HomeMy WebLinkAboutB16-0401_MEP-2_1483121131.pdfPARKING LEVEL - NEW WORK SCALE: 1/8" = 1'-0" 0 10' 20' GENERAL NOTES: 1. CONTRACTOR SHALL PERFORM PRE-TEST AND AIR BALANCE ON EXISTING FANS TO DETERMINE WHICH, IF ANY FANS PROVIDE SUPPLY AIR. PROVIDE REPORT TO AID IN ENGINEERS DETERMINATION OF WHETHER EXISTING SYSTEMS HAVE CAPACITY FOR CODE REQUIRED VENTILATION, AND WHETHER SPECIFICATION OF NEW EQUIPMENT IS NECESSARY. 2. REPLACE EXISTING 4' & 8' LAMPS 1:1 WITH (N) LED LAMPS AS SCHEDULED. INCLUDE IN COST THE REMOVAL OF EXISTING LIGHTING FIXTURES AND LAMPS. DISPOSE OF EXISTING FLUORESCENT LIGHTING EQUIPMENT PER LOCAL REGULATIONS AS REQUIRED. 3. (E) WET TYPE FIRE SPRINKLER SYSTEM TO BE REPLACED WITH (N) DRY TYPE FIRE SPRINKLER SYSTEM, AS NECESSITATED BY THE PLANNED UNCONDITIONED PARKING GARAGE. FLAG NOTES: CO SENSOR, INSTALLED 5' AFF. NO2 SENSOR, INSTALLED 5' AFF. ADDRESSABLE DETECTION AND VENTILATION CONTROL PANEL, SEE CONTROLS DRAWINGS. (D) EXISTING FANS AND INSTALL (N) EXHAUST FANS AND (N) SUPPLY FANS AT (E) ROOF PENETRATIONS. TYP 6. SHALL OPERATE CONTINUOUSLY AT LOW SPEED TO PROVIDE MINIMUM VENTILATION REQUIREMENT. RE: EXHAUST FAN SCHEDULE. REMOVE (D) LIGHTING FIXTURE AND INSTALL NEW TYPE S1 LIGHTING FIXTURE. TYPICAL OF EIGHTY EIGHT (88). REMOVE (D) LIGHTING FIXTURE AND INSTALL NEW TYPE S1E LIGHTING FIXTURE. TYPICAL OF THIRTY TWO (32). PROVIDE (N) APPROXIMATELY 9 SF DOUBLE DEFLECTION SUPPLY AIR GRILLE, TITUS 272RL OR EQUAL, AT OUTLETS. (E) GAS FIRED RADIANT HEAT PANELS TO REMAIN. TYP 12. (N) LP4 ELECTRICAL PANEL, FED FROM HP2 ELECTRICAL PANEL LOCATED IN MECHANICAL ROOM APPROXIMATELY 60 FT. DISTANT. VISIT SITE PRIOR TO BID TO VERIFY DISTANCE. (N) 30 KVA TRANSFORMER. NEW DISCONNECT. PROVIDE RACEWAY FROM (N) LP4 TO JUNCTION BOX, TYP. 2, FOR GARAGE DOOR OPERATOR (SIZE/ VOLTAGE REMAINS TO BE DETERMINED). INCLUDE (1) 3/4" C & (1) 1" C IN BASE BID. RELOCATE HOSE BIB TO NEW LOCATION SHOWN. REPLACE PLASTIC TUBING WITH SOLDERED COPPER PIPE. CONNECT (N) WALL MOUNT FIXTURE TO UNSWITCHED HOT LEG SERVING EGRESS FIXTURES. FINAL HEIGHT TO BE DETERMINED. ANTICIPATE 30' MOUNTING HEIGHT FOR PRICING PURPOSES. PROVIDE WEATHERPROOF CONVENIENCE POWER AT EACH FAN ON ROOF. IN THE EVENT EXISTING ROOF FANS ARE DEEMED SUITED FOR REQUIRED DUTY, A NEW ODA INTAKE LOUVER WILL BE REQUIRED. BASED ON RUSKIN ELF-6375DX. 1 2 3 NO2 CO NO2 CO NO2 CO NO2 CO NO2 CO NO2 CO NO2 CO NO2 CO NO2 CO NO2 CO SF 1 EF 2 SF 2 EF 3 SF 3 11 10 3 1 4 8 2 10 14 5 9 5 9 6 7 12 4 11 12 13 14 8 15 16 17 L L L L L H H H H H SUBSCRIPT DESIGNATES THRESHOLD SETTING FOR SENSOR PAIR (HIGH VS. LOW). SEE SEQUENCE OF OPERATION. W3 W3 J J 13 S1E S1E S1E S1E S1E S1E S1E S1E S1E S1E S1E S1E S1E S1E S1E S1E S1E S1E S1E S1E S1E S1E S1E S1E S1E S1E S1E S1E S1E S1E S1E S1E EF 1 16 16 16 16 16 16 7 6 15 15 17 ODA 65 SF M (303) 900-8782 PO Box 3699, Evergreen, CO 80437 STBENGR.COM INFO@STBENGR.COM 1295 WESTHAVEN DRIVE VAIL, CO 81657 12/30/16