HomeMy WebLinkAboutB16-0401_MEP-3_1483121133.pdf100/3
200/3
100/3
100/3
200/3
600/3
600/3
1200/3
M GF
100/3
200/3
200/3
T T
(E)
PANEL
"HP2"
(E) MDC - 480Y/277V, 3Ø, 4W, 1200A,
T
(E)
PANEL
"MC"
60/3
L
E N
(E)
PANEL
"EM"
(E)
PANEL
"LL"
(E)
PANEL
"HL"
(E) 30 KVA
TRANSFORMER
T
(E)
PANEL
"LP5"
(E)
PANEL
"LP4"
(E) 225 KVA
TRANSFORMER
(E) 112.5 KVA
TRANSFORMER
(E) 75 KVA
TRANSFORMER
(E)
PANEL
"LP2B"
(E)
PANEL
"LP2-2A"
(E)
PANEL
"LP2"
(E)
PANEL
"LP2A"
(E)
PANEL
"#1"
T
(E)
PANEL
"LP3"
(E)
PANEL
"HP3"
(E) 15 KVA
TRANSFORMER
T
(N)
PANEL
"LP4"
(N) 30 KVA
TRANSFORMER
100/3
CHILLER
ELEVATOR
SPARE
PANEL HP1
SPARE
CHILLER
CIRCULATION
PUMPS
POWER FEED FROM STANDBY
GENERATOR NOT VERIFIED.
(E) MANUAL TRANSFER
SWITCH.
INTERMEDIATE PARKING LEVEL
UPPER PARKING LEVEL
LOWER PARKING LEVEL
(E) MAIN
ELECTRICAL
ROOM
(E) MECHANICAL
ROOM
PROPOSED
PARKING
LEVEL
ELECTRICAL SERVICE TO
BUILDING.
SCALE: NONE
SINGLE LINE POWER DIAGRAM
1
(E) PANEL: HP2
FED FROM: VOLTAGE: 480Y/277V, 3 PHASE, 4 WIRE
LOCATION: MECHANICAL ROOM BUS AMPACITY: 600A
MOUNTING: SURFACE MAIN:
ENCLOSURE: NEMA 3 AIC:
CKT DESCRIPTION NOTES LOAD BREAKER PHASE BREAKER LOAD
DESCRIPTION NOTES
CKT
NO VA TYPE POLE AMPS AMPS POLE TYPE VA NO
1
UNIT HEATER ABOVE 3 20
A
40 3 STEAMER MEN'S LOCKER RM.
2
3 B 4
5 C 6
7 CASCADE CAMP 1 20 A 20 1 PING PONG 8
9 RACQUETBALL COURT LIGHTS 1 20 B 20 1 SQUASH 10
11 SPINNING 1 20 C 20 1 PILATES 12
13 BASKETBALL COURT LIGHTS 1 20 A
30 3 HVAC E LEVEL SOUTH MECH.
14
15 BASKETBALL COURT LIGHTS 1 20 B 16
17 BASKETBALL COURT LIGHTS 1 20 C 18
19 HVAC D LEVEL MECH. RM. UNIT TO
THE RIGHT
3 30
A
30 3 HVAC E LEVEL NORTH MECH.
20
21
B
22
23 C 24
25
HVAC D LEVEL MECH. RM. 3 30
A
30 3 SPARE
26
27 B 28
29 C 30
31
STEAMER WOMEN'S LOCKER RM. 3 40
A
40 3 SUB-PANEL LR - MEN'S SPA
32
33 B 34
35 C 36
37 SUB-PANEL LP4 - PARKING EXHAUST
AND SUPPLY FANS
3 50
A
150 3 MAIN FOR PANEL HP3 TENNIS COURTS
38
39
B
40
41 C 42
LOAD TYPES
CONNECTED LOAD (VA) SUBFEED PANEL
DEMAND LOAD (VA) GENERAL NOTES:
A B C TOTAL TOTAL FACTOR TOTAL A.
LIGHTING 0 0 0 0 0 125% 0 B.
RECEPTACLES 0 0 0 0 0 #DIV/0! (NEC 220) 0 SPECIFIC NOTES:
MOTORS 0 0 0 0 0 100% 0 1. OWNER AND/OR CONTRACTOR
LARGEST MOTOR 0 0 0 0 0 125% 0 SELECTED EQUIPMENT. FOR
EQUIPMENT 0 0 0 0 0 100% 0 INFORMATION ONLY. COORIDATE
APPLIANCES 0 0 0 0 0 0 0 ELECTRICAL REQUIREMENTS WITH
TOTAL DEMAND LOAD (KVA) = 0.0 SYSTEM DESIGNER PRIOR TO ROUGH-IN.
TOTAL DEMAND LOAD (A) = 0 2.
(N) PANEL: LP4
FED FROM: HP2 VOLTAGE: 208Y/120V, 3 PHASE, 4 WIRE
LOCATION: NORTHWST OF PARKING LEVEL BUS AMPACITY: 100A
MOUNTING: SURFACE MAIN: M.L.O.
ENCLOSURE: NEMA 3 AIC:
CKT DESCRIPTION NOTES LOAD BREAKER PHASE BREAKER LOAD
DESCRIPTION NOTES
CKT
NO VA TYPE POLE AMPS AMPS POLE TYPE VA NO
1
EF-1 3 20
A
20 3 SF-1
2
3 1490 B 1490 4
5 C 6
7
EF-2 3 20
A
20 3 SF-2
8
9 1490 B 1490 10
11 C 12
13
EF-3 3 20
A
20 3
`
SF-3
14
15 1490 B 1490 16
17 C 18
19 DRY SYSTEM COMPRESSOR 1 20 A 20 1 CO/NO2 CONTROL PANEL 20
21 POWER @ ROOF 1 20 B 20 1 SPARE 22
23 SPARE 1 20 C 20 1 SPARE 24
25 SPARE 1 20 A 20 1 SPACE 26
27 SPACE B 1 SPACE 28
29 SPACE C 1 SPACE 30
31 SPACE A 1 SPACE 32
33 SPACE B 1 SPACE 34
35 SPACE C 1 SPACE 36
37 SPACE A 1 SPACE 38
39 SPACE B 1 SPACE 40
41 SPACE C 1 SPACE 42
LOAD TYPES
CONNECTED LOAD (VA) SUBFEED 'GH1L' PANEL DEMAND LOAD (VA) GENERAL NOTES:
A B C TOTAL TOTAL FACTOR TOTAL A.
LIGHTING 0 0 0 0 0 125% 0 B.
RECEPTACLES 0 0 0 0 0 #DIV/0! (NEC 220) 0 SPECIFIC NOTES:
MOTORS 0 0 0 0 0 100% 0 1. OWNER AND/OR CONTRACTOR
LARGEST MOTOR 0 0 0 0 0 125% 0 SELECTED EQUIPMENT. FOR
EQUIPMENT 0 0 0 0 0 100% 0 INFORMATION ONLY. COORIDATE
APPLIANCES 0 0 0 0 0 0 0 ELECTRICAL REQUIREMENTS WITH
TOTAL DEMAND LOAD (KVA) = 0.0 SYSTEM DESIGNER PRIOR TO ROUGH-IN.
TOTAL DEMAND LOAD (A) = 0 2.
PROVIDE 4" CONCRETE
SHOPKEEPING PAD BENEATH (N)
TRANSFORMER.
(N) NEMA1 DISCONNECT ADJACENT
TRANSFORMER.
(3)#8, #10G, 1"C
M
POINT OF TEMPORARY METERING
REQ'D TO VERIFY RESERVE
CAPACITY OF (E) PANEL 'HP2' TO
SUPPORT. SEE SCOPE OVERVIEW
NOTS SHEET MEP-1.
INSTALL (N) BREAKER IN (E) 'HP2'
TO SERVE (N) PARKING LEVEL.
TRANSFORMER
PRIMARY VOLTAGE - 480V DELTA
XFMR KVA
SECONDARY VOLTAGE - 120/208V WYE
GROUNDING
ELECTRODE
CONDUCTOR
FEEDER
BREAKER
WIRE SIZE CONDUIT SIZE FLA FLA CONDUIT SIZE WIRE SIZE
MAIN
BREAKER
50A/3P 3 #8, #10 G. 1" 36 30 83 2" 4 #2, #8 G. 100A/3P #8
LOAD FOR DRY SYSTEM
COMPRESSOR IS AN
ASSUMPTION AT THIS TIME.
LUMINAIRE SCHEDULE
TYPE DESCRIPTION MOUNTING
LAMP
WATTS VOLT MANUFACTURER CATALOG NUMBER NOTES
QUANT. TYPE
W3
WALL MOUNTED LED PARKING LOT FIXTURE WITH INTEGRAL
PHOTOCELL AND TYPE 3 DISTRIBUTION
WALL LED 209W 277V LITHONIA
DSX1LED 60C 1000 4K T3M MVOLT PER DBLXD
/DLL127F1.5JU
S1 4' LED VAPOR TIGHT FIXTURE SURFACE LED 42W 277V LITHONIA VAP 4000LM FST WD MVOLT 40K 90CRI
S1E
4' LED VAPOR TIGHT FIXTURE WITH INTEGRAL EMERGENCY
BATTERY PACK
SURFACE LED 62W 277V LITHONIA
VAP 6000LM FST WD MVOLT 40K 90CRI
/BSL722C
GENERAL NOTES:
A. THE LUMINAIRE SCHEDULE CAN NOT BE USED INDEPENDENTLY OF THE DRAWINGS AND SPECIFICATIONS TO OBTAIN LUMINAIRE COSTS. THE INDIVIDUAL ESTABLISHING LUMINAIRE COSTS
SHALL NOT QUOTE PRICING WITHOUT FIRST SEEING APPLICABLE ELECTRICAL DRAWINGS. THE CONTRACTOR IS REPONSIBLE FOR PROVIDING NECESSARY DRAWINGS TO THE INDIVIDUAL
QUOTING LUMINAIRE PRICING.
B. ALL FINISHES SHALL BE SELECTED BY THE OWNER/OPERATOR PRIOR TO PURCHASING FIXTURES.
SPECIFIC NOTES:
1. EXTERIOR LIGHTS SHALL HAVE INTEGRAL PHOTOCELL TO ENSURE THEY DO NOT OPERATE DURING THE DAY AND BY EXTERNAL MOTION SENSOR TO ALLOW FOR AUTOMATIC OPERATION.
2. EXIT SIGN SHALL BE PROVIDED WITH INTEGRAL BATTERY AND WIRED USING UNSWITCHED LIGHTING BRANCH CIRCUIT CONDUCTOR TO ALLOW FOR CONTINUOUS OPERATION AND CHARGING.
3. EXIT SIGNS SHALL BE WALL MOUNTED TO FLUCH ELECTRICAL BOX, 6" ABOVE THE TOP OF THE DOOR FRAME.
(303)
900-8782 PO Box
3699,
Evergreen, CO 80437
STBENGR.COM
INFO@STBENGR.COM
1295
WESTHAVEN
DRIVE
VAIL, CO 81657
12/30/16