0"MAY EXTEND AS AWASTE OR VENT.CHROME WALLCOVERAND SCREW.PLUGGED TEE WITHCLEANOUT.WALL.FLOOR LINE.1/8 C.I. BEND.BALANCE OF PIPINGSAME AS CLEANOUT TOGRADE.MIN. HEIGHTPER MFR.BALL VALVETAKE-OFF FROM TOP OFCW PIPETRAP PRIMER VALVE,SIOUX CHIEF PRIMEPERFECT OR EQUAL.DISTRIBUTION UNIT(FOR MULTIPLEDRAINS)12" TYPE K SOFT COPPERLINE(S) TO FLOORDRAIN(S). QUANTITY ASREQUIRED. NO JOINTSBELOW GRADE.12"DIAGRAMTRAP PRIMER CONNECTIONNO SCALEFLOORAMDUPLEX SEWAGE EJECTOR DIAGRAMNO SCALEVENTINSTALL OFFSETS & UNIONSTO ALLOW COVER REMOVAL.CHECK VALVEGASKETED COVER.CONTINUE PER PLANS.CHECK VALVECONCRETE-CAST AROUNDBASIN. (MIN 4" THICK)FIBERGLASS BASIN.EJECTOR PUMPS.HIGH WATER ALARM LEVEL(AND BOTH PUMPS ON).GATE VALVESCONTINUE PER PLANS.HEAVY DUTY ACCESSCOVER.GOOSENECK VENT.PUMP CONTROL PANEL WITHALTERNATOR. MOUNT ON WALLAT 5'-0" A.F.F. (TO BOTTOM).DEPTH AS REQUIRED TO MEETINLET PIPE.NOTE:SEE PLANS FOR SIZE.ECLEANOUT DIAGRAMSFLOOR CLEANOUT (FCO)NO SCALESLOPE DN @ 1/4"/L.F.CLEANOUT TO GRADE (COTG)WASTE LINEFINISHED GRADE6"ADJUSTABLE GRADE CLEANOUT AND ACCESS ENCLOSURE WITH ANCHOR FLANGE,HEAVY DUTY TOP, AND VANDAL PROOF FASTENERS, ZURN, Z-1400-HD-KBRASSCLEANOUT PLUG W/COUNTER SUNK HEAD.ADJUSTABLE CLEANOUTAND ACCESS COVER ZURNZB-1400. TOP OF COVER TOBE FLUSH W/ TOP OF FLOOR.16" CONC. PAD TROWELSMOOTH & EDGE.1/8 C.I. BENDBALANCE OF PIPING SAMEAS CLEANOUT TO GRADE.FLOOR LINE1/8 C.I. BENDC.I. WASTE LINE.LGTH TO SUIT.1/8 BEND IF CLEANOUTOCCURS AT END OF LINE.PROVIDE FOLLOWING OPTIONS AS APPROPRIATECARPET MARKER - FOR CARPETED AREAS.SQUARE TOP - FOR CERAMIC TILE ORSIMILAR SQUARE PATTERN FLOOR.FLASHING CLAMP - FOR ABOVE GRADEWATER PROOFED AREAS.GISLAND VENT DIAGRAMNO SCALEDRAINBOARD2"SLOPE2"WVFLOORREQUIREMENTSC.O.SLOPE1. EXTEND VENT AS HIGH AS POSSIBLE BUT NOTLESS THAN THE DRAINBOARD HEIGHT & THENRETURNING IT DOWNWARD & CONNECTING IT TOTHE HORIZONTAL SINK DRAIN IMMEDIATELYDOWNSTREAM FROM THE VERTICAL FIXTUREDRAIN.2. THE RETURNED VENT SHALL BE CONNECTED TOTHE HORIZONTAL DRAIN THRU A Y-BRANCHFITTING & SHALL, IN ADDITION, BE PROVIDEDWITH A FOOT VENT TAKEN OFF THE VERTICALFIXTURE VENT BY MEANS OF A Y-BRANCHIMMEDIATELY BELOW THE FLOOR & EXTENDINGTO THE NEAREST PARTITION & THEN THRU THEROOF OR CONNECTED TO OTHER VENTS, IN ANAPPROVED MANNER.3. DRAINAGE FITTINGS SHALL BE USED ON ALLPARTS OF THE VENT BELOW THE FLOOR & A MIN.SLOPE OF 1/4"/FT BACK TO THE DRAIN SHALL BEMAINTAINED.4. THE RETURN DRAIN UNDER THE DRAINBOARDSHALL BE A ONE PIECE FITTING OR AN ASSEMBLYOF A 45°, A 90°, & A 45° IN THE ORDER NAMED.5. THE ISLAND SINK DRAIN, UPSTREAM OF THERETURNED VENT, SHALL SERVE NO OTHERFIXTURES.VENT LINENEARESTPARTITION.WALL CLEANOUT112"112"SINK DRAIN TO BUILDINGSEWER.CNO SCALEFSDDFTO FIRE PROTECTION SYSTEMS.CONTINUATION BY F.P.DESIGN/BUILDC CONTRACTOR.TEST VALVE; PIPE TO OUTSIDE.FLOW SWITCH TO ALARMS, SEE SPECS.DRAIN VALVE; PIPE INDIRECT TO FLOOR DRAINPER NFPA REQUIREMENTS, TYP.SHUT-OFF VALVE.DOUBLE CHECK TYPE BACKFLOW PREVENTER.TAMPER SWITCHES ON VALVES.FIRE SERVICE FLANGE.FLOOR SINKC.W. SERVICEFIRE ENTRY PIPING DIAGRAMDIAGRAM SHOWN FOR REFERENCE ONLY, CONFIRM FINALREQUIREMENTS WITH FIRE PROTECTION DESIGN BUILDCONTRACTOR AND ENGINEER OF RECORD.PIPE THRU ROOF DIAGRAMNO SCALE6" MIN.24 GA. GALV. ROOF JACK W/6" FLANGE BY M.C., SET INPLASTIC CEMENT BY G.C.PIPE BY M.C.24 GA. GALV. STORM COLLARBY M.C., CLAMP IN PLACE &CAULK WEATHERTIGHT.FINISHED ROOF FELTS BYG.C.SOLDERED LAP SEAMPIPE SLEEVE & CAULKING BYM.C.2" MIN.ROOF2 LAYERS OF FELT BYG.C.COOR'D ROOF PENETRATIONAND SEALING WITH ROOFMANUFACTURER.ANDINSTALLING CONTRACTOR.BDRAIN THRU WALL DIAGRAMSANITARY OR STORM BLDG.SLOPE 1/4"/L.F.NO SCALEC.O.T.G.BASEMENT WALL.COORDINATE WALL OPENING SIZEWITH PIPE MATERIAL AND SIZE ANDMANUFACTURER REQUIREMENTS.STORM OR SANITARYBLDG. DRAIN.LINK-SEAL OR EQUIVALENT.GRADEFAN COIL UNIT INSTALLATIONNO SCALESAFAN COIL UNITDOSAFILTER W/ ACCESSPANEL.ACOUSTICAL LINING.VOLUME DAMPER.RA DUCT.CONDENSATE DRAIN. PIPEINDIRECT TO APPROVEDRECEPTOR (PROVIDE MIN.2" DEEP TRAP).SHEET METAL DRAIN PAN,EQUIPPED WITH UL508WATER-LEVEL DETECTIONDEVICE THAT WILL SHUT-OFFEQUIPMENT.ROUND HANGER ROD TYP.WITH EXCEPTION OF FANCOILS LOCATED IN ATTIC.SPRING VIBRATIONISOLATORS, TYP.DOUBLE LOCKNUT.1. RETURN AIR PLENUM FULLSIZE OF UNIT CONNECTION.CEILINGMOTORIZED DAMPER.RADIANT/SNOWMELT MANIFOLD PIPING DIAGRAMNO SCALECONTROL VALVEON RADIANTZONES ONLY.MANIFOLD BOX (WALLMOUNTED FORRADIANT; LOCATED INSLAB OR LANDSCAPEBOX FOR SNOWMELT).MANUFACTURER'SMANIFOLD ASSY.LOOPBALANCE/ISOLATIONVALVEMANUFACTURER'SMANIFOLD ASSEMBLYWITH REVERSERETURN PIPING.RADIANT/SNOWMELTTUBING. LOOPQUANTIITY ASREQUIRED.1. PROVIDE MANUFACTURER'S MANIFOLDS AND ISOLATION VALVES WITH PIPING.2. FOR EXTERIOR MANIFOLD LOCATIONS PROVIDE WATERPROOF MANIFOLD BOX ORWATERPROOF CONTROL VALVE.TO PIPING MAINSAIR VENT AT HIGHPOINTS, TYPICAL.MANIFOLD BALANCEVALVE.LKFJWATER ENTRANCE DIAGRAMFMNO SCALESEE FIRE ENTRY DIAGRAM, THISSHEET. 2" LINE (VERIFY WITHFIRE PROTECTIONCONTRACTOR).DOMESTIC WATER SERVICESHUT-OFF VALVE.3/4" IRRIGATION LINE WITHAPPROVED REDUCED PRESSUREBACKFLOW PREVENTION DEVICE.(VFY. WITH IRRIGATIONCONTRACTOR).1-1/2" CW TO BUILDING.REDUCED PRESSURE TYPEBACKFLOW PREVENTER.CERTIFIED TESTER TO TEST.1" WATER METER WITHREMOTE READOUT.PRESSURE REDUCING VALVE, TYP.WATTS 223, 1" SET @ 60 PSI2" CW/FIRE SERVICE (VERIFYSIZE WITH FIRE PROTECTIONCONTRACTOR).:WATER METER AND BACKFLOWPREVENTER MUST BE MOUNTEDHORIZONTALLY.DMETER BYPASS.SPA/POOL HEAT EXCHANGER PIPING DIAGRAMNO SCALEAHWSHWRNORMAL CLOSEDCONTROL VALVE.HEAT EXCHANGER. MOUNT ON WALL WITHUNIT STRUT & INSULATE. COOR'D HEIGHTABOVE POOL FILTER WITH POOL/SPAINSTALLER TO MINIMIZE BACK PRESSUREON FILTER. PIPE W.C. FOR COUNTERFLOW.FROM SPA/POOLBY OTHERS.TO SPA/POOLPUMP &FILTER.AQUASTAT.POOL = 2-1/2"SPA = 2"ISOLATION VALVE.AANTI SCALDVALVE.H182 WEST MEADOW DRIVEVAIL, CO 81657PIETRINI RESIDENCEProject Number - 142807/30/14DESIGN REVIEWCOPYRIGHT 2014BANZEGEAUDIN(970) 949-6108(303) 278-3820(970) 221-5691(505) 323-9070(307) 739-3944Vail:Denver:Fort Collins:Albuquerque:Jackson:www.bgce.com09/05/14PERMIT SETM4.00MECHANICALDIAGRAMS