HomeMy WebLinkAboutB16-0254_E405_signed_1507144320.pdf3oc
J
J
J J kp
M
F
F
F
V J M
BALLROOM/
MEETING
ROOM
104
MEETING
STORAGE
153
C2
C1
C1
C1
C1
C1
C1
C1
C1
C1
C2
C2
C2
C2
C1
C1
C1
C1
C1
C1
C2
C1
C1
C1
C1
C1
C1
C1
C1
C1
C2
C2
C2
C1
C1
C1
C2
C1 C1 C1
C2
C2
C1
C1
C1
C1
C1
C1
C2 C1 C1 C1
C2
C1
C1
C1
X1
F1 F1 F1
R1 R1E R1 R1E R1
R1
R1E
R1
R1E
R1
R1 R1 R1 R1E
R1
R1E
R1
R1
R1E
ZONE 1
ZONE 2
26.31
ZONE 3
26.45 26.31
LTG-403
LTG-403
LTG-403
LTG-403
26.58
LLF
MOTORIZED
SCREEN SWITCH
+42" +42" +42"
PR
PR
PR
BALLROOM/
MEETING
ROOM
104
MEETING
STORAGE
153
26.54
26.45
B- 2
B- 4
B- 6
MOUNT RECEPTACLES HORIZONTAL
B- 23
26.31 BD
26.45
26.59
26.107
LLF
1
A 2 3 4 5 6 A B C D E
1
3 4 5 6 2
COPYRIGHT 2016 BASKERVILL. USE OF THIS WORK IN WHOLE OR IN
PART IS FORBIDDEN WITHOUT EXPRESSED WRITTEN CONSENT.
B C D E
DRAWING NO.
P.O. BOX 400, RICHMOND, VA 23218-0400
DRAWING TITLE
ISSUE
PROJECT
OWNER
®
9/19/2017
4:39:15 AM
ENLARGED PLANS -
BALLROOM
THE WIDEWATERS
GROUP
2.160036.0
DOUBLETREE VAIL,
CO CONVERSION
GUESTROOMS &
PUBLIC SPACES
RENOVATION
08/25/16 -
CONSTRUCTION
DOCUMENTS
E405
2211 N FRONTAGE
RD, VAIL, COLORADO
81657
SCALE: 1/4" = 1'-0" DRAWING REF: E111
3ALIGHTING PLAN - BALLROOM
SCALE: 1/4" = 1'-0" DRAWING REF: E121
6APOWER AND COMMUNICATIONS PLAN - BALLROOM
KEYNOTES
26.31 PROVIDE NEW LIGHTING CONTROLS / PANEL EQUAL TO LUTRON GRAFIK EYE QS.
26.45 CONNECT TO AVAILABLE 20A 1P 120V CIRCUIT MADE AVAILABLE DURING
DEMOLITION OR PROVIDE MATCHING AIC 20A 1P CIRCUIT BREAKER IN AVAILABLE
SPACE OF EXISTING PANELBOARD AS NEEDED. FIELD VERIFY PANEL
DESIGNATIONS AND CIRCUIT AVAILABILITY.
26.54 SAWCUT / TRENCH AND REPAIR FLOOR AS REQUIRED. PROVIDE RECESSED
FLOORBOX WITH RECEPTACLES. CONNECT TO EXISTING RECEPTACLE CIRCUIT
OR AVAILABLE 20A 1P 120V BREAKER.
26.58 PROVIDE JUNCTION BOXES AND LIGHTING CIRCUIT THRU NEW LIGHTING
CONTROLS. INSTALL PENDANT LIGHTING SUPPLIED BY OTHERS AND MAKE ALL
FINAL CONNECTIONS.
26.59 PROVIDE POWER TO RECESSED MOTORIZED SCREEN AS ADD / ALTERNATE.
26.107 PROVIDE 400A, 3วพ, 42P PANEL. EXTEND AND CONNECT TO 3P BREAKER IN
SWITCHGEAR WITH (4)#500KCMIL, (1)#2GND - 3 1/2"C. CONTRACTOR TO FIELD
COORDINATE PANEL LOCATION SO THAT PANEL CAN BE USED FOR FUTURE
DEVELOPMENT OF UPSTAIRS LODGING.
1 8/25/2016 FOR CONSTRUCTION SET
4 11/07/2016 ASI #2
9 7/21/17 CCD-05
10 9/15/17 CCD-06
Notes:
Receptacle 2520 VA 100.00% 2520 VA Total Est. Demand... 220 A
Power 30616 VA 100.00% 30616 VA Total Conn. Current: 220 A
Other 1580 VA 100.00% 1580 VA Total Est. Demand: 79317 VA
Lighting 369 VA 100.00% 369 VA Total Conn. Load: 79317 VA
HVAC 9126 VA 100.00% 9126 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 135 A 138 A 136 A
Total Load: 16147 VA 16576 VA 16288 VA
41 SPARE 20 A 1 0 VA 968... 42
39 SPARE 20 A 1 0 VA 747... 40
37 SPARE 20 A 1 0 VA 704...
3 200 A PANEL 'K' LOCATED IN KITCHEN
38
35 SPARE 20 A 1 0 VA 0 VA -- -- SPACE ONLY 36
33 SPARE 20 A 1 0 VA 0 VA -- -- SPACE ONLY 34
31 SPARE 20 A 1 0 VA 0 VA -- -- SPACE ONLY 32
29 SPARE 20 A 1 0 VA 0 VA -- -- SPACE ONLY 30
27 SPARE 20 A 1 0 VA 0 VA -- -- SPACE ONLY 28
25 SPARE 20 A 1 0 VA 0 VA -- -- SPACE ONLY 26
23 SPARE 20 A 1 0 VA 0 VA -- -- SPACE ONLY 24
21 SPARE 20 A 1 0 VA 0 VA -- -- SPACE ONLY 22
19 SPARE 20 A 1 0 VA 0 VA -- -- SPACE ONLY 20
17 SPARE 20 A 1 0 VA 0 VA -- -- SPACE ONLY 18
15 250... 0 VA -- -- SPACE ONLY 16
13
OUTDOOR PATIO INFRARED HEATER 35 A 2
250... 0 VA -- -- SPACE ONLY 14
11 250... 0 VA -- -- SPACE ONLY 12
9
OUTDOOR PATIO INFRARED HEATER 35 A 2
250... 0 VA -- -- SPACE ONLY 10
7 250... 0 VA -- -- SPACE ONLY 8
5
OUTDOOR PATIO INFRARED HEATER 35 A 2
250... 160... 6
3 250... 160...
4
1
OUTDOOR PATIO INFRARED HEATER 35 A 2
250... 160...
3 40 A
PANEL 'T LOCATED IN DUMPSTER
SHED
2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating:
Mounting: Surface Wires: 4 Mains Rating: 400 A
Supply From: Phases: 3 Mains Type:
Location: MEETING STORAGE 153 Volts: 120/208 Wye A.I.C. Rating: VERIFY
Branch Panel: LLF
09/07/2017
201709/0
10/04/17