HomeMy WebLinkAboutF14-0009 calcs.pdf Fire Sprinkler System Calculations For Charter Sports @Cascade Vail 1300 Westhaven Dr. Vail, CO 81657 Western States Fire Protection Co. 7026 S. Tucson Way Centennial, CO 80112 Office: (303) 792-0022 Fax: (303) 792-9049 WSFP# CS2268 April 16, 2014 Hydraulic Overview Job Number: CS2268 Report Description: Ordinary Group II Node Flow(gpm)Hose Flow(gpm)Static(psi)Residual(psi)Name 10 534.2 250.0 110.0 53.3Water Supply Identifier Pressure(psi)K-Factor(K)Flow(gpm) Job System Supplies Check Point Gauges CS2268 Charter Sports @ Cascade Vail 1300 Westhaven Dr Vail, CO CS2268 Charter Sports @ Cascade Vail Job Name: Address 1 Address 2 Design Engineer Phone FAX State Certification/License Number AHJ Job Site/Building Most Demanding Sprinkler Data Coverage Per Sprinkler System Pressure Demand Total Demand Area of Application Hose Streams Number Of Sprinklers Calculated System Flow Demand Pressure Result Job Number 537.3 @ 44.0 Water Supply at Node 10 (534.2, 250.0, 110.0, 53.3) 0.20gpm/ft² 5.6 K-Factor 26.0 at 21.6 225.00ft² 44.0 967.00ft² (Actual 971.09ft²) 250.0 12 287.3 Density +8.7 (16.4%) Address 3 © M.E.P.CAD, Inc.4/16/2014 Page 1AutoSPRINK® VR11 v11.0.30.0 5:39:21PM Hydraulic Graph Report Description: Ordinary Group II Job Number: CS2268 System Demand (Including Hose Allowance at Source) System Demand 53.3 @ 534.2 Residual: Pressure 110.0 Static: Pressure Water Supply at Node 10 Hydraulic Graph Water Supply at Node 10 44.0 @ 287.3 44.0 @ 537.3 Available Pressure at Time of Test 52.7 @ 537.3 © M.E.P.CAD, Inc.4/16/2014 Page 2AutoSPRINK® VR11 v11.0.30.0 5:39:23PM Device (gpm) Actual Flow Minimum Flow (gpm) (K) K-Factor (psi) Pressure Summary Of Outflowing Devices Report Description: Ordinary Group II Job Number: CS2268 Sprinkler 101 26.0 26.0 5.6 21.6 Sprinkler 102 26.1 26.0 5.6 21.6 Sprinkler 103 26.3 26.0 5.6 22.1 Sprinkler 104 26.4 26.0 5.6 22.1 Sprinkler 105 21.8 18.0 5.6 15.2 Sprinkler 106 21.9 14.4 5.6 15.3 Sprinkler 107 22.1 14.8 5.6 15.6 Sprinkler 108 22.1 14.1 5.6 15.6 Sprinkler 109 22.2 14.1 5.6 15.7 Sprinkler 110 22.9 14.8 5.6 16.7 Sprinkler 111 25.3 18.0 5.6 20.4 Sprinkler 112 24.3 14.1 5.6 18.8 Most Demanding Sprinkler Data © M.E.P.CAD, Inc.4/16/2014 Page 3AutoSPRINK® VR11 v11.0.30.0 5:39:25PM Pipe Type Diameter Flow Velocity Friction Loss Length Pressure Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq. Length Summary Upstream Total Length HWC Hydraulic Analysis Job Number: CS2268 Report Description: Ordinary Group II • • • • • Route 1 • • • • • Pf Pe Pv BL 1.049 26.0 9.65 0.211435 0'-6 0.5 101 12'-6 26.0 5.6 21.6 2'-0 -0.2 1 13'-0 21.9 2'-6 120 Sprinkler, E(2'-0) Pf Pe Pv BL 1.380 26.0 5.58 0.055609 13'-0 0.7 1 13'-0 21.9 2 13'-0 22.6 13'-0 120 Pf Pe Pv BL 1.380 52.1 11.17 0.200832 6'-7½2.5 2 13'-0 26.1 22.6 6'-0 3 13'-0 25.1 12'-7½ 120 Flow (q) from Route 2 PO(6'-0) Pf Pe Pv FM 3.260 104.7 4.02 0.011123 6'-6 0.1 3 13'-0 52.7 25.1 4 13'-0 25.2 6'-6 120 Flow (q) from Route 3 Pf Pe Pv FM 3.260 149.7 5.75 0.021548 6'-0 0.1 4 13'-0 45.0 25.2 5 13'-0 25.3 6'-0 120 Flow (q) from Route 7 Pf Pe Pv FM 3.260 218.3 8.39 0.043303 14'-0 0.6 5 13'-0 68.6 25.3 6 13'-0 25.9 14'-0 120 Flow (q) from Route 8 Pf Pe Pv FM 3.260 287.3 11.04 0.071988 16'-10¾2.6 6 13'-0 69.0 25.9 18'-9¾ 7 13'-0 28.5 35'-8-5/8 120 Flow (q) from Route 5 2E(9'-4-7/8) Pf Pe Pv FR 4.260 287.3 6.47 0.019562 30'-5-5/8 1.9 7 13'-0 28.5 65'-10 6.4 8 -1'-9-5/8 36.8 96'-3-5/8 120 5E(13'-2) Pf Pe Pv FR 6.357 287.3 2.90 0.002785 26'-7¼9.8 8 -1'-9-5/8 36.8 70'-4-7/8 2.1 9 -6'-8-7/8 48.8 97'-0-1/8 120 4E(17'-7¼), BFP(-8.1), PRV(-1.5) Pf Pe Pv FR 8.270 287.3 1.72 0.000581 32'-11¼0.0 9 -6'-8-7/8 48.8 18'-0 -4.8 10 4'-2¾44.0 50'-11¼ 140 E(18'-0), S 537.3 250.0 Hose Allowance At Source 10 • • • • • Route 2 • • • • • Pf Pe Pv BL 1.049 26.1 9.67 0.212201 0'-6 1.2 102 12'-6 26.1 5.6 21.6 5'-0 -0.2 2 13'-0 22.6 5'-6 120 Sprinkler, T(5'-0) • • • • • Route 3 • • • • • Pf Pe Pv BL 1.049 26.3 9.76 0.215992 0'-6 0.5 103 12'-6 26.3 5.6 22.1 2'-0 -0.2 11 13'-0 22.4 2'-6 120 Sprinkler, E(2'-0) Pf Pe Pv BL 1.380 26.3 5.64 0.056807 13'-0 0.7 11 13'-0 22.4 12 13'-0 23.1 13'-0 120 Pf Pe Pv BL 1.380 52.7 11.29 0.205160 6'-7½2.0 12 13'-0 26.4 23.1 3'-0 13 13'-0 25.1 9'-7½ 120 Flow (q) from Route 4 E(3'-0) Pf Pe Pv FM 3.260 52.7 2.02 0.003118 10'-0 0.0 13 13'-0 25.1 3 13'-0 25.1 10'-0 120 • • • • • Route 4 • • • • • Pf Pe Pv BL 1.049 26.4 9.78 0.216773 0'-6 1.2 104 12'-6 26.4 5.6 22.1 5'-0 -0.2 12 13'-0 23.1 5'-6 120 Sprinkler, T(5'-0) • • • • • Route 5 • • • • • Pf Pe Pv BL 1.049 21.8 8.10 0.152760 0'-6 0.8 105 12'-6 21.8 5.6 15.2 5'-0 -0.2 14 13'-0 15.8 5'-6 120 Sprinkler, T(5'-0) Pf Pe Pv BL 1.049 43.7 16.23 0.552863 10'-0 5.5 14 13'-0 21.9 15.8 15 13'-0 21.3 10'-0 120 Flow (q) from Route 6 Pf Pe Pv BL 1.380 69.0 14.81 0.338545 7'-7½4.6 15 13'-0 25.3 21.3 6'-0 6 13'-0 25.9 13'-7½ 120 Flow (q) from Route 11 PO(6'-0) • • • • • Route 6 • • • • • Pf Pe Pv BL 1.049 21.9 8.13 0.153961 3'-2½0.5 106 13'-0 21.9 5.6 15.3 14 13'-0 15.8 3'-2½ 120 Sprinkler • • • • • Route 7 • • • • • Pf Pe Pv BL 1.049 22.1 8.21 0.156589 11'-0 2.0 107 12'-6 22.1 5.6 15.6 2'-0 -0.2 16 13'-0 17.4 13'-0 120 Sprinkler, E(2'-0) © M.E.P.CAD, Inc.4/16/2014 Page 4AutoSPRINK® VR11 v11.0.30.0 5:39:28PM Pipe Type Diameter Flow Velocity Friction Loss Length Pressure Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq. Length Summary Upstream Total Length HWC Hydraulic Analysis Job Number: CS2268 Report Description: Ordinary Group II Pf Pe Pv BL 1.049 45.0 16.70 0.583040 8'-4½7.8 16 13'-0 22.9 17.4 5'-0 4 13'-0 25.2 13'-4½ 120 Flow (q) from Route 10 PO(5'-0) • • • • • Route 8 • • • • • Pf Pe Pv BL 1.049 22.1 8.21 0.156589 9'-6-1/8 2.0 108 12'-6 22.1 5.6 15.6 3'-0 -0.2 17 13'-0 17.3 12'-6-1/8 120 Sprinkler, E(2'-0), EE(1'-0) Pf Pe Pv BL 1.049 44.3 16.45 0.566904 6'-0-7/8 3.4 17 13'-0 22.2 17.3 18 13'-0 20.8 6'-0-7/8 120 Flow (q) from Route 9 Pf Pe Pv BL 1.380 68.6 14.72 0.334709 7'-7½4.6 18 13'-0 24.3 20.8 6'-0 5 13'-0 25.3 13'-7½ 120 Flow (q) from Route 12 PO(6'-0) • • • • • Route 9 • • • • • Pf Pe Pv BL 1.049 22.2 8.24 0.157922 4'-6 1.8 109 12'-6 22.2 5.6 15.7 7'-0 -0.2 17 13'-0 17.3 11'-6 120 Sprinkler, E(2'-0), T(5'-0) • • • • • Route 10 • • • • • Pf Pe Pv BL 1.049 22.9 8.49 0.166950 0'-6 0.9 110 12'-6 22.9 5.6 16.7 5'-0 -0.2 16 13'-0 17.4 5'-6 120 Sprinkler, T(5'-0) • • • • • Route 11 • • • • • Pf Pe Pv BL 1.049 25.3 9.40 0.201208 0'-6 1.1 111 12'-6 25.3 5.6 20.4 5'-0 -0.2 15 13'-0 21.3 5'-6 120 Sprinkler, T(5'-0) • • • • • Route 12 • • • • • Pf Pe Pv BL 1.049 24.3 9.02 0.186458 4'-7½2.2 112 12'-6 24.3 5.6 18.8 7'-0 -0.2 18 13'-0 20.8 11'-7½ 120 Sprinkler, E(2'-0), T(5'-0) 1.51 4.87 )(150 1.33 140 1.16 130 0.713 100 Equivalent Pipe Lengths of Valves and Fittings (C=120 only) Actual Inside Diameter Schedule 40 Steel Pipe Inside Diameter = Factor C Value Multiplier Value Of C Multiplying Factor © M.E.P.CAD, Inc.4/16/2014 Page 5AutoSPRINK® VR11 v11.0.30.0 5:39:28PM Pipe Type Diameter Flow Velocity Friction Loss Length Pressure Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq. Length Summary Upstream Total Length HWC Hydraulic Analysis Job Number: CS2268 Report Description: Ordinary Group II Pipe Type Legend AO Arm-Over BL Branch Line CM Cross Main DN Drain DR Drop DY Dynamic FM Feed Main FR Feed Riser MS Miscellaneous OR Outrigger RN Riser Nipple SP Sprig ST Stand Pipe UG Underground Units Legend Diameter Inch Elevation Foot Flow gpm Discharge gpm Velocity fps Pressure psi Length Foot Friction Loss psi/Foot HWC Hazen-Williams Constant Pt Total pressure at a point in a pipe Pn Normal pressure at a point in a pipe Pf Pressure loss due to friction between points Pe Pressure due to elevation difference between indicated points Pv Velocity pressure at a point in a pipe Fittings Legend ALV Alarm Valve AngV Angle Valve b Bushing BalV Ball Valve BFP Backflow Preventer BV Butterfly Valve C Cross Flow Turn 90° cplg Coupling Cr Cross Run CV Check Valve DelV Deluge Valve DPV Dry Pipe Valve E 90° Elbow EE 45° Elbow Ee1 11¼° Elbow Ee2 22½° Elbow f Flow Device fd Flex Drop FDC Fire Department Connection fE 90° FireLock(TM) Elbow fEE 45° FireLock(TM) Elbow flg Flange FN Floating Node fT FireLock(TM) Tee g Gauge GloV Globe Valve GV Gate Valve Ho Hose Hose Hose HV Hose Valve Hyd Hydrant LtE Long Turn Elbow mecT Mechanical Tee Noz Nozzle P1 Pump In P2 Pump Out PIV Post Indicating Valve PO Pipe Outlet PRV Pressure Reducing Valve PrV Pressure Relief Valve red Reducer/Adapter S Supply sCV Swing Check Valve Spr Sprinkler St Strainer T Tee Flow Turn 90° Tr Tee Run U Union WirF Wirsbo WMV Water Meter Valve Z Cap © M.E.P.CAD, Inc.4/16/2014 Page 6AutoSPRINK® VR11 v11.0.30.0 5:39:28PM The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 Model F1FR Series Quick Response Standard Spray Bulletin 014 Rev. KBulletin 014 Rev. K Model F1FR56 Sprinkler Types Standard Upright Standard Pendent Conventional Vertical Sidewall Horizontal Sidewall Model F1FR56 Recessed Sprinkler Types Standard Pendent/F1/F2/FP Horizontal Sidewall Model F1FR56 Concealed Sprinkler Types Standard Pendent Model F1FR42, F1FRXLH & F1FR28 Sprinkler Types Standard Upright Standard Pendent Model F1FR42, F1FRXLH & F1FR28 Recessed Sprinkler Types Standard Pendent Model F1FR56LL & F1FR42LL Low Lead Sprinkler Types* Standard Pendent Less than 0.25% Lead Content Listing & Approvals 1. Underwriters Laboratories Inc. and Certified for Canada (cULus). 2. Factory Mutual Approvals (FM) 3. Loss Prevention Council (LPCB, UK) 4. VdS Schadenverhütung GmbH 5. *NSF Certified to NSF/ANSi Standard 61 Annex G UL Listing Category Sprinklers, Automatic & Open (VNIV) Quick Response Sprinkler Product Description Reliable Models F1FR56, F1FR56LL, F1FR42, F1FR42LL, F1FRXLH & F1FR28 Series Sprinklers are quick response sprinklers which combine the durability of a standard sprin- kler with the attractive low profile of a decorative sprinkler. The Models F1FR56, F1FR56LL, F1FR42, F1FR42LL, F1FRXLH & F1FR28 Series Recessed automatic sprinklers utilize a 3.0 mm frangible glass bulb. These sprinklers have demonstrated response times in laboratory tests which are five to ten times faster than standard response sprinklers. This quick response enables the Model F1FR56, F1FR56LL, F1FR42, F1FR42LL, F1FRXLH & F1FR28 Series sprinklers Pendent Conventional Recessed Pendent/F1/F2 Upright Vertical Sidewall Horizontal Sidewall Recessed Horizontal Sidewall Recessed Pendent/FP Concealed Pendent XLH Upright XLH Pendent XLH Recessed Pendent F1/F2 XLH Recessed Pendent FP to apply water to a fire much faster than standard sprinklers of the same tem- perature rating. The glass bulb consists of an accu- rately controlled amount of special fluid hermetically sealed inside a precisely manufactured glass capsule. This glass bulb is specially constructed to provide fast thermal response. At normal temperatures, the glass bulb contains the fluid in both the liquid and vapor phases. The vapor phase can be seen as a small bubble. As heat is applied, the liquid expands, forcing the bubble smaller and smaller as the liq- uid pressure increases. Continued heating forces the liquid to push out against the bulb, causing the glass to shatter, opening the waterway and allowing the deflector to distrib- ute the discharging water. 2. Technical data: Models Discharge Coeffi cient Response Thread Size Max. Working Pressure Min. Working Pressure Temperature Rating Finish F1FR56 **F1FR56LL(1)K 5.6 Quick Response 1/2” NPT (R1/2) 175 PSI 7 PSI See “Temperature Ratings” Table. See “Finish Table” F1FR42 **F1FR42LL(1) F1FRXLH K 4.2 F1FR28 K 2.8 (1) Low Lead Sprinklers available only with Temperature Rating 200°F/93°C Material Data: Frame Defl ector Load Screw *Pintle Cup Washer Bulb DZR Brass QM Brass **Low Lead Brass CDA Alloy 260, CDA Alloy 220 or CDA Alloy510 CDA Alloy 360 or CDA Alloy 544 CDA Alloy 360 or CDA Alloy 544 CDA Alloy 651 or CDA Alloy 693 Nickel Alloy 440 or Alloy 360 coated with PTFE Adhesive Tape Glass Application Quick response sprinklers are used in fixed fire protection systems: Wet, Dry, Deluge or Preaction. Care must be exercised that the orifice size, temperature rating, deflector style and sprinkler type are in accordance with the latest published standards of the National Fire Protection Association or the approving Authority Having Jurisdiction. Quick response sprinklers are intended for installation as specified in NFPA 13. Quick response sprinklers and standard re- sponse sprinklers should not be intermixed. Model F1FR42, F1FRXLH Upright Pendent ConventionalUpright Model F1FR56, Upright, Pendent & Conventional Sprinklers Model F1FR42, F1FRXLH & F1FR28 Upright & Pendent Sprinklers Installation Wrench: Model D Sprinkler Wrench Installation Data: Nominal Orifi ce Thread Nominal K Factor Sprinkler Approval Sprinkler Identifi cation Number (SIN) Size US Metric Height Organization Upright Pendent Standard-Upright (SSU) and Pendent Deflectors Marked to Indicate Position 1/2” (15mm) (1)1/2” NPT (R1/2) 5.6 80 2.25” (57mm) 1,2,3,4 RA1425 (1)(2)(3)(4)RA1414(1)(2)(3)(4) 7/16” (10mm) 1/2” NPT (R1/2) 4.2 60 2.25” (57mm) 1 RA1423 (1)(4)RA1413(4) 3/8” (10mm) 1/2” NPT (R1/2) 2.8 40 2.25” (57mm) 1 RA1421 (1)(4)RA1411(4) Conventional-Install in Upright or Pendent Position 15mm (1)1/2” NPT (R1/2) 5.6 80 57mm 3, 4 RA1475 (3) (1) cULus listed corrosion resistant (Polyester coated) sprinkler. (2) Polyester coated FM approved sprinkler. (3) Polyester coated LPCB & VdS approved sprinkler RA1425, RA1414 & RA1475. (4) Electroless Nickel PTFE (Teflon®)* Plated - cULus listed Corrosion Resistant 3. Model F1FR56LL & F1FR42LL Pendent Sprinklers Installation Wrench: Model D Sprinkler Wrench Installation Data: Nominal Orifi ce Thread Nominal K Factor Sprinkler Approval Sprinkler Identifi cation Number (SIN) Size US Metric Height Organization Pendent Standard-Pendent Deflectors Marked to Indicate Position 1/2” (15mm) (1)1/2” NPT (R1/2) 5.6 80 2.25” (57mm) 1,5 RA1415 7/16” (11mm) 1/2” NPT (R1/2) 4.2 60 2.25” (57mm) 1,5 RA1410 (1) cULus listed corrosion resistant (Polyester coated) sprinkler. *DuPont Registered Trademark Model F1FR56 Quick Response Vertical Sidewall Sprinkler Installation Wrench: Model D Sprinkler Wrench Installation Position: Upright or Pendent Approval Type: Light Hazard Occupancy Installation Data: Nominal Orifi ce Thread Size Nominal K Factor Sprinkler Height Approval Organizations Sprinkler Identifi cation Numbers (SIN)US Metric ½” (15mm) ½” NPT (R1/2) 5.6 80 2.25” (57mm) 1,2,3,4 RA1485(2)(3) 15mm ½” NPT (R1/2) 5.6 80 2.25” (57mm) 4 (1) (1) LPC Approval is for pendent position only. (2) cULus Listed corrosion resistant (Polyester coated) sprinkler. (3) Electroless Nickel PTFE (Teflon®)* Plated - cULus listed Corrosion Resistant Sprinkler Type Defl ector to Ceiling Distance (Min. - Max.) Upright 4” (102mm) - 12” (305mm) Pendent 4” (102mm) - 12” (305mm) Vertical Sidewall Model F1FR56, F1FR56LL, F1FR42, F1FR42LL, F1FRXLH & F1FR28 F1 or F2 Model F1FR56, F1FR56LL, F1FR42, F1FR42LL, F1FRXLH & F1FR28 FP Model F1FR56, F1FR42, F1FRXLH & F1FR28 Quick Response Recessed Pendent Sprinkler(1) Installation Wrench: Model GFR2 Sprinkler Wrench Installation Data: Nominal Orifi ce Thread Size K Factor Sprinkler Height Sprinkler Identifi cation Number (SIN)US Metric 1/2” (15mm) 1/2” NPT(R½) 5.6 80 2.25” (57mm) RA1414 7/16” (10mm) 1/2” NPT (R1/2) 4.2 60 2.25” (57mm) RA1413 3/8” (10mm) 1/2” NPT (R1/2) 2.8 40 2.25” (57mm) RA1411 (1) Refer to escutcheon data table for approvals & dimensions Model F1FR56LL & F1FR42LL Quick Response Recessed Pendent Sprinkler(1) Installation Wrench: Model GFR2 Sprinkler Wrench Installation Data: Nominal Orifi ce Thread Size K Factor Sprinkler Height Sprinkler Identifi cation Number (SIN)US Metric 1/2” (15mm) 1/2” NPT(R½) 5.6 80 2.25” (57mm) RA1415 7/16” (10mm) 1/2” NPT (R1/2) 4.2 60 2.25” (57mm) RA1410 (1) Refer to escutcheon data table for approvals & dimensions 4.*DuPont Registered Trademark 5. Model F1FR56 Quick Response Horizontal Sidewall Sprinkler Defl ector: HSW Installation Wrench: Model D Sprinkler Wrench Installation Data: Horizontal Sidewall Nominal Orifi ce Thread Size Nominal K Factor Sprinkler Height Approval Organizations and Type of Approval Sprinkler Identifi cation Numbers (SIN)US Metric Light Hazard Ordinary Hazard ½” (15mm) ½” NPT (R1/2) 5.6 80 2.63” (67mm) 1,2 1 RA1435 (1)(2)(3) (1) cULus Listed corrosion resistant (Polyester coated) sprinkler. (2) Polyester coated FM approved sprinkler. (3) Electroless Nickel PTFE (Teflon®)* Plated - cULus listed Corrosion Resistant Horizontal Sidewall Note: For Recessed HSW Sprinklers use installation wrench GFR2. cULus permits use with F1, F2 or FP escutcheons for “Light Hazard” only. While FM limits use for the same hazard with the F2 escutcheon only. Model F1FR56 Quick Response Concealed Pendent Sprinklers Installation Wrench: Model RC1 Sprinkler Wrench Technical Data: Nominal Orifi ce “K” Factor Thread Size Model Temp. Rating Max. Ambient Temp Bulb Color Approvals Sprinkler Identifi cation Number(SIN)US Metric Sprinkler Cover ½” (15mm) 5.6 80 ½” NPT F1FR 135°F/57°C 135°F/57°C 100°F/38°C Orange 1 RA1414 ½” (15mm) 5.6 80 ½” NPT F1FR 155°F/68°C 135°F/57°C 100°F/38°C Red 1, 4 (1)RA1414 ½” (15mm) 5.6 80 ½” NPT F1FR 175°F/79°C 165°F/74°C 100°F/38°C Yellow 1 RA1414 ½” (15mm) 5.6 80 ½” NPT F1FR 200°F/93°C 165°F/74°C 150°F/65°C Green 1 RA1414 (1) For VdS only = 155°F/68°C Norbulb and 1/2” [12,7mm] adjustment. Model F1FR56LL Quick Response Concealed Pendent Sprinklers Installation Wrench: Model RC1 Sprinkler Wrench Technical Data: Nominal Orifi ce “K” Factor Thread Size Model Temp. Rating Max. Ambient Temp Bulb Color Approvals Sprinkler Identifi cation Number(SIN)US Metric Sprinkler Cover ½” (15mm) 5.6 80 ½” NPT F1FR56LL 200°F/93°C 165°F/74°C 150°F/65°C Green 1, 5 RA1414 *DuPont Registered Trademark Installation Aid A protective cap is included for use during installation. Important: The F1FR56 Sprinkler with Model CCP cover plate is not an FM Approved combination. Installation Quick response sprinklers are intended for installation as specified in NFPA 13. Quick response sprinklers and stan- dard response sprinklers should not be intermixed. The Model F1FR56, F1FR56LL, F1FR42, F1FR42LL, F1FRXLH & F1FR28 Recessed Quick Response Sprin- klers are to be installed as shown. The Model F1 or F2 Es- cutcheons illustrated are the only recessed escutcheons to be used with the Model F1FR56, F1FR56LL, F1FR42, F1FR42LL, F1FRXLH & F1FR28 Sprinklers. The use of any other recessed escutcheon will void all approvals and ne- gate all warranties. When installing Model F1FR56, F1FR56LL, F1FR42, F1FR42LL, F1FRXLH & F1FR28 Sprinklers, use the Model D Sprinkler Wrench. Use the Model GFR2 Wrench for install- ing F1FR56, F1FR56LL, F1FR42, F1FR42LL, F1FRXLH & F1FR28 Recessed Pendent Sprinklers. Any other type of wrench may damage these sprinklers. NOTE: A leak tight ½” NPT (R1/2) sprinkler joint can be obtained with a torque of 8-18 ft-lbs (10,8 - 24,4 N-m). Do not tighten sprinklers over maximum recommended torque. It may cause leakage or impairment of the sprinklers. The Models F1FR56/CCP & F1FR56LL/CCP Concealed Sprinkler use the ½” orifice, ½” NPT (R1/2), Model F1FR56 & F1FR56LL Pendent Sprinkler with a threaded Model CCP cup which is factory attached to the sprinklers. The Model F1FR56 Pndent is available in temperature rating of 135°F (57°C), 155°F (68°C), 175°F (79°C) or 200°F (93°C). The Model F1FR56LL Pendent is available only in a rating of 200°F (93°C). The concealed sprinkler assemblies are com- pleted by the installation of the attractive low profile Model CCP push on cover plate assembly, rated 135°F (57°C) or 165°F (74°C) for the F1FR56 and 165°F (74°C) for the FIFR56 LL. The cover plate and sprinkler cup assemblies are joined using a cover plate skirt with flexible tabs for threaded en- gagement. A choice of two cover plate assemblies provide either 1/2” (13mm) or 5/8” (8mm) of cover adjustment, Do not install these sprinklers in ceiling which have positive pressure in the space above. After a 25/8” (67mm) diameter hole is cut in the ceiling, the sprinkler is easily installed with the Model RC1 Wrench. A Teflon* based thread sealant should be applied to the sprin- kler threads only. The Model RC1 Wrench is then used to engage the sprinkler wrenching surfaces and to install the sprinkler in the fitting. When inserting or removing the wrench from the sprinkler/cup assembly, care should be tak- en to prevent damage to the sprinkler. DO NOT WRENCH ON ANY OTHER PART OF THE SPRINKLER. The cover plate is then pushed onto the cup. Final adjustment is made by hand turning the cover plate until the skirt flange makes full contact with the ceiling. Cover plate removal requires turning in the counter clockwise direction. After installation, inspect all sprinklers to ensure that there is a gap between the cover plate and ceiling and that the four cup slots are open and free from any air flow impedi- ment to the space above. Concealed cover plate/cup assemblies are listed only for use with specific sprinklers. The use of any other concealed cover plate/cup assembly with the Model F1FR56 Pendent Sprinkler or the use of the Model CCP Concealed cover plate assembly on any sprinkler with which it is not specifi- cally listed my prevent good fire protection and will void all guarantees, warranties, listings and approvals. Glass bulb sprinklers have orange bulb protectors to minimize bulb damage during shipping, handling and in- stallation. REMOVE THIS PROTECTION AT THE TIME THE SPRINKLER SYSTEM IS PLACED IN SERVICE FOR FIRE PROTECTION. Removal of the protectors before this time may leave the bulb vulnerable to damage. RASCO wrench- es are designed to install sprinklers when covers are in place. REMOVE PROTECTORS BY UNDOING THE CLASP BY HAND. DO NOT USE TOOLS TO REMOVE THE PRO- TECTORS. 6. *DuPont Registered Trade Mark Figure 1 Figure 2 Temperature Ratings Classifi cation Sprinkler Temperature Max. Ambient Temp.Bulb Color °C °F Ordinary Ordinary Intermediate Intermediate High (1) 57 68 79 93 141 135 155 175 200 286 100°F (38°C) 100°F (38°C) 150°F (66°C) 150°F (66°C) 225°F (107°C) Orange Red Yellow Green Blue (1) Not available for recessed sprinklers. Escutcheon Data (1) (1) SIN RA1435 – cULus permits use with F1, F2 or FP escutcheons for “light hazard” only, while FM limits use for same hazard with F2 escutcheon only. Maintenance The Model F1FR56, F1FR56LL, F1FR42, F1FR42LL, F1FRXLH and Model F1FR56, F1FR56LL, F1FR42, F1FR42LL, F1FRXLH & F1FR28 Recessed Sprinklers should be inspected and the sprinkler system maintained in accor- dance with NFPA 25. Do not clean sprinklers with soap and water, ammonia or any other cleaning fluids. Remove dust by using a soft brush or gentle vacuuming. Remove any sprinkler which has been painted (other than factory ap- plied) or damaged in any way. A stock of spare sprinklers should be maintained to allow quick replacement of dam- aged or operated sprinklers. Prior to installation, sprinklers should be maintained in the original cartons and packaging to minimize the potential for damage to sprinklers that would cause improper operation or non-operation. Sprinkler Types Standard Upright Standard Pendent Conventional Recessed Pendent Vertical Sidewall Horizontal Sidewall Recessed Horizontal sidewall Concealed pendent Maximum Working Pressure 175 psi (12 bar) 100% Factory tested hydrostatically to 500 psi (34.5 bar) Finishes (1) Standard Finishes Sprinkler Escutcheon Cover plate (1) Bronze Brass Chrome Chrome Plated Chrome White Polyester Plated Coated (4)(5)(6)White Painted Special Application Finishes Sprinkler Escutcheon Cover plate (1) Electroless Nickel PTFE(Teflon®)*(7) Electroless Nickel PTFE (Teflon®)* Bright Brass Bright Brass(3)Bright Brass Black Plating Black Plated Black Plated Black Paint Black Paint(2)(6)Black Paint Off White Off White(2)(6) Off White Satin Chrome Chrome Dull Chrome Dull (1) Other finishes and colors are available on special order. Consult the factory for details. Custom color painted sprinklers may not retain their UL Corrosion resistance listing. Coverplate custom paint is semi-gloss, unless specified otherwise. (2) cULus Listed only. (3) 200°F (93°C) maximum. (4) cULus listed “corrosion resistance” applies to SIN Numbers RA1435 (HSW), RA1485(VSW), RA1425 (Upright), RA1414 (Pendent) and RA1415 (Pendent) in standard black or white. Corrosion resistance in other polyester colors is available upon request. (5) FM Approvals finish as “Polyester coated” applies to SIN Number RA1414, RA1435 and RA1425 in standard black or white. (6) LPCB and VdS Approved finish applies only to RA1425, RA1414 and RA1475. (7) cULus listed Corrosion Resistant Ordering Information Specify: 1. Sprinkler Model 2. Sprinkler Type 3. Orifice Size 4. Deflector Type 5. Temperature Rating 6. Sprinkler Finish 7. Escutcheon Type 8. Escutcheon Finish (where applicable) 9. Cover plate Model 10. Cover plate Thread size 11. Cover plate Temperature 12. Cover plate Adjustment 13. Cover plate Finish Note: When Model F1FR56 Recessed sprinklers are ordered, the sprinklers and escutcheons are packaged separately. 7. *DuPont Registered Trademark Automatic sprinklers Flush automatic sprinklers Recessed automatic sprinklers Concealed automatic sprinklers Adjustable automatic sprinklers Dry automatic sprinklers Intermediate level sprinklers Open sprinklers Spray nozzles Alarm valves Retarding chambers Dry pipe valves Accelerators for dry pipe valves Mechanical sprinkler alarms Electrical sprinkler alarm switches Water flow detectors Deluge valves Detector check valves Check valves Electrical system Sprinkler emergency cabinets Sprinkler wrenches Sprinkler escutcheons and guards Inspectors test connections Sight drains Ball drips and drum drips Control valve seals Air maintenance devices Air compressors Pressure gauges Identification signs Fire department connection Reliable offers a wide selection of sprinkler components. Following are some of the many precision-made Reliable products that guard life and property from fire around the clock. Reliable...For Complete Protection The Reliable Automatic Sprinkler Co., Inc. (800) 431-1588 Sales Offices (800) 848-6051 Sales Fax (914) 829-2042 Corporate Offices www.reliablesprinkler.com Internet Address Manufactured by Recycled Paper Revision lines indicate updated or new data. EG. Printed in U.S.A. 04/14 P/N 9999970300 The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries. ES-A-C400/C400N/C400Z Features • Extremely Compact Design • 70% Lighter than Traditional Designs • 304 (Schedule 40) Stainless Steel Housing & Sleeve • Groove Fittings Allow Integral Pipeline Adjustment • Patented Link Check Provides Lowest Pressure Loss • Unmatched Ease of Serviceability • Available with Grooved Butterfly Valve Shutoffs • May be Used for Horizontal or N Pattern Installations • Replaceable Check Disc Rubber Job Name ________________________________________________ Contractor ______________________________________________ Job Location ______________________________________________ Approval _______________________________________________ Engineer _________________________________________________ Contractor’s P.O. No. ______________________________________ Approval _________________________________________________ Representative ___________________________________________ C400 OSY C400N BFG Ames product specifications in U.S. customary units and metric are ap prox i mate and are provided for reference only. For pre cise mea sure ments, please contact Ames Technical Service. Ames reserves the right to change or mod i fy product design, con struc tion, specifications, or ma te ri als without pri or notice and without incurring any obligation to make such changes and mod i fi ca tions on Ames products pre vi ous ly or sub se quent ly sold. The Colt C400, C400N, C400Z Reduced Pressure Zone Assemblies provide protection to the potable water system from contamination in accordance with national plumbing codes. The Colt C400, C400N, C400Z are normally used in health hazard applications for protection against backsiphonage, backpressure and the fouling of either check valve. Specifications The Colt C400, C400N, C400Z Reduced Pressure Zone Assemblies shall consist of two independent Link Check modules, a differential pressure relief valve located between and below the two modules, two drip tight shutoff valves, and required test cocks. Link Check modules and relief valve shall be contained within a sleeve accessible single housing constructed from 304 (Schedule 40) stainless steel pipe with groove end connections. Link Checks shall have reversible elastomer discs and in operation produce drip tight closure against the reverse flow of liquid caused by backpressure or backsiphonage. Assembly shall be Colt C400, C400N, C400Z as manufactured by the Ames Company. ColtTM Series C400, C400N, C400Z Reduced Pressure Zone Assemblies Sizes: 21⁄2" – 10" (65 – 250mm) www.amesfirewater.com IMPORTANT: INQUIRE WITH GOVERNING AUTHORITIES FOR LOCAL IN STAL LA TION RE QUIRE MENTS LEAD FREE* * The wetted surface of this product contacted by consumable water contains less than one quarter of one percent (0.25%) of lead by weight. Approvals For additional approval information please contact the factory or visit our website at www.amesfirewater.com Dimensions — Weights Configurations • Horizontal • “Z” pattern horizontal • “N” pattern horizontal Materials • Housing & Sleeve: 304 (Schedule 40) Stainless Steel • Elastomers: EPDM, Silicone and Buna ‘N’ • Link Checks: Noryl ®, Stainless Steel • Check Discs: Reversible Silicone or EPDM • Test Cocks: Bronze Body Nickel Plated • Pins & Fasteners: 300 Series Stainless Steel • Springs: Stainless Steel Noryl® is a registered trademark of SABIC Innovative PlasticsTM. C400 SIZE (DN) DIMENSIONS WEIGHT A C (OSY) C (NRS) D G H I J M P C400 C400N NRS OSY NRS OSY in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm lbs. kgs. lbs. kgs. lbs. kgs. lbs. kgs. 21⁄2 65 31 787 163⁄8 416 93⁄8 238 61⁄2 165 291⁄16 738 22 559 151⁄2 393 813⁄16 223 219⁄16 548 93⁄16 234 118 54 128 58 126 57 136 62 3 80 3111⁄16 805 187⁄8 479 101⁄4 260 611⁄16 170 301⁄4 768 223⁄4 578 171⁄8 435 93⁄16 233 231⁄8 587 101⁄2 267 134 61 148 67 147 67 161 73 4 100 3311⁄16 856 223⁄4 578 123⁄16 310 7 178 33 838 24 610 181⁄2 470 915⁄16 252 261⁄2 673 113⁄16 284 164 74 164 74 187 85 187 85 6 150 431⁄2 1105 301⁄8 765 16 406 81⁄2 216 443⁄4 1137 333⁄4 857 233⁄16 589 131⁄16 332 323⁄4 832 15 381 276 125 298 135 317 144 339 154 8 200 50 1270 373⁄4 959 1915⁄16 506 911⁄16 246 541⁄8 1375 405⁄8 1032 277⁄16 697 1511⁄16 399 371⁄8 943 173⁄16 437 441 200 483 219 516 234 558 253 10 250 571⁄2 1460 453⁄4 1162 2313⁄16 605 113⁄16 285 66 1676 50 1270 321⁄2 826 175⁄16 440 463⁄8 1178 20 508 723 328 783 355 893 405 950 431 A D C (open) G H J I P M Pressure — Temperature Tem per a ture Range: 33°F – 140°F (0.5°C – 60°C) Maximum Working Pres sure: 175psi (12.06 bar) Note: When installing a drain line on Series C400 backflow preventer use 400/500 air gap. See ES-A-AG/EL/TC for additional information. Available Models Suffix: NRS - non-rising stem resilient seated gate valves OSY - UL/FM outside stem and yoke resilient seated gate valves BFG - UL/FM grooved gear operated butterfly valves with tamper switch *OSY FxG - Flanged inlet gate connection and grooved outlet gate connection *OSY GxF - Grooved inlet gate connection and flanged outlet gate connection *OSY GxG - Grooved inlet gate connection and grooved outlet gate connection Available with grooved NRS gate valves - consult factory* Post indicator plate and operating nut available - consult factory* *Consult factory for dimensions B64.51013 M G H J I P C400N BFG/C400Z BFG SIZE (DN) DIMENSIONS WEIGHT G H I J M P C400N, C400Z in. mm in. mm in. mm in. mm in. mm in. mm in. mm lbs. kgs. 21⁄2 65 321⁄2 826 231⁄2 597 151⁄2 394 91⁄2 241 2113⁄16 555 1113⁄16 300 67 30 3 80 34 864 241⁄2 622 165⁄16 414 101⁄16 256 231⁄8 587 121⁄8 308 70 32 4 100 355⁄8 905 26 660 173⁄16 437 1015⁄16 279 2415⁄16 634 125⁄8 321 87 39 6 150 461⁄2 1181 3512⁄16 908 201⁄2 521 131⁄2 343 281⁄4 718 15 382 160 73 . Dimensions — Weights C400 BFG SIZE (DN) DIMENSIONS WEIGHT A C D P in. mm in. mm in. mm in. mm in. mm lbs. kgs. 4 100 2911⁄16 754 73⁄4 197 63⁄8 162 91⁄2 241 66 30 6 150 373⁄4 959 911⁄16 246 77⁄16 189 141⁄4 362 122 55 A C D P Capacity - C400 BFG * = Rated Flow ** = UL Tested kPa psi 172 25 138 20 103 15 69 10 34 5 0 0 0 100 200 300 400 500 600 700 800 gpm 0 380 760 1140 1520 1900 2280 2680 3040 lpm 15 fps 4.6 mps 4" (100 mm) kPa psi 110 16 96 14 83 12 69 10 55 8 41 6 28 4 14 2 0 0 0 200 400 600 800 1000 1200 1400 1600 gpm 0 760 1520 2280 3040 3800 4560 5300 6060 lpm 15 fps 4.6 mps 6" (150 mm) ****** ES-A-C400/C400N/C400Z 1006 © 2010 Ames Fire & Waterworks kPa psi 124 18 110 16 96 14 83 12 69 10 55 8 41 6 kPa psi 124 18 110 16 96 14 83 12 69 10 55 8 41 6 kPa psi 110 16 96 14 83 12 69 10 55 8 41 6 28 4 0 50 100 150 200 250 300 350 gpm 0 190 380 570 760 950 1140 1330 lpm 15 fps 4.6 mps kPa psi 110 16 96 14 83 12 69 10 55 8 41 6 kPa psi 179 26 152 22 124 18 96 14 69 10 41 6 0 100 200 300 400 500 gpm 0 380 760 1140 1520 1900 lpm 15 fps 4.6 mps 21⁄2" (65mm) 3" (80mm) * 0 300 600 900 1200 1500 gpm 0 1140 2280 3420 4560 5700 lpm 15 fps 4.6 mps 6" (150mm) 0 500 1000 1500 2000 2500 gpm 0 1900 3800 5700 7600 9500 lpm 15 fps 4.6 mps 8" (200mm) 0 100 200 300 400 500 600 700 800 gpm 0 380 760 1140 1520 1900 2280 2660 3040 lpm 15 fps 4.6 mps 4" (100mm) 0 500 1000 1500 2000 2500 3000 3500 gpm 0 1900 3800 5700 7600 9500 11400 13300 lpm fps mps 10" (250mm) * * * * * kPa psi 124 18 110 16 96 14 83 12 69 10 55 8 41 6 Z N H Z N H N Z H N Z H N Z H N Z H ** ** ** ** ** ** Capacity UL/FM Certified Flow Characteristics N&Z Flow characteristics collected using butterfly shutoff valves. See literatue S-Colt-400, 500 for gate valve flow characteristics * = Rated Flow ** = UL Tested Horizontal N - Pattern Z - Pattern www.amesfirewater.com A Watts Water Technologies Company USA: Backflow- 1427 N. Market Blvd • Suite #9 • Sacramento, CA 95834 • T: 916-928-0123 • F: 916-928-9333 Control Valves- 18550 Hansen Road • Houston, TX 77075 • T: 713-943-0688 • F: 713-944-9445 Canada: 5435 North Service Rd. • Burlington, ONT. L7L 5H7• T: 905-332-4090 • F: 905-332-7068 BERMAD Fire Protection 700 Series 700E Deluge Valve Data Description BERMAD 700E Deluge Valves are Y Type globe valves with integral unitized double chamber actuator that consists of one single moving assembly, which includes a diaphragm assembly, a flat seal disk and a stainless steel removable seat. These automatic water control valves are designed for high pressure service, in vertical or horizontal installations and are available in diameter sizes from 1½” to 16”; DN40 to DN400. The BERMAD 700E valves are used for water flow control in Deluge, Pressure Control Deluge, Preaction or Water/ Foam systems, and are manufactured from materials suitable for freshwater or alternative for seawater, foam concentrate or other corrosive fluids. The 700E Deluge Valve is held closed by system water pressure trapped in the control chamber. When the releasing system operates, pressure is released from the control chamber, and the seal disc opens to allow water to flow into the system. The 700E valve body design includes a single, full bore seat with unobstructed flow path, free of any in-line ribs, supporting cage, or stem guides. The 700E “Y Type” design provides high flow capabilities with minimum head loss. The integral unitized double-chambered actuator provides a combination of positive, immediate response with smooth hammer-free, drip-tight closing. The whole actuator can be easily removed for a quick in-line inspection and servicing. Valve actuation is accomplished by one moving assembly which includes a replaceable flat diaphragm, harnessed to the diaphragm assembly, a stainless steel stem and a flat seal disk assembly. The balanced seal-disk assembly with its resilient seal enables controlled actuation, high durability and perfect drip-tight sealing, even under harsh conditions. Accessories The BERMAD 700E Deluge Valve shall be trimmed with the original components and accessories per specification and in accordance with valve functions and applications. Where additional specifications and/or signaling devices are required for a specific application, refer to system data for the system used, and to the BERMAD data sheet and Installation, Operation & Maintenance for specific model required. Main Features ■ High Pressure Construction – 400 psi (28 bar) rating available ■ Integral unitized double chamber actuator with single moving assembly ■ In-line serviceable, field replaceable internals ■ Obstacle free, full bore ■ Available in corrosion resistant materials ■ Designed to be reset without opening the valve ■ Compatible with electric/hydraulic/pneumatic release and pressure control trim systems Approvals ■ UL Listed to UL 260 from 5 to 300 psi; 0.3 to 21 bar WP, 2” through 10”; DN50 through DN250 ■ ABS Approved for 300 psi; 21 bar WP, 1½” through 12”; DN40 through DN300 ■ Lloyd’s Register Type Approval for 300 psi; 21 bar WP, 1½” through 16”; DN40 through DN400 ■ Fire Test Certified to ISO 6182 part 5, 1½” through 16”; DN40 through DN400 Notes: 1. The 700E valve shall be trimmed with specific components & accessories. 2. The 700E valve must be installed and maintained in compliance with the most recent BERMAD publications. 1 BERMAD Fire Protection 700 Series700E Materials Specifications Construction Materials The BERMAD 700E valves are available in a variety of materials to ensure optimal suitability for a wide range of applications. For operation involving exposure to internal and/or external corrosive conditions, valves are constructed from corrosion-resistant materials making them suitable for use with seawater, brackish water, or corrosive environments such as seashore, petrochemical and other industrial facilities. Standard Configurations Item Number Description Firewater Valve 1 Cover Ductile Iron 2 Cover Bolt Stainless Steel 3 Cover Nut Stainless Steel 4 Separation Partition Ductile Iron 5 Stud Z.C. Plated Steel 6 Stud Nut Z.C. Plated Steel 7 Valve Body Ductile Iron 8 Spring S.S. 302 9 Removable Seat S.S. 304 10 Seal NBR (Buna-N) 11 Upper Plug (6-20”) Brass 12 Shaft Lock Nut S.S. 303 13 Shaft Nut S.S. 303 14 Diaphragm Washers S.S. 431 15 Diaphragm NBR (Buna-N) 16 Bearing Screw S.S. 303 17 Bearing Bronze 18 Shaft S.S. 303 19 Seal Disk S.S. 431 Specifications Castings■ Ductile Iron to ASTM A536 65-45-12 (coated)■ Cast Steel ASTM A216 Grade WCB (coated)■ Nickel Aluminum Bronze ASTM B148 C95800■ Stainless Steel 316 ASTM A351 Grade CF8M■ Super Duplex ASTM A890 Grade 5A■ Hastelloy C-276 Bolting:■ External Bolting: S.S.316 to ASTM A320 Gr.B8F Internal Wetted Parts:■ Stainless Steel 303 ASTM A582 95B S30300A■ Stainless Steel 304 ASTM A743 Grade CF8■ Stainless Steel 431 ASTM A743 Grade CA15M■ Bronze ASTM B505 Grade C83600 ■ Internal Spring - S.S. 302 Optional Internal Wetted Parts:■ Stainless Steel 316 ASTM A351 Grade CF8M■ Nickel Aluminum Bronze ASTM B148 C95800■ Monel 400■ Super Duplex ASTM A890 Grade 5A■ Hastelloy C-276■ Internal Spring - Inconel Elastomers (Diaphragm & Seals) ■ NBR, Polyamide fabric reinforced Nitrile (Buna-N), Temperature Rating 80°C■ EPDM, Polyamide fabric reinforced Ethylene-Propylene, Temperature Rating 90°C Coating■ Electrostatic Powder Coating Polyester■ High Built Epoxy Fusion-Bonded with UV Protection, Anti-Corrosion■ Color: Fire Red to RAL 3002 Note: Internal & External coating applied on Ductile Iron or Cast Steel Castings only. Material End Connection Standard Inlet & Outlet Class & Type Max. working pressure psi bar Ductile Iron Flanged ANSI B16.42 #150RF 250 17.4 Flanged ANSI B16.42 #300RF 400 28 Flanged ISO 7005-2 PN 16 235 16 Flanged ISO 7005-2 PN 25 365 25 Grooved ANSI C606 300 400 25 Threaded BSP/NPT 300/PN25 400 25 C.Steel, SS316, Duplex & Hastelloy Flanged ANSI B16.5 #150RF 250 17.4 Flanged ANSI B16.5 #300RF 400 28 Flanged ISO 7005-2 PN16 235 16 Flanged ISO 7005-2 PN25 365 25 Threaded BSP/NPT 300/PN25 400 25 Ni-Al Bronze Flanged ANSI B16.24 #150RF 250 17.4 Flanged ANSI B16.24 #300RF 400 28 Flanged ISO 7005-2 PN 16 235 16 Flanged ISO 7005-2 PN25 365 25 Notes 1. Factory pressure testing: Each valve is tested at 1.6 of pressure rating. 2. Water Temperature: 0.5 - 80ºC (33 - 122ºF) 3. Standard flange facing: Raised Face (RF), Serrated Finish. Flat Face (FF) flanges available on request. Pressure Rating 2 1 2 3 4 5 6 7 8 9 10 9 19 18 17 16 15 14 13 12 11 BERMAD Fire Protection 700 SeriesFP 700E Flow & Hydraulic Data gpm Flow RatePressure Loss0.1 1.0 10 100 1,000 0.5 40 65 50 500 5,000 psi 15.0 12.5 10.0 7.5 5.0 2.5 1.5 50 75 100 250 500 750 1,000 2,500 20,00015,00010,0005,000 7,500 m3/h bar 11/2”21/2” 2” 50 80 3” 100 4” 150 6” 200 8” 250 10” 300 12” 350 14” 400 16” Flow Chart Flow Properties DN 40-50 65 80 100 150 200 250 300 350 400 Inch 1½"-2” 2½" 3" 4" 6" 8" 10" 12" 14" 16"“Y”-TypeKv-Y 50 55 115 200 460 815 1,250 1,850 1,990 3,310 Cv-Y 58 64 133 230 530 940 1,440 2,140 2,300 3,820 K-Y 3.9 9.2 4.9 3.9 3.7 3.8 3.9 3.7 5.9 3.7 Leq-m, Y 10.3 33.4 21.6 23 37.5 53.9 70 85.6 159.9 112.7 Leq-feet, Y 33.8 109.5 70.8 75.6 123 176.9 229.5 280.8 524.5 369.6 AngleKv-A 55 61 127 220 506 897 1,375 2,035 2,189 3,641 Cv-A 64 70 146 250 580 1,040 1,590 2,350 2,530 4,210 K-A 3.2 7.6 4.0 3.2 3.1 3.1 3.2 3.1 4.9 3.0 Leq-m, A 8.5 27.6 17.8 19.0 37.0 44.6 57.8 70.7 132.1 93.1 Leq-feet, A 28 90.5 58.5 62.5 101.6 146.2 189.7 232 433.4 305.5 Valve flow coefficient, Kv or Cv Equivalent Pipe Length, Leq Flow resistance or Head loss coefficient, Cv = 1.155 Kv Where: Kv = Valve flow coefficient (flow in m3/h at 1bar Diff. Press.) Cv = Valve flow coefficient (flow in gpm at 1psi Diff. Press.) Q = Flow rate (m3/h ; gpm) ∆P = Differential pressure (bar ; psi) Gf = Liquid specific gravity (Water = 1.0) Kv(Cv)=Q Gf ∆P Leq=Lk.D K=∆H 2g V2 Where: K = Flow resistance or Head loss coefficient (dimensionless) ∆H = Head loss (m ; feet) V = Nominal size flow velocity (m/sec ; feet/sec.) g = Acceleration of gravity (9.81 m/sec2 ; 32.18 feet/sec2) Where: Leq = Equivalent nominal pipe length (m ; feet) Lk = Equivalent length coefficient for turbulent flow in clean commercial steel pipe (SCH 40) D = Nominal pipe diameter (m; feet) Note: The Leq values given are for general consideration only. Actual Leq may vary somewhat with each of the valve sizes. 3 6" PRV loss, for calculation only BERMAD Fire Protection 700 SeriesFP 700E Dimensions & Weights Size DN mm (inch)40 (1½”) 50 (2”) 65 (2½”) 80 (3”) 100 (4”) 150 (6”) 200 (8”) 250 (10”) 300 (12”) 350 (14”) 400 (16”)ANSI #150, ISO PN 16L (mm) 10 205 222 250 320 415 500 605 725 733 990 LG(4)(mm) - - - 250 320 415 500 - - - - W (mm) 165 165 178 200 223 320 390 480 550 550 740 R (mm) 78 83 95 100 115 143 172 204 242 268 300 La (mm) 124 124 149 152 190 225 265 320 396 400 450 ha (mm) 85 85 109 102 127 152 203 219 273 279 369 Hy (mm) 239 244 257 305 366 492 584 724 840 866 1,108 Ha (mm) 227 227 241 281 342 441 545 633 777 781 1,082 Weight Y (kg) 10.6 10.6 13 22 37 75 125 217 370 381 846 Weight A (kg) 10 10 12 21.5 35 71 118 205 350 370 800 ANSI #300, ISO PN 25L (mm) 210 210 222 264 335 433 524 637 762 767 1,024 W (mm) 165 165 185 207 250 320 390 480 550 570 740 R (mm) 78 83 95 105 127 159 191 223 261 295 325 La (mm) 124 124 149 159 200 234 277 336 415 419 467 ha (mm) 85 85 109 109 127 165 216 236 294 299 386 Hy (mm) 239 244 257 314 378 508 602 742 859 893 1,133 Ha (mm) 227 227 251 287 650 454 558 649 796 801 1,099 Weight Y (kg) 12.2 12.2 15 25 43 85 146 245 410 434 900 Weight A (kg) 11.5 11.5 13.5 23 41 81 138 233 390 421 855 Portsa (1) (mm) ½ ½ ½ ½ ½ ½ ½ ½ ½ ½ ½ b (1) (mm) ½ ½ ½ ½ ½ ½ ½ ½ ½ ½ ½ c (1) (mm) ¾ ¾ ¾ ¾ ¾ 2 2 2 2 2 2 d (2) (optional) (mm) ¾ ¾ 1½ 1½ 2 2 2 2 2 2 2 Control Vol. (3)(Liter) 0.125 0.125 0.125 0.3 0.45 2.15 4.5 8.5 12.4 12.4 29.9 MetricSi Flanged d L & LG R Hy a cb a La Ha a ha cb a b c W b c Y Body Type Angle Body Type (1) (a), (b), (c) are NPT thread ports (2) (d) is BSPT threaded Optional drain port (3) (Control Volume) is Control Chamber Displacement Volume of liquid pushed when valve opens (4) LG for Grooved ends (see available sizes) 4 BERMAD Fire Protection 700 SeriesFP 700E Dimensions & Weights Size (inch)1½” 2” 2½” 3” 4” 6” 8” 10” 12” 14” 16”ANSI #150, ISO PN 16L (inch) 8.1 8.1 8.3 9.8 12.6 16.3 19.7 23.8 28.5 28.9 39.0 LG(4)(inch) - - - 9.8 12.6 16.3 19.7 - - - - W (inch) 6.1 6.1 7.0 7.9 8.8 12.6 15.4 18.9 21.7 21.7 29.1 R (inch) 3.1 3.3 3.7 3.9 4.5 5.6 6.8 8.0 9.5 10.6 11.8 La (inch) 4.9 4.9 5.9 6.0 7.5 8.9 10.4 12.6 15.6 15.7 17.7 ha (inch) 3.3 3.3 4.3 4 5 6 8 8.6 10.7 11 14.5 Hy (inch) 9.4 9.6 10.1 12 14.4 19.4 23 28.5 33.1 34.1 43.6 Ha (inch) 8.9 8.9 9.9 11.1 13.5 17.4 21.5 24.9 30.6 30.7 42.6 Weight Y (Lbs.) 23 23 29 49 82 165 276 478 816 840 1,865 Weight A (Lbs.) 22 22 27 47 77 157 260 452 772 216 1,764 ANSI #300, ISO PN 25L (inch) 8.3 8.3 8.7 10.4 13.2 17 20.6 25.1 30 30.2 40.3 W (inch) 6.5 6.5 7.3 8.1 9.8 12.6 15.4 18.9 21.7 22.4 29.1 R (inch) 3.1 3.3 3.7 4.1 5 6.3 7.5 8.8 10.3 11.6 12.8 La (inch) 4.9 4.9 5.9 6.3 7.9 9.2 10.9 13.2 16.3 16.5 18.4 ha (inch) 3.3 3.3 4.3 4.3 5.3 6.5 8.5 9.3 11.6 11.8 15.2 Hy (inch) 9.4 9.6 10.1 12.4 14.9 20 23.7 29.2 33.8 35.2 44.6 Ha (inch) 8.9 8.9 9.9 11.3 13.8 17.9 22 25.6 31.3 31.5 43.3 Weight Y (Lbs.) 27 27 33 55 95 187 322 540 904 957 1,984 Weight A (Lbs.) 25 25 30 51 90 179 304 514 860 928 1,88 Portsa (1) (inch) ½ ½ ½ ½ ½ ½ ½ ½ ½ ½ ½ b (1) (inch) ½ ½ ½ ½ ½ ½ ½ ½ ½ ½ ½ c (1) (inch) ¾ ¾ ¾ ¾ ¾ 2 2 2 2 2 2 d (2) (optional) (inch) ¾ ¾ 1½ 1½ 2 2 2 2 2 2 2 Control Vol. (3)(Gal.) 0.04 0.04 0.04 0.08 0.12 0.57 1.19 2.25 3.28 3.28 7.88 EnglishUS Flanged d L & LG R Hy a cb a La Ha a ha cb a b c W b c Y Body Type Angle Body Type (1) (a), (b), (c) are NPT thread ports (2) (d) is BSPT threaded Optional drain port (3) (Control Volume) is Control Chamber Displacement Volume of liquid pushed when valve opens (4) LG for Grooved ends (see available sizes) 5 BERMAD Fire Protection 700 SeriesFP 700E Installation, Operation & Maintanence Electric Pneumatic Hydraulic Electric Pneumatic Hydraulic Valve Closed (Set Position) Line pressure applied to the upper control chamber of the valve creates a superior force that moves the valve to the closed position and provides drip tight sealing. Valve Open (Operating Conditions) Releasing the pressure from the upper control chamber to atmosphere or some other lower pressure zone causes the line pressure acting on the seal disc to move the valve to the open position. Proper operation of the 700E Deluge Valves depends upon their trim being installed in accordance with the appropriate trim configuration. Notes: ■ Wet pilot height should not exceed “Maximum Elevation Above Valve” (see data for specific model). ■ Any deviation in trim size or arrangement may adversely affect the proper operation of the deluge valve. ■ All the pilot system devices, must be UL Listed and compatible with the particular deluge system. Refer to current “UL Listed Fire Protection Equipment Directory”. Warning: The deluge valve and trim must be installed only in areas where they will not be subject to freezing temperatures. Installation Instructions 1. Allow enough room around the valve assembly for any adjustments and future maintenance. 2. Before the valve is installed, flush the pipeline to remove any dirt, scale, debris, etc. Not flushing the line may result in the valve’s becoming inoperable. 3. Install the valve in the pipeline so that the valve flow arrow appearing on the body casting is pointing in the desired direction. Ensure that the valve is positioned so that the actuator assembly can be easily removed for future maintenance. 4. Ensure that the Control Trim is mounted properly and all other components are positioned correctly as per illustration. 5. After installation in the main line, carefully inspect/ correct any damaged accessories, piping, tubing, or fittings. Ensure that there are no leaks. 6. Install the components comprising the Deluge Trim Package in their proper positions in compliance with all instructions, drawings, and technical specifications describing the BERMAD Deluge Valve, according to the relevant illustration. 7. All additional accessories, although not packed together with the BERMAD Deluge Valve, must be installed as shown in the relevant P&ID and other illustrations. Operation Principle of Operation The BERMAD 700E Deluge Valve (assembled with specific trim) is suitable for systems that include adequate detecting and piping systems with open nozzles. The deluge valve prevents water from entering system piping until required. The deluge valve is kept closed by pressure applied to the upper control chamber through a restricted priming line. In the SET position, the water pressure supplied through the priming line is trapped in the upper control chamber of the deluge valve by a check valve, and by the normally closed release device. The pressure trapped in the upper control chamber of the deluge valve presses the valve seal disk down, thereby sealing the valve and keeping the system piping dry. Under conditions of FIRE, when the pressure is released from the upper control chamber by the opening of the automatic releasing device or by manual release, the deluge valve opens and allows the inlet supply water to flow through the valve and into the system piping and alarm devices. Warning: Whenever the handle of the Manual Emergency Release is pulled, pressure is released from the upper control chamber, the deluge valve will open, and water will flow into system piping and alarm devices. Installation 6 BERMAD Fire Protection 700 SeriesFP 700E Installation, Operation & Maintanence Placing in Service/Resetting The deluge valve and the control trim shall be Placed in Service with accordance to the most recent IOM procedures for the specific model. After all relevant instructions are performed, slowly open the supply-isolating valve and check that no water flows into the system. The system is now operational and in stand-by mode. Maintenance Bermad Deluge Valves require no lubrication, no packing tightening, and require a minimum of maintenance. Removing the System from Service Warning: When taking a deluge system out of service, a fire patrol should be established in the system area. If automatic fire alarm signaling equipment is utilized, the proper authority should be notified that the system is being removed from service. The insuring body and owner’s representative should also be notified when the system is being taken out of service. Removal Instructions 1. Shut off the main supply-isolating valve. 2. Close the priming line valve to the deluge valve control chamber. 3. Open all drain valves. 4. Release the water pressure from the control chamber of the deluge valve by pulling the manual emergency release. 5. Place "Fire Protection System Out of Service" signs in the area protected by the system. Inspection and Testing 1. Warning:Do not turn off the water supply to make repairs without placing a roving fire patrol in the area covered by the system. The patrol should continue until the system is back in service. 2. Prior to turning off any valves or activating any alarms, notify local security guards and the central alarm station, if used, to avoid signaling a false alarm. 3. The deluge valve and the control trim shall be maintained with accordance to the most recent IOM procedures for the specific model. A periodic test schedule should be established also with accordance to the site conditions and owner regulations. 4. Take all additional measures as required by NFPA-25 “standard for the inspection, testing, and maintenance of water-based fire protection systems”. 5. The system should be checked weekly for “Normal Conditions”. 6. Clean the priming strainer prior to any resetting of the deluge valve. 7. The deluge valve must be activated at full flow at least annually. Take all necessary precautions to drain water and prevent damage in the area protected by the system. 8. After about five years of operation, replacement of diaphragm and other elastomers is recommended. Remove the actuator and disassemble it. Clean the seat area from sediments, clean the control tubing entry holes, and install a new diaphragm and other elastomers in place. Spare Parts 1. The Diaphragm and the Seals are the only spare parts needed for the main deluge valve, see attached “Valve Disassembly and Parts Breakdown” illustration. 2. It is not recommended to store spare rubber parts for long periods (rubber in improper storage conditions can harden and crack). 3. Contact your Bermad representative and order new rubber parts when required. 7 BERMAD Fire Protection 700 Series Bearing Assembly Shaft Diaphragm Washer O-Ring Diaphragm Spacer Disk Diaphragm Washer Nut Indicator Lock Nut Cover Disk Bolt Cover Plug (6” and up) O-Ring Eye Nut Bearing Screw Disk Separation Partition Bolt Stud Nut Locking Screw Seal Disk Assembly Seal Disk Wash. Screw Seal Seal Disk O-Ring Spring Nut Actuator Assembly Screw Removable Seat Nut Y Body Type Angle Body Type FP 700E Parts Valve Disassembling Parts Breakdown bermadfire@bermad.com • www.bermad.com © Copyright 2007-2012 Bermad CS Ltd. All Rights Reserved. The information contained in this document is subject to change without notice. BERMAD shall not be liable for any errors contained herein. PT7PE04-DATA 09.2012 8