Loading...
HomeMy WebLinkAboutF14-0040 Equipment.pdfVILLAGE INN PLAZA UNIT 402 100 EAST MEADOW DR. VAIL, CO 81658 EQUIPMENT SUBMITTAL 8/12/2014 CORPORATION 57 HEREFORD LANE EDWARDS, CO 81632 PH: (970) 914-5014 Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Flat-Plate Concealed Pendent Wet Pipe and Dry Pipe Systems Page 1 of 6 APRIL 2013 TFP443 Worldwide Contacts www.tyco-fire.com General Description The TYCO RAPID RESPONSE Series LFII Residential Flat-Plate Concealed Pendent Sprinklers (TY2524) are decora-tive, fast response, fusible solder sprin-klers designed for use in residential oc-cupancies such as homes, apartments, dormitories, and hotels. The Cover Plate/Retainer Assembly con-ceals the sprinkler operating compo-nents above the ceiling. The flat profile of the Cover Plate provides the optimum aesthetically appealing sprinkler design. Additionally, the concealed design of the Series LFII Residential Flat-Plate Con-cealed Pendent Sprinklers provides 1/2 inch (12,7 mm) vertical adjustment. This adjustment provides a measure of flex-ibility when cutting fixed sprinkler drops. The Series LFII Residential Flat-Plate Concealed Pendent Sprinklers are in-tended for use in the following systems: • wet and dry pipe residential sprin-kler systems for one- and two-fam-ily dwellings and mobile homes per NFPA 13D • wet and dry pipe residential sprin-kler systems for residential occu-pancies up to and including four sto-ries in height per NFPA 13R • wet and dry pipe sprinkler systems for the residential portions of any occupancy per NFPA 13 The Series LFII Residential Sprinklers have been designed with heat sensitiv-ity and water distribution characteristics proven to help in the control of residen- tial fires and to improve the chance for occupants to escape or be evacuated. The Series LFII Residential Flat-Plate Concealed Pendent Sprinklers are shipped with a Disposable Protective Cap. The Protective Cap protects the sprinkler during ceiling installation or finish. After ceiling installation is com-plete, the Protective Cap is removed and the Cover Plate/Retainer Assem-bly is installed. Removing the Protec-tive Cap is required for proper sprinkler performance. Dry Pipe System ApplicationThe Series LFII Residential Flat-Plate Concealed Pendent Sprinkler offers a laboratory approved option for design-ing dry pipe residential sprinkler sys-tems, whereas, most residential sprin-klers are laboratory approved for wet systems only. Through extensive testing, it has been determined that the number of design sprinklers (hydraulic design area) for the Series LFII Residential Flat-Plate Con-cealed Sprinklers (TY2524) need not be increased over the number of design sprinklers (hydraulic design area) speci-fied for wet pipe sprinkler systems, as is customary for density/area sprinkler systems designed per NFPA 13, 13D, or 13R. Consequently, the Series LFII Residen-tial Flat-Plate Concealed Sprinklers (TY2524) offer the features of non-wa-ter filled pipe in addition to not having to increase the number of design sprinklers (hydraulic design area) for systems de-signed to NFPA 13, 13D, or 13R. Non-water filled pipe will permit options for areas sensitive to freezing. NOTICE The Series LFII Residential Flat-Plate Concealed Pendent Sprinklers (TY2524) described herein must be installed and maintained in compliance with this doc-ument and the applicable standards of the National Fire Protection Association, in addition to the standards of any au-thorities having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for maintain-ing their fire protection system and de-vices in proper operating condition. The installing contractor or sprinkler manu-facturer should be contacted with any questions. Sprinkler Identification Number (SIN) TY2524 IMPORTANTAlways refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal-lation of sprinkler systems and com-ponents. Improper handling and in-stallation can permanently damage a sprinkler system or its components and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. TFP443Page 2 of 6 3-3/16" DIA.(81,0 mm) 1/2"NPT 2-1/2" DIA. (63,5 mm) MOUNTING SURFACE3/16"(4,8 mm) 1/8" GAP(3,2 mm) FACE OFSPRINKLERFITTING 7/8" (22,2 mm) 1-1/8" (28,6 mm) TIP DEFLECTOR INOPERATED POSITION 1/2" (12,7 mm)THREADEDADJUSTMENT SPRINKLER- SUPPORT CUP ASSEMBLY OPERATED SPRINKLER 1-7/8"±1/4"(47,6 mm±6,4 mm) SPRINKLER- SUPPORT CUP ASSEMBLY COVER- RETAINER ASSEMBLY COVER PLATE RETAINER DISPOSABLEPROTECTIVE CAP SPRINKLER/SUPPORT CUP ASSEMBLY COVER PLATE/RETAINER ASSEMBLY COVER PLATE EJECTION SPRING RETAINER WITH THREAD DIMPLES SOLDER TAB SEALINGASSEMBLY COMPRESSION SCREW DEFLECTOR(OPERATEDPOSITION) SPRINKLERWRENCHINGAREA SOLDER LINK ELEMENT LEVER DEFLECTOR CAP BODY(1/2" NPT) SADDLE SUPPORTCUP WITHROLL FORMEDTHREADS GUIDEPIN GUIDE PIN HOUSING THREAD INTO SUPPORT CUP UNTIL MOUNTING SURFACE IS FLUSH WITH CEILING WRENCHRECESS PUSH WRENCH IN TO ENSURE ENGAGEMENT WITH SPRINKLER WRENCHING AREA FIGURE 3 RAPID RESPONSE SERIES LFII RESIDENTIAL FLAT-PLATE (TY2524) INSTALLATION DIMENSIONS/PROTECTIVE CAP/ACTIVATED DEFLECTOR FIGURE 1 RAPID RESPONSE SERIES LFII RESIDENTIAL FLAT-PLATE CONCEALED PENDENT SPRINKLER (TY2524) FIGURE 2 W-TYPE 18 SPRINKLER WRENCH TFP443 Page 3 of 6 Technical Data ApprovalsUL and C-UL Listed The TYCO RAPID RESPONSE Series LFII Residential Flat-Plate Concealed Pendent Sprinklers are only listed with the Series LFII Concealed Cover Plates having a factory-applied finish. For details on approvals, refer to the De-sign Criteria section. Maximum Working Pressure175 psi (12,1 bar) Discharge CoefficientK=4.9 GPM/psi1/2 (70,6 LPM/bar1/2) Temperature RatingSprinkler: 160°F (71°C) Cover Plate: 139°F (59°C) Vertical Adjustment1/2 inch (12,7 mm) FinishesRefer to the Ordering Procedure section. Physical CharacteristicsCover Plate/Retainer Assembly:Cover Plate . . . . . . . . . . . . . CopperEjection Spring ....Stainless SteelRetainer ................Brass Sprinkler/Support Cup Assembly:Body ...................Brass Cap ...................Bronze Saddle . . . . . . . . . . . . . . . . . . Brass Sealing Assembly . . . . . . .Beryllium Nickel w/ TEFLON Soldered Link Halves . . . . . . NickelLever ..................BronzeCompression Screw . . . . . . . BrassDeflector . . . . . . . . . . . . . . . BronzeGuide Pin Housing........BronzeGuide Pins .............BronzeSupport Cup . . . . . . . . . . . . . . Steel Operation When exposed to heat from a fire, the Cover Plate, which is normally soldered to the Retainer at three points, falls away to expose the Sprinkler/Support Cup As-sembly. At this point, the Deflector, sup-ported by the Guide Pins, drops down to its operated position. The Solder Link Element of the Sprinkler/Support Cup Assembly is comprised of two link halves that are soldered togeth-er with a thin layer of solder. When the rated temperature is reached, the sol-der melts and the two link halves sepa-rate, allowing the sprinkler to activate and flow water. Design Criteria The TYCO RAPID RESPONSE Series LFII Residential Flat-Plate Concealed Pendent Sprinklers (TY2524) are UL and C-UL Listed for installation in ac-cordance with this section: Residential Sprinkler Design GuideWhen conditions exist that are outside the scope of the provided criteria, re-fer to the Residential Sprinkler Design Guide TFP490 for the manufacturer's recommendations that may be accept-able to the authority having jurisdiction. System TypePer the UL Listing, wet pipe and dry pipe systems may be utilized. Per the C-UL Listing, only wet pipe systems may be utilized. Refer to Technical Data Sheet TFP485 about the use of Residential Sprinklers in residential dry pipe systems. Ceiling TypesSmooth flat horizontal, or beamed, or sloped, in accordance with the 2013 Edition of NFPA 13D, 13R or 13 as applicable. Hydraulic Design (NFPA 13D and 13R)For systems designed to NFPA 13D or NFPA 13R, the minimum required sprin-kler flow rate are given in Tables A and B as a function of temperature rating and the maximum allowable coverage areas. The sprinkler flow rate is the mini-mum required discharge from each of the total number of “design sprinklers” as specified in NFPA 13D or NFPA 13R. The number of “design sprinklers” spec-ified in NFPA 13D and 13R for wet pipe systems is to be applied when designing dry pipe systems. Hydraulic Design (NFPA 13)For systems designed to NFPA 13, the number of design sprinklers is to be the four most hydraulically demanding sprinklers. The minimum required dis-charge from each of the four sprinklers is to be the greater of the following: • The flow rates given in Tables A and B as a function of temperature rating and the maximum allowable cover-age area • A minimum discharge of 0.1 gpm/ft2. over the “design area” comprised of the four most hydraulically demand-ing sprinklers for the actual coverage areas being protected by the four sprinklers The number of “design sprinklers” specified in NFPA 13 for wet pipe sys-tems is to be applied when designing dry pipe systems. Dry Pipe System Water DeliveryWhen using the Series LFII Residential Flat-Plate Concealed Pendent Sprinklers (TY2524) in dry pipe sprinkler systems, the time for water delivery must not ex-ceed 15 seconds for the most remote operating sprinkler. Obstruction to Water Distribution.Sprinklers are to be located in accor-dance with the obstruction rules of NFPA 13D, 13R, and 13 as applicable for residential sprinklers as well as with the obstruction criteria described within the Technical Data Sheet TFP490. Operational SensitivityInstall sprinklers relative to the ceiling mounting surface as shown in Figure 3. The Series LFII Residential Flat-Plate Concealed Pendent Sprinklers must not be used in applications where the air pressure above the ceiling is greater than that below. Down drafts through the Support Cup can delay sprinkler op-eration in a fire situation. Sprinkler SpacingThe minimum spacing between sprin-klers is 8 feet (2,4 m). The maximum spacing between sprinklers cannot ex-ceed the length of the coverage area (Table A) being hydraulically calculated (e.g., a maximum of 12 feet for a 12 ft. x 12 ft. coverage area or 20 feet for a 20 ft. x 20 ft. coverage area.) TFP443Page 4 of 6 Maximum Coverage Area (a) Ft. x Ft. (m x m) Maximum Spacing Ft. (m) WET PIPE SYSTEM Minimum Flow and Residual Pressure(b, c) Ordinary Temp Rating 160°F (71°C)Deflector to Ceiling Installation Type Minimum Spacing Ft. (m) Flow GPM (L/min) Pressure PSI (bar) 12 x 12(3,7 x 3,7)12(3,7)13 (49,2)7.0 (0,48)Smooth Ceilings 7/8 to 1-1/8 inches. Beamed Ceilings per NFPA 13D 13R, or 13 Installed in beam 7/8 to 1-1/8 inches below bottom of beam Concealed 8 (2,4) 14 x 14(4,3 x 4,3)14(4,3)13 49,2)7.0 (0,48) 16 x 16(4,9 x 4,9)16(4,9)13(49,2)7.0 (0,48) 18 x 18(5,5 x 5,5)18(5,5)17 (64,3)12.0 (0,83) 20 x 20(6,1 x 6,1)20(6,1)20 (75,7)16.7 (1,15) (a) For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which Hydraulic Design section under the Design Criteria are stated. (b) The Minimum Flow requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pres- sures are calculated using the nominal K-factor. Refer to “Hydraulic Design” in the Design Criteria section for details. (c) For NFPA 13 residential applications, the greater of 0.1 gpm/ft.2 over the design area or the flow in accordance with the criteria in this table must be used. TABLE A WET PIPE SYSTEM SERIES LFII RESIDENTIAL FLAT-PLATE CONCEALED PENDENT SPRINKLER (TY2524) NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA Maximum Coverage Area (a) Ft. x Ft. (m x m) Maximum Spacing Ft. (m) DRY PIPE SYSTEM Minimum Flow and Residual Pressure(b) Ordinary Temp Rating 160°F (71°C)Deflector to Ceiling Installation Type Minimum Spacing Ft. (m) Flow GPM (L/min) Pressure PSI (bar) 12 x 12(3,7 x 3,7)12(3,7)15 (56,8)9.4 (0,65)Smooth Ceilings 7/8 to 1-1/8 inches. Beamed Ceilings per NFPA 13D 13R, or 13 Installed in beam 7/8 to 1-1/8 inches below bottom of beam Concealed 8 (2,4) 14 x 14(4,3 x 4,3)14(4,3)15 (56,8)9.4 (0,65) 16 x 16(4,9 x 4,9)16(4,9)16 (60,6)10,7 (0,74) 18 x 18(5,5 x 5,5)18(5,5)17 (64,3)12.0 (0,83) 20 x 20(6,1 x 6,1)20(6,1)21 (79,5)18,4 (1,27) (a) For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which Hydraulic Design section under the Design Criteria are stated. (b) The Minimum Flow requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K-factor. Refer to “Hydraulic Design” in the Design Criteria section for details. (c) For NFPA 13 residential applications, the greater of 0.1 gpm/ft.2 over the design area or the flow in accordance with the criteria in this table must be used. TABLE B DRY PIPE SYSTEM SERIES LFII RESIDENTIAL FLAT-PLATE CONCEALED PENDENT SPRINKLER (TY2524) NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA Worldwide Contacts www.tyco-fire.com General Description The TYCO RAPID RESPONSE Series LFII Residential Horizontal Sidewall Sprinklers (TY2334) are decorative, fast response, frangible bulb sprin-klers designed for use in residential occupancies such as homes, apart-ments, dormitories, and hotels. When aesthetics and optimized flow charac-teristics are the major consideration, the Series LFII Residential Sprinklers (TY2334) should be the first choice. The Series LFII Residential Sprinklers are intended for use in the following scenarios: • wet pipe residential sprinkler systems for one-and two-family dwellings and mobile homes per NFPA 13D • wet pipe residential sprinkler systems for residential occupancies up to and including four stories in height per NFPA 13R • wet pipe sprinkler systems for the residential portions of any occupancy per NFPA 13 The recessed version of the Series LFII Residential Sprinklers is intended for use in areas with finished walls. It employs a two-piece Style 20 Recessed Escutcheon. The Recessed Escutcheon provides 1/4 inch (6,4 mm) of recessed adjustment or up to 1/2 inch (12,7 mm) of total adjustment from the flush mounting surface position. The adjustment provided by the Recessed Escutcheon reduces the accuracy to which the pipe nipples to the sprinklers must be cut. The Series LFII Residential Sprinklers has been designed with heat sensitivity and water distribution characteristics proven to help in the control of residen-tial fires and to improve the chance for occupants to escape or be evacuated. NOTICE The Series LFII Residential Horizontal Sidewall Sprinklers (TY2334) described herein must be installed and maintained in compliance with this document and with the applicable standards of the National Fire Protection Association, in addition to the standards of any author-ities having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for main-taining their fire protection system and devices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. Sprinkler Identification Number (SIN) TY2334 Technical Data ApprovalsUL and C-UL Listed NSF Certified to NSF/ANSI 61 For details on approvals, refer to the Design Criteria section. Maximum Working PressureMaximum 175 psi (12,1 bar) Discharge CoefficientK= 4.4 GPM/psi1/2 (63,4 LPM/bar1/2) Temperature Rating155°F (68°C) or 175°F (79°C) FinishesNatural BrassSignal White Chrome Plated Physical CharacteristicsFrame....................BrassButton...................BronzeSealing Assembly. . . . . . . . .Beryllium Nickel w/ TEFLONBulb .................3 mm GlassCompression Screw. . . . . . . . BronzeDeflector.................Copper RAPID RESPONSE Series LFII Residential Sprinklers 4.4 K-factor Horizontal Sidewall Wet Pipe Systems Page 1 of 6 APRIL 2013 TFP412 IMPORTANT Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and installation of sprinkler systems and components. Improper handling and installation can permanently damage a sprinkler system or its components and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Worldwide Contacts www.tyco-fire.com Sealing-3 54 * 6 Compression of Deector. is indicated on top Temperature rating Bulb Deector- -- * 1 Components: 2 Button Frame- -WRENCH STYLE 20RECESSED ESCUTCHEON FLATS 2-7/8" DIA. RECESSED (73,0 mm)5 NOMINAL PLATE SEATINGSURFACE ESCUTCHEON MAKE-IN CENTERLINE OF WATERWAY 7/16" (11,1 mm) (54,0 mm) (38,1 mm) DEFLECTORBOSS (11,1 mm)7/16" END-OF- 2-1/8" 1-1/2" DEFLECTOR TOP-OF- 4 26* 1 3 Assembly Screw TOP1/2" NPT FLATSWRENCH FIGURE 1 RAPID RESPONSE SERIES LFII RESIDENTIAL HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS (TY2334) 1-1/4" (31,8 mm) 1" (25,4 mm) MOUNTING PLATE TY2334 MOUNTINGSURFACE CLOSURE (73,0 mm) 1/2" (12,7 mm) (57,2 mm)2-1/4" DIA. 1/4" (6,4 mm) 1/8"(3,2 mm) (11,1±3,2 mm) SPRINKLER FITTING FACE OF 7/16±1/8" 2-7/8" DIA. BOSS END-OF-DEFLECTOR TOP-OF-DEFLECTOR 7/16"(11,1 mm) FIGURE 2 STYLE 20 RECESSED ESCUTCHEON FOR USE WITH THE RAPID RESPONSE SERIES LFII RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER (TY2334) WRENCH RECESS(END "A" USED FOR TY2334) FIGURE 3 W-TYPE 6 SPRINKLER WRENCH RECESS WRENCH WITH SPRINKLER ENGAGEMENT IN TO ENSURE WRENCHING AREA PUSH WRENCH FIGURE 4 W-TYPE 7 RECESSED SPRINKLER WRENCH TFP412Page 2 of 6 Operation The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb allowing the sprinkler to activate and flow water. Design Criteria The TYCO RAPID RESPONSE Series LFII (TY2334) Residential Horizontal Sidewall Sprinklers are UL and C-UL Listed for installation in accordance with this section. Residential Sprinkler Design GuideWhen conditions exist that are outside the scope of the provided criteria, refer to the Residential Sprinkler Design Guide TFP490 for the manufacturer’s recommendations that may be accept-able to the local authority having jurisdiction. System TypeOnly wet pipe systems may be utilized. Ceiling TypeSmooth flat horizontal, or beamed, or sloped, in accordance with the 2013 Edition of NFPA 13D, 13R, or 13 as applicable. Hydraulic Design (NFPA 13D and 13R)For systems designed to NFPA 13D or NFPA 13R, the minimum required sprinkler flow rate are given in Table A as a function of temperature rating and the maximum allowable coverage areas. The sprinkler flow rate is the minimum required discharge from each of the total number of “design sprinklers” as specified in NFPA 13D or NFPA 13R. Hydraulic Design(NFPA 13)For systems designed to NFPA 13, the number of design sprinklers is to be the four most hydraulically demanding sprinklers. The minimum required discharge from each of the four sprinklers is to be the greater of the following: • The flow rates given in Table A as a function of temperature rating and the maximum allowable coverage area. • A minimum discharge of 0.1 gpm/ft2 over the “design area” comprised of the four most hydrau-lically demanding sprinklers for the actual coverage areas being protected by the four sprinklers. Obstruction to Water DistributionSprinklers are to be located in accor-dance with the obstruction rules of NFPA 13D, 13R, and 13 as applicable for residential sprinklers as well as with the obstruction criteria described within the Technical Data Sheet TFP490. Operational SensitivityThe sprinklers are to be installed with an end of defector-boss to wall distance of 1-1/8 to 6 inches. In addition the top-of-deflector-to-ceiling distance is to be within the range (Ref. Table A) being hydraulically calculated. Sprinkler SpacingThe minimum spacing between sprin-klers is 8 feet (2,4 m). The maximum spacing between sprinklers cannot exceed the width of the coverage area (Ref. Table A) being hydraulically calcu-lated (e.g., maximum 12 feet for a 12 ft. x 12 ft. coverage area, or 16 feet for a 16 ft. x 20 ft. coverage area). Installation The TYCO RAPID RESPONSE Series LFII (TY2334) Residential Horizontal Sidewall Sprinklers must be installed in accordance with this section. General InstructionsDo not install any bulb-type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprinkler held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 inch (1,6 mm). A leak-tight 1/2 inch NPT sprinkler joint should be obtained by applying a minimum to maximum torque of 7 to 14 ft.-lbs. (9,5 to 19,0 Nm). Higher levels of torque can distort the sprinkler Inlet with consequent leakage or impairment of the sprinkler. Do not attempt to compensate for insufficient adjustment in the sprinkler by under- or over-tightening the sprinkler. Re-adjust the position of the sprinkler fitting to suit. Series LFII Residential Horizontal Sidewall SprinklersThe Series LFII Horizontal Sidewall Sprinklers must be installed in accor-dance with the following instructions. Step 1. Horizontal sidewall sprin-klers are to be installed in the hori-zontal position with their centerline of waterway perpendicular to the back wall and parallel to the ceiling. The word “TOP” on the Deflector is to face towards the ceiling with the front edge of the Deflector parallel to the ceiling. Step 2. With pipe thread sealant applied to the pipe threads, hand tighten the sprinkler into the sprinkler fitting. Step 3. Tighten the sprinkler into the sprinkler fitting using only the W-Type 6 Sprinkler Wrench (Ref. Figure 3). With reference to Figure 1, the W-Type 6 Sprinkler Wrench is to be applied to the wrench flats. Series LFII Residential Recessed Horizontal Sidewall SprinklersThe Series LFII Recessed Horizontal Sidewall Sprinklers must be installed in accordance with the following instructions. Step A. Recessed horizontal side-wall sprinklers are to be installed in the horizontal position with their center-line of waterway perpendicular to the back wall and parallel to the ceiling. The word “TOP” on the Deflector is to face towards the ceiling. Step B. After installing the Style 20 Mounting Plate over the sprinkler threads and with pipe thread sealant applied to the pipe threads, hand tighten the sprinkler into the sprinkler fitting. Step C. Tighten the sprinkler into the sprinkler fitting using only the W-Type 7 Recessed Sprinkler Wrench (Ref. Figure 4). With reference to Figure 1, the W-Type 7 Recessed Sprinkler Wrench is to be applied to the sprinkler wrench flats. Step D. After the wall has been installed or the finish coat has been applied, slide on the Style 20 Closure over the Series LFII Sprinkler and push the Closure over the Mounting Plate until its flange comes in contact with the wall. TFP412 Page 3 of 6 TABLE A WET PIPE SYSTEMSSERIES LFII (TY2334) RESIDENTIAL HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS NFPA 13D, 13R AND 13 WET PIPE HYDRAULIC DESIGN CRITERIA Max. Coverage Area (a) Width x Length (d) Ft. x Ft. (m x m) Max. Spacing Ft. (m) WET PIPE SYSTEM Minimum Flow and Residual Pressure(b, c) Ordinary Temp. Rating 155°F (68°C) Intermediate Temp. Rating 175°F (79°C)Deflector to Ceiling Installation Type Minimum Spacing Ft. (m) Flow GPM (L/min) Pressure PSI (bar) Flow GPM (L/min) Pressure PSI (bar) 12 x 12 (3,7 x 3,7)12 (3,7)13 (49,2)8.7 (0,60)13 (49,2)8.7 (0,60) 4 to 6 inches Recessed using Style 20 Escutcheon or non-recessed per NFPA 13D, 13R, or 13 8(2,4) 14 x 14 (4,3 x 4,3)14 (4,3)14 (53,0)10.1 (0,70)14 (53,0)10.1 (0,70) 16 x 16 (4,9 x 4,9)16 (4,9)16 (60,6)13.2 (0,91)16 (60,6)13.2 (0,91) 16 x 18 (4,9 x 5,5)16 (4,9)19 (71,9)18.6 (1,28)19 (71,9)18.6 (1,28) 16 x 20 (4,9 x 6,1)16 (4,9)23 (87,1)27.3 (1,88)23 (87,1)27.3 (1,88) 18 x 18 (5,5 x 5,5)18 (5,5)23 (87,1)27.3 (1,88)23 (87,1)27.3 (1,88) 18 x 20 (5,5 x 6,1)18 (5,5)26 (98,4)34.9 (2,41)26 (98,4)34.9 (2,41) 12 x 12 (3,7 x 3,7)12 (3,7)13 (49,2)8.7 (0,60)13 (49,2)8.7 (0,60) 6 to 12 inches 14 x 14 (4,3 x 4,3)14 (4,3)14 (53,0)10.1 (0,70)14 (53,0)10.1 (0,70) 16 x 16 (4,9 x 4,9)16 (4,9)17 (64,3)14.9 (1,03)17 (64,3)14.9 (1,03) 16 x 18 (4,9 x 5,5)16 (4,9)20 (75,7)20.7 (1,43)20 (75,7)20.7 (1,43) 16 x 20 (4,9 x 6,1)16 (4,9)23 (87,1)27.3 (1,88)23 (87,1)27.3 (1,88) 18 x 18 (5,5 x 5,5)18 (5,5)23 (87,1)27.3 (1,88)23 (87,1)27.3 (1,88) 18 x 20 (5,5 x 6,1)18 (5,5)26 (98,4)34.9 (2,41)26 (98,4)34.9 (2,41) (a) For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b) Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K-factor. Refer to Hydraulic Design under the Design Criteria section. (c) For NFPA 13 residential applications, the greater of 0.1 gpm/ft2 over the design area or the flow in accordance with the criteria in this table must be used. (d) The Width x Length dimension refers to the Width (backwall where the sprinkler is located) times the Length (horizontal throw of sprinkler). TFP412Page 4 of 6 A H E A D O F T H E F L O W ® www.nibco.com NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455 www.nibco.com 4 All of the advantages found in copper as a metal have been capitalized to the utmost in the manufacture of NIBCO Fittings. Because of the accuracy of construc tion and design, copper plumbing is more efficient and less expensive. NIBCO manufactures nine general types of fittings: Wrot Pressure; Cast Pressure; Wrot Drainage; Cast Drainage; Flanges; Flared Tube; Threaded Bronze; Insert Fittings for PEX; Barbed Insert Fittings for Polybutylene. Each has its particular place and use and each offers its own advantages when used for the proper service requirement. ALLOY AND FINISH — NIBCO Fittings are made from highest quality raw materials available — Cast Fittings are made from Copper Alloy C84400 which consists of 81% Copper, 7% Lead, 3% Tin, and 9% Zinc per ASTM Specification B584. Wrot Copper Fittings are made from commercially pure copper mill products per ASTM Specifications B75 Alloy C12200. NIBCO fittings are produced to meet requirements of applicable standards wherever practicable. NIBCO brand wrot and cast fittings are manufactured in the U.S.A. and Mexico. The manufacturing plants at Stuarts Draft, VA, Nacogdoches, TX and Reynosa, Mexico are registered to ISO 9002 quality standards. Following is suggested phrasing to be incorporated in your specifications or bills of material for Copper Tube Fittings. WROT SOLDER JOINT FITTINGS — “Wrot Solder Joint Fittings shall be produced to one of the following specifications: 1. Material and workmanship shall be in accordance with ASME/ANSI B16.22; Wrought Copper and Copper Alloy Solder Joint Pressure Fittings.” Specifications 2. The dimensional, material and workmanship shall meet the requirements of MSS SP-104; Wrought Copper Solder Joint Pressure Fittings.” 3. The dimensional, material and workmanship of 5"–12" copper fittings shall meet the requirements of MSS SP-109 “Welded Fabricated Copper Solder Joint Pressure Fittings.” 4. Certified to ANSI/NSF 61. CAST COPPER ALLOY SOLDER JOINT FITTINGS — “Cast Copper Alloy Solder Joint Fittings shall be in accor dance with ANSI Std. B16.18.” WROT DRAINAGE FITTINGS — “Wrot Drainage Fittings shall be in accordance with ASME/ANSI Std. B16.29.” CAST COPPER ALLOY SOLDER JOINT DRAINAGE FITTINGS — “Cast Copper Alloy Solder Joint Drainage Fittings shall be in accordance with ASME Std. B16.23.” CAST COPPER ALLOY FLARED TUBE FITTINGS — “Cast Copper Alloy Flared Tube Fittings shall be in accor- dance with ASME/ANSI Std. B16.26. CAST COPPER ALLOY FLANGES AND FLANGED FITTINGS— CLASS 150 — Cast Copper Alloy Flanges and Flanged Fittings shall meet the requirements of MSS SP-106 and/or the workmanship and dimensions of Federal Specifications WW-F-406 or ASME Std. B16.24. CLASS 125 — Material, workmanship and dimensions of flanges shall be in accordance with MSS SP-106. CAST BRONZE THREADED FITTINGS — “Cast Bronze Threaded Fittings shall be in accordance with ANSI/ASME B16.15.” POLYBUTYLENE COPPER INSERT TYPE VALVES AND FITTINGS — “Wrot Copper Insert Fittings shall be manufactured per the following specifications: MSS SP-103 or ASTM F1380.” NIBCO Copper Tube Fittings are all produced to above Standards. To simplify, write your specifications to read: “Copper Tube Fittings to be in accordance with specifications as outlined in NIBCO Catalog c-cf-0602.” WROT COPPER MEDICAL MEDICAL GAS SYSTEM COMPONENTS — Wrot copper fittings that are to be installed in medical gas applications shall be prepared in accordance with NFPA 99, Health Care Facilities Gas and Vacuum Systems and the Compressed Gas Association, Pamphlet G4.1. Packaging shall be adequately protective and include labeling that identifies the preparer and states that the product has been cleaned and bagged for oxygen or med gas service. For technical information and dimensions refer to the engineering section contained in this catalog. Revision 3/29/04 A H E A D O F T H E F L O W ® www.nibco.com NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455 www.nibco.com 6 703-2 Fitting Adapter Ftg x F – Cast APPROX. DIM. B NOM. SIZE NET WT./LBS. INCHES 1/2 x 1/4 0.11 17/32 3/4 x 1/2 0.12 19/16 1 x 3/4 0.38 131/32 1 x 1/2 0.15 17/16 2 1/2 1.65 215/16 3 2.47 31/4 703-5 Special Drop Adapter C x F – Cast APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES 1/2 0.16 3/4 3/4 0.24 31/32 703-5B Drop Adapter C x F – Cast APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES 1/2 0.15 3/4 ADAPTERS 603 Adapter C x F – Wrot APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES 1/8 0.03 13/32 1/8 x 1/4 0.03 1/2 1/4 0.03 5/8 1/4 x 3/8 0.05 21/32 3/8 0.04 11/16 3/8 x 1/2 0.09 29/32 3/8 x 1/4 0.03 9/16 1/2 0.09 27/32 1/2 x 3/4 0.14 1 1/2 x 3/8 0.04 17/32 1/2 x 1/4 0.05 1/2 5/8 x 3/4 0.12 29/32 5/8 x 1/2 0.11 3/4 3/4 0.15 29/32 3/4 x 1 0.21 11/8 3/4 x 1/2 0.10 5/8 1 0.24 31/32 1 x 1 1/4 0.28 17/32 1 x 3/4 0.19 25/32 1 x 1/2 0.24 5/8 1 1/4 0.33 13/32 1 1/4 x 1 1/2 0.40 11/4 1 1/4 x 1 0.27 31/32 1 1/2 0.44 11/8 1 1/2 x 2 0.50 11/32 2 0.63 13/32 2 x 1 1/2 0.74 13/16 2 1/2 1.13 – 3 1.94 – 703 Adapter C x F – Cast APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES 1/4 x 1/2 0.13 27/32 1/2 x 1 0.30 1 3/4 x 1 1/4 0.55 11/8 3/4 x 3/8 0.17 3/4 1 x 1 1/2 0.68 13/32 1 1/4 x 1 0.27 31/32 1 1/4 x 3/4 0.29 3/4 1 1/2 x 2 0.78 11/32 1 1/2 x 1 0.37 25/32 1 1/2 x 1 1/4 0.47 11/4 2 x 1 1/4 0.76 27/32 2 1/2 1.62 13/8 3 2.34 11/2 4 4.05 19/16 603-2Fitting Adapter Ftg x F – Wrot APPROX. DIM. B NOM. SIZE NET WT./LBS. INCHES 1/4 0.03 13/32 3/8 0.06 13/16 1/2 0.09 17/16 1/2 x 3/8 0.05 11/4 3/4 0.13 111/16 1 0.27 21/32 1 1/4 0.31 21/8 1 1/2 0.43 25/16 2 0.61 217/32 Consult price sheet for Made to Order items and for minimum order quantities. Revision 2/6/07 A H E A D O F T H E F L O W ® www.nibco.com NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455 www.nibco.com 9 Consult price sheet for Made to Order items and for minimum order quantities. CAPS 617 Tube Cap C – Wrot APPROX. DIM. N NOM. SIZE NET WT./LBS. INCHES 1/8 0.01 1/32 1/4 0.01 3/32 3/8 0.01 3/32 1/2 0.02 3/32 5/8 0.03 1/8 3/4 0.04 1/8 1 0.07 5/32 1 1/4 0.10 3/32 1 1/2 0.16 1/8 2 0.27 5/32 2 1/2 0.50 7/32 3 0.78 7/32 4 1.66 1/4 717 Tube Cap C – Cast APPROX. DIM. N NOM. SIZE NET WT./LBS. INCHES 5 5.48 7/16 6 9.07 17/32 717-D Drain Cap – Cast APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES 1/2 0.06 21/32 COUPLINGS 600 Reducing Coupling C x C – Wrot APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES 1/8 x 3/16 O.D. 0.01 5/32 5/16 O.D. x 1/8 0.01 3/16 1/4 x 5/16 O.D. 0.01 3/16 1/4 x 1/8 0.01 3/16 3/8 x 1/4 0.02 3/16 3/8 x 5/16 O.D. 0.01 1/4 3/8 x 1/8 0.01 1/4 1/2 x 3/8 0.03 3/16 1/2 x 1/4 0.02 1/4 1/2 x 1/8 0.03 11/32 5/8 x 1/2 0.05 3/16 5/8 x 3/8 0.04 11/32 5/8 x 1/4 0.03 13/32 3/4 x 5/8 0.07 3/16 3/4 x 1/2 0.06 9/32 3/4 x 3/8 0.06 3/8 3/4 x 1/4 0.05 11/32 1 x 3/4 0.11 11/32 1 x 5/8 0.09 3/8 1 x 1/2 0.10 11/32 1 x 3/8 0.10 13/32 1 1/4 x 1 0.16 5/16 1 1/4 x 3/4 0.18 17/32 1 1/4 x 5/8 0.18 5/8 1 1/4 x 1/2 0.14 7/16 1 1/2 x 1 1/4 0.23 5/16 1 1/2 x 1 0.22 9/16 1 1/2 x 3/4 0.20 3/8 1 1/2 x 1/2 0.19 1/2 2 x 1 1/2 0.41 9/16 2 x 1 1/4 0.35 11/16 2 x 1 0.37 7/16 2 x 3/4 0.34 17/32 2 x 1/2 0.35 23/32 2 1/2 x 2 0.59 9/16 2 1/2 x 1 1/2 0.65 11/16 2 1/2 x 1 1/4 0.65 13/16 2 1/2 x 1 0.73 29/32 Continues… APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES 3 x 2 1/2 0.98 1/2 3 x 2 1.06 15/16 3 x 1 1/2 0.92 11/32 3 1/2 x 3 1.52 1/2 4 x 3 1/2 2.12 19/32 4 x 3 1.92 27/32 4 x 2 1/2 1.77 1 4 x 2 1.92 11/4 5 x 4 3.50 331/32 5 x 3 3.18 115/32 5 x 2 1/2 3.50 13/16 5 x 2 3.09 21/32 6 x 5 5.70 11/8 6 x 4 5.24 11/2 6 x 3 5.04 2 6 x 2 1/2 5.13 21/4 6 x 2 4.89 21/2 8 x 6 13.06 119/32 8 x 4 12.22 219/32 8 x 3 11.79 33/32 8 x 2 1/2 12.64 33/8 600-RS Coupling with Rolled Tube Stop C x C – Wrot APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES 1/8 O.D. 0.01 1/16 3/16 O.D. 0.01 3/32 1/8 0.01 1/16 5/16 O.D. 0.01 3/32 1/4 0.01 1/16 3/8 0.01 3/32 1/2 0.03 3/32 5/8 0.04 3/32 3/4 0.06 3/32 7/8 0.09 3/32 1 0.11 3/32 1 1/4 0.16 1/8 1 1/2 0.23 1/8 2 0.41 1/8 2 1/2 0.65 1/8 3 0.93 1/8 3 1/2 1.45 5/32 4 1.93 7/32 Revision 2/6/07 A H E A D O F T H E F L O W ® www.nibco.com NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455 www.nibco.com 12 ELBOWS continued Consult price sheet for Made to Order items and for minimum order quantities. 706-2 45° Fitting Elbow Ftg x C – Cast APPROX. DIM. B DIM. C NOM. SIZE NET WT./LBS. INCHES INCHES 4 4.31 311/32 15/16 607 90° Elbow – Close Rough C x C – Wrot APPROX. DIM. C DIM. D NOM. SIZE NET WT./LBS. INCHES INCHES 1/8 0.01 13/32 13/32 1/4 0.02 9/32 9/32 3/8 0.03 1/2 1/2 1/2 0.04 3/8 3/8 1/2 x 3/8 0.04 9/16 21/32 3/4 0.10 17/32 17/32 3/4 x 5/8 0.12 29/32 7/8 3/4 x 1/2 0.10 17/32 3/4 1 0.21 23/32 23/32 1 x 3/4 0.16 23/32 5/8 1 1/4 0.31 11/32 11/32 1 1/4 x 1 0.31 15/8 115/32 1 1/2 0.46 17/32 17/32 1 1/2 x 1 1/4 0.35 15/32 13/32 2 0.84 11/2 11/2 2 x 1 1/2 0.58 17/16 11/4 2 1/2 1.41 127/32 127/32 3 2.07 23/32 23/32 3 1/2 2.94 23/8 23/8 4 4.23 225/32 225/32 5 7.74 27/8 27/8 6 10.95 37/16 37/16 8 29.50 423/32 423/32 707 90° Elbow – Close Rough C x C – Cast APPROX. DIM. C DIM. D NOM. SIZE NET WT./LBS. INCHES INCHES 1 1/4 x 1 0.42 15/8 115/32 1 1/4 x 3/4 0.34 9/16 13/16 1 1/4 x 1/2 0.28 15/32 27/32 1 1/2 x 1 0.54 11/16 1 1 1/2 x 3/4 0.42 19/32 31/32 1 1/2 x 1/2 0.40 5/8 29/32 2 x 1 1/4 0.86 7/8 11/4 2 x 1 0.78 3/4 11/4 2 x 3/4 0.69 5/8 11/4 2 1/2 x 2 2.16 13/16 19/32 3 x 2 1/2 2.26 111/16 11/2 3 x 2 2.68 13/8 19/16 4 x 3 5.18 129/32 215/32 607-I 90° Elbow – Intermediate Radius C x C – Wrot APPROX. DIM. C DIM. D NOM. SIZE NET WT./LBS. INCHES INCHES 1/2 0.06 19/32 19/32 5/8 0.09 7/8 7/8 3/4 0.14 13/16 3/16 1 0.24 11/16 11/16 607-LT 90° Elbow – Long Radius C x C – Wrot APPROX. DIM. C DIM. D NOM. SIZE NET WT./LBS. INCHES INCHES 3/16 O.D. 0.01 13/32 13/32 1/8 0.01 13/32 13/32 5/16 O.D. 0.02 9/16 9/16 1/4 0.02 17/32 17/32 1/4 x 1/8 0.01 19/32 1/2 3/8 0.04 23/32 23/32 1/2 0.08 7/8 7/8 1/2 x 3/8 0.06 13/16 13/16 1/2 x 1/4 0.03 25/32 21/32 5/8 0.10 13/32 13/32 5/8 x 1/2 0.09 11/16 11/16 3/4 0.16 11/8 11/8 3/4 x 5/8 0.13 11/4 13/32 3/4 x 1/2 0.10 11/8 11/16 7/8 0.28 119/32 119/32 1 0.28 17/16 17/16 1 x 3/4 0.20 11/4 11/8 1 x 5/8 0.15 113/32 13/32 1 1/4 0.42 17/8 17/8 1 1/4 x 1 0.33 125/32 11/2 1 1/2 0.66 21/4 21/4 2 1.23 215/16 215/16 2 1/2 1.96 311/16 311/16 3 2.93 41/32 41/32 4 5.95 51/4 51/4 Revision 2/7/07 A H E A D O F T H E F L O W ® www.nibco.com NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455 www.nibco.com 15 707-6 90° Union Elbow C x C – Cast APPROX. DIM. A DIM. C NOM. SIZE NET WT./LBS. INCHES INCHES 3/8 0.17 31/32 5/16 1/2 0.24 1 7/16 3/4 0.39 117/32 9/16 1 0.64 121/32 23/32 1 1/4 1.07 119/32 23/32 708 90° Flanged Sink Elbow C x F – Cast NOM. APPROX. DIM. A DIM. C DIM. F SIZE NET WT./LBS. INCHES INCHES INCHES 1/2 0.20 7/8 9/16 13/4 764 90° Double Elbow C x C x C – Cast APPROX. DIM. C DIM. D NOM. SIZE NET WT./LBS. INCHES INCHES 1 x 3/4 x 3/4 0.33 3/4 21/32 ELBOWS continued Consult price sheet for Made to Order items and for minimum order quantities. FITTING REDUCERS APPROX. DIM. B NOM. SIZE NET WT./LBS. INCHES 4 x 3 1/2 2.09 25/8 4 x 3 2.00 31/32 4 x 2 1/2 1.56 31/32 4 x 2 1.76 313/32 5 x 4 3.30 39/16 5 x 3 2.97 41/16 5 x 2 1/2 3.30 411/32 5 x 2 2.88 411/16 6 x 5 5.56 43/16 6 x 4 5.09 49/16 6 x 3 4.67 51/16 6 x 2 1/2 4.47 511/32 6 x 2 4.51 519/32 8 x 6 12.33 515/32 8 x 5 10.35 515/16 8 x 4 11.10 67/16 8 x 3 10.63 615/16 8 x 2 1/2 11.41 73/16 8 x 2 10.86 77/16 741 Companion Flange C – Cast NOM. APPROX. DIM. B DIM. F DIM. G DIM. W SIZE NET WT./LBS. INCHES INCHES INCHES INCHES 1/2 0.55 1/8 31/2 3/16 23/8 3/4 0.71 1/8 37/8 3/16 23/4 1 1.26 1/8 41/4 1/4 31/8 1 1/4 1.42 1/8 45/8 1/4 31/2 1 1/2 1.82 1/8 5 5/16 37/8 2 2.76 1/8 6 3/8 43/4 2 1/2 4.29 1/8 7 3/8 51/2 3 5.26 1/8 71/2 7/16 6 4 7.60 1/8 9 7/16 71/2 5 9.04 1/8 10 7/16 81/2 6 12.68 1/8 11 1/2 91/2 NOTE: Dim. B = Tube Stop to Flange Face 600-2 Fitting Reducer Ftg x C – Wrot APPROX. DIM. B NOM. SIZE NET WT./LBS. INCHES 1/4 x 1/8 0.01 15/32 3/8 x 1/4 0.01 19/32 3/8 x 1/8 0.01 25/32 1/2 x 3/8 0.03 11/16 1/2 x 1/4 0.02 25/32 5/8 x 1/2 0.04 7/8 5/8 x 3/8 0.04 31/32 5/8 x 1/4 0.03 11/32 3/4 x 5/8 0.06 31/32 3/4 x 1/2 0.06 11/8 3/4 x 3/8 0.05 11/8 3/4 x 1/4 0.05 13/32 1 x 3/4 0.10 17/32 1 x 5/8 0.09 13/8 1 x 1/2 0.09 11/4 1 x 3/8 0.08 19/32 1 1/4 x 1 0.15 15/16 1 1/4 x 3/4 0.16 11/2 1 1/4 x 1/2 0.13 13/8 1 1/2 x 1 1/4 0.23 113/32 1 1/2 x 1 0.21 15/8 1 1/2 x 3/4 0.20 17/8 1 1/2 x 1/2 0.16 119/32 2 x 1 1/2 0.40 131/32 2 x 1 1/4 0.34 23/32 2 x 1 0.35 127/32 2 x 3/4 0.35 127/32 2 x 1/2 0.34 131/32 2 1/2 x 2 0.65 131/32 2 1/2 x 1 1/2 0.65 23/8 2 1/2 x 1 1/4 0.60 27/32 2 1/2 x 1 0.78 29/32 3 x 2 1/2 1.03 21/4 3 x 2 0.99 29/16 3 x 1 1/2 0.81 219/32 3 x 1 1/4 1.29 31/4 3 1/2 x 3 1.48 211/32 Continues… FLANGES – CLASS 125 Revision 2/8/07 A H E A D O F T H E F L O W ® www.nibco.com NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455 www.nibco.com 18 APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. C F G 1 x 1/2 x 1 0.29 11/16 1 21/32 1 x 1/2 x 3/4 0.27 9/16 13/16 3/4 1 x 1/2 x 1/2 0.22 15/32 25/32 23/32 1 1/4 0.43 13/16 3/16 13/16 1 1/4 x 1 1/4 x 2 1.13 130/32 130/32 13/32 1 1/4 x 1 1/4 x 1 1/2 0.60 13/16 13/16 29/32 1 1/4 x 1 1/4 x 1 0.45 25/32 25/32 29/32 1 1/4 x 1 1/4 x 3/4 0.37 21/32 21/32 3/4 1 1/4 x 1 1/4 x 1/2 0.30 1/2 1/2 25/32 1 1/4 x 1 1/4 x 3/8 0.34 23/32 23/32 29/32 1 1/4 x 1 x 1 1/4 0.43 13/16 11/32 13/16 1 1/4 x 1 x 1 0.47 25/32 7/8 29/32 1 1/4 x 1 x 3/4 0.35 21/32 25/32 7/8 1 1/4 x 1 x 1/2 0.30 1/2 5/8 29/32 1 1/4 x 3/4 x 1 1/4 0.42 13/16 11/8 13/16 1 1/4 x 3/4 x 1 0.45 25/32 11/32 29/32 1 1/4 x 3/4 x 3/4 0.37 21/32 15/16 7/8 1 1/4 x 3/4 x 1/2 0.30 1/2 3/4 29/32 1 1/4 x 1/2 x 1 1/4 0.41 13/16 17/32 13/16 1 1/2 0.61 31/32 31/32 29/32 1 1/2 x 1 1/2 x 2 1.11 125/32 125/32 13/32 1 1/2 x 1 1/2 x 1 1/4 0.62 29/32 29/32 11/16 1 1/2 x 1 1/2 x 1 0.55 11/16 11/16 7/8 1 1/2 x 1 1/2 x 3/4 0.45 11/16 11/16 11/32 1 1/2 x 1 1/2 x 1/2 0.40 1/2 1/2 11/32 1 1/2 x 1 1/4 x 1 1/2 0.62 11/32 13/16 29/32 1 1/2 x 1 1/4 x 1 1/4 0.62 31/32 13/32 31/32 1 1/2 x 1 1/4 x 1 0.51 25/32 1 11/32 1 1/2 x 1 1/4 x 3/4 0.49 11/16 13/16 11/32 1 1/2 x 1 1/4 x 1/2 0.41 1/2 25/32 11/32 1 1/2 x 1 x 1 1/2 0.59 11/32 111/32 29/32 1 1/2 x 1 x 1 1/4 0.63 29/32 11/8 11/16 1 1/2 x 1 x 1 0.54 25/32 11/16 11/32 1 1/2 x 1 x 3/4 0.44 11/16 31/32 15/16 1 1/2 x 1 x 1/2 0.39 1/2 25/32 11/32 1 1/2 x 3/4 x 1 1/2 0.62 11/32 17/16 11/16 1 1/2 x 3/4 x 1 1/4 0.58 29/32 111/32 11/16 1 1/2 x 3/4 x 1 0.54 25/32 11/4 11/32 1 1/2 x 3/4 x 3/4 0.47 11/16 13/32 29/32 1 1/2 x 3/4 x 1/2 0.39 1/2 29/32 31/32 1 1/2 x 1/2 x 1 1/2 0.62 11/32 113/32 31/32 Continues… APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. C F G 2 1.30 19/32 19/32 11/32 2 x 2 x 2 1/2 2.34 2 2 121/32 2 x 2 x 1 1/2 1.17 11/4 11/4 123/32 2 x 2 x 1 1/4 1.12 9/32 9/32 17/8 2 x 2 x 1 0.90 27/32 27/32 11/4 2 x 2 x 3/4 0.88 19/32 19/32 11/4 2 x 2 x 1/2 1.17 11/4 11/4 21/4 2 x 1 1/2 x 2 1.16 19/32 17/8 111/32 2 x 1 1/2 x 1 1/2 1.15 11/4 13/4 123/32 2 x 1 1/2 x 1 1/4 1.15 7/32 13/4 111/32 2 x 1 1/2 x 3/4 0.83 21/32 15/16 17/32 2 x 1 1/2 x 1/2 1.12 11/4 125/32 21/4 2 x 1 1/4 x 2 1.58 19/32 115/32 19/32 2 x 1 1/4 x 1 1/2 1.16 11/4 131/32 123/32 2 x 1 1/4 x 1 1/4 1.19 15/16 111/32 111/32 2 x 1 1/4 x 1 0.90 27/32 19/32 111/32 2 x 1 1/4 x 3/4 0.85 21/32 1 18/27 2 x 1 x 2 1.11 11/8 125/32 11/4 2 x 1 x 1 0.89 27/32 19/32 111/32 2 x 3/4 x 2 1.15 19/32 23/16 11/4 2 x 1/2 x 2 1.15 19/32 23/8 11/4 2 1/2 2.40 15/8 15/8 15/8 2 1/2 x 2 1/2 x 2 1.97 15/16 15/16 121/32 2 1/2 x 2 1/2 x 1 1/2 1.53 13/32 13/32 121/32 2 1/2 x 2 1/2 x 1 1/4 1.72 13/32 13/32 127/32 2 1/2 x 2 1/2 x 1 1.34 25/32 25/32 111/16 2 1/2 x 2 1/2 x 3/4 1.34 25/32 25/32 113/16 2 1/2 x 2 1/2 x 1/2 1.34 25/32 25/32 21/8 2 1/2 x 2 x 2 1/2 1.99 121/32 23/32 121/32 2 1/2 x 2 x 2 1.95 111/32 15/8 123/32 2 1/2 x 2 x 1 1/2 1.57 13/32 213/32 121/32 2 1/2 x 2 x 1 1/4 1.57 13/32 119/32 127/32 2 1/2 x 2 x 1 1.40 25/32 19/32 13/4 2 1/2 x 2 x 3/4 1.35 25/32 19/32 127/32 2 1/2 x 1 1/2 x 1 1/2 1.76 13/32 113/32 13/8 2 1/2 x 1 1/4 x 2 1/2 2.40 121/32 27/16 121/32 2 1/2 x 1 x 2 1/2 2.04 121/32 223/32 121/32 2 1/2 x 3/4 x 2 1/2 2.00 121/32 211/16 121/32 2 1/2 x 1/2 x 2 1/2 2.46 11/2 27/32 11/2 Continues… APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. C F G 3 3.15 17/8 17/8 21/32 3 x 3 x 2 1/2 3.55 129/32 129/32 23/8 3 x 3 x 2 3.19 115/32 115/32 131/32 3 x 3 x 1 1/2 3.08 115/32 115/32 29/32 3 x 3 x 1 1/4 3.10 115/32 115/32 27/16 3 x 3 x 1 2.12 27/32 27/32 131/32 3 x 3 x 3/4 2.39 27/32 27/32 23/16 3 x 3 x 1/2 1.82 27/32 27/32 23/8 3 x 2 1/2 x 3 3.08 17/8 23/8 131/32 3 x 2 1/2 x 2 1/2 3.12 129/32 211/32 25/32 3 x 2 1/2 x 2 2.28 115/32 127/32 131/32 3 x 2 x 3 3.62 129/32 217/32 115/16 3 x 2 x 2 1/2 3.56 129/32 29/16 25/16 3 x 2 x 2 3.22 115/32 131/32 131/32 3 x 1 1/2 x 3 3.13 129/32 225/32 23/32 3 x 1 1/4 x 3 3.63 129/32 225/32 115/16 3 x 1 x 3 3.20 131/32 219/32 23/16 3 x 3/4 x 3 3.55 131/32 229/32 23/16 3 1/2 5.20 217/32 217/32 217/32 4 8.12 213/32 213/32 217/32 4 x 4 x 3 6.70 21/32 21/32 221/32 4 x 4 x 2 1/2 6.65 21/32 21/32 35/32 4 x 4 x 2 5.82 115/32 115/32 27/16 4 x 4 x 1 1/2 3.94 111/32 111/32 217/32 4 x 4 x 1 1/4 4.04 111/32 111/32 229/32 4 x 4 x 1 3.72 1 1 29/16 4 x 4 x 3/4 3.70 1 1 211/16 4 x 3 x 4 7.05 225/32 37/32 217/32 4 x 3 x 3 5.03 21/32 215/32 215/32 4 x 3 x 2 1/2 5.04 21/32 215/32 229/32 4 x 3 x 2 5.87 115/32 131/32 27/16 4 x 2 1/2 x 4 7.19 225/32 315/32 227/32 4 x 2 x 4 7.08 225/32 319/32 227/32 Continued on next page. NOTE: Tee sizes are read Run x Run x Outlet. 611 Tee C x C x C – Wrot continued TEES continued Consult price sheet for Made to Order items and for minimum order quantities. Revision 2/8/07 A H E A D O F T H E F L O W ® www.nibco.com NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455 www.nibco.com 49 U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. Copper Water Tube continued DIMENSIONAL DATA – COPPER WATER TUBE – TYPE “M” TYPE “M” Hard Drawn Only: 20-ft. (6.1m) Straight Lengths Usage: For general purpose plumbing, heating and drainage installations. Tolerances Hard Drawn (Hard Drawn Only) Outside Tubing OD Nominal Wall Weight Bursting Safe Working Nominal Diameter Thickness Per Foot PressureA PressureB Water Tube Min. Max. Size (In Inches) Inch (mm) Inch (mm) Inch (mm) Inch (mm) Lb (kg) psi (bars) psi (bars) 1/4 0.375 (9.53) 0.373 (9.47) 0.376 (9.55) N/A N/A N/A N/A N/A N/A N/A N/A 3/8 0.500 (12.70) 0.497 (12.62) 0.501 (12.73) 0.025 (0.64) 0.145 (0.07) N/A N/A 855 (59) 1/2 0.625 (15.88) 0.622 (15.80) 0.626 (15.90) 0.028 (0.71) 0.204 (0.09) 6135 (423) 741 (51) 5/8 0.750 (19.05) 0.747 (18.97) 0.751 (19.08) N/A N/A N/A N/A N/A N/A N/A N/A 3/4 0.875 (22.23) 0.872 (22.15) 0.876 (22.25) 0.032 (0.81) 0.328 (0.15) 4717 (325) 611 (42) 1 1.125 (28.58) 1.122 (28.50) 1.127 (28.63) 0.035 (0.89) 0.465 (0.21) 3865 (266) 506 (35) 1 1/4 1.375 (34.93) 1.372 (34.85) 1.377 (34.98) 0.042 (1.07) 0.682 (0.31) 3875 (267) 507 (35) 1 1/2 1.625 (41.28) 1.621 (41.17) 1.627 (41.33) 0.049 (1.24) 0.940 (0.43) 3550 (245) 497 (34) 2 2.125 (53.98) 2.121 (53.87) 2.127 (54.03) 0.058 (1.47) 1.460 (0.66) 2935 (202) 448 (31) 2 1/2 2.625 (66.68) 2.621 (66.57) 2.627 (66.73) 0.065 (1.65) 2.030 (0.92) 2800 (193) 411 (28) 3 3.125 (79.38) 3.121 (79.27) 3.127 (79.43) 0.072 (1.83) 2.680 (1.22) 2665 (184) 380 (26) 3 1/2 3.625 (92.08) 3.621 (91.97) 3.627 (92.13) 0.083 (2.11) 3.580 (1.62) N/A N/A 378 (26) 4 4.125 (104.78) 4.121 (104.67) 4.127 (104.83) 0.095 (2.41) 4.660 (2.11) 2215 (153) 377 (26) 5 5.125 (130.18) 5.121 (130.07) 5.127 (130.23) 0.109 (2.77) 6.660 (3.02) 2490 (172) 349 (24) 6 6.125 (155.58) 6.121 (155.47) 6.127 (155.63) 0.122 (3.10) 8.920 (4.05) 2000 (138) 328 (23) 8 8.125 (206.38) 8.119 (206.22) 8.127 (206.43) 0.170 (4.32) 16.500 (7.48) 2285 (158) 344 (24) 10 10.125 (257.18) 10.119 (257.02) 10.127 (257.23) 0.212 (5.38) 25.600 (11.61) N/A N/A 344 (24) 12 12.125 (307.98) 12.119 (307.82) 12.127 (308.03) 0.254 (6.45) 36.700 (16.65) N/A N/A 345 (24) Note: Information and data contained in these charts, as taken from ASTM Specifications B 88. Rated internal pressure for copper water tube based on the strength of the tube alone and applicable to systems using suitable mechanical joints. A Based on actual laboratory test data provided by Copper Development Association, Inc. B Based upon 150°F (65.6°C) with an allowable stress of 9500 psi (668 kPa). Revision 5/12/02 A H E A D O F T H E F L O W ® www.nibco.com NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455 www.nibco.com 62 1" TYPE “M” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 1.1265 inches (28.613 mm) Nominal O.D. = 1.1250 inches (28.575 mm) Minimum O.D. = 1.1235 inches (28.537 mm) Nominal I.D. = 1.0558 inches (26.797 mm) Nominal Wall Thickness = 0.0350 inches (0.889 mm) Flow Area = 0.8742 sq. inches (563.98 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 2.50 0.18 0.41 0.92 158 0.04 0.41 0.28 5.00 0.64 1.49 1.84 315 0.14 1.49 0.56 7.50 1.36 3.15 2.75 473 0.31 3.15 0.84 10.00 2.31 5.37 3.67 631 0.52 5.37 1.12 12.50 3.49 8.11 4.59 789 0.79 8.11 1.40 15.00 4.90 11.36 5.51 946 1.11 11.36 1.68 17.50 6.52 15.11 6.42 1104 1.47 15.11 1.96 20.00 8.34 19.35 7.34 1262 1.89 19.35 2.24 22.50 10.38 24.06 8.26 1419 2.35 24.06 2.52 25.00 12.61 29.24 9.18 1577 2.85 29.24 2.80 27.50 15.05 34.88 10.09 1735 3.40 34.88 3.08 30.00 17.68 40.97 11.01 1893 4.00 40.97 3.36 32.50 20.51 47.51 11.93 2050 4.64 47.51 3.64 35.00 23.52 54.49 12.85 2208 5.32 54.49 3.92 37.50 26.73 61.91 13.76 2366 6.05 61.91 4.19 40.00 30.12 69.76 14.68 2523 6.81 69.76 4.47 42.50 33.70 78.04 15.60 2681 7.62 78.04 4.75 45.00 37.47 86.74 16.52 2839 8.47 86.74 5.03 47.50 41.41 95.87 17.43 2997 9.37 95.87 5.31 50.00 45.54 105.41 18.35 3154 10.30 105.41 5.59 52.50 49.84 115.37 19.27 3312 11.28 115.37 5.87 55.00 54.33 125.74 20.19 3470 12.29 125.74 6.15 1 1/4" TYPE “K” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 1.3765 inches (34.963 mm) Nominal O.D. = 1.3750 inches (34.925 mm) Minimum O.D. = 1.3735 inches (34.887 mm) Nominal I.D. = 1.2450 inches (31.623 mm) Nominal Wall Thickness = 0.0650 inches (1.651 mm) Flow Area = 1.2174 sq. inches (785.41 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 5.00 0.29 0.67 1.32 315 0.06 0.67 0.40 10.00 1.03 2.40 2.64 631 0.23 2.40 0.80 15.00 2.19 5.08 3.95 946 0.49 5.08 1.20 20.00 3.73 8.65 5.27 1262 0.84 8.65 1.61 25.00 5.64 13.06 6.59 1577 1.27 13.06 2.01 30.00 7.90 18.30 7.91 1893 1.79 18.30 2.41 35.00 10.51 24.34 9.22 2208 2.38 24.34 2.81 40.00 13.46 31.17 10.54 2523 3.04 31.17 3.21 45.00 16.74 38.75 11.86 2839 3.79 38.75 3.61 50.00 20.35 47.09 13.18 3154 4.60 47.09 4.02 55.00 24.27 56.18 14.49 3470 5.49 56.18 4.42 60.00 28.52 65.99 15.81 3785 6.45 65.99 4.82 65.00 33.07 76.52 17.13 4101 7.48 76.52 5.22 70.00 37.94 87.76 18.45 4416 8.58 87.76 5.62 75.00 43.11 99.71 19.77 4732 9.75 99.71 6.02 80.00 48.58 112.35 21.08 5047 10.99 112.35 6.43 U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. Revision 5/12/02 A H E A D O F T H E F L O W ® www.nibco.com NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455 www.nibco.com 63 1 1/4" TYPE “L” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 1.3765 inches (34.963 mm) Nominal O.D. = 1.375 inches (34.925 mm) Minimum O.D. = 1.3735 inches (34.887 mm) Nominal I.D. = 1.265 inches (32.131 mm) Nominal Wall Thickness = 0.0550 inches (1.397 mm) Flow Area = 1.2568 sq. inches (810.85 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 5.00 0.26 0.62 1.28 315 0.06 0.62 0.39 10.00 0.96 2.22 2.55 631 0.22 2.22 0.78 15.00 2.02 4.70 3.83 946 0.46 4.70 1.17 20.00 3.45 8.00 5.11 1262 0.78 8.00 1.56 25.00 5.22 12.09 6.38 1577 1.18 12.09 1.95 30.00 7.31 16.94 7.66 1893 1.65 16.94 2.33 35.00 9.73 22.53 8.93 2208 2.20 22.53 2.72 40.00 12.45 28.84 10.21 2523 2.82 28.84 3.11 45.00 15.49 35.86 11.49 2839 3.50 35.86 3.50 50.00 18.83 43.58 12.76 3154 4.26 43.58 3.89 55.00 22.46 51.98 14.04 3470 5.08 51.98 4.28 60.00 26.39 61.06 15.32 3785 5.97 61.06 4.67 65.00 30.61 70.81 16.59 4101 6.92 70.81 5.06 70.00 35.11 81.21 17.87 4416 7.94 81.21 5.45 75.00 39.89 92.27 19.15 4732 9.02 92.27 5.84 80.00 44.96 103.97 20.42 5047 10.17 103.97 6.22 1 1/4" TYPE “M” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 1.3765 inches (34.963 mm) Nominal O.D. = 1.3750 inches (34.925 mm) Minimum O.D. = 1.3735 inches (34.887 mm) Nominal I.D. = 1.2910 inches (32.7914 mm) Nominal Wall Thickness = 0.0420 inches (1.067 mm) Flow Area = 1.3090 sq. inches (844.52 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 5.00 0.24 0.56 1.23 315 0.05 0.56 0.37 10.00 0.87 2.01 2.45 631 0.20 2.01 0.75 15.00 1.83 4.26 3.68 946 0.41 4.26 1.12 20.00 3.12 7.25 4.90 1262 0.71 7.25 1.49 25.00 4.72 10.95 6.13 1577 1.07 10.95 1.87 30.00 6.62 15.34 7.35 1893 1.50 15.34 2.24 35.00 8.81 20.40 8.58 2208 1.99 20.40 2.61 40.00 11.28 26.12 9.80 2523 2.55 26.12 2.99 45.00 14.03 32.48 11.03 2839 3.17 32.48 3.36 50.00 17.05 39.47 12.25 3154 3.86 39.47 3.74 55.00 20.34 47.08 13.48 3470 4.60 47.08 4.11 60.00 23.90 55.31 14.71 3785 5.41 55.31 4.48 65.00 27.72 64.14 15.93 4101 6.27 64.14 4.86 70.00 31.80 73.56 17.16 4416 7.19 73.56 5.23 75.00 36.13 83.57 18.38 4732 8.17 83.57 5.60 80.00 40.72 94.17 19.61 5047 9.21 94.17 5.98 U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. Revision 5/12/02 A H E A D O F T H E F L O W ® www.nibco.com NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455 www.nibco.com 81 Copper Water Tube continued COPPER TUBE – TYPES, STANDARDS, APPLICATIONS, TEMPERS AND LENGTHS Commercially Available Lengths Tube Type Color Code Standard Application Nominal or Standard Sizes Drawn Annealed Type K Green ASTM B 88 Domestic Water Service Distribution Straight Lengths: 1/4-inch to 8-inch 20 ft. (6.1m) 20 ft. (6.1m) Fire Protection 10-inch 18 ft. (5.5m) 18 ft. (5.5m) Solar 12-inch 12 ft. (3.7m) 12 ft. (3.7m) Fuel/Fuel Oil Coils: 1/4-inch to 1-inch – 60 ft. (18.3m) HVAC – 100 ft. (30.5m) Snow Melting 11/4-inch & 11/2-inch – 60 ft. (18.3m) 2-inch – 40 ft. (12.2m) – 45 ft. (13.7m) Type L Blue ASTM B 88 Domestic Water Service Distribution Straight Lengths: 1/4-inch to 10-inch 20 ft. (6.1m) 20 ft. (6.1m) Fire Protection 12-inch 18 ft. (5.5m) 18 ft. (5.5m) Solar Fuel/Fuel Oil Natural Gas Coils: 1/4-inch to 1-inch – 60 ft. (18.3m) Liquified Petroleum (LP) Gas – 100 ft. (30.5m) HVAC 11/4-inch & 11/2-inch – 60 ft. (18.3m) Snow Melting 2-inch – 40 ft. (12.2m) – 45 ft. (13.7m) Type M Red ASTM B 88 Domestic Water Service Distribution Straight Lengths: 1/4-inch to 12-inch 20 ft. (6.1m) N/A Fire Protection Solar Fuel/Fuel Oil HVAC Snow Melting DWV Yellow ASTM B 306 Drain Straight Lengths: 11/4-inch to 8-inch 20 ft. (6.1m) N/A Waste Vent HVAC Solar ACR Blue ASTM B 280 Air Conditioning Straight Lengths: 1/4-inch to 41/8-inch 20 ft. (6.1m) 20 ft. (6.1m)1 Refrigeration Natural Gas Coils: 1/8-inch to 15/8-inch – 50 ft. (15.3m)1 Liquified Petroleum (LP) Gas OXY Type K ASTM B 819 Medical Gas Straight Lengths: 1/4-inch to 8-inch 20 ft. (6.1m) N/A MED Green OXY/MED OXY/ACR Type L ACR/MED Blue Type G Yellow ASTM B 837 Natural Gas Straight Lengths: 3/8-inch to 11/8-inch 12 ft. (3.7m) 12 ft. (3.7m)1 Liquified Petroleum (LP) Gas 20 ft. (6.1m) 20 ft. (6.1m)1 Coils: 3/8-inch to 7/8-inch – 60 ft. (18.3m)1 – 100 ft. (30.5m)1 1 Available as special order only. U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. Revision 5/12/02 PHD Manufacturing, Inc. • 44018 Columbiana-Waterford Road • Columbiana, OH 44408Toll Free (800) 321-2736 • Phone: (330) 482-9256 • Fax: (330) 482-2763 • www.phd-mfg.com AdjustAble swivel Ring HAngeRs FUNCTION: Designed for the suspension of non-insulated stationary pipe lines. The knurled insert nut that allows a vertical adjustment after installation, is tapped to NFPA reduced rod size standards. Fig. 141F has a layer of felt which separates the pipe from the hanger to reduce vibration and sound. APPROVALS: Underwriters’ Laboratories Listed in the U.S. (UL), Canada (CUL), and Factory Mutual Approved for sizes 3⁄4" to 8". Complies with Federal Specifications A-A-1192A (Type 10), and Manufacturers’ Standardization Society ANSI/SP-69 and SP-58 (Type 10). ORDERING: Specify pipe size and figure number. Fig. 141 & 141FNFPA SWIVELRING HANGER Fig. 141 PRE-GALVANIZED Fig. 141F PRE-GALVANIZED WITH FELT LINING FUNCTION: Designed for the suspension of non-insulated stationary pipe lines. The knurled insert nut, allows for vertical adjustment after installation. Fig. 151F has a layer of felt which separates the pipe from the hanger to reduce vibration and sound. APPROVALS: Underwriters’ Laboratories Listed in the U.S. (UL) and Factory Mutual Approved for all sizes. Complies with Federal Specification A-A-1192A (Type 10), and Manufacturers’ Standardization Society ANSI/SP-69 and SP-58 (Type 10). ORDERING: Specify pipe size and figure number. Fig. 151 & 151FSWIVELRING HANGER Fig. 151 PRE-GALVANIZED Fig. 151F PRE-GALVANIZED WITH FELT LINING Note: If ordering Fig. 151F felt lined hangers for pipe sizes of 31/2" or under, order the next largest size to allow for the thickness of the felt lining. MATERIAL: Low carbon steel RodSizeA Max. Rec.Load/lbs.Wt. Each(in lbs.)PipeSize B Adj.C D E RodSizeA PipeSize Wt. Each(in lbs.)Max. Rec.Load/lbs.Adj.CB D E Note: If ordering Fig. 141F felt lined hangers for pipe sizes of 31/2" or under, order the next largest size to allow for the thickness of the felt lining.MATERIAL: Low carbon steel 1/2 3/8 17/8 17/16 23/4 31/16 300 .10 3/4 3/8 111/16 11/8 21/2 31/16 300 .10 1 3/8 15/8 1 21/2 33/16 300 .10 11/4 3/8 115/16 11/16 213/16 39/16 300 .11 11/2 3/8 21/8 11/16 31/8 37/8 300 .11 2 3/8 27/16 11/8 35/16 43/8 300 .14 21/2 3/8 31/16 15/8 315/16 53/8 525 .19 3 3/8 311/16 17/8 49/16 65/16 525 .23 31/2 3/8 33/4 17/8 45/8 65/8 525 .25 4 3/8 43/16 17/8 51/16 75/16 650 .30 5 1/2 45/8 15/8 55/8 83/8 1000 .50 6 1/2 55/8 21/4 61/2 913/16 1000 .58 8 1/2 613/16 27/16 715/16 121/4 1000 .90 21/2 1/2 23/4 11/4 311/16 51/8 600 .33 3 1/2 31/8 11/8 4 57/8 600 .35 31/2 1/2 35/8 11/2 45/16 65/8 600 .37 4 5/8 37/8 11/4 415/16 71/8 1000 .48 5 5/8 43/8 13/8 55/8 81/2 1000 .57 6 3/4 55/16 2 611/16 101/8 1250 1.06 8 3/4 615/16 25/8 85/16 127/8 1250 1.32 PHD Manufacturing, Inc. • 44018 Columbiana-Waterford Road • Columbiana, OH 44408Toll Free (800) 321-2736 • Phone: (330) 482-9256 • Fax: (330) 482-2763 • www.phd-mfg.com THREADED ACCESSORIES Fig. 20 & 21 CONTINUOUS THREADED ROD Fig. 20* PLAINFig. 21 ELECTRO-GALVANIZED Max. Rec.Load/lbs.RodSize 650°F 750°F6 ft.12 ft.10 ft. PackagingFeet Per Bundle Wt. PerFoot/lbs. FUNCTION: Useful in applications where stud lengths cannot be predetermined. MATERIAL: Low carbon steel ORDERING: Specify rod size, length and figure number. *Available in stainless steel. To order, specify 304 or 316 and add suffix SS to figure number. Price on request. 1/4-20 300 500 600 240 210 .12 3/8-16 150 250 240 610 540 .29 1/2-13 72 120 144 1130 1010 .54 5/8-11 48 80 96 1810 1610 .83 3/4-10 30 50 60 2710 2420 1.25 7/8-9 24 40 48 3770 3360 1.65 1-8 12 20 24 4960 4420 2.25 5 To find a distributor near you, call 800-BUILDEX Not less than 2” nominal width (1-1/2”) up to 3-1/2” pipe; not less than 3” (2-1/2”) nominal width 4” & 5” pipe Minimum 2-1/2” from bottom for branch lines. Minimum 3” from bottom for main lines. Exception: This requirement shall not apply to 2” or thicker nailing strips resting on top of steel beams. Floor Joist HORIZONTAL MOUNT WOOD WOOD WOOD WOOD WOODSIDEWINDERS® for Wood Installs HORIZONTALLY into the side of wood structures easily and quickly! Approvals Rod Size Part Number Model Screw Descriptions Ultimate Pullout (lbs)UL Test Load (lbs)Box Qty Case Qty 1/4"8018957 SWG 100 1/4 x 1"622 (Fir)25 125 1/4"8019957 SWG 200 1/4 x 2"1725 (Fir)25 125 3/8"8020957 SWG 10 1/4 x 1"622 (Fir)300 25 125 3/8"8021957 SWG 20 1/4 x 2"1725 (Fir)1050 25 125 3/8"8073925 SWG 20-SS 1/4 x 2"1725 (Fir)850 25 125 3/8"8022925 SWG 25-380 3/8 x 2-1/2"2249 (Fir)1500 25 125 3/8"8023925 SWG 30 1/4 x 3"1884 (Fir)25 125#14 SW Red Nut Driver Part # 8114910 SPECIAL NUT DRIVER SYSTEM: The nut drivers were designed with a unique spin-off feature which provides a fast and safe installation each time. When the face of the driver comes into contact with the material you are installing into, continue drilling until nut driver spins free. Installation is then complete. Warranty requires the use of the appropriate nut driver for installations. INSTALLATION STEPS - VERTICAL INTO WOOD & STEEL: 1. Insert the appropriate nut driver into a 3/8” or 1/2” portable drill. 2. Insert the SAMMYS into the #14 (black) nut driver (p/n 8113910). Drill should be in a vertical position. 3. Push the face of the nut driver tight to the member. When the nut driver spins freely on the SAMMYS, stop drill and remove. 4. The SAMMYS is now ready to receive 1/4”, 3/8”, 1/2” or metric all thread rod, bolt stock. (The 1/2” requires the #14SW red nut driver) Note: When installing DSTR, follow the above instructions, then add retainer nut and torque to 20 foot lbs. for maximumpullout in purlin steel. INSTALLATION STEPS - HORIZONTAL INTO WOOD & STEEL: 1. Insert the appropriate nut driver into a 3/8” or 1/2” portable drill. 2. Insert the SAMMYS into the #14SW (red) nut driver (p/n 8114910). With drill unit in a horizontal position and at a right angle to the structural member, begin installation. 3. When the nut driver spins free on the SAMMYS, stop the drill and remove. 4. The unit is now ready to receive 1/4”, 3/8” or metric all thread rod or bolt stock. Note: When installing SWDR, follow the above instructions, then add retainer nut and torque to 20 foot lbs. for maximum pullout in purlin steel. Composite/TrussConsult truss manufacturer for recommended installation point. *Pre-drilling may be required for Model SWG 25-380 (tools available on pg 10 ) Product Features • No pre-drilling required. • Quick to install using the Sammy Nut Driver with an 18V cordless drill/driver. • Saves time from traditional methods. • Reduces installation cost. • Made in the U.S.A. Installs VERTICALLY and swivels up to 17° in wood structure