HomeMy WebLinkAboutS002.pdfCONCRETE MIX TABLE NOTES:
PROPORTIONS OF MATERIALS IN CONCRETE MIX SHALL BE ESTABLISHED TO:
- PROVIDE THE MINIMUM COMPRESSIVE STRENGTH AS INDICATED IN THE MIX TABLE. DO NOT
EXCEED THE MAXIMUM WATER-CEMENT RATIO NOTED.
- PROVIDE WORKABILITY AND CONSISTENCY TO PERMIT CONCRETE TO BE WORKED READILY INTO
FORMS AND AROUND REINFORCEMENT UNDER CONDITIONS OF PLACEMENT TO BE EMPLOYED,
WITHOUT SEGREGATION OR EXCESSIVE BLEEDING. CONTRACTOR SHALL SELECT APPROPRIATE
SLUMP. USE ADMIXTURES AS REQUIRED TO OBTAIN DESIRED RESULTS.
USE TYPE I / II PORTLAND CEMENT UNLESS NOTED OTHERWISE. FOR CONCRETE MIXES USED ON
FLOORS MINIMUM CEMENTITIOUS CONTENT SHALL BE 540 POUNDS PER CUBIC YARD
FOR CONCRETE PLACED BY PUMPING PROVIDE CONCRETE MIX FLOWABILITY TO FACILITATE
PUMPING. ENTRAINED AIR MAY BE USED TO FACILITATE PUMPING SUBJECT TO THE PROVISIONS OF
NOTE b BELOW.
a. FOR THE MAXIMUM COARSE AGGREGATE SIZE INDICATED, USE THE FOLLOWING AGGREGATE SIZE
NUMBERS PER ASTM C33:
3/4”: #67 AGGREGATE
1”: #57 AGGREGATE
b. WHERE AIR CONTENT IS INDICATED IN THE MIX TABLE, PROVIDE AIR ENTRAINING ADMIXTURE.
TOTAL AIR CONTENT LIMITS INCLUDE BOTH ENTRAINED AND ENTRAPPED AIR +/- 1 1/2%. ‘NP’ IN
COLUMN INDICATES ADDITION OF ENTRAINED AIR IS NOT PERMITTED EXCEPT WHERE CONTRACTOR
CAN DEMONSTRATE THAT SLABS WITH ENTRAINED AIR WILL HAVE A FINISH ACCEPTABLE TO THE
ARCHITECT WITHOUT BLISTERS. AIR CONTENT NOTED IS BASED ON 3/4" AGGREGATE. IF 3/8”
AGGREGATE IS USED, INCREASE AIR CONTENT BY 1 1/2%.
c. ABBREVIATIONS FOR OTHER REQUIREMENTS AS FOLLOWS:
AE = SEE ARCH FOR FINISH, COLOR AND MOCK UP REQUIREMENTS. USE ADMIXTURES TO INCREASE
CONCRETE WORKABILITY/SLUMP AS REQUIRED TO ACHIEVE REQUIRED FINISH.
Project number
Date
Drawn by
MM JOB #: 15.0197.S.01PRINCIPAL/EOR: PDPROJECT MANAGER: KHDESIGNERS: JW/KHDATE PRINTED:FILE PATH:07/02/2015
C:\Proj\15.0197-994Ptarmigan-RS15_kevinh.rvt7/2/2015 2:34:32 PMS002
NOTES
M15.0197.S.01LOT 3 / 994 PTARMIGAN RDVAIL,COHughes Residence07.02.2015
KH
CONCRETE NOTESGENERAL NOTES
1. GENERAL:
1A.ENGINEER: REFERENCES ON THE STRUCTURAL DRAWINGS TO ‘ENGINEER’ MEAN THE STRUCTURAL
ENGINEER OF RECORD. OTHER ENTITIES ARE SPECIFICALLY NOTED AS “CONTRACTOR’S ENGINEER”,
“MECHANICAL ENGINEER”, ETC.
1B.THESE NOTES SUPPLEMENT THE PLANS AND DETAILS, WHICH SHALL BE REFERENCED FOR ADDITIONAL
REQUIREMENTS.
1C.UNDERGROUND UTILITIES: LOCATE EXISTING UTILITIES AND NOTIFY ARCHITECT OF EXISTING
UTILITIES OR SUBGRADE CONDITIONS WHICH INTERFERE WITH WORK.
1D.STRUCTURAL ELEMENTS ARE CENTERED ON GRID LINES AND GRID LINE INTERSECTIONS UNLESS
DIMENSIONED OTHERWISE. THE OUTSIDE FACE OF WOOD FRAMED EXTERIOR WALLS IS AT GRID UNLESS
DIMENSIONED OTHERWISE.
2. EXISTING STRUCTURES:
2A.CONTRACT DOCUMENTS HAVE BEEN PREPARED USING AVAILABLE DRAWINGS AND SITE OBSERVATION AS
PERMITTED BY ACCESS RESTRICTIONS DURING DESIGN.
2B.THE EXISTING STRUCTURE AND FOUNDATION SHALL BE DEMOLISHED IN ITS ENTIRETY BEFORE
CONSTRUCTING THE NEW STRUCTURE.
3. USE OF DRAWINGS:
3A.DO NOT SCALE DRAWINGS.
3B.WHERE DISCREPANCIES OCCUR BETWEEN PLANS, DETAILS, GENERAL NOTES AND SPECIFICATIONS, THE
MORE STRINGENT REQUIREMENTS SHALL GOVERN. DETAILS ON DRAWINGS TAKE PRECEDENCE OVER
GENERAL NOTES AND TYPICAL DETAILS. DETAILS NOTED TYPICAL APPLY TO ALL SIMILAR CONDITIONS.
WHERE NO SPECIFIC DETAILS ARE SHOWN, CONSTRUCTION SHALL CONFORM TO SIMILAR WORK
ELSEWHERE ON THE PROJECT.
4. TEMPORARY CONDITIONS:
4A.THE STRUCTURE IS DESIGNED TO FUNCTION AS A UNIT UPON COMPLETION. THE CONTRACTOR IS
RESPONSIBLE FOR FURNISHING ALL TEMPORARY BRACING AND/OR SUPPORT THAT MAY BE REQUIRED AS
THE RESULT OF THE CONTRACTOR’S CONSTRUCTION METHODS AND/OR SEQUENCES. REFER TO
“LATERAL LOAD RESISTING SYSTEM DESCRIPTION” IN DESIGN CRITERIA FOR ADDITIONAL INFORMATION.
4B.FOUNDATION WALLS SHALL NOT BE BACKFILLED UNTIL THE SLABS-ON-GRADE AND UPPER DIAPHRAGMS
ARE IN-PLACE AND REACH FULL STRENGTH UNLESS ADEQUATE BRACING IS PROVIDED. USE ONLY HAND
OPERATED TOOLS FOR COMPACTION ADJACENT TO FOUNDATION WALLS AND GRADE BEAMS. GRADE
BEAMS SHALL BE BACKFILLED EVENLY ON BOTH SIDES.
5. SUBMITTALS AND SUBSTITUTIONS:
5A.SUBMITTALS: REFER TO SUMBITTAL NOTES FOR DETAILED REQUIREMENTS.
- IF THE CONTRACTOR REQUESTS A CHANGE FROM THE STRUCTURAL DRAWINGS, IT SHALL BE
APPROVED BY THE ARCHITECT AND DESIGNED BY MARTIN/MARTIN, INC. PRIOR TO SUBMITTING SHOP
DRAWINGS. VARIATION SHALL BE INDICATED ON THE SHOP DRAWINGS. CONTRACTOR SHALL COMPENSATE
MARTIN/MARTIN, INC. FOR MAKING THE CHANGE.
- CONSTRUCTION DOCUMENTS SHALL NOT BE REPRODUCED FOR USE IN SUBMITTALS
- ALL SHOP DRAWINGS SHALL REFERENCE THE STRUCTURAL DRAWING NUMBER AND DETAIL USED TO
PREPARE THE SUBMITTAL
5B.SUBSTITUTIONS: ARCHITECTS APPROVAL SHALL BE SECURED FOR ALL SUBSTITUTIONS
5C.NONCONFORMANCE: NOTIFY ARCHITECT OF CONDITIONS NOT CONSTRUCTED PER THE CONTRACT
DOCUMENTS PRIOR TO PROCEEDING WITH CORRECTIVE WORK. SUBMIT PROPOSED REPAIR TO THE
ARCHITECT FOR ACCEPTANCE. CONTRACTOR SHALL COMPENSATE MARTIN/MARTIN, INC. FOR DESIGNING
THE REPAIR.
6. OSHA STANDARDS:
6A.THE STRUCTURE IS DESIGNED TO FUNCTION AS A UNIT UPON COMPLETION. NOTHING SHOWN ON THE
STRUCTURAL DRAWINGS SHALL BE CONSTRUED AS ELIMINATING THE NEED FOR THE CONTRACTOR TO
COMPLY WITH ALL OSHA REQUIREMENTS.
6B.THE CONTRACTOR SHALL ADD ALL NECESSARY BOLTS, ANCHOR BOLTS, PLATES, STIFFENER PLATES,
STABILIZER PLATES, BRIDGING, BRACING, BEARING SEATS, COLUMN SPLICES, ETC., AS WELL AS CLOSURES
FOR OPENINGS. IN ADDITION, FIELD WELD ANYTHING THAT MAY BE CONSIDERED A TRIP HAZARD, SUCH AS
SHEAR STUDS, AFTER PROTECTIVE DECKING IS INSTALLED.
6C.WHERE THE STRUCTURAL DRAWINGS APPEAR TO CONFLICT WITH OSHA REQUIREMENTS, THE
STRUCTURAL DRAWINGS REPRESENT FINAL CONDITIONS ONLY. THE CONTRACTOR SHALL ADD ALL
ERECTION FRAMING NECESSARY TO COMPLY WITH OSHA.
7. CONSTRUCTION ENGINEERING:
7A.THE STRUCTURE DEFINED ON THE CONTRACT DOCUMENTS HAS BEEN DESIGNED ONLY FOR LOADS
ANTICIPATED ON THE STRUCTURE DURING ITS SERVICE LIFE. PROVIDE ALL REQUIRED ENGINEERING AND
OTHER MEASURES TO ACHIEVE THE MEANS, METHODS, AND SEQUENCES OF WORK. SUCH ENGINEERING
MAY INCLUDE, BUT IS NOT LIMITED TO:
- LAYOUT
- DESIGN FOR FORMWORK
- DESIGN OF CONCRETE MIXES
- ERECTION PROCEDURES WHICH ADDRESS STABILITY OF THE FRAME DURING CONSTRUCTION
- WELD PROCEDURES
- DESIGN OF TEMPORARY BRACING OF WALLS FOR WIND, SEISMIC, OR SOIL LOADS
- SURVEYING TO VERIFY CONSTRUCTION TOLERANCES
- EVALUATION OF TEMPORARY CONSTRUCTION LOADS ON STRUCTURE DUE TO EQUIPMENT AND
MATERIALS
- STRUCTURAL ENGINEERING TO RESIST ANY OTHER LOADS NOT IDENTIFIED ON DESIGN DRAWINGS
8. COORDINATION:
8A.STRUCTURAL DRAWINGS ARE NOT STAND-ALONE DOCUMENTS AND ARE INTENDED TO BE USED IN
CONJUNCTION WITH CIVIL, ARCHITECTURAL, MECHANICAL, ELECTRICAL, AND DRAWINGS FROM OTHER
DISCIPLINES. THE CONTRACTOR SHALL COORDINATE ALL REQUIREMENTS OF THE CONTRACT
DOCUMENTS INTO SHOP DRAWINGS AND WORK.
8B.COORDINATE DIMENSIONS OF ALL OPENINGS, BLOCKOUTS, DEPRESSIONS, ETC., WITH ARCHITECTURAL
DRAWINGS, DRAWINGS FROM OTHER DISCIPLINES, AND FIELD CONDITIONS PRIOR TO SHOP DRAWING
SUBMITTAL.
8C.SEE ARCHITECTURAL PLANS FOR INTERIOR PARTITIONS. PARTITION FRAMING SHALL BE CONNECTED
TO THE PRIMARY STRUCTURE IN SUCH A WAY SO AS TO ALLOW FOR VERTICAL LIVE LOAD DEFLECTIONS OF
SPAN/360 OF THE FLOOR FRAMING. DO NOT MAKE RIGID VERTICAL AND HORIZONTAL CONNECTIONS TO
THE PRIMARY STRUCTURE IN THE PLANE OF THE PARTITION.
1. GENERAL:
1A.ALL WORK SHALL CONFORM WITH ACI 301, LATEST EDITION, UNLESS NOTED OTHERWISE IN
DRAWINGS.
1B.DETAIL BARS IN ACCORDANCE WITH THE LATEST EDITIONS OF PUBLICATION SP-66: “ACI DETAILING
MANUAL” WITH ADDED REQUIREMENTS OF THE PROJECT SPECIFICATION AND ACI 318: “BUILDING
CODE REQUIREMENTS FOR STRUCTURAL CONCRETE.”
2. REINFORCING MATERIALS:
2A.SEE ‘REINFORCING MATERIALS TABLE’
3. REINFORCING FABRICATION:
3A.SPLICES:
- NO SPLICING OF REINFORCEMENT PERMITTED EXCEPT AS NOTED ON DRAWINGS. MAKE BARS
CONTINUOUS AROUND CORNERS. WHERE PERMITTED, SPLICES MAY BE MADE BY CONTACT LAPS OR
MECHANICAL CONNECTORS.
- SEE ‘LAP SPLICE SCHEDULE’ FOR LAP LENGTHS.
- SPLICE CONTINUOUS TOP AND BOTTOM BARS IN WALLS, BEAMS, AND GRADE BEAMS ‘LTS’ UNLESS
NOTED OTHERWISE.
3B.MISCELLANEOUS REINFORCING REQUIREMENTS:
- PROVIDE ADDITIONAL BARS OR STIRRUPS REQUIRED TO SECURE REINFORCING IN PLACE DURING
CONCRETE PLACEMENT.
- MAKE ALL REINFORCING BAR BENDS IN THE FABRICATOR’S SHOP UNLESS NOTED.
- NO WELDING OF REINFORCING PERMITTED UNLESS NOTED ON DRAWINGS. WHERE PERMITTED,
PERFORM WELDING IN ACCORDANCE WITH AWS D1.4, LATEST EDITION.
- PROVIDE ADDED REINFORCING TO TRIM ALL OPENINGS, NOTCHES, AND REENTRANT CORNERS AS
NOTED IN TYPICAL DETAILS.
4. STRUCTURAL CONCRETE MIX REQUIREMENTS:
4A.SEE ‘CONCRETE MIX TABLE’
5. SLAB-ON-GRADE:
5A.VERIFY ALKALINITY OF CONCRETE SURFACE, SLAB VAPOR TRANSMISSION, AND SLAB
FLATNESS/LEVELNESS ARE COMPATIBLE WITH FLOORING SYSTEM AND ADHESIVES PRIOR TO
INSTALLING FLOORING.
5B.TAKE PRECAUTIONS TO MINIMIZE SLAB CURLING. GRIND SLAB OR USE LEVELING COMPOUND IF
FLOOR FLATNESS AND LEVELNESS VALUES ARE NOT ACCEPTABLE TO THE ARCHITECT.
6. NON-SHRINK GROUT:
6A.CONFORM TO ASTM C1107.
6B.ACHIEVE 6000 PSI COMPRESSIVE STRENGTH AT 28 DAYS.
7. PLACING REINFORCEMENT:
7A.REINFORCEMENT PROTECTION:
- SEE ‘CONCRETE COVER TABLE’
- SEE ACI 318-11 7.5 FOR REINFORCEMENT PLACING TOLERANCES AND ACI 117 FOR ADDITIONAL
REQUIREMENTS
7B.PROVIDE ACCESSORIES NECESSARY TO PROPERLY SUPPORT REINFORCING AND WELDED WIRE
REINFORCEMENT AT POSITIONS SHOWN ON PLANS. ALL REINFORCING, DOWELS, BOLTS, AND
EMBEDDED PLATES SHALL BE SET AND TIED IN PLACE BEFORE THE CONCRETE IS POURED.
“STABBING” INTO PREVIOUSLY PLACED CONCRETE IS NOT PERMITTED.
8. CONSTRUCTION/CONTROL JOINTS:
8A.SUBMIT DRAWINGS SHOWING CONSTRUCTION AND CONTROL JOINT LOCATIONS ALONG WITH THE
SEQUENCE OF POURS. CONSTRUCTION JOINT LOCATIONS AND CASTING SEQUENCE SHALL BE
ARRANGED TO MINIMIZE THE EFFECTS OF ELASTIC AND LONG-TERM SHORTENING/SHRINKAGE.
8B.CONSTRUCTION JOINTS IN SLABS-ON-GRADE SHALL BE LOCATED TO ACCOMMODATE THE
MAXIMUM LENGTH AND AREA THE CONTRACTOR CAN REASONABLY POUR, FINISH, AND JOINT IN THE
SAME DAY.
9. MEP AND OTHER OPENINGS AND EMBEDMENTS:
9A.PROVIDE SLEEVES AT OPENINGS (SUCH AS THOSE REQUIRED FOR PLUMBING AND ELECTRICAL
PENETRATIONS) BEFORE PLACING CONCRETE. DO NOT CUT REINFORCING WHICH MAY CONFLICT.
CORING OF CONCRETE IS NOT PERMITTED.
9B.REFER TO TYPICAL DETAILS FOR SPACING LIMITS ON SLEEVES AND FOR REQUIREMENTS FOR
EMBEDDED CONDUIT AND PIPE.
CONCRETE MIX TABLE
CONC MIX TYPEINTENDED USE 28 DAY STRENGTH, f'c (KSI)CONCRETE WEIGHTMAX W/C RATIO, INCLUDING FLY ASHMAX AGGREGATE SIZE (IN), NOTE aTOTAL AIR CONTENT (%), NOTE bOTHER REQUIREMENTS, NOTE c1 FOOTINGS 3 NWC -- 1 -- --
2 GRADE BMS, FND
WALLS
4.5 NWC 0.45 3/4 5 --
3 ALL CONC EXPOSED TO
WEATHER OR DEICERS:
SITE WALLS
5 NWC 0.40 3/4 6 --
4 INT SLABS ON GRADE 3.5 NWC 0.50 3/4 NP --
5 ARCHITECTURALLY
EXPOSED CONC
CHIMNEY
4.5 NWC 0.45 3/8 6 AE
REINFORCING MATERIAL TABLE
REINF ELEMENT ASTM Fy (KSI) Fu (KSI)
TYP REINFORCING A615 60 90
WELDED & FIELD BENT REINF A706 60 80
WELDED WIRE REINFORCING, SMOOTH A185 65 75
STEEL MATERIAL TABLE
STEEL ELEMENT ASTM/TYPE Fy (KSI)
Fu
(KSI)COMMENTS
ANCHOR RODS F1554 GR 55 55 75 WELDABLE, HEAVY HEX
HEADED
BOLTS A325 OR F1852 -- 120 BOLTS ARE 3/4"Ø UNO, USE
TENSION-CONTROLLED
WHERE POSSIBLE
DAS A496 70 80 --
HAS A108 51 65 STUDS ARE 3/4"Ø UNO
OTHER SHAPES A36 36 58 --
PLATES A36 36 58 --
RECT HSS A500 GR C 50 62 --
WELDING ELECTRODES E70 PER AWS
WF, WT A992 50 65 --
ANCHOR TYPE
POST-INSTALLED ANCHOR TABLE
PRODUCT
ADHESIVE
(IN CONCRETE)
HILTI HIT-HY 200
ADHESIVE ANCHOR
RODS
SCREW ANCHORS
EXPANSION ANCHORS
(IN CONCRETE)
--
HILTI KWIK BOLT TZ
HILTI KWIK HUS-EZ
Fy (KSI) COMMENTS
--
36
MIN
--
Fu (KSI)
--
58
MIN
--
SUBMIT CALCULATIONS
FOR SUBSTITUTIONS
-- --
THREADED ROD,
UNGREASED
SUBMIT CALCULATIONS
FOR SUBSTITUTIONS
SUBMIT CALCULATIONS
FOR SUBSTITUTIONS
ADHESIVE
(IN CONCRETE W/>12"
EMBEDMENT)
HILTI HIT-RE 500 SD -- -- SUBMIT CALCULATIONS
FOR SUBSTITUTIONS
STEEL NOTES
1. CONNECTIONS:
1A.PROVIDE CONNECTIONS AS SHOWN IN THE ‘STEEL BEAM CONNECTION SCHEDULES’ AND DETAILS
HEREIN.
2. WELDING REQUIREMENTS:
2A.WELDERS: HAVE IN POSSESSION CURRENT EVIDENCE OF PASSING THE APPROPRIATE AWS.
QUALIFICATION TESTS.
2B.MINIMUM WELDS: AISC SPECIFICATION, NOT LESS THAN 3/16” FILLET, CONTINUOUS UNLESS
OTHERWISE NOTED.
2C.WELD SIZES AND LENGTHS CALLED FOR ON THE DRAWINGS ARE THE NET EFFECTIVE REQUIRED.
INCREASE WELD SIZE IF GAPS EXIST AT THE FAYING SURFACE.
2D.WELD SIZES SHALL BE AS SHOWN UNLESS A GREATER SIZE IS REQUIRED BY ANSI/AISC 360-10 TABLES
J2.3 AND J2.4.
2E.ALL GROOVE WELDS SHALL BE COMPLETE PENETRATION UNLESS NOTED.
2F.FIELD WELDING SYMBOLS INDICATE SUGGESTED CONSTRUCTION PROCEDURES.
3. STRUCTURAL STEEL INSTALLATION:
3A.ALL HIGH STRENGTH BOLTS WHERE NOTED ON THE DRAWINGS AS TYPE “SC” OR OTHER TYPE
FOLLOWED BY “PT”, SHALL BE TENSIONED TO THE VALUES OF TABLE J3.1 OF ANSI/AISC 360-10 . OTHER
HIGH-STRENGTH BOLTS MAY BE INSTALLED SNUG TIGHT AS DEFINED BY AISC.
WOOD NOTES
1. LAMINATED MEMBER SIZES:
1A.LVL, PSL, LSL, GLU-LAM AND AND OTHER FABRICATED MEMBERS (TJI) SIZES SHOWN ARE NET. OTHER
MEMBER SIZES ARE NOMINAL.
2. FRAMING LUMBER:
2A.DRY (19% MAXIMUM MOISTURE CONTENT AT THE TIME OF INSTALLATION), DOUGLAS FIR-LARCH WITH
MINIMUM DESIGN VALUES BASED ON THE 2012 NDS. SEE ‘FRAMING LUMBER TABLE’ FOR MINIMUM GRADES.
2B.BEAMS AND STRINGERS USED WITH CANTILEVERS OR CONTINUOUS SPANS SHALL BE GRADED TO
PROVIDE THE SPECIFIED ALLOWABLE STRESSES OVER THE ENTIRE MEMBER LENGTH.
3. FABRICATED LUMBER:
3A.FABRICATED LUMBER DESIGNATIONS ARE THOSE MANUFACTURED BY WEYERHAEUSER.
3B.FABRICATED LUMBER IS DESIGNATED ON THE DRAWINGS AS ONE OF THE FOLLOWING: TJI JOISTS,
MICROLLAM (LVL), PARALLAM (PSL), TIMBERSTRAND (LSL) OR RIMBOARD.
3C.THE MANUFACTURER SHALL PROVIDE WEB STIFFENERS ON I-JOISTS, END BLOCKING, BRIDGING, AND
ERECTION BRACING AS REQUIRED. SEE “DESIGN CRITERIA” FOR DESIGN DEAD AND LIVE LOADS.
3D.FABRICATED LUMBER SHALL BE DRY.
3E.SEE ‘FABRICATED LUMBER TABLE’ FOR MINIMUM PROPERTIES (AT NORMAL LOAD DURATIONS).
3F.FABRICATED RIMBOARD SHALL BE LAMINATED STRAND LUMBER.
3G.SEE ‘RIMBOARD TABLE’ FOR MINIMUM PROPERTIES.
4. GLUED LAMINATED MEMBERS:
4A.COMBINATION SYMBOL:
- SINGLE SPAN: [24F-V4]
- MULTI- SPAN: [24F-V8]
4B.MINIMUM DESIGN VALUES ARE BASED ON THE 2012 NDS.
5. SHEATHING:
5A.WOOD STRUCTURAL PANELS (WSP)
- WOOD STRUCTURAL PANELS SHALL BE APA RATED SHEATHING CONFORMING TO U.S. DEPARTMENT OF
COMMERCE STANDARD PS-2 AND APA PERFORMANCE STANDARD PRP-108, LATEST EDITIONS.
- ALL WOOD PANELS SHALL BE EXPOSURE 1.
6. BLOCKING AND BRIDGING:
6A.PROVIDE FULL HEIGHT SOLID BLOCKING (MINIMUM WIDTH TO MATCH WIDTH OF FRAMING) BETWEEN ALL
FRAMING MEMBERS (SOLID SAWN JOISTS AND RAFTERS, FABRICATED JOISTS AND RAFTERS AND TRUSSES)
AT SUPPORTS.
7. NAILING:
7A.UNLESS NOTED OTHERWISE ON THE DRAWINGS, PROVIDE BOX NAILS COMMON NAILS WITH SIZES SHOWN
IN THE TABLE BELOW. MINIMUM NAILING SHALL BE IN ACCORDANCE WITH THE TYPICAL WOOD CONNECTION
SCHEDULE AND IBC 2012 TABLE 2304.9.1.
7B.WHERE COMMON NAILS ARE SPECIFIED, BOX NAILS OF EQUAL LENGTH MAY BE SUBSTITUTED PROVIDED
ONE BOX NAIL IS ADDED FOR EVERY THREE COMMON NAILS SPECIFIED.
8. METAL CONNECTORS:
8A.FRAMING CONNECTORS SHALL CONFORM TO IBC 2012 SECTION 1711.1. FRAMING CONNECTOR
DESIGNATIONS ARE THOSE MANUFACTURED BY SIMPSON STRONG-TIE COMPANY, SAN LEANDRO,
CALIFORNIA. OTHER MANUFACTURER’S PRODUCTS MAY BE USED IF APPROVED BY THE ENGINEER. FURNISH
NAILS AND/OR BOLTS OF DIAMETER, LENGTH, AND NUMBER SPECIFIED BY THE MANUFACTURER FOR EACH
CONNECTOR.
8B.ALL CONNECTOR HOLES SHALL BE FILLED WITH PROPER NAILS/BOLTS INCLUDING OPTIONAL NAIL
LOCATIONS FOR UPLIFT. ALL BOLT HOLES SHALL BE DRILLED INTO FRAMING MEMBERS. MAXIMUM HOLE
DIAMETER IS 1/16” LARGER THAN THE BOLT DIAMETER.
9. OPENINGS:
9A.OPENING, POCKETS, ETC., SHALL NOT BE PLACED IN BEAMS, JOISTS, RAFTERS, STUDS, POSTS,
COLUMNS, TIMBER AND OTHER STRUCTURAL MEMBERS UNLESS DETAILED ON THE STRUCTURAL
DRAWINGS.
PRODUCT
FABRICATED LUMBER TABLE
DEPTH
11 7/8"
TYPE
MR
(FT-
LB)
11 7/8" TJI-210
VR
(LBS)
EI (x10
^6 in^
2-lbs)
3 1/2" END
REACTION
(LBS)
INTERMEDIATE
REACTION
(LBS)REMARKS
TYPE OF USE
LSL FRAMING LUMBER SCHEDULE
GRADE
EXTERIOR STUDS 1.3E
LOAD BEARING STUDS (AND COLUMNS
ASSEMBLED FROM STUDS)
NON-LOAD BEARING STUDS
ROOF JOIST & RAFTERS
BEAMS & STRINGERS
FLOOR-JOIST
EXPOSED FRAMING
DECKING
POSTS & TIMBER
LSL MEMBERS DEEPER THAN 5 1/2"
Fb (PSI) Fv (PSI) E (PSI)
1,700 425 1,300,000
I-JOIST 3,795 1,655 315 1,655 2,505 --
11 7/8"11 7/8" TJI-360 I-JOIST 6,180 1,705 419 1,705 2,815 --
14"14" TJI-360 I-JOIST 7,335 1,955 612 1,865 2,815 --
1.3E 425 1,300,000
1.3E 425 1,300,000
1.3E 425 1,300,000
1.3E 425 1,300,000
1.3E 425 1,300,000
1.3E 425 1,300,000
1.3E 425 1,300,000
1.3E 425 1,300,000
1.5E 2,250 505 1,500,000
9 1/2"5 1/4" PSL BEAM 19,585 9,645 750 -- -- --
11 7/8"5 1/4" PSL BEAM 29,855 12,055 1,466 -- -- --
16"5 1/4" PSL BEAM 52,430 16,240 3,584 -- -- --
1,700
1,700
1,700
1,700
1,700
1,700
1,700
1,700
5 1/4"5 1/4" PSL GIRT 5507 4,226 76 -- -- --
No. Description Date
PERMIT SET 07.02.2015