HomeMy WebLinkAboutB17-0027_M-300_1490802540.pdfSystem No. C-AJ-1184 SECTION A-A 1. Floor or Wall Assembly -- Min 4-1/2 in. thick reinforced lightweight or normal weight (100-150 pcf) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Floor may also be constructed of any min 7-1/2 in. thick UL Classified hollow core Precast Concrete Units*. Max diam of opening is 14 in. when concrete floor or wall is used and max 7 in. when precast concrete units are used. See Concrete Blocks (CAZT) and Precast Concrete Units (CFTV) categories in the Fire Resistance Directory for names of manufacturers. 2. Through-Penetrants -- One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the firestop system. The annular space between pipe, conduit or tubing and periphery of opening shall be min 0 in. (point contact) to max 3-1/4 in. Pipe, conduit or tubing to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A. Steel Pipe -- Nom 10 in. diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe -- Nom 10 in. diam (or smaller) cast or ductile iron pipe. C. Conduit -- Nom 4 in. diam (or smaller) steel electrical metallic tubing or steel conduit. D. Copper Tubing -- Nom 4 in. diam (or smaller) Type L (or heavier) copper tubing. E. Copper Pipe -- Nom 4 in. diam (or smaller) regular (or heavier) copper pipe. 3. Forms -- (Not Shown, Optional) -- Used as a form to prevent leakage of fill material during installation. Forms to be rigid sheet material, cut to fit the contour of the penetrating item and positioned as required to accommodate the required thickness of fill material. Forms to be removed after fill material has cured. Additional forming material may be used concrete block wall is penetrated. A min 1/2 in. thickness of min 4 pcf mineral wool batt insulation is firmly packed into the annulus as a permanent form and recessed from both surfaces of the wall as required to accommodate the required thickness of fill material. 4. Fill, Void or Cavity Material* -- Sealant -- Min 1 in. thickness of fill material applied within the annulus. At the point contact location between through penetrant and concrete, a min 1/2 in. diam bead of fill material shall be applied at the concrete through penetrant interface. When precast concrete units are used, the fill material shall be installed within annular space, flush with lower surface of floor. When concrete block wall is penetrated, a min 1 in. thickness of fill material shall be applied within the annulus flush with both surfaces of wall. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC -- FS605 or FS-ONE Sealant *Bearing the UL Classification Mark A Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. March 12, 1999 F Rating -- 3 Hr T Rating -- 0 Hr A 4 2 1 C C L A S S I F I E D Classified by Underwriters Laboratories, Inc. to UL 1479 and CAN/ULC-S115 US System No. C-AJ-1421 SECTION A-A A A 4B 2 3 4B 1 4A C C L A S S I F I E D Classified by Underwriters Laboratories, Inc. to UL 1479 and CAN/ULC-S115 US ANSI/UL1479 (ASTM E814) CAN/ULC S115 ) 5DWLQJ ²  RU +U ) 5DWLQJ ²  RU  +U 7 5DWLQJV ²  +U )7 5DWLQJV ²  +U / 5DWLQJ $W $PELHQW ² /HVV 7KDQ  CFM/sq ft )+ 5DWLQJ ²  RU  +U / 5DWLQJ $W  ) ² /HVV 7KDQ  CFM/sq ft )7+ 5DWLQJV ²  +U 6HH ,WHP & / 5DWLQJ $W $PELHQW ² /HVV 7KDQ  CFM/sq ft / 5DWLQJ $W  ) ² /HVV 7KDQ  CFM/sq ft  )ORRU RU :DOO $VVHPEO\ ² 0LQ  LQ  PP WKLFN UHLQIRUFHG OLJKWZHLJKW RU QRUPDO ZHLJKW  SFI RU  NJP concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 6 in. (152 mm). See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.  0HWDOOLF 6OHHYH ² 2SWLRQDO 1RP  LQ  PP GLDP RU VPDOOHU 6FKHGXOH  RU KHDYLHU VWHHO VOHHYH FDVW RU JURXWHG LQWR floor or wall assembly, flush with floor or wall surfaces.  7KURXJK3HQHWUDQW ² 2QH PHWDOOLF SLSH RU FRQGXLW WR EH LQVWDOOHG HLWKHU FRQFHQWULFDOO\ RU HFFHQWULFDOO\ ZLWKLQ WKH ILUHVWRS V\VWHP The annular space between pipe, tube or conduit and periphery of opening shall be min 0 in. (0 mm) (point contact) to max 5-3/8 in. (137 mm). Pipe or conduit to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic pipes or conduits may be used: $ 6WHHO 3LSH ² 1RP  LQ  PP GLDP RU VPDOOHU 6FKHGXOH  RU KHDYLHU VWHHO SLSH % ,URQ 3LSH ² 1RP  LQ  PP GLDP RU VPDOOHU FDVW RU GXFWLOH LURQ SLSH & &RSSHU 3LSH ² 1RP  LQ  PP GLDP RU VPDOOHU 5HJXODU RU KHDYLHU FRSSHU SLSH ' &RSSHU 7XELQJ ² 1RP  LQ  PP GLDP RU VPDOOHU 7\SH / RU KHDYLHU FRSSHU WXELQJ ( &RQGXLW ² 1RP  LQ  PP GLDP RU VPDOOHU VWHHO FRQGXLW ) &RQGXLW ² 1RP  LQ  PP GLDP RU VPDOOHU VWHHO HOHFWULFDO PHWDOOLF WXELQJ (07  )LUHVWRS 6\VWHP ² 7KH ILUHVWRS V\VWHP VKDOO FRQVLVW RI WKH IROORZLQJ $ 3DFNLQJ 0DWHULDO ² 0LQ  LQ  PP WKLFNQHVV RI PLQ  SFI  NJP PLQHUDO ZRRO EDWW LQVXODWLRQ ILUPO\ SDFNHG LQWR opening as a permanent form. Packing material to be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of fill material. % )LOO 9RLG RU &DYLW\ 0DWHULDO  6HDODQW ² 0LQ  LQ  PP WKLFNQHVV RI ILOO PDWHULDO DSSOLHG ZLWKLQ WKH DQQXOXV IOXVK ZLWK WRS surface of floor or with both surfaces of wall. For 3 Hr rated assemblies, a min 1/4 in. (6 mm) diam bead of fill material shall be applied at the concrete/pipe interface at the point contact location on the top surface of floor and on both surfaces of wall. +,/7, &216758&7,21 &+(0,&$/6 ',9 2) +,/7, ,1& ² )621( 6HDODQW RU &3 6HOI/HYHOLQJ )LUHVWRS 6HDODQW CP604 shall be used in floor applications only. When CP604 is used, F Rating is 2 Hr. *Bearing the UL Classification Mark Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. November 21, 2012 UNIT 9203 FOUR SEASONS RESORT & RESIDENCES VAIL, CO JDR CHK BY: SCALE: SHEET: JOB #: DRW BY: TITLE: DATE: N/A BJH UNIT 9203 REMODEL SEAL & SIGNATURE: 17006.00 2/22/17 MECHANICAL SCHEMATICS 16 OF 22 M-300 ISSUE DATE COMMENT CLIENT: Tim & Nancy Buese Unit 9203 FOUR SEASONS VAIL 1 Vail Road VAIL, CO 81657 ARCHITECT: Creative Design Associates 434 BROADWAY, 5TH FLOOR NEW YORK, NY 10013 t. 212-748-8900 WESTERN US 4700 E BROMLEY LN, SUITE 105 BRIGHTON, CO 80601 t. 646-747-2171 c. 917-756-0057 dsorenson@ralcompanies.com INTERIOR DESIGN: Duet Design Group, LLC 901 ACOMA SUITE 200 DENVER, CO 80204 t. 303-783-9327 miranda@duetdesigngroup.com MECH/PLUMBING ENGINEER: Rader Engineering PO BOX 8610 AVON, CO 80620 t. 970-845-7910 BryanH@raderengineering.com ELECTRICAL ENGINEER: C3S Incorporated 3212 WEST 45TH AVENUE DENVER, CO 80211 t. 303-480-5144 theresa@c3sengineeringinc.com LIGHTING DESIGN: 186 Lighting Design Group, Inc. 1200 BANNOCK STREET DENVER, CO 80204 t. 303-534-5350 gmackell@186group.com KITCHEN DESIGN: exquisite kitchen design 601 SOUTH BROADWAY SUITE F DENVER, CO 80209 303-282-0382 mikalo@myekdesign.com 1 FOR PERMIT 2/22/17 2/22/17 03/29/17