HomeMy WebLinkAboutB16-0254_E401a_signed_1507144320.pdfJ
J
J
J
J
J
J
J
J
J
J M
M
kp
J
J
J
J
CR
DL
CR
26.32
LD- 1
SKI BOOT
REMOVAL
AREA
110
VESTIBULE
101
LOBBY
LOUNGE
WITH
CONNECTIVITY
ZONE
102
?
?
CHECK-IN
107
LOBBY BAR
103
TYPICAL OF (3)
R3
R2E
R1E
R2 R2
R2 R1E
R2
R2
R2
R2
R3
R3
R3
R3 R3
R3 R3
R3 R3 R3E R3 R3E
R3
R3
R3 R3E R3 R3
LD- 3
X1
CONNECT TO
CORRIDOR
LIGHTING CIRCUIT
26.43
26.44
R2
TYPICAL
26.45 26.43
LD- 5
LD- 4
LD- 8
R4
R4
6A
E401a
C3
TYPICAL ACROSS TOP
26.35
LD- 2
LD- 6
26.58
26.58
TYPICAL
TYPICAL
OF (3)
BOH
MASTER
LIGHTING
KEYPAD
R4
R4 1
E401a
C4
C4
26.38
26.37
26.33
LTG-401
LTG-403
LTG-402
X2
X2
X3
X2
26.61
TYPICAL
C5
X3
+96"
R2E
R2E
26.62
X2
X1
R3
MAIN FLOOR
100' - 0"
2ND FLOOR
114' - 2"
02_SECOND FLOOR -1
112' - 0"
01_MAIN FLOOR
100'
- 0"
02_SECOND FLOOR -1
112'
- 0"
2ND FLOOR -
REFLECTED CEILING
PLAN
114'
- 2"
C4
C3 26.35
26.36
MAIN FLOOR
100' - 0"
2ND FLOOR
114' - 2"
O
02_SECOND FLOOR -1
112' - 0"
01_MAIN FLOOR
100' - 0"
02_SECOND FLOOR -1
112' - 0"
2ND FLOOR -
REFLECTED CEILING
PLAN
114'
- 2"
FP1
26.60
TYPICAL OF (80)
1 A 2 3 4 5 6 A B C D E
1
3 4 5 6 2
COPYRIGHT 2016 BASKERVILL. USE OF THIS WORK IN WHOLE OR IN
PART IS FORBIDDEN WITHOUT EXPRESSED WRITTEN CONSENT.
B C D E
DRAWING
NO.
P.O. BOX 400, RICHMOND, VA 23218-0400
DRAWING TITLE
ISSUE
PROJECT
OWNER
®
9/19/2017
4:39:09 AM
ENLARGED FLOOR
PLAN -
LOBBY/LOUNGE/BAR
LIGHTING
THE WIDEWATERS
GROUP
2.160036.0
DOUBLETREE VAIL,
CO CONVERSION
GUESTROOMS &
PUBLIC SPACES
RENOVATION
08/25/16 -
CONSTRUCTION
DOCUMENTS
E401a
2211 N FRONTAGE
RD, VAIL, COLORADO
81657
SCALE: 1/4" = 1'-0" DRAWING REF: E111
4AENLARGED FLOOR PLAN - LOBBY/LOUNGE/BAR
KEYNOTES
26.32 PROVIDE OCCUPANCY/VACANCY SWITCHING EQUAL TO LUTRON MAESTRO
MS-Z101.
26.33 PROVIDE RECESSED JUNCTION BOXES AND LIGHTING CIRCUIT THRU NEW
LIGHTING CONTROLS. INSTALL PENDANT LIGHTING SUPPLIED BY OTHERS AND
MAKE ALL FINAL CONNECTIONS.
26.35 PROVIDE LED TAPE ACROSS TOP OF BAR MILLWORK EQUAL TO FIXTURE LISTED
IN SCHEDULE. SEE MILLWORK DRAWINGS A606 AND A607 FOR ADDITIONAL
INFORMATION. FIELD COORDINATE SWITCHING.
26.36 PROVIDE LED TAPE TO UNDERSIDE OF BAR COUNTER TOP MILLWORK EQUAL TO
FIXTURE LISTED IN SCHEDULE. SEE MILLWORK DRAWINGS A606 AND A607 FOR
ADDITIONAL INFORMATION. INFORMATION. FIELD COORDINATE SWITCHING.
26.37 PROVIDE POWER TO FOCAL LIGHTING. PROVIDE 16'-0" OF LENGTH LIGHTING
EQUAL TO FIXTURE SCHEDULE AT 14'-6" AFF. LIGHTING TO BE SWITCHED BT
BREAKER AT PANEL.
26.38 PROVIDE LED TAPE AT REGISTRATION DESK MILL WORK. SEE DRAWING A605 FOR
ADDITIONAL INFORMATION. FIELD COORDINATE SWITCHING.
26.43 CONNECT AHEAD OF SWITCHING AS NIGHT LIGHT.
26.44 PROVIDE CEILING MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR.
26.45 CONNECT TO AVAILABLE 20A 1P 120V CIRCUIT MADE AVAILABLE DURING
DEMOLITION OR PROVIDE MATCHING AIC 20A 1P CIRCUIT BREAKER IN AVAILABLE
SPACE OF EXISTING PANELBOARD AS NEEDED. FIELD VERIFY PANEL
DESIGNATIONS AND CIRCUIT AVAILABILITY.
26.58 PROVIDE JUNCTION BOXES AND LIGHTING CIRCUIT THRU NEW LIGHTING
CONTROLS. INSTALL PENDANT LIGHTING SUPPLIED BY OTHERS AND MAKE ALL
FINAL CONNECTIONS.
26.60 PROVIDE RECESSED LED SQUARE PUCK LIGHTS AT FIREPLACE FACADE AS
MANUFACTURED BY THE VOLT LIGHTING GROUP. CONTACT BILL AT 800-789-3810.
SEE ARCHITECTS DRAWING A401D FOR ADDITIONAL INFORMATION.
26.61 PROVIDE EGRESS LIGHTING EQUAL TO FIXTURE LISTED IN FIXTURE SCHEDULE
ON EXPOSED ROOF TRUSS AT @ 21'-0" AFF. PAINT CONDUIT TO MATCH.
26.62 EXTEND AND CONNECT TO EXTERIOR LIGHTING CIRCUIT.
SCALE: 1/4" = 1'-0" DRAWING REF: E401a
6AENLARGED BAR LIGHTING DETAIL
Notes:
Total Est. Demand... 17 A
Total Conn. Current: 17 A
Power 3900 VA 100.00% 3900 VA Total Est. Demand: 6186 VA
Other 0 VA 0.00% 0 VA Total Conn. Load: 6186 VA
Lighting 2286 VA 100.00% 2286 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 23 A 29 A 5 A
Total Load: 2514 VA 3119 VA 552 VA
19 20
17 18
15 16
13 14
11 12
9 CORRIDORS 140A, 140, 140B LTS 20 A 1 662... 312... 1 20 A PREFUNCTION 152 LIGHTING 10
7 ELEV LOBBY 140A, 107C LIGHTS 20 A 1 445... 465... 1 20 A LOBBY LOUNGE LIGHTING 8
5 VESTIBULE 101 LIGHTING 20 A 1 52 VA 500... 1 20 A FRONT DESK FOCAL WALL LIGHTS 6
3 LBY/LOUNGE RECESSED LTS 20 A 1 624... 152... 1 20 A CHECK-IN DESK LIGHTNIG 4
1 LBY/LOUNGE PENDANT LIGHTING 20 A 1 150... 104... 1 20 A SKI BOOT REMOVAL AREA 110 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating:
Mounting: Surface Wires: 4 Mains Rating: 100 A
Supply From: Phases: 3 Mains Type:
Location: LUGGAGE ROOM 118 Volts: 120/208 Wye A.I.C. Rating:
Branch Panel: LD
1 8/25/2016 FOR CONSTRUCTION SET
4 11/07/2016 ASI #2
6 1/09/2017 CCD-03
10 9/15/17 CCD-06
LOBBY DIMMING SCHEDULE
SCALE: 1/4" = 1'-0" DRAWING REF: E401a
1ENLARGED FIREPLACE LIGHTING DETAIL
09/07/2017
201709/0
10/04/17