HomeMy WebLinkAboutM500 CONTROLS.pdfGENERAL CONTROLS NOTES:SCALE:3CONTROL SYSTEM ARCHITECTURE (BACNET)NONEBACNETWEBSERVERSUPERVISORY NETWORKCONTROLLER (TYP.)UNITARY EQUIPMENTCONTROLLER (TYP.)BACNET COMM BUS (TYP.)GENERIC I/O CONTROLLER (TYP.)INTERNET(BY OTHERS)LAN(BY OTHERS):NEW DDC SYSTEM SHALL BE CAPABLEOF INTERFACING WITH EXISTINGREMOTE OPERATOR WORKSTATIONSAND EXISTING DDC SYSTEMS IN OTHERFACILITIES.DESCRIPTION:THE BUILDING CONTROL SYSTEM (BCS) SHALL CONSIST OF AN ASHRAE STANDARD 134COMPLIANT (BACNET COMPATIBLE) FOR CONTROL OF HVAC & PLUMBING SYSTEMSWITH ALL STATUS FEEDBACK AND OCCUPANT CONTROL AVAILABLE THROUGH THEWEB INTERFACE. MAJOR COMPONENTS INCLUDING THE BOILERS AND ERV SHALL BEPROVIDED BY MANUFACTURER WITH BCS COMPATIBLE CONTROLLERS WITH ALLAVAILABLE INFORMATION WITHIN COMMUNICATED TO AND GRAPHICALLYREPRESENTED IN THE BCS.REMOTE ACCESS:PROVIDE REMOTE ACCESS VIA WEB BASED INTERFACE. REMOTE ACCESS SHALLHAVE, AT A MINIMUM, THE FOLLOWING VARIOUS LEVELS OF CONTROL CAPABILITYBASED ON CREDENTIALS PROVIDED DURING LOG-IN:1. VIEW ONLY - NO ADJUSTMENT CAPABILITIES. PROVIDE 'VIEW ONLY' REMOTEACCESS LOCATION AND CREDENTIALS TO ENGINEER AND COMMISSIONINGAGENT UPON STARTUP OF SYSTEM. CREDENTIALS PROVIDED TO ENGINEERAND COMMISSIONING AGENT SHALL NOT EXPIRE DURING THE PERIOD OF THEWARRANTY.2. OCCUPANT LEVEL - SIMILAR LEVEL OF CONTROL TO THAT AVAILABLE VIAHOME AUTOMATION TOUCH SCREENS.3. TECHNICIAN LEVEL - FULL CONTROL, TROUBLESHOOTING, ADJUSTMENT, ANDPROGRAMMING CAPABILITIES.BCS SHALL UTILIZE REMOTE ACCESS TO THE WEB TO AUTOMATICALLY CALIBRATE ITSINTERNAL TIME-OF-YEAR CLOCK ON A MONTHLY BASIS WITH THE OFFICIAL WORLDTIME.GRAPHICS:AS INDICATED IN THE POINTS LISTS, ALL BCS POINTS SHALL BE REPRESENTED BYGRAPHIC DISPLAY ON THE WEB BASED INTERFACE. ITEMS SUCH AS PUMPS, FANS,CONTROL VALVES, AND DAMPER MOTORS SHALL BE REPRESENTED BY ANIMATEDGRAPHIC DISPLAYS. GRAPHICAL FLOOR PLANS SHALL INDICATE AIRSIDE ZONEDESIGNATIONS AS WELL AS THEIR SPACE TEMPERATURE SETPOINT, SPACETEMPERATURE. BACKGROUND COLOR OF ZONES SHALL BE CHANGED AS FOLLOWS:1. NONE - SPACE TEMPERATURE WITHIN 3°F OF SETPOINT.2. RED - SPACE TEMPERATURE GREATER THAN 3°F ABOVE SETPOINT.3. BLUE -SPACE TEMPERATURE LOWER THAN 3°F BELOW SETPOINT.GRAPHICAL FLOOR PLANS SHALL ALSO INDICATE DE-CENTRALIZED EQUIPMENT BYLOCATION AND DESIGNATION. ANIMATED GRAPHICS ARE NOT REQUIRED ON THEGRAPHICAL FLOOR PLAN SCREEN. ADDITIONAL INFORMATION FOR A GIVEN ZONE ORPIECE OF EQUIPMENT SHALL BE EASILY ACCESSED BY DOUBLE-CLICKING ITSASSOCIATED FLOOR PLAN GRAPHIC.LINE VOLTAGE POWER REQUIREMENTS FOR CONTROLS SYSTEM HAVE BEENESTIMATED ON PLAN; CONTROLS CONTRACTOR TO FIELD COORDINATE WITH DIV. 26CONTRACTOR FOR REQUIREMENTS. DIV. 26 CONTRACTOR TO INCLUDE CONTROLSPOWER IN BASE BID.DDC SYSTEM SHALL ALSO BE EXPANDABLE TO ACCOMMODATE FUTURE CORE ANDSHELL BUILDOUT HVAC SYSTEMS.EXHAUST FANS SERVING THE MECHANICAL, ELECTRICAL, AND ELEVATOR MACHINEROOMS SHALL BE CONTROLLED BY INDIVIDUAL SPACE MOUNTED COOLINGTHERMOSTAT SET AT 80°F (ADJ).UPON A RISE IN SPACE TEMPERATURE ABOVE SETPOINT PLUS DIFFERENTIAL,EXHAUST FANS SHALL ENABLE. CONVERSELY, UPON A DECREASE IN SPACETEMPERATURE BELOW SETPOINT PLUS DIFFERENTIAL, EXHAUST FANS SHALLDISABLE.THESE FANS ARE NOT INTENDED TO BE ON THE DDC SYSTEM.SCALE:5THERMOSTAT CONTROL SCHEMATICNONEEXHAUST FANUNIT MOTORSTARTERMSTSTATANALOG INPUT TO BCSCONTROLS LEGENDTEMPSENSORAIAOBIBOANALOG OUTPUT FROM BCSBINARY INPUT TO BCSBINARY OUTPUT FROM BCSCARBON MONOXIDE SENSORCARBON DIOXIDE SENSORCURRENT SWITCHFLOW SWITCHHUMIDITY SENSORMOTOR STARTER DAMPER MOTORRELAYSMOKE DETECTORTEMPERATURE SENSORVARIABLE FREQUENCY DRIVECPFREEZSTATSENSOR-THERMOSTAT SWITCHSPACE MOUNTED STATEQUIPMENT MANUFACTURER'S CONTROLPANELDIFFERENTIAL PRESSURE SWITCHDIFFERENTIAL PRESSURE TRANSDUCERFLOW SENSORAIRFLOW MEASURING STATIONAFMSCOCO2CSDPSDPTFRZFSFHEMSDMRLYSSMKTETSTATVFDEMERGENCY POWER OFFEPOEXHAUST FANS SERVING RESIDENTIAL POWDER ROOMS AND BATHROOMS SHALLENABLE UPON CLOSE OF A WALL MOUNTED SWITCH. CONVERSELY, FAN SHALLDISABLE UPON OPEN OF THE SWITCH.WALL SWITCHSCALE:4SWITCH CONTROL SCHEMATICNONEEXHAUST FAN WALLSCALE:1GLOBAL CONTROLS COMPONENTSNONETEHEAIAIOSA TEMPOSA HUMIDITYAIOSA CO2 CONCENTRATIONCO2SCALE:2PUMP CONTROL SCHEMATICNO SCALESUMP AND SEWAGE EJECTORPUMPS SHALL CYCLE ON WHEN PUMP ON LEVEL IS REACHED AND OFFWHEN PUMP OFF LEVEL IS REACHED. PUMPS SHALL GO INTO AUDIBLEALARM WHEN ALARM ON/HIGH WATER LEVEL IS REACHED. PUMPS SP-1ARE INTENDED FOR PRIMARY/STANDBY OPERATION; ONE PUMP IS TO RUNAT A TIME, THE STANDBY ONLY COMES ON IF PRIMARY FAILS.STORM VAULT SUMP PUMPS TO HAVE FLOAT SWITCHES INSTALLED ATLEVELS SHOWN IN CIVIL DOCUMENTS. PUMPS SP-4 ARE INTENDED FORPRIMARY/STANDBY OPERATION; ONE PUMP IS TO RUN AT A TIME, THESTANDBY ONLY COMES ON IF PRIMARY FAILS.CONTROL PANEL TO HAVE OUTPUTS FOR CONNECTION TO DDC SYSTEM. IFHIGH WATER ALARM IS SIGNALED, A SIGNAL WILL BE SENT THROUGH THECONTROLS SYSTEM TO ALERT THE BUILDING OPERATOR.SCALE:6CONTROL SCHEMATICNO SCALESPA HEAT EXCHANGERUPON A DROP IN SPA WATER TEMPERATURE AS SIGNALED BY ANAQUASTAT, THE LOAD SIDE CONTROL VALVE SHALL OPEN. CONVERSELY,CONTROL VALVE SHALL BE CLOSED WHEN SUPPLY TEMPERATURE IS ATSETPOINT. UPON AN INCREASE IN SPA SIDE TEMP (104°F (ADJ.)), THE SPASIDE "SCALD" PROTECTION VALVE SHALL CLOSE AND SOUND AN ALARM ATAN OWNER DESIGNATED LOCATION.AHWRHWSASCALE:7VENTILATOR CONTROLS SCHEMATICNO SCALEHEAT RECOVERYHEAT RECOVERY VENTILATOR SHALL OPERATE CONTINUOUSLY VIA 'ON' POSITION OFMANUAL WALL SWITCH.THE UNIT SHALL OPERATE VIA MANUFACTURER'SFROST CONTROLS FOR A SETAMOUNT OF TIME TO AVOID FROST CONDITIONS.R.A.O.S.A.S.A.EXHHRVCPBOOUTDOOR CONDENSING UNITRSRLSCALE:8UNIT CONTROL SCHEMATICNONEWINE ROOM AIR CONDITIONINGFAN COIL UNIT AND OUTDOOR CONDENSING UNIT TO OPERATE IN ACCORDANCE WITH THE MANUFACTURER'SPACKAGED CONTROL SYSTEM TO MAINTAIN SPACE TEMPERATURE SETPOINTS. SPACE TEMPERATURESETPOINT SHALL BE INITIALLY SET AT 55°F FOR COOLING.THE OUTDOOR COMPRESSOR IS CYCLED ON AND OFF TO MEET COOLING ZONE DEMANDS.THE SUPPLY AIR FAN OPERATES AT THE FACTORY WIRED SPEED FOR CYCLING ON WITH COOLING.CPTHERMOSTATINDOOR FAN COIL UNIT182 WEST MEADOW DRIVEVAIL, CO 81657PIETRINI RESIDENCEProject Number - 142807/30/14DESIGN REVIEWCOPYRIGHT 2014BANZEGEAUDIN(970) 949-6108(303) 278-3820(970) 221-5691(505) 323-9070(307) 739-3944Vail:Denver:Fort Collins:Albuquerque:Jackson:www.bgce.com09/05/14PERMIT SETM5.00MECHANICALCONTROLS