HomeMy WebLinkAboutB17-0027_M-300_1490802540.pdfSystem No. C-AJ-1184
SECTION A-A
1. Floor or Wall Assembly -- Min 4-1/2 in. thick reinforced lightweight or normal weight (100-150 pcf) concrete. Wall may
also be constructed of any UL Classified Concrete Blocks*. Floor may also be constructed of any min 7-1/2 in. thick UL
Classified hollow core Precast Concrete Units*. Max diam of opening is 14 in. when concrete floor or wall is used and
max 7 in. when precast concrete units are used.
See Concrete Blocks (CAZT) and Precast Concrete Units (CFTV) categories in the Fire Resistance Directory for names
of manufacturers.
2. Through-Penetrants -- One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within
the firestop system. The annular space between pipe, conduit or tubing and periphery of opening shall be min 0 in.
(point contact) to max 3-1/4 in. Pipe, conduit or tubing to be rigidly supported on both sides of floor or wall assembly.
The following types and sizes of metallic pipes, conduits or tubing may be used:
A. Steel Pipe -- Nom 10 in. diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe -- Nom 10 in. diam (or smaller) cast or ductile iron pipe.
C. Conduit -- Nom 4 in. diam (or smaller) steel electrical metallic tubing or steel conduit.
D. Copper Tubing -- Nom 4 in. diam (or smaller) Type L (or heavier) copper tubing.
E. Copper Pipe -- Nom 4 in. diam (or smaller) regular (or heavier) copper pipe.
3. Forms -- (Not Shown, Optional) -- Used as a form to prevent leakage of fill material during installation. Forms to be
rigid sheet material, cut to fit the contour of the penetrating item and positioned as required to accommodate the
required thickness of fill material. Forms to be removed after fill material has cured. Additional forming material may be
used concrete block wall is penetrated. A min 1/2 in. thickness of min 4 pcf mineral wool batt insulation is firmly packed
into the annulus as a permanent form and recessed from both surfaces of the wall as required to accommodate the
required thickness of fill material.
4. Fill, Void or Cavity Material* -- Sealant -- Min 1 in. thickness of fill material applied within the annulus. At the point
contact location between through penetrant and concrete, a min 1/2 in. diam bead of fill material shall be applied at the
concrete through penetrant interface. When precast concrete units are used, the fill material shall be installed within
annular space, flush with lower surface of floor. When concrete block wall is penetrated, a min 1 in. thickness of fill
material shall be applied within the annulus flush with both surfaces of wall.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC -- FS605 or FS-ONE Sealant
*Bearing the UL Classification Mark
A
Reproduced by HILTI, Inc. Courtesy of
Underwriters Laboratories, Inc.
March 12, 1999
F Rating -- 3 Hr
T Rating -- 0 Hr
A
4
2
1
C C
L
A
S
S
I
F
I
E
D
Classified by
Underwriters Laboratories, Inc.
to UL 1479 and CAN/ULC-S115
US
System No. C-AJ-1421
SECTION A-A
A
A
4B
2
3
4B
1
4A
C
C
L
A
S
S
I
F
I
E
D
Classified by
Underwriters Laboratories, Inc.
to UL 1479 and CAN/ULC-S115
US
ANSI/UL1479 (ASTM E814) CAN/ULC S115
) 5DWLQJ ² RU +U ) 5DWLQJ ² RU +U
7 5DWLQJV ² +U )7 5DWLQJV ² +U
/ 5DWLQJ $W $PELHQW ² /HVV 7KDQ
CFM/sq ft
)+ 5DWLQJ ² RU +U
/ 5DWLQJ $W ) ² /HVV 7KDQ
CFM/sq ft
)7+ 5DWLQJV ² +U 6HH ,WHP &
/ 5DWLQJ $W $PELHQW ² /HVV 7KDQ
CFM/sq ft
/ 5DWLQJ $W ) ² /HVV 7KDQ
CFM/sq ft
)ORRU RU :DOO $VVHPEO\ ² 0LQ LQ PP WKLFN UHLQIRUFHG OLJKWZHLJKW RU QRUPDO ZHLJKW SFI RU NJP
concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 6 in. (152 mm).
See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.
0HWDOOLF 6OHHYH ² 2SWLRQDO 1RP LQ PP GLDP RU VPDOOHU 6FKHGXOH RU KHDYLHU VWHHO VOHHYH FDVW RU JURXWHG LQWR
floor or wall assembly, flush with floor or wall surfaces.
7KURXJK3HQHWUDQW ² 2QH PHWDOOLF SLSH RU FRQGXLW WR EH LQVWDOOHG HLWKHU FRQFHQWULFDOO\ RU HFFHQWULFDOO\ ZLWKLQ WKH ILUHVWRS V\VWHP
The annular space between pipe, tube or conduit and periphery of opening shall be min 0 in. (0 mm) (point contact) to max 5-3/8
in. (137 mm). Pipe or conduit to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of
metallic pipes or conduits may be used:
$ 6WHHO 3LSH ² 1RP LQ PP GLDP RU VPDOOHU 6FKHGXOH RU KHDYLHU VWHHO SLSH
% ,URQ 3LSH ² 1RP LQ PP GLDP RU VPDOOHU FDVW RU GXFWLOH LURQ SLSH
& &RSSHU 3LSH ² 1RP LQ PP GLDP RU VPDOOHU 5HJXODU RU KHDYLHU FRSSHU SLSH
' &RSSHU 7XELQJ ² 1RP LQ PP GLDP RU VPDOOHU 7\SH / RU KHDYLHU FRSSHU WXELQJ
( &RQGXLW ² 1RP LQ PP GLDP RU VPDOOHU VWHHO FRQGXLW
) &RQGXLW ² 1RP LQ PP GLDP RU VPDOOHU VWHHO HOHFWULFDO PHWDOOLF WXELQJ (07
)LUHVWRS 6\VWHP ² 7KH ILUHVWRS V\VWHP VKDOO FRQVLVW RI WKH IROORZLQJ
$ 3DFNLQJ 0DWHULDO ² 0LQ LQ PP WKLFNQHVV RI PLQ SFI NJP PLQHUDO ZRRO EDWW LQVXODWLRQ ILUPO\ SDFNHG LQWR
opening as a permanent form. Packing material to be recessed from top surface of floor or from both surfaces of wall as
required to accommodate the required thickness of fill material.
% )LOO 9RLG RU &DYLW\ 0DWHULDO 6HDODQW ² 0LQ LQ PP WKLFNQHVV RI ILOO PDWHULDO DSSOLHG ZLWKLQ WKH DQQXOXV IOXVK ZLWK WRS
surface of floor or with both surfaces of wall. For 3 Hr rated assemblies, a min 1/4 in. (6 mm) diam bead of fill material shall be
applied at the concrete/pipe interface at the point contact location on the top surface of floor and on both surfaces of wall.
+,/7, &216758&7,21 &+(0,&$/6 ',9 2) +,/7, ,1& ² )621( 6HDODQW RU &3 6HOI/HYHOLQJ )LUHVWRS 6HDODQW
CP604 shall be used in floor applications only.
When CP604 is used, F Rating is 2 Hr.
*Bearing the UL Classification Mark
Reproduced by HILTI, Inc. Courtesy of
Underwriters Laboratories, Inc.
November 21, 2012
UNIT 9203
FOUR SEASONS
RESORT & RESIDENCES
VAIL, CO
JDR
CHK BY:
SCALE:
SHEET:
JOB #:
DRW BY:
TITLE:
DATE:
N/A
BJH
UNIT 9203
REMODEL
SEAL & SIGNATURE:
17006.00
2/22/17
MECHANICAL
SCHEMATICS
16 OF 22
M-300
ISSUE DATE COMMENT
CLIENT:
Tim & Nancy Buese
Unit 9203
FOUR SEASONS VAIL
1 Vail Road
VAIL, CO 81657
ARCHITECT:
Creative Design Associates
434 BROADWAY, 5TH FLOOR
NEW YORK, NY 10013
t. 212-748-8900
WESTERN US
4700 E BROMLEY LN, SUITE 105
BRIGHTON, CO 80601
t. 646-747-2171
c. 917-756-0057
dsorenson@ralcompanies.com
INTERIOR DESIGN:
Duet Design Group, LLC
901 ACOMA SUITE 200
DENVER, CO 80204
t. 303-783-9327
miranda@duetdesigngroup.com
MECH/PLUMBING ENGINEER:
Rader Engineering
PO BOX 8610
AVON, CO 80620
t. 970-845-7910
BryanH@raderengineering.com
ELECTRICAL ENGINEER:
C3S Incorporated
3212 WEST 45TH AVENUE
DENVER, CO 80211
t. 303-480-5144
theresa@c3sengineeringinc.com
LIGHTING DESIGN:
186 Lighting Design Group, Inc.
1200 BANNOCK STREET
DENVER, CO 80204
t. 303-534-5350
gmackell@186group.com
KITCHEN DESIGN:
exquisite kitchen design
601 SOUTH BROADWAY SUITE F
DENVER, CO 80209
303-282-0382
mikalo@myekdesign.com
1
FOR PERMIT
2/22/17
2/22/17
03/29/17