HomeMy WebLinkAboutF14-0020 CUT SHEETS.pdfGeneral Description The Tyco ®Rapid Response™, Series LFII (TY2334) Residential Horizontal Sidewall Sprinklers are decorative, fast response, frangible bulb sprin- klers designed for use in residential occupancies such as homes, apart- ments, dormitories, and hotels. When aesthetics and optimized flow charac- teristics are the major consideration, the Series LFII (TY2334) should be the first choice. The Series LFII are to be used in wet pipe residential sprinkler systems for one- and two-family dwellings and mo- bile homes per NFPA 13D; wet pipe residential sprinkler systems for resi- dential occupancies up to and includ- ing four stories in height per NFPA 13R; or, wet pipe sprinkler systems for the residential portions of any occu- pancy per NFPA 13. The Series LFII (TY2334) has a 4.4 (63,4) K-factor that provides the re- quired residential flow rates at reduced pressures, enabling smaller pipe sizes and water supply requirements. The recessed version of the Series LFII (TY2334) is intended for use in areas with finished walls. It employs a two-piece Style 20 Recessed Escutch- eon. The Recessed Escutcheon pro- vides 1/4 inch (6,4 mm) of recessed adjustment or up to 1/2 inch (12,7 mm) of total adjustment from the flush mounting surface position. The adjust- ment provided by the Recessed Es- cutcheon reduces the accuracy to which the pipe nipples to the sprinklers must be cut. The Series LFII (TY2334) has been designed with heat sensitivity and water distribution characteristics proven to help in the control of residen- tial fires and to improve the chance for occupants to escape or be evacuated. WARNINGS The Series LFII (TY2334) Residential Horizontal Sidewall Sprinklers de- scribed herein must be installed and maintained in compliance with this document, as well as with the applica- ble standards of the National Fire Pro- tection Association, in addition to the standards of any other authorities hav- ing jurisdiction.Failure to do so may impair the performance of these de- vices. The owner is responsible for maintain- ing their fire protection system and de- vices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. Sprinkler/Model Identification Number SIN TY2334 Page 1 of 6 TFP412DECEMBER, 2007 Series LFII Residential Horizontal Sidewall Sprinklers 4.4 K-factor Technical Services:Tel: (800) 381-9312 / Fax: (800) 791-5500 IMPORTANT Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and in- stallation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 2 of 6 TFP412 FIGURE 1 SERIES LFII (TY2334) RESIDENTIAL HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS FIGURE 2 STYLE 20 RECESSED ESCUTCHEON FOR USE WITH THE SERIES LFII (TY2334) RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER Sealing-3 5 4 * 6 Compression of Deflector. is indicated on top Temperature rating Bulb Deflector- - - * 1 Components: 2 Button Frame- -WRENCH STYLE 20 RECESSED ESCUTCHEON FLATS 2-7/8" DIA. RECESSED (73,0 mm)5 NOMINAL PLATE SEATING SURFACE ESCUTCHEON MAKE-IN CENTERLINE OF WATERWAY 7/16" (11,1 mm) (54,0 mm) (38,1 mm) DEFLECTOR BOSS (11,1 mm) 7/16" END-OF- 2-1/8" 1-1/2" DEFLECTOR TOP-OF- 4 26* 1 3 Assembly Screw TOP1/2" NPT FLATS WRENCH 1-1/4" (31,8 mm) 1" (25,4 mm) MOUNTING PLATE TY2334 MOUNTING SURFACE CLOSURE (73,0 mm) 1/2" (12,7 mm) (57,2 mm) 2-1/4" DIA. 1/4" (6,4 mm) 1/8" (3,2 mm) (11,1±3,2 mm) SPRINKLER FITTING FACE OF 7/16±1/8" 2-7/8" DIA. BOSS END-OF- DEFLECTOR TOP-OF- DEFLECTOR 7/16" (11,1 mm) FIGURE 3 W-TYPE 6 SPRINKLER WRENCH FIGURE 4 W-TYPE 7 RECESSED SPRINKLER WRENCH WRENCH RECESS (END "A" USED FOR TY2334) RECESS WRENCH WITH SPRINKLER ENGAGEMENT IN TO ENSURE WRENCHINGAREA PUSH WRENCH Technical Data Approvals: UL and C-UL Listed. Maximum Working Pressure: 175 psi (12,1 bar) Discharge Coefficient: K = 4.4 GPM/psi 1/2 (63,4 LPM/bar 1/2) Temperature Rating: 155°F/68°C or 175°F/79°C Finishes: White Polyester Coated, Chrome Plated, or Natural Brass Physical Characteristics: Frame . . . . . . . . . . . . . . Brass Button . . . . . . . . . . . . . Bronze Sealing Assembly . . . . . . . . . . . . . . . Beryllium Nickel w/Teflon† Bulb . . . . . . . . . 3 mm dia. Glass Compression Screw . . . . . Bronze Deflector . . . . . . . . . . . Copper †Dupont Registered Trademark Operation The glass Bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass Bulb allowing the sprinkler to activate and flow water. Design Criteria The Tyco ®Rapid Response™, Series LFII (TY2334) Residential Horizontal Sidewall Sprinklers are UL and C-UL Listed for installation in accordance with the following criteria. NOTE When conditions exist that are outside the scope of the provided criteria, refer to the Residential Sprinkler Design Guide TFP490 for the manufacturer’s recommendations that may be accept- able to the local Authority Having Ju- risdiction. System Type.Only wet pipe systems may be utilized. Hydraulic Design.The minimum re- quired sprinkler flow rate for systems designed to NFPA 13D or NFPA 13R are given in Table A, B, C, and D as a function of temperature rating and the maximum allowable coverage areas. The sprinkler flow rate is the minimum required discharge from each of the total number of “design sprinklers” as specified in NFPA 13D or NFPA 13R. For systems designed to NFPA 13, the number of design sprinklers is to be the four most hydraulically demanding sprinklers. The minimum required dis- charge from each of the four sprinklers is to be the greater of the following: •The flow rates given in Tables A, B, C, and D for NFPA 13D and 13R as a function of temperature rating and the maximum allowable coverage area. •A minimum discharge of 0.1 gpm/sq. ft. over the “design area” comprised of the four most hydraulically de- manding sprinklers for the actual coverage areas being protected by the four sprinklers. Obstruction To Water Distribution. Locations of sprinklers are to be in accordance with the obstruction rules of NFPA 13 for residential sprinklers. Operational Sensitivity.The sprin- klers are to be installed with an end-of- deflector-boss to wall distance of 1- 3/8 to 6 inches or in the recessed po- sition using only the Style 20 Re- cessed Escutcheon as shown in Figure 2. In addition the top-of-deflector-to-ceil- ing distance is to be within the range (Ref. Table A, B, C, or D) being hy- draulically calculated. Sprinkler Spacing.The minimum spacing between sprinklers is 8 feet (2,4 m). The maximum spacing be- tween sprinklers cannot exceed the width of the coverage area (Ref. Table A) being hydraulically calculated (e.g., maximum 12 feet for a 12 ft. x 12 ft. coverage area, or 16 feet for a 16 ft. x 20 ft. coverage area). Installation The Series LFII (TY2334) must be in- stalled in accordance with the follow- ing instructions: NOTES Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprinkler held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 inch (1,6 mm). A 1/2 inch NPT sprinkler joint should be obtained with a minimum to maxi- mum torque of 7 to 14 ft.lbs. (9,5 to 19,0 Nm). Higher levels of torque may distort the sprinkler inlet with conse- quent leakage or impairment of the sprinkler. Do not attempt to compensate for in- sufficient adjustment in an Escutcheon Plate by under- or over-tightening the Sprinkler. Readjust the position of the sprinkler fitting to suit. The Series LFII Horizontal Sidewall Sprinklers must be installed in ac- cordance with the following instruc- tions. Step 1.Horizontal sidewall sprinklers are to be installed in the horizontal position with their centerline of water- way perpendicular to the back wall and parallel to the ceiling. The word “TOP” on the Deflector is to face towards the ceiling with the front edge of the De- flector parallel to the ceiling. Step 2.With pipe thread sealant ap- plied to the pipe threads, hand tighten the sprinkler into the sprinkler fitting. Step 3.Tighten the sprinkler into the sprinkler fitting using only the W-Type 6 Sprinkler Wrench (Ref. Figure 3). With reference to Figure 1, the W-Type 6 Sprinkler Wrench is to be applied to the wrench flats. The Series LFII Recessed Horizontal Sidewall Sprinklers must be installed in accordance with the following in- structions. Step A.Recessed horizontal sidewall sprinklers are to be installed in the horizontal position with their centerline of waterway perpendicular to the back wall and parallel to the ceiling. The word “TOP” on the Deflector is to face towards the ceiling. Step B.After installing the Style 20 Mounting Plate over the sprinkler threads and with pipe thread sealant applied to the pipe threads, hand tighten the sprinkler into the sprinkler fitting. Step C. Tighten the sprinkler into the sprinkler fitting using only the W-Type 7 Recessed Sprinkler Wrench (Ref. Figure 4). With reference to Figure 1, the W-Type 7 Recessed Sprinkler Wrench is to be applied to the sprinkler wrench flats. Step C.After the wall has been in- stalled or the finish coat has been ap- plied, slide on the Style 20 Closure over the Series LFII Sprinkler and push the Closure over the Mounting Plate until its flange comes in contact with the wall. TFP412 Page 3 of 6 (Continued on Page 8) Page 4 of 6 TFP412 (a) For coverage area dimensions less than or between those indicated, it is necessary to use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b) Width (backwall where sprinkler is located) x Length (horizontal throw of sprinkler). (c) Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K-factor. Refer to Hydraulic Design Criteria Section for details. (d) Sidewall sprinklers, where installed under a ceiling with a slope greater than 0 inch rise for a 12 inch run to a slope up to 2 inch rise for 12 inch run, must be located per one of the following: •Locate the sprinklers at the high point of the slope and positioned to discharge down the slope. •Locate the sprinklers along the slope and positioned to discharge across the slope. TABLE A NFPA 13D AND NFPA 13R WET PIPE HYDRAULIC DESIGN CRITERIA FOR THE SERIES LFII (TY2334) RESIDENTIAL HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS FOR HORIZONTAL CEILING (Maximum 2 Inch Rise for 12 Inch Run) 12 x 12 (3,7 x 3,7) Maximum Coverage Area (a) Width x Length (b) Ft. x Ft. (m x m) Minimum Flow (c)and Residual Pressure 14 x 14 (4,3 x 4,3) 16 x 16 (4,9 x 4,9) 16 x 18 (4,9 x 5,5) 16 x 20 (4,9 x 6,1) 14 GPM (53,0 LPM) 10.1 psi (0,70 bar) 16 GPM (60,6 LPM) 13.2 psi (0,91 bar) 19 GPM (71,9 LPM) 18.6 psi (1,28 bar) 23 GPM (87,1 LPM) 27.3 psi (1,88 bar) 13 GPM (49,2 LPM) 8.7 psi (0,60 bar) 155°F/68°C Top-Of-Deflector- To- Ceiling: 4 to 6 Inches (100 to 150 mm) 175°F/79°C Top-Of-Deflector- To- Ceiling: 6 to 12 Inches (150 to 300 mm) 155°F/68°C 175°F/79°C 13 GPM (49,2 LPM) 8.7 psi (0,60 bar) 14 GPM (53,0 LPM) 10.1 psi (0,70 bar) 16 GPM (60,6 LPM) 13.2 psi (0,91 bar) 19 GPM (71,9 LPM) 18.6 psi (1,28 bar) 23 GPM (87,1 LPM) 27.3 psi (1,88 bar) 12 (3,7) 14 (4,3) 16 (4,9) 16 (4,9) 16 (4,9) Maximum Spacing Ft. (m) 18 x 18 (5,5 x 5,5) 18 (5,5) 18 x 20 (5,5 x 6,1) 18 (5,5) 26 GPM (98,4 LPM) 34.9 psi (2,41 bar) 13 GPM (49,2 LPM) 8.7 psi (0,60 bar) 13 GPM (49,2 LPM) 8.7 psi (0,60 bar) 14 GPM (53,0 LPM) 10.1 psi (0,70 bar) 14 GPM (53,0 LPM) 10.1 psi (0,70 bar) 17 GPM (64,3 LPM) 14.9 psi (1,03 bar) 17 GPM (64,3 LPM) 14.9 psi (1,03 bar) 20 GPM (75,7 LPM) 20.7 psi (1,43 bar) 20 GPM (75,7 LPM) 20.7 psi (1,43 bar) 23 GPM (87,1 LPM) 27.3 psi (1,88 bar) 23 GPM (87,1 LPM) 27.3 psi (1,88 bar) 23 GPM (87,1 LPM) 27.3 psi (1,88 bar) 23 GPM (87,1 LPM) 27.3 psi (1,88 bar) 23 GPM (87,1 LPM) 27.3 psi (1,88 bar) 23 GPM (87,1 LPM) 27.3 psi (1,88 bar) 26 GPM (98,4 LPM) 34.9 psi (2,41 bar) 26 GPM (98,4 LPM) 34.9 psi (2,41 bar) 26 GPM (98,4 LPM) 34.9 psi (2,41 bar) ELEVATION TFP412 Page 5 of 6 (a) For coverage area dimensions less than or between those indicated, it is necessary to use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b) Width (backwall where sprinkler is located) x Length (horizontal throw of sprinkler). (c) Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K-factor. Refer to Hydraulic Design Criteria Section for details.. TABLE B NFPA 13D AND NFPA 13R WET PIPE HYDRAULIC DESIGN CRITERIA FOR THE SERIES LFII (TY2334) RESIDENTIAL HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS FOR SPRINKLERS AT THE HIGH POINT OF THE SLOPE AND DISCHARGING DOWN THE SLOPE (Greater Than 2 Inch Rise for 12 Inch Run Up To 8 Inch Rise for 12 Inch Run) 12 x 12 (3,7 x 3,7) Maximum Coverage Area(a) Width x Length (b) Ft. x Ft. (m x m) 14 x 14 (4,3 x 4,3) 16 x 16 (4,9 x 4,9) 16 x 18 (4,9 x 5,5) 16 x 20 (4,9 x 6,1) 12 (3,7) 14 (4,3) 16 (4,9) 16 (4,9) 16 (4,9) Maximum Spacing Ft. (m) 23 GPM (87,1 LPM) 27,3 psi (1,88 bar) Minimum Flow (c)and Residual Pressure (I) Two sprinkler design with the sprinklers at the high point of the slope and positioned to discharge down the slope. Top-Of-Deflector- To- Ceiling: 4 to 6 Inches (100 to 150 mm) Top-Of-Deflector- To- Ceiling: 6 to 12 Inches (150 to 300 mm) 155°F/68°C 175°F/79°C 155°F/68°C 175°F/79°C I I I I I I I I I I I I I I I I I I I I 18 x 18 (5,5 x 5,5) 18 (5,5) 18 x 20 (5,5 x 6,1) 18 (5,5) 23 GPM (87,1 LPM) 27,3 psi (1,88 bar) 23 GPM (87,1 LPM) 27,3 psi (1,88 bar) 23 GPM (87,1 LPM) 27,3 psi (1,88 bar) I 23 GPM (87,1 LPM) 27,3 psi (1,88 bar) I 23 GPM (87,1 LPM) 27,3 psi (1,88 bar) I 23 GPM (87,1 LPM) 27,3 psi (1,88 bar) 23 GPM (87,1 LPM) 27,3 psi (1,88 bar) I I 26 GPM (98,4 LPM) 34.9 psi (2,41 bar) I 26 GPM (98,4 LPM) 34.9 psi (2,41 bar) I 26 GPM (98,4 LPM) 34.9 psi (2,41 bar) 26 GPM (98,4 LPM) 34.9 psi (2,41 bar) I 23 GPM (87,1 LPM) 27,3 psi (1,88 bar) 23 GPM (87,1 LPM) 27,3 psi (1,88 bar) 23 GPM (87,1 LPM) 27,3 psi (1,88 bar) 23 GPM (87,1 LPM) 27,3 psi (1,88 bar) 23 GPM (87,1 LPM) 27,3 psi (1,88 bar) 23 GPM (87,1 LPM) 27,3 psi (1,88 bar) 23 GPM (87,1 LPM) 27,3 psi (1,88 bar) 23 GPM (87,1 LPM) 27,3 psi (1,88 bar) 23 GPM (87,1 LPM) 27,3 psi (1,88 bar) 23 GPM (87,1 LPM) 27,3 psi (1,88 bar) 23 GPM (87,1 LPM) 27,3 psi (1,88 bar) 23 GPM (87,1 LPM) 27,3 psi (1,88 bar) 23 GPM (87,1 LPM) 27,3 psi (1,88 bar) 23 GPM (87,1 LPM) 27,3 psi (1,88 bar) 23 GPM (87,1 LPM) 27,3 psi (1,88 bar) 23 GPM (87,1 LPM) 27,3 psi (1,88 bar) ELEVATION MAXIMUM8" 12" Care and Maintenance The Tyco ®Rapid Response™, Series LFII (TY2334) must be maintained and serviced in accordance with the follow- ing instructions: NOTES Absence of an Escutcheon Plate may delay the sprinkler operation in a fire situation. Before closing a fire protection system main control valve for maintenance work on the fire protection system which it controls, permission to shut down the affected fire protection sys- tem must be obtained from the proper authorities and all personnel who may be affected by this action must be no- tified. Sprinklers which are found to be leak- ing or exhibiting visible signs of corro- sion must be replaced. Automatic sprinklers must never be painted, plated, coated, or otherwise altered after leaving the factory. Modi- fied sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. Care must be exercised to avoid dam- age to the sprinklers - before, during, and after installation. Sprinklers dam- aged by dropping, striking, wrench twist/slippage, or the like, must be re- placed. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb. (Ref. Installation Section). The owner is responsible for the in- spection, testing, and maintenance of their fire protection system and de- vices in compliance with this docu- ment, as well as with the applicable standards of the National Fire Protec- tion Association (e.g., NFPA 25), in addition to the standards of any other authorities having jurisdiction. The in- stalling contractor or sprinkler manu- facturer should be contacted relative to any questions. NOTE The owner must assure that the sprin- klers are not used for hanging of any objects and that the sprinklers are only cleaned by means of gently dusting with a feather duster; otherwise, non- operation in the event of a fire or inad- vertent operation may result. Automatic sprinkler systems should be inspected, tested, and maintained by a qualified Inspection Service in accord- ance with local requirements and/or national codes. Limited Warranty Products manufactured by Tyco Fire & Building Products (TFBP) are war- ranted solely to the original Buyer for ten (10) years against defects in mate- rial and workmanship when paid for and properly installed and maintained under normal use and service. This warranty will expire ten (10) years from date of shipment by TFBP. No warranty is given for products or com- ponents manufactured by companies not affiliated by ownership with TFBP or for products and components which have been subject to misuse, improper installation,corrosion, or which have not been installed, maintained, modi- fied or repaired in accordance with ap- plicable Standards of the National Fire Protection Association, and/or the standards of any other Authorities Having Jurisdiction. Materials found by TFBP to be defective shall be either repaired or replaced, at TFBP’s sole option. TFBP neither assumes, nor authorizes any person to assume for it, any other obligation in connection with the sale of products or parts of prod- ucts. TFBP shall not be responsible for sprinkler system design errors or inac- curate or incomplete information sup- plied by Buyer or Buyer’s repre- sentatives. In no event shall TFBP be liable, in contract, tort, strict liability or under any other legal theory, for incidental, indirect, special or consequential dam- ages, including but not limited to labor charges, regardless of whether TFBP was informed about the possibility of such damages, and in no event shall TFBP’s liability exceed an amount equal to the sales price. The foregoing warranty is made in lieu of any and all other warranties, ex- press or implied, including warranties of merchantability and fitness for a par- ticular purpose. This limited warranty sets forth the ex- clusive remedy for claims based on failure of or defect in products, materi- als or components, whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full ex- tent permitted by law. The invalidity, in whole or part, of any portion of this warranty will not affect the remainder. Ordering Procedure When placing an order, indicate the full product name. Contact your local distributor for availability.. Sprinkler Assembly: Series LFII (TY2334), K=4.4, Residen- tial Horizontal Sidewall Sprinkler with (specify) temperature rating and (specify) finish, P/N (specify). 155°F/68°C or Chrome Plated . . . . . . . . . P/N 51-215-9-155 155°F/68°C White Polyester. . . . . . . . . P/N 51-215-4-155 155°F/68°C Natural Brass. . . . . . . . . . . P/N 51-215-1-155 175°F/79°C or Chrome Plated . . . . . . . . . P/N 51-215-9-175 175°F/79°C White Polyester. . . . . . . . . P/N 51-215-4-175 175°F/79°C Natural Brass. . . . . . . . . . . P/N 51-215-1-175 Recessed Escutcheon: Specify: Style 20 Recessed Escutch- eon with (specify*) finish, P/N (spec- ify*). *Refer to Technical Data Sheet TFP770. Sprinkler Wrench: Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387. Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001. Page 6 of 6 TFP412 © 2007 TYCO FIRE & BUILDING PRODUCTS,451 North Cannon Avenue, Lansdale, Pennsylvania 19446 Wrot Copper and Bronze Solder-Joint Pressure Fittings Dimensions of Soldered-Joint Ends (in inches) Male End Female End Inside Standard Diameter Water Ouside Inside Wall of Tube Diameter Length Diameter Depth Thickness Fitting Size A K F G T O Min. Max. Min. Min, Max. Min. Avg. Min. Engineering Data Elkhart Products Corporation 39 Working Pressures and Solder The table of maximum working pressures below must be understood to reflect what is generally considered as good engineering practice under reasonably constant and favorable conditions; i.e., pressures which are fairly steady, absence of particularly corrosive media, etc. Unusual conditions require increased safety factors and therefore, lower working pressures should be used. Rated Internal Working Pressures of Piping System Made of Copper Water Tube and Soldered Fittings Service POUNDS PER SQUARE INCH Solder Used Temp. Water (a) in joints °F Copper Water Tube-Nominal Sizes 1⁄8" to 1" 1 1⁄4" to 2" 2 1⁄2" to 4" 5" to 8" Incl. Incl. Incl. Incl. * 50-50 100 200 175 150 135 Tin-Lead (b)150 150 125 100 90 200 100 90 75 70 250 85 75 50 45 95-5 100 500 400 300 270 Tin-Antimony 150 400 350 275 250 (c) (d)200 300 250 200 180 250 200 175 150 135 Brazing Alloys Temperature and pressure ratings consistent with the Melting at or materials and procedures employed. above 1000° F. *The data given for 50% tin-50% lead applies also for the 40% tin-60% lead alloy. The values in this table are based on data in the National Bureau of Standards Publications, “Building Materials and Structures Reports BMS 58 and BMS 83.” (a) Including other noncorrosive liquids and gases (b) ASTM B32, Alloy Grade Sn 50 (c) ASTM B32, Alloy Grade Sb 5 (d) The Safe Drinking Water Act Amendment of 1986 prohibits the use in potable water. Systems of any solder having a lead content in excess of 2%. NOTE: The table at left is from data published by the Copper and Brass Research Association. Estimated Quantity of 50-50 Solder Required to Make 100 Joints Size in Inches 3/8 1/2 3/4 1 1 1/4 1 1/2 2 2 1/2 3 3 1/2 4 5 6 8 Quantity in Pounds .5 .75 1.0 1.4 1.7 1.9 2.4 3.2 3.9 4.5 5.5 8 15 32 1. The quantity of hard solder used is dependent in the skill of the operator, but for estimating purposes, 75% of the above figures may be used. 2. Two ounces of Solder Flux will be required for each pound of solder. 0.252 0.256 0.25 0.377 0.381 0.31 0.502 0.506 0.38 0.627 0.631 0.50 0.752 0.756 0.62 0.877 0.881 0.75 1.128 1.132 0.91 1.378 1.382 0.97 1.628 1.633 1.09 2.128 2.133 1.34 2.628 2.633 1.47 3.128 3.133 1.66 3.628 3.633 1.91 4.128 4.133 2.16 5.128 5.133 2.66 6.128 6.133 3.09 8.128 8.133 3.97 1/8 0.248 0.251 0.31 1/4 0.373 0.376 0.38 3/8 0.497 0.501 0.44 1/2 0.622 0.626 0.56 5/8 0.747 0.751 0.69 3/4 0.872 0.876 0.81 1 1.122 1.127 0.97 1 1/4 1.372 1.377 1.03 1 1/2 1.621 1.627 1.16 2 2.121 2.127 1.41 2 1/2 2.621 2.627 1.53 3 3.121 3.127 1.72 3 1/2 3.621 3.627 1.97 4 4.121 4.127 2.22 5 5.121 5.127 2.72 6 6.121 6.127 3.22 8 8.119 8.127 4.09 KT O A T G OF T T O A T G OF T T Male End Female End .019 0.18 .023 0.30 .026 0.39 .029 0.52 .031 0.63 .033 0.74 .040 0.98 .044 1.23 .051 1.47 .059 1.94 .067 2.42 .075 2.89 .086 3.37 .096 3.84 .111 4.70 .124 5.72 .173 7.55 Engineering Data Fitting Material: Copper Alloy #122, Phosphorus Deoxidized-High Residual Phosphorus (DHP). Composition: 99% Copper; .015-.040% Phosphorus. Weld Material: Silicon Bronze. Meets specification American Welding Society (AWS) A5.7-91R and American Metals Society. Weld Specifications: Tensile Strength-Up to 58,000 PSI Yield Strength-Up to 25,000 PSI Elongation in 2"-53% to 55% Hardness-80 to 100 Brinell (500kg. Load) Temperature: Melt 1832°F, Flow 1931°F. Method of Joining: Electric Weld. Dimensions & Specifications: EPC Welded fittings are produced in accordance with specifications shown in Manufactures Standardization Society (MSS) SP-109 for wrought copper, and copper alloy solder-joint pressure fittings. Testing: Each fitting is individually tested with air under water. The burst pressure of EPC welded fittings exceeds the recommended working pressure of comparable diameter, annealed, straight, seamless ASTM B88- 96-A type “L” copper water tube by a safety factor of 4:1 or more. Wrot Copper Fittings Large Diameter Welded Design 40 Elkhart Products Corporation †Slight variations from these weights must be expected in practice. Extracted from American National Standard Wrought Copper and Bronze Solder-Joint Drainage Fittings (ANSI B16.29) with permission of the publisher. The American Society of Mechanical Engineers, 345 East 47th St., New York, N.Y. Copper Water Tube-Standard Dimensions and Weights Outside Inside Diameter, Inches Wall Thickness, Inches †Pounds per Linear Foot Nominal Dia., In. Tube Types Type Type Type Type Type Type Type Type Type Type Type Type Size K-L-M- K L M DWV K L M DWV K L M DWV Inches DWV 1/4 .375 .305 .315 - - .035 .030 .025 - .145 .126 .106 - 3/8 .500 .402 .430 - - .049 .035 .025 - .269 .198 .145 - 1/2 .625 .527 .545 - - .049 .040 .028 - .344 .285 .204 - 5/8 .750 .652 .666 - - .049 .042 .030 - .418 .362 .263 - 3/4 .875 .745 .785 - - .065 .045 .032 - .641 .455 .328 - 1 1.125 .995 1.025 - - .065 .050 .035 - .839 .655 .465 - 1 1/4 1.375 1.245 1.265 1.291 1.295 .065 .055 .042 .040 1.04 .884 .682 .650 1 1/2 1.625 1.481 1.505 1.527 1.541 .072 .060 .049 .042 1.36 1.14 .940 .809 2 2.125 1.959 1.985 2.009 2.041 .083 .070 .058 .042 2.06 1.75 1.46 1.07 2 1/2 2.625 2.435 2.465 2.495 - .095 .080 .065 - 2.93 2.48 2.03 - 3 3.125 2.907 2.945 2.981 3.035 .109 .090 .072 .045 4.00 3.33 2.68 1.69 3 1/2 3.625 3.385 3.425 3.459 - .120 .100 .083 - 5.12 4.29 3.58 - 4 4.125 3.857 3.905 3.935 4.009 .134 .110 .095 .058 6.51 5.38 4.66 2.87 5 5.125 4.805 4.875 4.907 4.981 .160 .125 .109 .072 9.67 7.61 6.66 4.43 6 6.125 5.741 5.845 5.881 5.959 .192 .140 .122 .083 13.9 10.2 8.92 6.10 8 8.125 7.583 7.725 7.785 - .271 .200 .170 - 25.9 19.3 16.5 - Wrot Copper Solder-Joint Drainage Fittings Dimensions of Soldered-Joint Ends (in inches) See Diagram Page 39 Male End Female End Inside Metal Diameter Size Outside Diameter Length Inside Diameter Depth Thickness of Fitting AKFGTO Min. Max. Min. Min. Max. Min. Min. Min. 1 1/4 1.372 1.377 0.56 1.378 1.382 0.50 0.040 1.29 1 1/2 1.621 1.627 0.62 1.628 1.633 0.56 0.042 1.53 2 2.121 2.127 0.69 2.128 2.133 0.62 0.042 2.01 3 3.121 3.127 0.81 3.128 3.133 0.75 1.045 2.98 4 4.121 4.127 1.06 4.128 4.133 1.00 0.058 3.93 36 ➀ ADAPTERS ELBOWS COUPLINGS FIGURE 5. Selected Pressure Fittings GENERAL NOTES: (a) Fittings are designated by size in the order: 1x2x3 (b) Fitting designs and drawings are for illustration only. Page 6 Note: Screws must be installed with appropriate nut driver to comply with warranty Item# Model Screw Description BoxQty Weight (per 100) Case Qty 50 DSTR 100 1/4-20x1 100 6.25 1000 51 DST100 1/4-14x1 100 5.25 1000 52 DST150 1/4-14x1 1/2 100 5.50 1000 53 DST200 1/4-14x2 100 6.00 1000 54 DST250 1/4-14x2 1/2 100 6.75 1000 55 DST300 1/4-14x3 100 7.25 1000 56 TEK500 12-24x1 1/2 100 5.50 1000 Use #14 Nut Driver (Item #100) STEEL • 1/4" Rod(Vertical Mount) Item# Model Screw Description Minimum Thickness Maximum Thickness Actual Pullout BoxQty Weight (per 100) Case Qty 601 DST2.0 1/4-14x2 .188"-3/16" 1/4" 50 6.75 500 1113 DST2.5 1/4-14x2 1/2 .188"-3/16" 1/4" 50 7.25 500 422 DSTR 1.0 1/4-20x1 .036"-20 ga 1/4" 1510# / 20 ga 50 500.00 7 28 DSTR 5.16 5/16-18x1 1/4 .036"-20 ga 1/4" 2220# / 20 ga 50 8.00 500 443 DST5.16 5/16-18x1 1/4 .188"-3/16" 1/4" 1500+# / 3/16" 50 6.75 500 05 TEK5.0 12-24x1 1/2 .25"-1/4" 1/2" 3125# / 1/4" 50 6.00 500 STEEL • 1/2" Rod(Vertical Mount) Use #14SW NutDriver (Item#101) Approvals Item# Model Screw Description FMTest Load, lb. ULTest Loadlb. UL/FM Pipe Size Minimum Thickness Maximum Thickness Actual Pullout Box UL•FM•NFPA 29 DSTR1 1/2"12-24x11/2 1475# 1500# 3/4-4 1/4" 1/2" 1510# / 1/4"1 UL•FM•NFPA 30 DSTR1"1/4-20x1 1475# 1500# 3/4-4 .036"-20 ga 1/4" 1510# / 20 ga 1 UL•NFPA 31 DSTR516 5/16-18x11/4 1500# 4 .036"-20 ga 1/4" 2200# / 20 ga 1 NFPA 32 DST10 1/4-14x1 .036"-20 ga 1/4" 446# / 20 ga 1 NFPA 33 DST15 1/4-14x11/2 1/4" 970# / 16 ga 1 NFPA 34 DST20 1/4-14x2 1/4"1 NFPA 35 DST25 1/4-14x21/2 1/4"1 NFPA 36 DST30 1/4-14x3 1/4"1 UL•NFPA 37 DST516 5/16-18x11/4 1500# 4 .188"-3/16" 1/4" 1500# / 3/16"1 FM•NFPA 38 TEK50 12-24x11/2 1475# 1/4" 1/2" 3125# / 1/4"1 STEEL • 3/8" Rod(Vertical Mount) Use #14 Nut Driver (Item #100) Note: Screw diameter/design/ performance for the DST 10 (1" length) through the DST 30 (3" length) are constant. Only the lengths vary. STEEL — Sammys For fastening/anchoring in high vibratory environments, consult local code authorities for accepted anchoring devices #14 (Item #100-black) Sammys 1/4”, 3/8” rod UL Listings and CAD Drawings are available at www.SammySuperScrew.com #14SW (Item #101-red) Sidewinders & Sammys 1/2” rod Self-Drilling • Self-tapping Page 7Note: Screws must be installed with appropriate nut driver to comply with warranty Item# Model Screw Description Minimum Thickness Maximum Thickness Actual Shear/Pullout BoxQty Weight (per 100) Case Qty 2003 SWD100 1/4-14x1 .066"-16 ga 1/4" 1477# / 16 ga 100 6.00 1000 407 SWD200 1/4-14x2 .066"-16 ga 1/4" 1477# / 16 ga 100 6.50 1000 206 SWDR100 1/4-20 .036"-20 ga 1/4" 1900# / 20 ga 100 6.00 1000 STEEL • 1/4" Rod(Horizontal Mount) Use #14SW Nut Driver (Item #101) Approval s Item# Model Screw Description ULTest Loadlb. UL/FM Pipe Size Minimum Thickness Maximum Thickness Actual Shear/Pullout Box Qty Weigh (per 100 NFPA 39 SWD10 1/4-14x1 .066"-16 ga 1/4" 1477# / 16 ga 100 6.00 NFPA 40 SWD15 1/4-14x1 1/2 100 7.50 NFPA 41 SWD20 1/4-14x2 100 6.50 NFPA 42 SWD516 5/16-18x1 1/4 100 7.00 UL•NFPA 46 SWDR 1 1/2" 1/4-20x1 1/2 1500# 4 .25"-1/4" 1/2" 2375# / .25"-1/4" 100 7.25 UL•NFPA 43 SWDR 1" 1/4-20x1 1500# 4 .036"-20 ga 1/4" 1900# / 20 ga 100 7.00 UL•NFPA 44 SWDR 516 5/16-18x1 1/4 1500# 4 .036"-20 ga 1/4" 2480# / 20 ga 100 8.25 NFPA 45 SWT15 12-24x1 1/2 .25"-1/4" 1/2" 100 6.25 Use #14SW Nut Driver (Item #101) STEEL • 3/8" Rod (Horizontal Mount) Note: Screw diameter/design/performance forSWD 10 (1" length) through SWD 20 (2" length) are constant. Only the lengthsvarry. STEEL —Sidewinders steel screw shown with retainer nut SWDR screws include retainer nut #14SW (Item #101-red) Sidewinders & Sammys 1/2” rod For fastening/anchoring in high vibratory environments, consult local code authorities for accepted anchoring devices PERFORMANCE DATA FOR STEEL Model Dia. Pt. .114 .092 .365 .132 DST 10 1/4 #3 1265# 2750# SWD10 1/4 #3 1120# 1420# Aluminum Curtain Wall Extrusion (average lbs. ultimate) Fastener Thickness Ultimate Pullout Values Model Dia. Pt. 20 18 16 14 12 3/16 1/4 DST 1/4 #3 446# 613# 970# 1145# 1544# 3190# DST 516 5/16 #3 457# 568# 1209# 1712# 2422# 3716# TEK50 #12 #5 487# 699# 913# 1527# 3270# 3593# DSTR1 1/2"#12 #5 3270# 3593# DSTR1"1/4 #3 1510# DSTR516 5/16 #3 2200# Ultimate Pullout Values - Sammys (average lbs. ultimate) Fastener Steel Gauge Model Dia. Pt. 20 18 16 14 12 3/16 1/4 SWD 1/4 #3 1477# SWDR1 1/2"#12 #5 2375# SWDR 1"1/4 #3 1900# 1900# SWDR516 5/16 #3 2480# 2480# Ultimate Shear / Pullout Values - Sidewinders (average lbs. ultimate) Fastener Steel Gauge Gauge No.1/4 3/16 12 14 16 18 20 22 24 26 Decimal Equivalent .25 .188 .105" .075" .060" .048" .036" .030" .024" .018" SHEET STEEL GAUGES Self-Drilling • Self-tapping 302 RING HANGER SIZE - MATERIAL- Stainless Steel - (Type 304) CONFORMS WITH: MAXIMUM TEMPERATURE FUNCTION - INSTALLATION FEATURES ORDERING - 1/2 thru 8 inch pipe. Federal Specification WW-H-171 (Type 10, ManufacturersStandardization SocietyANSI/MSS-SP-58 (Type 10). - 650 F. Pipe hanger component for use on steel or copper piping. For use with CPVC - consult factory. -P - * Stainless steel swivel nut. * Custom fit swivel nut for better retention in ring body. Part #, pipe size. Note: On Copper - Insulate pipe. 0 er NFPA-13, 13R and 13D. *Sized and listed exclusively for use with #310 Surge Restrainer. 08/03 PIPE 1/2 3/4 1 1 1/4 1 1/2 2 2 1/2 3 3 1/2 4 5 6 8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 1/2 1/2 1/2 400 400 400 400 400 400 600 600 600 1000 1250 1250 1250 10 10 10 10 10 10 10 10 10 10 12 12 12 * Order Part #300m LOAD LBS. METRIC* ROD MAX REC.IMPERIAL PIPE ROD 20 25 32 40 50 65 80 100 125 150 200 Note: 1/2" Ring Hanger not <FM> approved 650 ALLTHREADED ROD 10' - 0' LENGTHS SIZE MATERIAL FINISH ORDERING - 1/4 thru 1 1/2 inch rod in 10' - 0" lengths. - Carbon Steel. - Plain, Electro-Galvanized and Stainless Steel. - Part #, rod diameter and finish. 1/4 3/8 1/2 5/8 3/4 7/8 1 1 1/4 1 1/2 240 610 1130 1810 2710 3770 4960 8000 11630 215 540 1010 1610 2420 3360 4420 7140 10370 NOTE; maximum Temperature: 750°F ROD SIZE MAX. REC. LOAD LBS. FOR SERVICE TEMP. 650°F 750°F 2/00