HomeMy WebLinkAboutComment Letter.pdf12364 West Alameda Parkway, Suite 135, Lakewood, Colorado 80228 ● 303-985-3300 ● Fax 303-985-5594
Date: July 24, 2014
Mike Vaughan
Fire Marshal
Vail Fire and Emergency Services
Vail, Colorado
mvaughan@vailgov.com
RE: Cummings Residence
4936 Juniper Lane
Dear: Mike,
Per our conversation on 7-23-14 via Phone the 10% water supply reduction required from the state
of Colorado is taken off of the water supply and not through the hydraulic calculation program. The
margin of safety for the remote areas can be seen on pages 5 of the hydraulic calculations.
The VFES water derate was calculated in the water supply and revised calculations have been
updated.
The witness for the water flow test has been revised.
The NFPA 13 2013 edition will be reference for all code related items
Space has be created to allow Town of Vail Stamp
Hangers have been verified with pipe manufacture to use Hanger LOK hangers.
Don’t hesitate to contact me if you have any questions, or need additional information.
Thanks for your help.
Sincerely,
Veritas Fire Engineering, Inc.
Ken Sutton, P.E.
Sr. Fire Protection Engineer
Veritas Fire Engineering, Inc.