HomeMy WebLinkAbout135 Model F1 Res Sprinklers05gpm.pdfReliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 Bulletin 135 Rev. MBulletin 135 Rev. M
Model F1
Residential Sprinklers for
Design Density of .05 gpm/ft2
Types:
1. F1 Res 30 Pendent
2. F1 Res 30 Recessed Pendent/F2
3. F1 Res 30 Recessed Pendent/FP
4. F1 Res 49 Pendent
5. F1 Res 49 Recessed Pendent/F1
6. F1 Res 49 Recessed Pendent/FP
7. F1 Res 58 Pendent
8. F1 Res 58 Recessed Pendent/F1
9. F1 Res 58 Recessed Pendent/FP
10. F1 Res 76 Pendent
11. F1 Res 76 Recessed Pendent/F1
12. F1 Res 76 Recessed Pendent/FP
13. F1 Res 30 CCP Pendent
14. F1 Res 49 CCP Pendent
15. F1 Res 58 CCP Pendent
16. F1 Res 76 CCP Pendent
17. F1 Res 44 HSW
18. F1 Res 44 Recessed HSW/F2
19. F1 Res 58 HSW
20. F1 Res 58 HSWX
21. KRes58 HSWX
22. F1 Res 58 HSW Recessed HSW/F2
23. F1 Res 44 SWC
Listings & Approvals
1. Listed by Underwriters Laboratories Inc. and
UL Certified for Canada (cULus)
Sprinklers for .10 Density: Refer to Bulletin 176
UL Listing Category
Residential Automatic Sprinkler
UL Guide Number
VKKW
Patents
US Patent No. 6,516,893 applies to the Model F1 Res 49
& 58 Pendent Sprinklers
US Patent No. 7,353,882 applies to Model F1 Res 44 & 58
HSW Sprinklers
US Patent No. 7,784,555 applies to Model F1 Res 44 SWC
Sprinklers
Product Description
Model F1 Res Pendent sprinklers (Figs. 1, 2, 3, & 4) are fast
response sprinklers combining excellent durability, high sensitiv-
ity glass-bulb and low profile decorative design. The F1 Res
F1 Res 30, 49, 58 & 76
Recessed Pendent / FP
F1 Res 30, 49, 58 & 76
Recessed Pendent / F1
F1 Res 44 & 58
Recessed HSW/F2
F1 Res 30, 49, 58 & 76
CCP Pendent
F1 Res 44 SWC
Horizontal Sidewall sprinklers (Figs. 5, 6 & 7) are equally attrac-
tive when above ceiling piping cannot be used.
The 3mm glass-bulb pendent sprinklers permit the efficient use
of residential water supplies for sprinkler coverage in residential
fire protection design.
The low flow F1 Res sprinklers are specially engineered for fast
thermal response to meet the sensitive fire protection applica-
tion needs of the latest residential market standards (UL 1626
Standard). Upon fire conditions, rising heat causes a sprinkler’s
heat-sensitive element, glass bulb or link to actuate, releasing the
waterway for water flow onto the deflector, evenly distributing the
discharged water to control a fire.
Technical Data:
• Thermal Sensor: Soldered Element (Link) or Nominal 3mm glass-bulb
• Sprinkler Frame : Brass Casting
• Sprinklers’ Pressure Rating : 175 psi
Factory Hydrostatically Tested to 500 psi
• Thread Size: ½” NPT (R½)
• K-Factor: 3.0 (43.2) (Actual) - F1 Res 30 Pendent Sprinkler
4.9 (70.6) (Actual) - F1 Res 49 Pendent Sprinkler
5.8 (83.5) (Actual) - F1 Res 58 Pendent & HSW Sprinkler
7.6 (109)(Actual) - F1 Res 76 Pendent Sprinkler
4.4 (63) (Actual) - F1 Res 44 HSW Sprinkler• Density: Minimum 0.05 gpm/ft2
Model F1 Res Sprinklers engineered for the lowest fl ows
to meet the minimum design density of .05 gpm/ft2
F1 Res 58 HSWX
2.
Application
Model F1 Res Sprinklers are used for Residential Fire Pro-
tection according to UL 1626 Standard*. For ceiling types:
Smooth Flat Horizontal, or beamed, or sloped, in accordance
with NFPA 13D, 13R, or 13 2013 editions. Be sure that orifice
size, temperature rating, deflector style and sprinkler type are
in accordance with the latest published standards of The Na-
tional Fire Protection Association or the approving authority
having jurisdiction.
Installation
Models F1 Res sprinklers are to be installed as shown.
Model F1, F2 and FP Escutcheons, illustrated herewith, are
the only recessed escutcheons to be used with Model F1 Res
sprinklers. Use of any other recessed escutcheon will void all
approvals and warranties. For installing Model F1 Res Pen-
dent sprinklers use only the Model D sprinkler Wrench; for
installing Models F1 Res Recessed Pendent, CCP & SWC
sprinklers use only the Model GFR2 sprinkler wrench; for in-
stalling Model F1 Res Recessed HSW sprinklers use only the
Model GFR2 Sprinkler Wrench. Use of wrenches other than
those specified may damage these sprinklers. Install F1 Res
44 with a ceiling to deflector distance of 4” - 12”. Flow arrow
on deflector must point away from near wall and “Top” mark-
ing must face ceiling.
Technical Data: F1Res 30 Pendent and Recessed Pendent (SIN R3511)
Thread
Size
Nominal Orifi ce
Inch (mm)
Max. Pressure
psi (bar)
Sprinkler Temp. Rating Max. Ambient Temp. Actual K
Factor
Sprinkler Length
Inch (mm)°F °C °F °C
½” NPT (R½)21/64” (8.2) 175 (12)
155175 6879 100 38 3.0 (43.2) 2.25 (57)
Max. Coverage area
Ft x Ft (m x m)
Max.
Spacing
Ft (m)
Ordinary Temp. Rating
(155°F/68°C)
Intermediate Temp. Rating
(175°F/79°C)Top of Defl ector to Ceiling
Inch (mm)
Minimum
Spacing
Ft (m)Flow
GPM (L/min)
Pressure
PSI (bar)
Flow
GPM (L/min)
Pressure
PSI (bar)
12 x 12 (3,6 x 3,6) 12 (3,6) 8 (30,3) 7.0 (0,48) 8 (30,3) 7.0 (0,48)
Smooth Ceilings 1¼ to 4 (31.7 to 102)
using F2 escutcheon.
Beamed Ceilings per NFPA 13D, 13R
or 13 installed in beams 1¼ to 1¾ (31.7 to 44.4) using F2 escutcheon
8 (2,4)14 x 14 (4,3 x 4,3) 14 (4,3) 10 (37,8) 11 (0,76) 10 (37,8) 11 (0,76)
16 x 16 (4,9 x 4,9) 16 (4,9) 13 (49) 18.8 (1,3) 13 (49) 18.8 (1,3)
For Ceiling types refer to NFPA 13, 13R or 13D
• Model F1 Res 30, 49, 58 & 76 Pendent
• Model F1 Res 30 Recessed Pendent / F2
• Model F1 Res 49, 58 & 76 Recessed Pendent / F1
Fig. 1 Fig. 2
F1 escutcheon, 3/4” (19mm) adjustment
Escutcheon*, F1 or F2, Data:
Type Adjustment
Inch (mm)
“A”
Inch (mm)
Face of fi tting to ceiling
Inch (mm)
“B”
Defl ector Distance below bottom of beam
Inch (mm)
F1 ¾ (19.0)
Min. Recessed = 15/8 (41.3)Max. Recessed = 7/8 (22.2)
3/8 (9.5)11/8 (28.6)13/4 (44.4)1 (25.4)
F2 ½ (12.7)
Min. Recessed = 15/8 (41.3)
Max. Recessed = 11/8 (28.6)
3/8 (9.5)
7/8 (22.2)
13/4 (44.4)
1¼ (31.7)
* Note: Escutcheons F1 or F2 may be used with Model F1 Res 49, 58 & 76 Recessed Pendent Sprinkler
3.
Technical Data: F1Res 49 Pendent and Recessed Pendent (SIN R3516)
Thread
Size
Nominal Orifi ce
Inch (mm)
Max.
Pressure
psi (bar)
Sprinkler
Temp. Rating
Max.
Ambient Temp.
Actual
K
Factor
Sprinkler
Length
Inch (mm)°F °C °F °C
½” NPT
(R½)7/16” (11) 175 (12)
155
175
68
79
100
150
38
66 4.9 (70.6) 2.25 (57)
Max. Coverage area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
(155°F/68°C)
Intermediate Temp. Rating
(175°F/79°C)Top of Defl ector
to Ceiling
Inch (mm)
Minimum
Spacing
Ft (m)Flow
GPM (L/min)
Pressure
PSI (bar)
Flow
GPM (L/min)
Pressure
PSI (bar)
12 x 12 (3,6 x 3,6) 12 (3,6) 13 (49) 7.0 (0,48) 13 (49) 7.0 (0,48)
Smooth Ceilings 1¼ to 4 (31.7 to
102) using F2 escutcheon.
1 to 4 (25.4 to 102) using F1
escutcheon.
Beamed Ceilings per NFPA 13D, 13R or 13 installed in
beams 1¼ to 1¾ (31.7 to
44.4) using F2 escutcheon, 1
to 1¾ (25.4 to 44.4) using F1
escutcheon
8 (2,4)
14 x 14 (4,3 x 4,3) 14 (4,3) 13 (49) 7.0 (0,48) 13 (49) 7.0 (0,48)
16 x 16 (4,9 x 4,9) 16 (4,9) 13 (49) 7.0 (0,48) 13 (49) 7.0 (0,48)
18 x 18 (5,5 x 5,5) 18 (5,5) 17 (64,3) 12 (0,83) 17 (64,3) 12 (0,83)
20 x 20 (6,1 x 6,1) 20 (6,1) 20 (75,7) 16.7 (1,14) 20 (75,7) 16,7 (1,14)
For Ceiling types refer to NFPA 13, 13R or 13D
Max. Coverage area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
(155°F/68°C)
Intermediate Temp. Rating
(175°F/79°C)Top of Defl ector
to Ceiling
Inch (mm)
Minimum
Spacing
Ft (m)Flow
GPM (L/min)
Pressure
PSI (bar)
Flow
GPM (L/min)
Pressure
PSI (bar)
12 x 12 (3,6 x 3,6) 12 (3,6) 15 (57) 9.4 (0,65) 15 (57) 9.4 (0,65)Smooth Ceilings 4 to 8 (100 to
203) using F2 escutcheon.4 to 8 (100 to 203) using F1
escutcheon.
Beamed Ceilings per NFPA 13D,
13R or 13 installed in beams
4¼ to 8 (108 to 203) using F2 escutcheon, 4 to 8 (100 to 203)
using F1 escutcheon
8 (2,4)
14 x 14 (4,3 x 4,3) 14 (4,3) 16 (60,5) 10.6 (0,73) 16 (60,5) 10.6 (0,73)
16 x 16 (4,9 x 4,9) 16 (4,9) 17 (64,3) 12.0 (0,83) 17 (64,3) 12.0 (0,83)
18 x 18 (5,5 x 5,5) 18 (5,5) 19 (72) 15.0 (1,0) 19 (72) 15.0 (1,0)
20 x 20 (6,1 x 6,1) 20 (6,1) 22 (83,2) 20.2 (1,4) 22 (83,2) 20.2 (1,4)
Technical Data: F1Res 58 Pendent and Recessed Pendent (SIN R3513)
Thread
Size
Nominal Orifi ce
Inch (mm)
Max.
Pressure
psi (bar)
Sprinkler
Temp. Rating
Max.
Ambient Temp.Actual
K Factor
Sprinkler
Length
Inch (mm)°F °C °F °C
½” NPT
(R½)½” (13) 175 (12)
155
175
68
79
100
150
38
66 5.8 (83.5) 2.25 (57)
Max. Coverage area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
(155°F/68°C)
Intermediate Temp. Rating
(175°F/79°C)Top of Defl ector
to Ceiling
Inch (mm)
Minimum
Spacing
Ft (m)Flow
GPM (L/min)
Pressure
PSI (bar)
Flow
GPM (L/min)
Pressure
PSI (bar)
12 x 12 (3,6 x 3,6) 12 (3,6) 16 (61) 7.6 (0,53) 16 (61) 7.6 (0,53)Smooth Ceilings 1¼ to 4 (31.7 to
102) using F2 escutcheon.
1 to 4 (25.4 to 102) using F1 escutcheon.
Beamed Ceilings per NFPA 13D,
13R or 13 installed in beams
1¼ to 1¾ (31.7 to 44.4) using
F2 escutcheon, 1 to 1¾ (25.4 to 44.4) using F1 escutcheon
8 (2,4)
14 x 14 (4,3 x 4,3) 14 (4,3) 16 (61) 7.6 (0,53) 16 (61) 7.6 (0,53)
16 x 16 (4,9 x 4,9) 16 (4,9) 16 (61) 7.6 (0,53) 16 (61) 7.6 (0,53)
18 x 18 (5,5 x 5,5) 18 (5,5) 19 (72) 10.8 (0,75) 19 (72) 10.8 (0,75)
20 x 20 (6,1 x 6,1) 20 (6,1) 22 (83,3) 14.4 (1,0) 22 (83,3) 14.4 (1,0)
For Ceiling types refer to NFPA 13, 13R or 13D
Note: The F1 Res 76 will use a 1” x ¾” reducer.
FP push-on/thread-off escutcheon
Fig. 3 Fig. 4
4.
• Model F1 Res 30, 49, 58 & 76 CCP Pendent*• Model F1 Res 30, 49, 58 & 76
Recessed Pendent / FP
Technical Data: F1 Res 76 Pendent and Recessed Pendent (SIN R7618)
Thread
Size
Nominal Orifi ce
Inch (mm)
Max.
Pressure
psi (bar)
Sprinkler
Temp. Rating
Max.
Ambient Temp.K
Factor
Sprinkler
Length
Inch (mm)°F °C °F °C
3/4” NPT (R3/4)17/32” (13.5) 175 (12)
155175 6879 100150 3866 7.6 (109) 2.25 (57)
Max. Coverage area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
(155°F/68°C)
Intermediate Temp. Rating
(175°F/79°C)Top of Defl ector to Ceiling
Inch (mm)
Minimum
Spacing
Ft (m)Flow
GPM (L/min)
Pressure
PSI (bar)
Flow GPM
(L/min)
Pressure
PSI (bar)
12 x 12 (3,6 x 3,6) 12 (3,6) 21 (79,5) 7.6 (0,53) 21 (79,5) 7.6 (0,53)Smooth Ceilings 4¼ to 8 (108
to 203) using F2 escutcheon.4 to 8 (100 to 203) using F1
escutcheon.
Beamed Ceilings per NFPA 13D, 13R or 13 installed in
beams 4¼ to 8 (108 to 203) us-ing F2 escutcheon, 4 to 8 (100
to 203) using F1 escutcheon
8 (2,4)
14 x 14 (4,3 x 4,3) 14 (4,3) 21 (79,5) 7.6 (0,53) 21 (79,5) 7.6 (0,53)
16 x 16 (4,9 x 4,9) 16 (4,9) 21 (79,5) 7.6 (0,53) 21 (79,5) 7.6 (0,53)
18 x 18 (5,5 x 5,5) 18 (5,5) 21 (79,5) 7.6 (0,53) 21 (79,5) 7.6 (0,53)
20 x 20 (6,1 x 6,1) 20 (6,1) 23 (87,1) 9.2 (0,63) 23 (87,1) 9.2 (0,63)
For Ceiling types refer to NFPA 13, 13R or 13D
CCP Cover Plate Data:
“A”
Cover Adjustment
Inch (mm)
“B”
CCP Height
Inch (mm)
“C”
Defl ector Distance below bottom
of beam
Inch (mm)
½ (12.7)15/16 (24) ½ (13) - 1
(25.4)
5/16 (7.9)3/4 (19) ½ (13) - 1
(25.4)
FP Escutcheon Data:
FP Position “A”
Inch (mm)
“B”
Defl ector Distance below bottom
of beam
Inch (mm)
Max. Recessed 7/16 (11) ½ (12.7)
Min. Recessed 15/16 (24) 1 (25.4)
Note: Sprinklers shown in Fig. 3 and Fig. 4 are not suitable for installation in ceilings which have positive pressure in
the space above.
* Not listed for corrosion resistance.
5.
Technical Data: F1Res 30 CCP Pendent and Recessed Pendent/FP (SIN R3511)
Thread
Size
Nominal
Orifi ce
Inch (mm)
Max.
Pressure
psi (bar)
CCP Assembly
Temp. Rating
Max.
Ambient Temp.K
Factor
Sprinkler
Length
Inch (mm)°F °C °F °C
½” NPT (R½)21/64” (8.2) 175 (12) 135 57 100 38 3.0 (43.2) 2.25 (57)
Max. Coverage area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
(155°F/68°C)Top of Defl ector to Ceiling
Inch (mm)
Minimum
Spacing
Ft (m)Flow
GPM (L/min)
Pressure
PSI (bar)
12 x 12 (3,6 x 3,6) 12 (3,6) 8 (30,3) 7.0 (0,48)
Smooth Ceilings ½ to 1 (13 to 25.4) using CCP.
½ to 1 (13 to 25.4) using FP escutcheon.
Beamed Ceilings per NFPA 13D, 13R or 13 installed in
beams ½ to 1 (13 to 25.4) using CCP.½ to 1 (13 to 25.4) using FP escutcheon.
8 (2,4)
14 x 14 (4,3 x 4,3) 14 (4,3) 11 (37,8) 13.4 (0,92)
For Ceiling types refer to NFPA 13, 13R or 13D
Technical Data: F1Res 49 CCP Pendent and Recessed Pendent/FP (SIN 3516)
Thread
Size
Nominal
Orifi ce
Inch
(mm)
Max.
Pressure
psi (bar)
CCP
Assembly
Temp.
Rating
Max.
Ambient
Temp.
K
Factor
Sprinkler
Length
Inch (mm)
°F °C °F °C
½” NPT (R½)7/16” (11) 175 (12) 135 57 100 38 4.9 (70.6) 2.25 (57)
Max. Coverage
area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
(155°F/68°C)Top of Defl ector to Ceiling
Inch (mm)
Minimum
Spacing
Ft (m)Flow
GPM (L/min)
Pressure
PSI (bar)
12 x 12 (3,6 x 3,6) 12 (3,6) 13 (49) 7.0 (0,48)Smooth Ceilings ½ to 1 (13 to 25.4) using
CCP.
½ to 1 (13 to 25.4) using FP escutcheon.
Beamed Ceilings per NFPA 13D, 13R or 13
installed in beams ½ to 1 (13 to 25.4) using CCP.
½ to 1 (13 to 25.4) using FP escutcheon.
8 (2,4)
14 x 14 (4,3 x 4,3) 14 (4,3) 13 (49) 7.0 (0,48)
16 x 16 (4,9 x 4,9) 16 (4,9) 14 (53) 8.2 (0,56)
18 x 18 (5,5 x 5,5) 18 (5,5) 18 (68,1) 13.5 (0,93)
20 x 20 (6,1 x 6,1) 20 (6,1) 20 (75,7) 16.7 (1,14)
For Ceiling types refer to NFPA 13, 13R or 13D
Technical Data: F1Res 58 CCP Pendent and Recessed Pendent/FP (SIN R3513)
Thread
Size
Nominal
Orifi ce
Inch (mm)
Max.
Pressure
psi (bar)
CCP Assembly
Temp. Rating
Max.
Ambient Temp.K
Factor
Sprinkler
Length
Inch (mm)°F °C °F °C
½” NPT
(R½)1/2” (13) 175 (12) 135 57 100 38 5.8 (83.5) 2.25 (57)
Max. Coverage
area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
(155°F/68°C)Top of Defl ector to Ceiling
Inch (mm)
Minimum
Spacing
Ft (m)Flow
GPM (L/min)
Pressure
PSI (bar)
12 x 12 (3,6 x 3,6) 12 (3,6) 16 (61) 7.6 (0,53)
Smooth Ceilings ½ to 1 (13 to 25.4) using CCP.
½ to 1 (13 to 25.4) using FP escutcheon.Beamed Ceilings per NFPA 13D, 13R or 13 installed in beams ½ to
1 (13 to 25.4) using CCP.
½ to 1 (13 to 25.4) using FP escutcheon.
8 (2,4)
14 x 14 (4,3 x 4,3) 14 (4,3) 16 (61) 7.6 (0,53)
16 x 16 (4,9 x 4,9) 16 (4,9) 16 (61) 7.6 (0,53)
18 x 18 (5,5 x 5,5) 18 (5,5) 19 (72) 10.8 (0,75)
20 x 20 (6,1 x 6,1) 20 (6,1) 22 (83,3) 14.4 (1,0)
For Ceiling types refer to NFPA 13, 13R or 13D
6.
• Model F1 Res 44 & 58 HSW
• Model F1 Res 44 & 58 Recessed HSW/F2
F2 escutcheon,
1/2” (13mm) adjustment
Escutcheon, F2, Data:
Type Adjustment
Inch (mm)
Face of Fitting
to wall
Inch (mm)
F2 1/2 (13)3/16 - 11/16
(4.7 - 17.4)
Fig. 5
Technical Data: F1Res 76 CCP Pendent and Recessed Pendent/FP (SIN R7618)
Thread
Size
Nominal
Orifi ce
Inch (mm)
Max.
Pressure
psi (bar)
CCP Assembly
Temp. Rating
Max.
Ambient Temp.K
Factor
Sprinkler
Length
Inch (mm)°F °C °F °C
3/4” NPT (R3/4)17/32” (13.5) 175 (12) 135 57
100150 3866 7.6 (109) 2.25 (57)
Max. Coverage
area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
(155°F/68°C)Top of Defl ector to Ceiling
Inch (mm)
Minimum
Spacing
Ft (m)Flow
GPM (L/min)
Pressure
PSI (bar)
12 x 12 (3,6 x 3,6) 12 (3,6) 21 (79,5) 7.6 (0,53)
Smooth Ceilings ½ to 1 (13 to 25.4) using CCP.
½ to 1 (13 to 25.4) using FP escutcheon.
Beamed Ceilings per NFPA 13D, 13R or 13 installed in beams ½
to 1 (13 to 25.4) using CCP.
½ to 1 (13 to 25.4) using FP escutcheon.
8 (2,4)
14 x 14 (4,3 x 4,3) 14 (4,3) 21 (79,5) 7.6 (0,53)
16 x 16 (4,9 x 4,9) 16 (4,9) 21 (79,5) 7.6 (0,53)
18 x 18 (5,5 x 5,5) 18 (5,5) 22 (83,3) 8.4 (0,58)
20 x 20 (6,1 x 6,1) 20 (6,1) 25 (94,6) 10.8 (0,74)
For Ceiling types refer to NFPA 13, 13R or 13D
Technical Data: F1Res 44 HSW & HSW/F2 (SIN R3531)
Thread
Size
Nominal
Orifi ce
Inch (mm)
Max.
Pressure
psi (bar)
Sprinkler
Temp. Rating
Max.
Ambient
Temp.
K
Factor
Sprinkler
Length
Inch (mm)°F °C °F °C
½” NPT
(R½)3/8” (10) 175 (12)
155
175
68
79
100
150
38
66 4.4 (63) 2.45 (62)
7.
Max. Coverage area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
(155°F/68°C)
Intermediate Temp. Rating
(175°F/79°C)Top of Defl ector to
Ceiling
Inch (mm)
Minimum
Spacing
Ft (m)Flow
GPM (L/min)
Pressure
PSI (bar)
Flow
GPM (L/min)
Pressure
PSI (bar)
12 x 12 (3,6 x 3,6) 12 (3,6) 12 (45,4) 7.5 (0,52) 12 (45,4) 7.5 (0,52)
4 to 6 (100 to 152);½ (13) recessed
using F2 escutcheon
8 (2,4)
14 x 14 (4,3 x 4,3) 14 (4,3) 14 (53,0) 10.2 (0,71) 14 (53,0) 10.2 (0,71)
16 x 16 (4,9 x 4,9) 16 (4,9) 16 (60,6) 13.3 (0,92) 16 (60,6) 13.3 (0,92)
16 x 18 (4,9 x 5,5) 16 (4,9) 18 (68,1) 16.8 (0,53) 18 (68,1) 16.8 (0,53)
18 x 18 (5,5 x 5,5) 18 (5,5) 19 (72,0) 18.7 (1,29) 19 (72,0) 18.7 (1,29)
16 x 20 (4,9 x 6,1) 16 (4,9) 23 (87,1) 27.4 (1,89) 23 (87,1) 27.4 (1,89)
12 x 12 (3,6 x 3,6) 12 (3,6) 14 (53,0) 10.2 (0,71) 14 (53,0) 10.2 (0,71)
6 to 12 (152 to 305);
½ (13) recessedusing F2 escutcheon
14 x 14 (4,3 x 4,3) 14 (4,3) 16 (60,6) 13.3 (0,92) 16 (60,6) 13.3 (0,92)
16 x 16 (4,9 x 4,9) 16 (4,9) 17 (64,4) 15.0 (1,04) 17 (64,4) 15.0 (1,04)
16 x 18 (4,9 x 5,5) 16 (4,9) 20 (75,7) 20.7 (1,43) 20 (75,7) 20.7 (1,43)
16 x 20 (4,9 x 6,1) 16 (4,9) 23 (87,1) 27.4 (1,89) 23 (87,1) 27.4 (1,89)
For Ceiling types refer to NFPA 13, 13R or 13D
Escutcheon, F2, Data:
Type Adjustment
Inch (mm)
Face of Fitting
to wall
Inch (mm)
F2 1/2 (13)3/16 - 11/16
(4.7 - 17.4)
Technical Data: F1Res 58 HSW & HSW/F2 (SIN R3533)
Thread
Size
Nominal
Orifi ce
Inch
(mm)
Max.
Pressure
psi (bar)
Sprinkler
Temp. Rating
Max.
Ambient
Temp.
K
Factor
Sprinkler
Length
Inch
(mm)°F °C °F °C
½” NPT
(R½)1/2” (13) 175 (12)
155
175
68
79
100
150
38
66 5.8 (83.5) 2.45 (62)
Max. Coverage area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
(155°F/68°C)
Intermediate Temp. Rating
(175°F/79°C)Top of Defl ector to
Ceiling
Inch (mm)
Minimum
Spacing
Ft (m)Flow
GPM (L/min)
Pressure
PSI (bar)
Flow
GPM (L/min)
Pressure
PSI (bar)
12 x 12 (3,6 x 3,6) 12 (3,6) 16 (60,6) 7.6 (0,53) 16 (60,6) 7.6 (0,53)
4 to 6 (100 to 152);
½ (13) recessed
using F2 escutcheon
8 (2,4)
14 x 14 (4,3 x 4,3) 14 (4,3) 18 (68,2) 9.7 (0,69) 18 (68,2) 9.7 (0,69)
16 x 16 (4,9 x 4,9) 16 (4,9) 21 (79,5) 13.2 (0,91) 21 (79,5) 13.2 (0,91)
16 x 18 (4,9 x 5,5) 16 (4,9) 25 (94,7) 18.6 (1,28) 25 (94,7) 18.6 (1,28)
16 x 20 (4,9 x 6,1) 16 (4,9) 29 (109,8) 25.0 (1,73) 29 (109,8) 25.0 (1,73)
12 x 12 (3,6 x 3,6) 12 (3,6) 22 (83,3) 14.4 (1,0) 22 (83,3) 14.4 (1,0)
6 to 12 (152 to 305); ½ (13) recessed
using F2 escutcheon
14 x 14 (4,3 x 4,3) 14 (4,3) 22 (83,3) 14.4 (1,0) 22 (83,3) 14.4 (1,0)
16 x 16 (4,9 x 4,9) 16 (4,9) 26 (98,4) 20.1 (1,39) 26 (98,4) 20.1 (1,39)
16 x 18 (4,9 x 5,5) 16 (4,9) 31 (117,4) 28.6 (1,97) 31 (117,4) 28.6 (1,97)
For Ceiling types refer to NFPA 13, 13R or 13D
• Model F1 Res 44 SWC*
Fig. 6
Technical Data: F1Res 44 SWC (SIN R3531)
Thread
Size
Nominal
Orifi ce
Inch (mm)
Max.
Pressure
psi (bar)
Cover
Temp.
Rating
Max.
Ambient
Temp.
K
Factor
Sprinkler
Length
Inch (mm)°F °C °F °C
½” NPT
(R½)3/8” (10) 175 (12) 135 57 100 38 4.4 (63) 2.45 (62)
Max. Coverage area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
(155°F/68°C)Top of Defl ector to
Ceiling
Inch (mm)
Minimum
Spacing
Ft (m)Flow
GPM (L/min)
Pressure
PSI (bar)
12 x 12 (3,6 x 3,6) 12 (3,6) 13 (49,2) 8.7 (0,60)
4 to 6 (100 to 152);½ (13) recessed
using F2 escutcheon
8 (2,4)
14 x 14 (4,3 x 4,3) 14 (4,3) 14 (53,0) 10.2 (0,71)
16 x 16 (4,9 x 4,9) 16 (4,9) 17 (64,3) 15.0 (1,1)
16 x 18 (4,9 x 5,5) 16 (4,9) 19 (71,8) 18.7 (1,13)
16 x 20 (4,9 x 6,1) 16 (4,9) 23 (87,1) 27.4 (1,89)
12 x 12 (3,6 x 3,6) 12 (3,6) 14 (52,9) 10.2 (0,71)
6 to 12 (152 to 305);
½ (13) recessed
using F2 escutcheon
14 x 14 (4,3 x 4,3) 14 (4,3) 15 (56,7) 11.7 (0,81)
16 x 16 (4,9 x 4,9) 16 (4,9) 18 (68,1) 16.8 (1,16)
16 x 18 (4,9 x 5,5) 16 (4,9) 20 (75,6) 20.7 (1,43)
For Ceiling types refer to NFPA 13, 13R or 13D
8.
* Not listed for corrosion resistance.
9.
Technical Data: F1Res 58 HSWX (SIN RA3533)
Thread
Size
Nominal
Orifi ce
Inch (mm)
Max.
Pressure
psi (bar)
Sprinkler
Temp. Rating
Max.
Ambient
Temp.
K
Factor
Sprinkler
Length
Inch (mm)
Sprinkler
Identifi cation
Number (SIN)°F °C °F °C
Bulb ½” NPT
(R½)1/2” (13) 175 (12)
155
175
68
79
100
150
38
66 5.8 (83.5) 2.45 (62) RA3533
Max. Coverage area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
(155°F/68°C)
Intermediate Temp. Rating
(175°F/79°C)Top of Defl ector to
Ceiling
Inch (mm)
Minimum
Spacing
Ft (m)Flow
GPM (L/min)
Pressure
PSI (bar)
Flow
GPM (L/min)
Pressure
PSI (bar)
18 x 20 (5,5 x 6,1) 18 (5,5) 30 (114) 26.8 (1,85) 30 (114) 26.8 (1,85)
4 to 6 (100 to 152);½ (13) recessed
using F2 escutcheon
8 (2,4)
20 x 20 (6,1 x 6,1) 20 (6,1) 30 (114) 26.8 (1,85) 30 (114) 26.8 (1,85)
16 x 22 (4,9 x 7,3) 16 (4,9) 33 (125) 32.4 (2,23) 33 (125) 32.4 (2,23)
16 x 24 (4,9 x 7,3) 16 (4,9) 38 (144) 42.9 (2,96) 38 (144) 42.9 (2,96)
14 x 26 (4,3 x 7,9) 14 (4,3) 42 (160) 52.4 (3,75) 42 (160) 52.4 (3,75)
18 x 20 (5,5 x 6,1) 18 (5,5) 35 (133) 36.4 (2,5) 35 (133) 36.4 (2,5)
6 to 12 (152 to 305);
½ (13) recessed
using F2 escutcheon
16 x 22 (4,9 x 6,7) 16 (4,9) 38 (144) 42.9 (2,96) 38 (144) 42.9 (2,96)
16 x 24 (4,9 x 7,3) 16 (4,9) 42 (160) 52.4 (3,6) 42 (160) 52.4 (3,6)
14 x 26 (4,3 x 7,9) 14 (4,3) 46 (174) 62.9 (4,34) 46 (174) 62.9 (4,34)
For Ceiling types refer to NFPA 13, 13R or 13D
• Model F1 Res 58 HSWX (Bulb)
• Model KRes58 HSWX (Link)
Fig. 7
10.
Maintenance
Model F1 Res 30, 49, F1 Res 58, F1 Res 76 and F1 Res
44 Sprinklers should be inspected and the sprinkler sys-
tem maintained in accordance with NFPA 25, 13, 13D,
and 13R. Do not clean sprinkler with soap and water, Am-
monia or any other cleaning fluids. Remove dust by using
a soft brush or gentle vacuuming. Remove any sprinkler
which has been painted (other than factory applied) or
damaged in any way. A stock of spare sprinklers should
be maintained to allow quick replacement of damaged or
operated sprinklers. Prior to installation, sprinklers should
remain in the original cartons and packaging until used.
This will minimize the potential for damage to sprinklers
that could cause improper operation or non-operation.
Model F1 Res 30, 49 & 58 Pendent
Sprinkler Specifi cations
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258-93-E)] low flow residential pendent sprin-
klers engineered to provide a minimum design density of
0.05 gpm/ft2 over the listed coverage area. Listed flows
as specified by the manufacturer’s technical data sheets
are to be used. Residential sprinklers shall be installed
in conformance with the manufacturer’s installation guide-
lines and the applicable installation standard. Deflector-
to-ceiling distance listing shall be 1” to 8” maximum, only
for F1Res 49. Sprinkler frame and deflector shall be of
bronze frame construction having a ½” NPT thread. Wa-
ter seal assembly shall consist of a Teflon* coated Bel-
leville spring washer with top-loaded extruded or cold
head cup with 3 mm glass bulb containing no plastic
parts, and having a temperature rating of [155°F (68°C)]
[175°F (79°C)]. Sprinklers shall have a nominal K-factor
of 3.0, 4.9 and 5.8. Standard finish: [Bronze] [Chrome-
plated] [White Polyester] [Special finish– specify]. Resi-
dential pendent sprinklers shall be Reliable Model F1 Res
30, 49 & 58, SIN R3511, R3516 & R3513 (Bulletin 135).
Model F1 Res 49 & 58 Recessed Pendent/F1,
Model F1 Res 30, 49 & 58 Recessed Pendent/
F2, Model F1 Res 30, 49 & 58 Recessed Pendent/
FP
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258-93-E)] low flow residential recessed pen-
dent sprinklers engineered to provide a minimum design
density of 0.05 gpm/ft2 over the listed coverage area.
Listed flows as specified by the manufacturer’s technical
data sheets are to be used. Residential sprinklers shall
be installed in conformance with the manufacturer’s in-
stallation guidelines and the applicable installation stan-
dard. Deflector-to-ceiling distance listing shall be 1” to 8”
maximum, only for F1Res 49. Sprinkler frame and deflec-
tor shall be of bronze frame construction having a ½” NPT
thread. Water seal assembly shall consist of a Teflon*
coated Belleville spring washer with top-loaded extruded
Technical Data: KRes58 HSWX (RA3593)
Thread
Size
Nominal
Orifi ce
Inch (mm)
Max.
Pressure
psi (bar)
Max.
Ambient
Temp.
K
Factor
Sprinkler
Length
Inch (mm)
Sprinkler
Identifi cation
Number (SIN)°F °C
Link ½” NPT
(R½)1/2” (13) 175 (12) 100 38 5.8 (83.5) 2.45 (62) RA3593
Max. Coverage area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
(165°F/74°C)Top of Defl ector to
Ceiling
Inch (mm)
Minimum
Spacing
Ft (m)Flow
GPM (L/min)
Pressure
PSI (bar)
18 x 20 (5,5 x 6,1) 18 (5,5) 29 (109) 25 (1,72)
4 to 6 (100 to 152);½ (13) recessed
using F2 escutcheon
8 (2,4)
20 x 20 (6,1 x 6,1) 20 (6,1) 30 (114) 26.8 (1,85)
16 x 22 (4,9 x 7,3) 16 (4,9) 33 (125) 32.4 (2,23)
16 x 24 (4,9 x 7,3) 16 (4,9) 38 (144) 42.9 (2,96)
14 x 26 (4,3 x 7,9) 14 (4,3) 42 (160) 52.4 (3,75)
18 x 20 (5,5 x 6,1) 18 (5,5) 35 (133) 36.4 (2,5)
6 to 12 (152 to 305);
½ (13) Recessedusing F2 escutcheon
16 x 22 (4,9 x 6,7) 16 (4,9) 38 (144) 42.9 (2,96)
16 x 24 (4,9 x 7,3) 16 (4,9) 42 (160) 52.4 (3,6)
14 x 26 (4,3 x 7,9) 14 (4,3) 46 (174) 62.9 (4,34)
For Ceiling types refer to NFPA 13, 13R or 13D
*DuPont Registered Trademark
11.
or cold head cup with 3 mm glass bulb containing no
plastic parts, and having a temperature rating of [155°F
(68°C)] [175°F (79°C)]. Sprinklers shall have a nomi-
nal K-factor of 3.0, 4.9 & 5.8. Standard finish: [Bronze]
[Chrome-plated] [White Polyester] [Special finish– spec-
ify]. Recessed escutcheon assembly shall be a steel,
two-piece escutcheon [with ½” adjustment (Model F2)]
[with ¾” adjustment (Model F1)] [of push-on and thread
off design with ½” adjustment (Model FP)]. Standard fin-
ish shall be [brass][bright chrome] [white painted]. Resi-
dential recessed pendent sprinklers shall be Reliable
[Model F1 Res 30, 49 & 58 Recessed Pendent/F1] [Model
F1 Res 30, 49 & 58 Recessed Pendent/F2] [Model F1 Res
30, 49 & 58 Recessed Pendent/FP] SIN R3511, R3516 &
R3513 (Bulletin 135).
Model F1 Res 30, 49 & 58 CCP Pendent
(Concealed)
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258-93-E)] low flow residential concealed
sprinklers engineered to provide a minimum design den-
sity of 0.05 gpm/ft2 over the listed coverage area. Listed
flows as specified by the manufacturer’s technical data
sheets are to be used. Residential sprinklers shall be in-
stalled in conformance with the manufacturer’s installa-
tion guidelines and the applicable installation standard.
Sprinkler frame and deflector shall be of bronze frame
construction having a ½” NPT thread. Water seal as-
sembly shall consist of a Teflon* coated Belleville spring
washer with top-loaded extruded or cold head cup with 3
mm glass bulb containing no plastic parts, and having a
temperature rating of 155°F (68°C). Cover plate assem-
bly shall consist of a brass cover plate and copper alloy
retainer flange. Method of attaching the cover plate to the
sprinkler cup shall be a push-on and thread-off design
allowing a ½” cover plate adjustment. Cover plate tem-
perature rating shall be 135°F (57°C). A plastic protec-
tive cap shall be provided and factory installed inside the
sprinkler cup to protect the sprinkler from damage, which
could occur during construction before the cover plate
is installed. Standard cover plate finish: [White] [Custom
Color– specify]. ]. Concealed pendent sprinklers shall
be Reliable Model F1 Res 30, 49 & 58 CCP, SIN R3511,
R3516 & R3513 (Bulletin 135).
Model F1 Res 44, F1 Res 58 Horizontal
Sidewall, F1 Res 58 HSWX & KRes58 HSWX
Residential Sprinkler Specifi cations
Sprinklers shall be [cULus Listed] low flow residential
horizontal sidewall sprinklers engineered to provide a
minimum design density of 0.05 gpm/ft2 over the listed
coverage area. Listed flows as specified by the manu-
facturer’s technical data sheets are to be used. Residen-
tial sprinklers shall be installed in conformance with the
manufacturer’s installation guidelines and the applicable
installation standard. Sprinkler frame and deflector shall
be of bronze frame construction having a ½” NPT thread.
Water seal assembly shall consist of a Teflon* coated Bel-
leville spring washer with top-loaded extruded or cold
head cup with 3 mm glass bulb containing no plastic
parts, and having a temperature rating of [155°F (68°C)]
[175°F (79°C)]. The solder element (Link) version, the
water seal consist of a cap with a bellville spring washer
and a temperature rating of 165°F (74°C). The recessed
assembly forthe HSWX (Bulb & Link) should be a steel
two pieces escutcheon with 1/2” adjustment (Model F2)
standard finish should be Bright Chrome and white paint-
ed. The F1 Res 58 HSW is also available with low lead
frame. F1 Res 58 HSW and HSWX sprinklers shall have a
nominal K Factor of 5.8 and F1 Res 44 a nominal K factor
of 4.4. Standard finish: [Bronze] [Chrome-plated] [White
Polyester] [Special finish– specify]. Residential horizontal
sidewall sprinklers shall be Reliable Model F1 Res 44, F1
Res 58, F1 Res 58 HSWX & Model KRes58 HSWX, SIN
R3531, RA3533 & RA3593 (Bulletin 135).
Model F1 Res 44 Recessed
Horizontal Sidewall Sprinkler
Use description for the Model F1 Res 44 horizontal side-
wall sprinkler with the following modifications: Replace
“horizontal sidewall sprinkler” with “recessed horizontal
sprinkler.” Add: Recessed escutcheon assembly shall be
a steel, two-piece escutcheon with ½” adjustment (Model
F2). Standard finish shall be [brass][bright chrome] [white
painted] [Special finish– specify]. Residential recessed
horizontal sidewall sprinklers shall be Reliable Model F1
Res 44/F2, SIN R3531 (Bulletin 135).
Model F1 Res 76 Pendent
Sprinklers shall be [cULus Listed] low flow residential
pendent sprinklers engineered to provide a minimum
design density of 0.05 gpm/ft2 over the listed coverage
area. Listed flows as specified by the manufacturer’s
technical data sheets are to be used. Residential sprin-
klers shall be installed in conformance with the manufac-
turer’s installation guidelines and the applicable installa-
tion standard. Sprinkler frame and deflector shall be of
bronze frame construction having a ¾” NPT thread. Wa-
ter seal assembly shall consist of a Teflon* coated Bel-
leville spring washer with machined or cold head cup with
3 mm glass bulb containing no plastic parts, and having
a temperature rating of [155°F (68°C)] [175°F (79°C)].
Sprinklers shall have a nominal K-factor of 7.6. Standard
finish: [Bronze] [Chrome-plated] [White Polyester] [Spe-
cial finish– specify]. Residential pendent sprinklers shall
be Reliable Model F1 Res 76, SIN R7618 (Bulletin 135).
*DuPont Registered Trademark
Reliable Automatic Sprinkler Co., Inc.(800) 431-1588 Sales Offices
(800) 848-6051 Sales Fax
(914) 829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address
Manufactured by
Recycled
Paper
Revision lines indicate updated or new data.
EG. Printed in U.S.A. 07/14 P/N 9999970235
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
a temperature rating of 155°F (68°C). Cover plate assem-
bly shall consist of a brass cover plate and copper alloy
retainer flange. Method of attaching the cover plate to the
sprinkler cup shall be a push-on and thread-off design
allowing a ½” cover plate adjustment. Cover plate tem-
perature rating shall be 135°F (57°C). A plastic protec-
tive cap shall be provided and factory installed inside the
sprinkler cup to protect the sprinkler from damage, which
could occur during construction before the cover plate
is installed. Standard cover plate finish: [White] [Custom
Color– specify]. ]. Concealed pendent sprinklers shall be
Reliable Model F1 Res 76 CCP, SIN R7618 (Bulletin 135).
Finishes (1)
Standard Finishes
Sprinkler F1, F2, FP
Escutcheons Cover Plates
Bronze
Chrome Plated
White and Black
Polyester(2) Coated
Brass
Bright Chrome Plated
White Painted
White Painted
Chrome
Special Application Finishes
Sprinkler F1, F2, FP
Escutcheons
Electroless Nickel PTFE(Teflon®)(2)
Bright Brass
Black PlatedBlack Paint
Off White Chrome Dull
Electroless Nickel PTFE (Teflon®)
Bright Brass
Black PlatedBlack Paint
Off White Chrome Dull
(1) Other finishes and colors are available on special order.
Consult factory for details.
(2) cULus listed Corrosion Resistant
Note: Paint or any other coating applied over the factory finish will void
all approvals and warranties.
Ordering Information
Specify:
1. Sprinkler Model
2. Sprinkler Type
3. Temperature Rating
4. Sprinkler Finish
5. Escutcheon Finish
6. Cover Plate Finish
Model F1 Res 76 Recessed Pendent/F1,
Model F1 Res 76 Recessed Pendent/F2,
Model F1 Res 76 Recessed Pendent/FP
Sprinklers shall be [cULus Listed] low flow residential
recessed pendent sprinklers engineered to provide a
minimum design density of 0.05 gpm/ft2 over the listed
coverage area. Listed flows as specified by the manu-
facturer’s technical data sheets are to be used. Residen-
tial sprinklers shall be installed in conformance with the
manufacturer’s installation guidelines and the applicable
installation standard. Sprinkler frame and deflector shall
be of bronze frame construction having a ¾” NPT thread.
Water seal assembly shall consist of a Teflon* coated Bel-
leville spring washer with machined or cold head cup with
3 mm glass bulb containing no plastic parts, and hav-
ing a temperature rating of [155°F (68°C)] [175°F (79°C)].
Sprinklers shall have a nominal K-factor of 7.6. Standard
finish: [Bronze] [Chrome-plated] [White Polyester] [Spe-
cial finish– specify]. Recessed escutcheon assembly
shall be a steel, two-piece escutcheon [with ½” adjust-
ment (Model F2)] [with ¾” adjustment (Model F1)] [of
push-on and thread off design with ½” adjustment (Mod-
el FP)]. Standard finish shall be [brass][bright chrome]
[white painted]. Residential recessed pendent sprinklers
shall be Reliable [Model F1 Res 76 Recessed Pendent/
F1] [Model F1 Res 76 Recessed Pendent/F2] [Model F1
Res 76 Recessed Pendent/FP] SIN R7618 (Bulletin 135).
Model F1 Res 76 CCP Pendent (Concealed)
Sprinklers shall be [cULus Listed] low flow residential
concealed sprinklers engineered to provide a minimum
design density of 0.05 gpm/ft2 over the listed coverage
area. Listed flows as specified by the manufacturer’s
technical data sheets are to be used. Residential sprin-
klers shall be installed in conformance with the manufac-
turer’s installation guidelines and the applicable installa-
tion standard. Sprinkler frame and deflector shall be of
bronze frame construction having a ¾” NPT thread. Wa-
ter seal assembly shall consist of a Teflon* coated Bel-
leville spring washer with machined or cold head cup with
3 mm glass bulb containing no plastic parts, and having
*DuPont Registered Trademark