HomeMy WebLinkAboutComment Letter.pdf12364 West Alameda Parkway, Suite 135, Lakewood, Colorado 80228 ● 303-985-3300 ● Fax 303-985-5594 Date: July 24, 2014 Mike Vaughan Fire Marshal Vail Fire and Emergency Services Vail, Colorado mvaughan@vailgov.com RE: Cummings Residence 4936 Juniper Lane Dear: Mike, Per our conversation on 7-23-14 via Phone the 10% water supply reduction required from the state of Colorado is taken off of the water supply and not through the hydraulic calculation program. The margin of safety for the remote areas can be seen on pages 5 of the hydraulic calculations. The VFES water derate was calculated in the water supply and revised calculations have been updated. The witness for the water flow test has been revised. The NFPA 13 2013 edition will be reference for all code related items Space has be created to allow Town of Vail Stamp Hangers have been verified with pipe manufacture to use Hanger LOK hangers. Don’t hesitate to contact me if you have any questions, or need additional information. Thanks for your help. Sincerely, Veritas Fire Engineering, Inc. Ken Sutton, P.E. Sr. Fire Protection Engineer Veritas Fire Engineering, Inc.