Loading...
HomeMy WebLinkAboutB17-0282_E000_1507064548.pdfRETAIL-1 WORK NOTES: IF EXISTING CONDUIT IS IN GOOD CONDITION AND IS 3", IT MAY BE REUSED FOR NEW SERVICE FEEDERS. FIELD INVESTIGATE AND NOTIFY ENGINEER OF RESULTS. REUSE EXISTING FEEDERS FOR RETAIL PANELS. 1 RETAIL-0 M 200A MLO 200A MLO MECH 200A MLO RDP 400A MCB N G 2 T (E) UTILITY XFMR 120/208V, 3PH, 4W M M 800A BUSWAY 120/208V, 3PH, 4W 200A/3P 200A/3P B 100A MLO 1 2 2 A 200A MLO 200/4 100/4 200/4 400/4 800N #2/0 BLDG STEEL #2/0 C.W. PIPE #1/0 SPRINKLER/GAS PIPE #1/0 GND ROD 1 OWNER PROJECT NO.: 21074.00 VAIL, COLORADO 81657 311 BRIDGE STREET LANDSCAPE SHERRY DORWARD P.O. BOX 3766 VAIL, CO 81658 ARCHITECT ARCHITECT 4240 ARCHITECTURE 3507 RINGSBY CT. STUITE 117 DENVER, CO 80216 HILL BUILDING RENOVATION 39°38'24"N 106°22'25"W STRUCTURAL MONROE NEWELL 70 BENCHMARK RD. SUITE 204 AVON, CO 81620 ENGINEER MEP DMCE ENGINEERING 5737 6TH AVE. LAKEWOOD, CO 80214 ENGINEER CIVIL ALPINE ENGINEERING, INC. 34510 HIGHWAY 6 UNIT A-9 EDWARDS, CO 81632 ENGINEER TOWN OF VAIL USE ISS.# DESCRIPTION DATE S BUILDING PERMIT ISSUE 2017-07-07 01 BUILDING DEPT COMM. 2017-08-16 1 02 PERMIT REVISIONS 2017-08-25 2 03 FOR CONSTRUCTION 2017-09-01 3 1 NO SCALE POWER ONE-LINE DIAGRAM E000 ELECTRICAL LEGEND AND NOTES 6'-8" 6'-6"MAX ELEC EQUIP 18"MAX 44" TOP OF BOX F 6"MIN F 7'-6" 48"MAX 3"MIN WALL MOUNTED F S T GENERAL NOTES: 1. DIMENSIONS ARE TO CENTER OF DEVICE WITH TRIM.A U.O.N. 2. ALL MOUNTING HEIGHTS SHALL CONFORM TO THE LATEST EDITION OF THE AMERICANS WITH DISABILITIES ACT, (ADA). 1 NO SCALE DEVICE MOUNTING HEIGHT DETAIL LOAD CENTER 48" TOP BREAKER 50" ELECTRICAL LEGEND SYMBOL RECESSED DOWN LIGHT DESCRIPTION LIGHTING WALL WASHER WALL MOUNTED FIXTURE WALL MOUNTED LINEAR FIXTURE TRACK LIGHTING SURFACE TROFFER RECESSED TROFFER FLUORESCENT STRIP LIGHT CEILING MOUNTED EXIT SIGNS, SHADING INDICATES FACE(S) ARROW(S) AS INDICATED WALL MOUNTED EXIT SIGNS, SHADING INDICATES FACE(S) ARROW(S) AS INDICATED EMERGENCY LIGHTING UNIT COMBINATION EXIT SIGN / EMERGENCY LIGHTING UNIT K KEYLESS PORCELAIN LAMP HOLDER DECORATIVE PENDANT FIRE ALARM SMOKE DETECTOR. F F F F THERMAL DETECTOR. MANUAL PULL STATION, MTD 46" A.F.F. UON. AUDIBLE / VISIBLE NOTIFICATION APPLIANCE, MTD 80" A.F.F. OR 6" BELOW CEILING, UON. VISIBLE ONLY NOTIFICATION APPLIANCE. SYMBOL DESCRIPTION DEVICES CEILING - JUNCTION BOX. J J WALL - JUNCTION BOX. NON-FUSED DISCONNECT SWITCH. FUSED DISCONNECT SWITCH. WALL-DUPLEX RECEPTACLE SLASH INDICATES ABOVE-COUNTER MOUNTING HEIGHT (TYPICAL ALL DEVICES) FLOOR-DUPLEX RECEPTACLE CEILING-MOUNT DUPLEX RECEPTACLE SHADING INDICATES SPLIT WIRED WALL-TWO DUPLEX RECEPTACLES IN TWO GANG BOX. FLOOR-TWO DUPLEX RECEPTACLES IN TWO GANG BOX CEILING-TWO DUPLEX RECEPTACLES IN TWO GANG BOX WALL-SPECIAL PURPOSE RECEPTACLE, CONFIGURATION NOTED FLOOR MOUNTED COMBO POWER / TELE / DATA OUTLET FLOOR - TELECOMMUNICATIONS OUTLET WALL - TELECOMMUNICATIONS OUTLET WALL-COAXIAL CABLE OUTLET OCCUPANCY SENSOR S3 Sa SINGLE POLE SWITCH, SUBSCRIPT INDICATES SWITCHING ZONE S4 SD SLV SOS THREE-WAY SWITCH FOUR-WAY SWITCH DIMMER SWITCH LOW VOLTAGE SWITCH OCCUPANCY SENSOR SWITCH DISTRIBUTION / RACEWAY SWITCHGEAR / SWITCHBOARD. BRANCH CIRCUIT PANELBOARD. T TRANSFORMER. LINE TYPES ( ) ( ) BOLD LINES INDICATE NEW OR RELOCATED EQUIPMENT. RELOCATED EQUIPMENT MAY INCLUDE "RL". SCREENED LINES INDICATE EXISTING EQUIPMENT TO REMAIN. ( ) DASHED LINES INDICATE FUTURE. ( ) SCREENED DASHED LINES INDICATES EQUIPMENT TO BE DEMOLISHED OR REMOVED. ONE-LINE DIAGRAM T TRANSFORMER (# = KVA). # TRANSFORMER WITH GROUND SECONDARY, KVA SIZE & VOLTAGE RATIO AS NOTED. M DISCONNECT SWITCH FUSE UTILITY METER GROUND FEEDER SCHEDULE LOAD CENTER/PANELBOARD ABBREVIATIONS A AMPERES AC ABOVE COUNTER AFCI ARC-FAULT CIRCUIT INTERRUPTED AF AMPERE FRAME, AMPERE FUSE AFF ABOVE FINISHED FLOOR AFG ABOVE FINISHED GRADE AIC AMPERES INTERRUPTING CAPACITY ANN ANNUNCIATOR AT AT AMPERE TRIP ATS AUTOMATIC TRANSFER SWITCH AWG AMERICAN WIRE GAUGE C CONDUIT CATV CABLE TELEVISION CB CIRCUIT BREAKER CCTV CLOSED CIRCUIT TELEVISION E EXISTING EC EMPTY CONDUIT EM EMERGENCY EMT ELECTRIC METALLIC TUBING EP EXPLOSION PROOF EPO EMERGENCY POWER OFF EWC ELECTRIC WATER COOLER FA FIRE ALARM FACP FIRE ALARM CONTROL PANEL G GROUND GND GROUND GFI GROUND FAULT INTERRUPTER HOA HAND / OFF / AUTOMATIC IG ISOLATED GROUND IMC INTERMEDIATE METAL CONDUIT ISC SHORT CIRCUIT CURRENT KAIC KILO-AMPERES INTERRUPTING CAPACITY KCMIL THOUSAND CIRCULAR MILLIMETERS MAX MAXIMUM MCB MAIN CIRCUIT BREAKER MCC MOTOR CONTROL CENTER MCM THOUSAND CIRCULAR MILLIMETERS MTD MOUNTED MDC MAIN DISTRIBUTION CENTER MIN MINIMUM MLO MAIN LUGS ONLY NEC NATIONAL ELECTRIC CODE N NEW NIC NOT IN CONTRACT NL NIGHT LIGHT NC NORMALLY CLOSED NO NORMALLY OPEN NTS NOT TO SCALE OC ON CENTER OFCI OWNER FURNISHED, CONTRACTOR INSTALLED OFOI OWNER FURNISHED, OWNER INSTALLED PC PULLCHAIN RGS RIGID STEEL RL RELOCATE RM REMOVE RMS ROOT MEAN SQUARE SB STANDBY SC SPLIT CIRCUIT SDP SUB-DISTRIBUTION PANEL ST SHUNT TRIP SYM SYMMETRICAL TP TAMPER PROOF TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION TYP TYPICAL UON UNLESS OTHERWISE NOTED V VOLTS VFD VARIABLE FREQUENCY DRIVE W/ WITH W/O WITH-OUT WP WEATHERPROOF XFMR TRANSFORMER 1 ### ### WORK NOTE REFERENCE MECHANICAL EQUIPMENT REFERENCE NOTE: 1. NOT ALL SYMBOLS ON THIS LEGEND ARE NOT NECESSARILY USED ON THIS PROJECT. 2. ELEVATIONS INDICATED ON LEGEND ARE TO CENTER, U.O.N. PHOTOELECTRIC SENSOR OS PC GFCI DUPLEX RECEPTACLE GFCI QUAD RECEPTACLE GENERAL PROJECT NOTES NOTE: RE: ARCHITECTURAL DRAWINGS FOR ADDITIONAL CONSTRUCTION REQUIREMENTS 1. THE CONTRACTOR SHALL PROVIDE ALL LABOR AND MATERIAL NECESSARY FOR A COMPLETE, OPERATIONAL AND PROPERLY FUNCTIONING ELECTRICAL SYSTEM 2. MATERIALS AND INSTALLATION SHALL COMPLY WITH CODES, LAWS AND ORDINANCES OF FEDERAL, STATE AND LOCAL GOVERNING BODIES HAVING JURISDICTION. 3. MATERIALS AND EQUIPMENT SHALL BE LISTED AND/OR LABELED BY U.L., ETL, CSA OR ANOTHER RECOGNIZED TESTING LAB. ALL MATERIAL, EQUIPMENT, WIRING DEVICES, ETC. SHALL BE NEW, UNLESS SPECIFICALLY INDICATED AS EXISTING TO BE REUSED. 4. THE CONTRACTOR SHALL PREPARE AND SUBMIT TO GOVERNMENTAL AGENCIES ANY SHOP DRAWINGS REQUIRED BY THESE AGENCIES FOR APPROVAL. THE CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS, GOVERNMENTAL FEES, TAXES AND LICENSES NECESSARY FOR THE PROPER EXECUTION AND COMPLETION OF THE ELECTRICAL WORK. THIS CONTRACTOR SHALL SECURE AND PAY ALL FEES AND PERMITS PERTAINING TO THIS CONTRACT, SHALL BE RESPONSIBLE FOR WORKER'S IDENTIFICATION AND BADGING, SAFETY, AND LIABILITY INSURANCE. PROVIDE BARRICADES, WARNING SIGNS, AND TRASH REMOVAL FOR THE SAFETY OF THE WORKERS UNDER THIS CONTRACTOR'S EMPLOY. 5. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT/ENGINEER/OWNER OF ANY MATERIALS OR APPARATUS BELIEVED TO BE INADEQUATE, UNSUITABLE, IN VIOLATION OF LAWS, ORDINANCES, RULES OR REGULATIONS OF AUTHORITIES HAVING JURISDICTION. 6. THE CONTRACTOR SHALL PREPARE THE DOCUMENTS, INCLUDING DRAWINGS, REQUIRED TO OBTAIN APPROVAL OF THE EQUIPMENT AND LOCATIONS OF THE DEVICES THAT COMPRISE THE FIRE ALARM LIFE SAFETY SYSTEM. WHERE REQUIRED, THE DRAWINGS AND CUT SHEETS SHALL BE PROVIDED TO A PROFESSIONAL ENGINEER FOR REVIEW AND APPROVAL. THE APPROVED DRAWINGS WILL BE STAMPED, SIGNED AND RETURNED TO E.C. TO SUBMIT TO THE BUILDING DEPARTMENT. 7. THE CONTRACTOR SHALL CAREFULLY EXAMINE THE CONTRACT DOCUMENTS, VISIT THE SITE, AND THOROUGHLY BECOME FAMILIAR WITH THE BUILDING STANDARDS, LOCAL JURISDICTIONAL CODES AND REQUIREMENTS, AND LOCAL CONDITIONS RELATING TO THE WORK. FAILURE TO DO SO WILL NOT RELIEVE THE CONTRACTOR OF THE OBLIGATIONS OF THE CONTRACT. SUBMISSION OF PROPOSAL IN CONNECTION WITH THIS WORK SHALL IMPLY THAT THE BIDDER HAS EXAMINED THE JOB SITE. NO EXTRA CHARGE WILL BE ALLOWED FOR CHANGES AS A RESULT FROM FAILURE TO EXAMINE THE JOB SITE. 8. THE CONTRACTOR SHALL PROVIDE TEMPORARY POWER AND WIRING FOR THE PERFORMANCE OF ALL TRADES, FOR THE ENTIRE PERIOD OF CONSTRUCTION AND SHALL REMOVE ALL TEMPORARY WIRING AT THE COMPLETION OF CONSTRUCTION. 9. ALL MATERIALS AND EQUIPMENT SHALL BE ERECTED, INSTALLED, CONNECTED, CLEANED, ADJUSTED, TESTED, CONDITIONED, AND PLACED IN SERVICE IN ACCORDANCE WITH THE MANUFACTURER'S DIRECTIONS AND RECOMMENDATIONS. 10. ALL CUTTING, DRILLING AND PATCHING OF MASONRY, STEEL OR IRON WORK BELONGING TO THE BUILDING MUST BE DONE BY THIS CONTRACTOR IN ORDER THAT HIS WORK MAY BE PROPERLY INSTALLED, BUT UNDER NO CONDITIONS MAY STRUCTURAL WORK BE CUT, EXCEPT AT THE DIRECTION OF THE ARCHITECT-DESIGNER OR THEIR REPRESENTATIVE. 11. ALL WORK REQUIRED FOR THE INSTALLATION AS SHOWN ON DRAWINGS INCLUDING LABOR, EQUIPMENT AND MATERIALS SHALL BE IN STRICT COMPLIANCE WITH THE BUILDING STANDARDS. 12. PROVIDE COMPLETE METAL RACEWAY SYSTEMS AND ENCLOSURES FOR ALL WIRING THROUGHOUT THE EXTENT OF THE REQUIRED SYSTEM. 13. ALL TELE/ DATA BOXES SHALL BE PROVIDED WITH A 1/2” CONDUIT AND BUSHING WITH PULL STRING RUN TO ACCESSIBLE LOCATION. ELECTRICAL METALLIC TUBING (EMT) SHALL BE USED FOR ALL WALL OUTLETS & TELEPHONE WIRING RUNNING IN WALLS OR ABOVE HARD CEILINGS. 14. ALL RECEPTACLES NOTED AS ISOLATED GROUND (IG) OR DEDICATED OR CIRCUITED AS DEDICATED SHALL BE PROVIDED WITH A DEDICATED GROUND AND NEUTRAL. 15. MINIMUM CONDUIT SIZE SHALL BE 3/4" UNLESS OTHERWISE INDICATED. CONDUITS LARGER THAN 2" DIAMETER OR CONDUITS OF ANY SIZE ROUTED OUTDOORS SHALL BE INTERMEDIATE METAL CONDUIT (IMC). 16. FLEXIBLE CONDUIT CONNECTIONS TO RECESSED LIGHTING FIXTURES SHALL BE MADE WITH FLEXIBLE STEEL CONDUIT, 3/8 INCH MINIMUM. 17. FINAL CONNECTIONS TO MOTORS SHALL BE MADE WITH LIQUID TIGHT FLEXIBLE STEEL CONDUIT, 1/2 INCH MINIMUM. 18. WIRE NO. 8 AND SMALLER INSTALLED IN DRY LOCATIONS SHALL BE TYPE THWN OR THHN THERMOPLASTIC 600V INSULATED COPPER CONDUCTORS. NO WIRE SMALLER THAN NO.12 SHALL BE USED FOR LIGHTING OR POWER WIRING. WIRE NO. 8 AND LARGER SHALL BE STRANDED. ALL CONDUCTORS INSTALLED IN EXTERIOR OR WET LOCATIONS SHALL BE TYPE THWN 600V INSULATED COPPER CONDUCTORS. 19. ALL NEW CIRCUIT BREAKERS FOR NEW PANELBOARDS SHALL MATCH NEW BUILDING STANDARD PANELBOARD MANUFACTURER AND BREAKER TYPE. THE CONTRACTOR SHALL PROVIDE NEW ACCURATE AND DETAILED TYPE WRITTEN PANEL DIRECTORIES PER NEC 408.4 FOR ALL NEW PANELS. NUMBERED CIRCUITS ARE FOR CONVENIENCE OF DESIGN ONLY. E.C. TO FIELD VERIFY ACTUAL CIRCUIT NUMBERS USED AND CORRECTLY INDICATE ON "AS-BUILT" DRAWINGS. THE E.C. SHALL REMOVE ALL ABANDONED CIRCUITS. 20. PROVIDE #10 FOR BRANCH CIRCUITS OVER 75' AT 120V. E.C. TO FIELD VERIFY BRANCH CIRCUIT LENGTHS AND SIZE CONDUCTORS FOR VOLTAGE DROP PER NEC. 21. EACH SWITCH, LIGHT, RECEPTACLE AND ALL OTHER DEVICES SHALL BE PROVIDED AND INSTALLED WITH A GALVANIZED OR SHERARDIZED PRESSED STEEL JUNCTION BOX OF NOT LESS THAN NO. 14 U.S. GAUGE STEEL. CONDUITS SHALL BE FASTENED WITH LOCKNUTS AND BUSHINGS AND ALL UNUSED KNOCKOUTS MUST BE LEFT SEALED. THERE MUST BE SUFFICIENT ROOM FOR WIRES AND BUSHINGS AND DEEP BOXES SHALL BE INSTALLED WHERE REQUIRED. BOXES SHALL BE SECURELY AND ADEQUATELY SUPPORTED. 22. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL SPECIAL OUTLET BOXES THAT MAY BE REQUIRED TO ENCLOSE RECEPTACLES. 23. PROVIDE LOCAL DISCONNECT SWITCHES FOR ALL MOTORS (PLENUM APPROVED WHERE REQUIRED). 25. THE E.C. SHALL INCLUDE IN HIS COST THE REMOVAL OF ALL EXISTING ELECTRICAL DEVICES, CONDUITS, FIXTURES 26. AND EQUIPMENT THAT IS NOT TO BE REUSED DISCARD ALL EQUIPMENT AS REQUIRED. E.C. SHALL BE RESPONSIBLE FOR DISCONNECTING PRIMARY SERVICE AND TEMPORARY POWER. 27. PROVIDE WARRANTY GUARANTEED FOR A PERIOD OF ONE YEAR AFTER COMPLETION AND ACCEPTANCE. REPLACE ALL DEFECTIVE WORKMANSHIP, EQUIPMENT AND MATERIALS WITHOUT ADDITIONAL CHARGES. 28. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR THE SAFEKEEPING OF HIS/HER OWN PROPERTY ON THE JOB SITE. THE OWNER OR TENANT ASSUMES NO RESPONSIBILITY FOR PROTECTION OF THIS CONTRACTOR'S PROPERTY AGAINST FIRE, THEFT, OR ENVIRONMENTAL CONDITIONS. 29. WHERE CONDUIT, CABLES, DUCTWORK OR PIPING PASSES THROUGH FIRE RATED FLOORS, WALLS, OR PARTITIONS, THE SLEEVES SHALL BE COMPLETELY SEALED WITH A FIRE STOP MATERIAL THAT IS U.L. LISTED (EQUAL TO DOW CORNING) AND ACCEPTED BY THE BUILDING DEPARTMENT AND FIRE DEPARTMENT AS BEING SUITABLE FOR THE SERVICE. THIS MATERIAL SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S PUBLISHED INSTRUCTIONS IN ORDER TO MAINTAIN THE FIRE RATING OF THE PENETRATED WALL, FLOOR, OR PARTITION. INSTALLATION SHALL BE A THROUGH-PENETRATION FIRESTOP SYSTEM INSTALLED AS TESTED IN ACCORDANCE WITH ASTM AND UL . THE FIRE RATING SHALL MATCH THE RATING OF THE BARRIER BEING PENETRATED. 30. SUBMIT AN ELECTRONIC COPY OR SIX (6) SETS OF SHOP DRAWINGS, CONTROL DIAGRAMS, AND EQUIPMENT CUTS TO THE ENGINEER FOR APPROVAL PRIOR TO STARTING RELATED WORK. SHOP DRAWINGS SHALL INCLUDE MANUFACTURER'S NAMES, CATALOG NUMBERS, CUTS, DIAGRAMS AND OTHER SUCH DESCRIPTIVE DATA AS MAY BE REQUIRED TO IDENTIFY AND REVIEW THE EQUIPMENT. SUBMITTALS SHALL BE IN LOGICAL GROUPS, PARTIAL SUBMITTALS WILL NOT BE REVIEWED. 31. UPON COMPLETION OF CONSTRUCTION, SUPPLY THE ENGINEER WITH ONE COMPLETE SET OF FULL SIZE AS-BUILT DRAWINGS. PROVIDE THE OWNER WITH THREE (3) SETS OF OPERATION AND MAINTENANCE MANUALS FOR EACH TYPE OF EQUIPMENT INSTALLED. 32. THIS CONTRACTOR SHALL ASSUME ALL ADDED EXPENSES TO ALL TRADES ASSOCIATED WITH THE INSTALLATION OF SUBMITTED AND APPROVED ALTERNATE EQUIPMENT. 33. THE CONTRACTOR SHALL COORDINATE THE LAYOUT OF THE FIRE ROOM WITH ALL OTHER DISCIPLINES, ESPECIALLY THE FIRE ALARM AND FIRE PROTECTION DESIGN-BUILD CONTRACTORS PRIOR TO ANY WORK. 34. IF ANY CHANGES ARE MADE TO ACCOMMODATE FIELD CONDITIONS NOTIFY THE ENGINEER IMMEDIATELY OF WHAT THE CHANGES WERE, THE REASON FOR THE CHANGES, AND THE COST IMPACTS. 35. LOCATE ALL ELECTRICAL SWITCHBOARDS, PANELBOARDS AND ELECTRICAL DISTRIBUTION EQUIPMENT IN DEDICATED SPACES AND PROTECTED FROM DAMAGE WITH ADEQUATE WORKING CLEARANCE ACCORDANCE WITH NEC 110 REQUIREMENTS. PROVIDE PROTECTION FROM ANY FOREIGN SYSTEM INSTALLED ABOVE THE DEDICATED EQUIPMENT SPACE PER NEC 110.26(E). 36. LIGHTING CONTROLS TO INCLUDE TIMECLOCK/PHOTOCELL FOR EXTERIOR LIGHTING WITH MANUAL OVERRIDE CAPABILITY, OCCUPANCY SENSORS, DIMMING SWITCHES, AND TOGGLE SWITCHES. 10/03/17