HomeMy WebLinkAboutB16-0254_E407_signed_1506372240.pdf3
3
G
D
D D
D D D G G
J
J
J
J
J
J
J
J
KITCHEN
151
DISHWASHING
106
B
K
K- 14
26.65
26.66
26.67
B
K
K- 17
height
height
34" 68"
65"
KITCHEN
151
K- 1
K- 5
K- 9
34"
K- 13
K- 15
K- 19
K- 21
K- 23
K- 25
K- 27 K- 29
K- 31
K- 33
K- 35
K- 37
K- 39 K- 28,30
K-
47,49,51
K-
41,43,45
26.114
26.115
26.116
B- 12
+44"
B- 14
K- 53
1 A 2 3 4 5 6 A B C D E
1
3 4 5 6 2
COPYRIGHT 2016 BASKERVILL. USE OF THIS WORK IN WHOLE OR IN
PART IS FORBIDDEN WITHOUT EXPRESSED WRITTEN CONSENT.
B C D E
DRAWING NO.
P.O. BOX 400, RICHMOND, VA 23218-0400
DRAWING TITLE
ISSUE
PROJECT
OWNER
®
9/19/2017
4:39:18 AM
ENLARGED KITCHEN
DETAILS AND
PANELBOARD
SCHEDULE
THE WIDEWATERS
GROUP
2.160036.0
DOUBLETREE VAIL,
CO CONVERSION
GUESTROOMS &
PUBLIC SPACES
RENOVATION
08/25/16 -
CONSTRUCTION
DOCUMENTS
E407
2211 N FRONTAGE
RD, VAIL, COLORADO
81657
12 9/15/17 CCD-07
KEYNOTES
26.65 PROVIDE 2X4 LAY-IN LIGHTING EQUAL TO LITHONIA 2ALT4 5000LM MVOLT.
26.66 PROVIDE 2X2 LAY-IN LIGHTING EQUAL TO ETI 54309141.
26.67 PROVIDE 1X2 LAY-IN LIGHTING EQUAL TO PIXI FLT12R27MD1622A.
26.114 PROVIDE SINGLE POINT CONNECTION TO DISH MACHINE CONTROL PANEL. FEED
WITH (3) #10, (1) #10 GND-3/4" CONDUIT AND FLEXIBLE CONNECTION.
26.115 PROVIDE SINGLE POINT CONNECTION TO DISH MACHINE BOOSTER HEATER.
FEED WITH (3) #3, (1) #8 GND- 1 1/4"C.
26.116 PROVIDE POWER TO MENU BOARD. VERIFY CONNECTION TYPE AND HEIGHT IN
FIELD.
SCALE: 3/8" = 1'-0" DRAWING REF: E111
3AENLARGED KITCHEN LIGHTING PLAN
SCALE: 3/8" = 1'-0" DRAWING REF: E1216AENLARGED KITCHEN POWER PLAN
Notes:
Receptacle 2520 VA 100.00% 2520 VA Total Est. Demand... 151 A
Power 10616 VA 100.00% 10616 VA Total Conn. Current: 151 A
Other 1580 VA 100.00% 1580 VA Total Est. Demand: 54517 VA
Lighting 369 VA 100.00% 369 VA Total Conn. Load: 54517 VA
HVAC 9126 VA 100.00% 9126 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 143 A 147 A 165 A
Total Load: 17149 VA 17578 VA 19790 VA
53 KITCHEN FIRE SUPPRESSION 20 A 1 500... 0 VA 1 20 A SPARE 54
51 720... 0 VA 1 20 A SPARE 52
49 720... 0 VA 1 20 A SPARE 50
47
COOLER CONDENSING UNIT 15 A 3
720... 0 VA 1 20 A SPARE 48
45 816... 0 VA 1 20 A SPARE 46
43 816... 0 VA 1 20 A SPARE 44
41
FREEZER CONDENSING UNIT 15 A 3
816... 42
39 COOLER EVAPORATOR COIL 15 A 1 528... 40
37 KITCHEN 151 WALK-IN FREEZER 15 A 1 120... 38
35 KITCHEN 151 WALK-IN COLLER 15 A 1 120... 36
33 KITCHEN 151 RECEPTACLE 20 A 1 180... 34
31 KITCHEN 151 RECEPTACLE 20 A 1 180... 32
29 KITCHEN 151 RECEPTACLE 20 A 1 180... 129... 30
27 KITCHEN 151 RECEPTACLE 20 A 1 180... 129...
2 20 A FREEZER EVAPORATOR COIL
28
25 KITCHEN 151 RECEPTACLE 20 A 1 180... 800... 26
23 KITCHEN 151 RECEPTACLE 20 A 1 180... 800... 24
21 KITCHEN 151 RECEPTACLE 20 A 1 180... 800...
3 90 A DISHMACHINE BOOSTER HEATER
22
19 KITCHEN 151 RECEPTACLE 20 A 1 180... 210... 20
17 KITCHEN 151 HEAT LAMP / TABLE 20 A 1 158... 210... 18
15 KITCHEN 151 RECEPTACLE 20 A 1 360... 210...
3 35 A DISHMACHINE
16
13 KITCHEN 151 RECEPTACLE 20 A 1 180... 369... 1 20 A KITCHEN LIGHTING 14
11 SHUNT TRIP -- -- 0 VA 210... 12
9 KITCHEN 151 RECEPTACLE 20 A 1 180... 210... 10
7 SHUNT TRIP -- -- 0 VA 210...
3 35 A RTU-A1 LOCATED ON ROOFTOP
8
5 KITCHEN 151 RECEPTACLE 20 A 1 180... 940... 6
3 SHUNT TRIP -- -- 0 VA 940... 4
1 KITCHEN 151 RECEPTACLE 20 A 1 180... 940...
3 15 A MAU-1 LOCATED ON ROOFTOP
2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating:
Mounting: Surface Wires: 4 Mains Rating: 200 A
Supply From: LLF Phases: 3 Mains Type:
Location: KITCHEN 151 Volts: 120/208 Wye A.I.C. Rating:
Branch Panel: K
09/07/2017
201709/0
09/25/17