HomeMy WebLinkAboutB17-0282_E000_1507064548.pdfRETAIL-1
WORK NOTES:
IF EXISTING CONDUIT IS IN GOOD CONDITION AND IS 3", IT MAY BE REUSED FOR NEW
SERVICE FEEDERS. FIELD INVESTIGATE AND NOTIFY ENGINEER OF RESULTS.
REUSE EXISTING FEEDERS FOR RETAIL PANELS.
1
RETAIL-0
M
200A
MLO
200A
MLO
MECH
200A
MLO
RDP
400A
MCB
N
G
2
T
(E) UTILITY XFMR
120/208V, 3PH, 4W
M M
800A BUSWAY 120/208V, 3PH, 4W
200A/3P 200A/3P
B
100A
MLO
1
2
2
A
200A
MLO
200/4 100/4 200/4
400/4
800N #2/0 BLDG STEEL
#2/0 C.W. PIPE
#1/0 SPRINKLER/GAS PIPE
#1/0 GND ROD
1
OWNER
PROJECT NO.: 21074.00
VAIL, COLORADO
81657
311 BRIDGE
STREET
LANDSCAPE SHERRY DORWARD
P.O. BOX 3766
VAIL, CO 81658
ARCHITECT
ARCHITECT 4240 ARCHITECTURE
3507 RINGSBY CT. STUITE 117
DENVER, CO 80216
HILL BUILDING
RENOVATION
39°38'24"N
106°22'25"W
STRUCTURAL MONROE NEWELL
70 BENCHMARK RD. SUITE 204
AVON, CO 81620
ENGINEER
MEP DMCE ENGINEERING
5737 6TH AVE.
LAKEWOOD, CO 80214
ENGINEER
CIVIL ALPINE ENGINEERING, INC.
34510 HIGHWAY 6 UNIT A-9
EDWARDS, CO 81632
ENGINEER
TOWN OF VAIL USE
ISS.# DESCRIPTION DATE
S BUILDING PERMIT ISSUE 2017-07-07
01 BUILDING DEPT COMM. 2017-08-16
1
02 PERMIT REVISIONS 2017-08-25
2
03 FOR CONSTRUCTION 2017-09-01
3
1
NO SCALE
POWER ONE-LINE DIAGRAM
E000
ELECTRICAL
LEGEND AND
NOTES
6'-8"
6'-6"MAX
ELEC
EQUIP
18"MAX
44"
TOP OF BOX
F
6"MIN
F
7'-6"
48"MAX
3"MIN
WALL
MOUNTED
F
S
T
GENERAL NOTES:
1. DIMENSIONS ARE TO CENTER OF DEVICE WITH TRIM.A U.O.N.
2. ALL MOUNTING HEIGHTS SHALL CONFORM TO THE LATEST EDITION
OF THE AMERICANS WITH DISABILITIES ACT, (ADA).
1 NO SCALE
DEVICE MOUNTING HEIGHT DETAIL
LOAD
CENTER
48"
TOP BREAKER
50"
ELECTRICAL LEGEND
SYMBOL
RECESSED DOWN LIGHT
DESCRIPTION
LIGHTING
WALL WASHER
WALL MOUNTED FIXTURE
WALL MOUNTED LINEAR FIXTURE
TRACK LIGHTING
SURFACE TROFFER
RECESSED TROFFER
FLUORESCENT STRIP LIGHT
CEILING MOUNTED EXIT SIGNS, SHADING
INDICATES FACE(S) ARROW(S) AS
INDICATED
WALL MOUNTED EXIT SIGNS, SHADING
INDICATES FACE(S) ARROW(S) AS
INDICATED
EMERGENCY LIGHTING UNIT
COMBINATION EXIT SIGN / EMERGENCY
LIGHTING UNIT
K KEYLESS PORCELAIN LAMP HOLDER
DECORATIVE PENDANT
FIRE ALARM
SMOKE DETECTOR.
F
F
F
F
THERMAL DETECTOR.
MANUAL PULL STATION, MTD 46" A.F.F. UON.
AUDIBLE / VISIBLE NOTIFICATION
APPLIANCE, MTD 80" A.F.F. OR 6" BELOW
CEILING, UON.
VISIBLE ONLY NOTIFICATION APPLIANCE.
SYMBOL DESCRIPTION
DEVICES
CEILING - JUNCTION BOX.
J
J WALL - JUNCTION BOX.
NON-FUSED DISCONNECT SWITCH.
FUSED DISCONNECT SWITCH.
WALL-DUPLEX RECEPTACLE
SLASH INDICATES ABOVE-COUNTER
MOUNTING HEIGHT (TYPICAL ALL DEVICES)
FLOOR-DUPLEX RECEPTACLE
CEILING-MOUNT DUPLEX RECEPTACLE
SHADING INDICATES SPLIT WIRED
WALL-TWO DUPLEX RECEPTACLES IN TWO
GANG BOX.
FLOOR-TWO DUPLEX RECEPTACLES IN TWO
GANG BOX
CEILING-TWO DUPLEX RECEPTACLES IN
TWO GANG BOX
WALL-SPECIAL PURPOSE RECEPTACLE,
CONFIGURATION NOTED
FLOOR MOUNTED COMBO POWER / TELE /
DATA OUTLET
FLOOR - TELECOMMUNICATIONS OUTLET
WALL - TELECOMMUNICATIONS OUTLET
WALL-COAXIAL CABLE OUTLET
OCCUPANCY SENSOR
S3
Sa
SINGLE POLE SWITCH, SUBSCRIPT
INDICATES SWITCHING ZONE
S4
SD
SLV
SOS
THREE-WAY SWITCH
FOUR-WAY SWITCH
DIMMER SWITCH
LOW VOLTAGE SWITCH
OCCUPANCY SENSOR SWITCH
DISTRIBUTION / RACEWAY
SWITCHGEAR / SWITCHBOARD.
BRANCH CIRCUIT PANELBOARD.
T
TRANSFORMER.
LINE TYPES
( )
( )
BOLD LINES INDICATE NEW OR RELOCATED
EQUIPMENT. RELOCATED EQUIPMENT MAY
INCLUDE "RL".
SCREENED LINES INDICATE EXISTING
EQUIPMENT TO REMAIN.
( )
DASHED LINES INDICATE FUTURE.
( )
SCREENED DASHED LINES INDICATES
EQUIPMENT TO BE DEMOLISHED OR
REMOVED.
ONE-LINE DIAGRAM
T
TRANSFORMER (# = KVA).
#
TRANSFORMER WITH GROUND
SECONDARY, KVA SIZE & VOLTAGE RATIO
AS NOTED.
M
DISCONNECT SWITCH
FUSE
UTILITY METER
GROUND
FEEDER SCHEDULE
LOAD CENTER/PANELBOARD
ABBREVIATIONS
A AMPERES
AC ABOVE COUNTER
AFCI ARC-FAULT CIRCUIT INTERRUPTED
AF AMPERE FRAME, AMPERE FUSE
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AIC AMPERES INTERRUPTING CAPACITY
ANN ANNUNCIATOR
AT AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AWG AMERICAN WIRE GAUGE
C CONDUIT
CATV CABLE TELEVISION
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
E EXISTING
EC EMPTY CONDUIT
EM EMERGENCY
EMT ELECTRIC METALLIC TUBING
EP EXPLOSION PROOF
EPO EMERGENCY POWER OFF
EWC ELECTRIC WATER COOLER
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
G GROUND
GND GROUND
GFI GROUND FAULT INTERRUPTER
HOA HAND / OFF / AUTOMATIC
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
ISC SHORT CIRCUIT CURRENT
KAIC KILO-AMPERES INTERRUPTING CAPACITY
KCMIL THOUSAND CIRCULAR MILLIMETERS
MAX MAXIMUM
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MCM THOUSAND CIRCULAR MILLIMETERS
MTD MOUNTED
MDC MAIN DISTRIBUTION CENTER
MIN MINIMUM
MLO MAIN LUGS ONLY
NEC NATIONAL ELECTRIC CODE
N NEW
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NC NORMALLY CLOSED
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OFCI OWNER FURNISHED, CONTRACTOR
INSTALLED
OFOI OWNER FURNISHED, OWNER INSTALLED
PC PULLCHAIN
RGS RIGID STEEL
RL RELOCATE
RM REMOVE
RMS ROOT MEAN SQUARE
SB STANDBY
SC SPLIT CIRCUIT
SDP SUB-DISTRIBUTION PANEL
ST SHUNT TRIP
SYM SYMMETRICAL
TP TAMPER PROOF
TVSS TRANSIENT VOLTAGE SURGE
SUPPRESSION
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
V VOLTS
VFD VARIABLE FREQUENCY DRIVE
W/ WITH
W/O WITH-OUT
WP WEATHERPROOF
XFMR TRANSFORMER
1
###
###
WORK NOTE REFERENCE
MECHANICAL EQUIPMENT REFERENCE
NOTE:
1. NOT ALL SYMBOLS ON THIS LEGEND ARE NOT
NECESSARILY USED ON THIS PROJECT.
2. ELEVATIONS INDICATED ON LEGEND ARE TO CENTER,
U.O.N.
PHOTOELECTRIC SENSOR
OS
PC
GFCI DUPLEX RECEPTACLE
GFCI QUAD RECEPTACLE
GENERAL PROJECT NOTES
NOTE: RE: ARCHITECTURAL DRAWINGS FOR ADDITIONAL CONSTRUCTION REQUIREMENTS
1. THE CONTRACTOR SHALL PROVIDE ALL LABOR AND MATERIAL NECESSARY FOR A COMPLETE,
OPERATIONAL AND PROPERLY FUNCTIONING ELECTRICAL SYSTEM
2. MATERIALS AND INSTALLATION SHALL COMPLY WITH CODES, LAWS AND ORDINANCES OF
FEDERAL, STATE AND LOCAL GOVERNING BODIES HAVING JURISDICTION.
3. MATERIALS AND EQUIPMENT SHALL BE LISTED AND/OR LABELED BY U.L., ETL, CSA OR ANOTHER
RECOGNIZED TESTING LAB. ALL MATERIAL, EQUIPMENT, WIRING DEVICES, ETC. SHALL BE NEW,
UNLESS SPECIFICALLY INDICATED AS EXISTING TO BE REUSED.
4. THE CONTRACTOR SHALL PREPARE AND SUBMIT TO GOVERNMENTAL AGENCIES ANY SHOP
DRAWINGS REQUIRED BY THESE AGENCIES FOR APPROVAL. THE CONTRACTOR SHALL SECURE
AND PAY FOR ALL PERMITS, GOVERNMENTAL FEES, TAXES AND LICENSES NECESSARY FOR THE
PROPER EXECUTION AND COMPLETION OF THE ELECTRICAL WORK. THIS CONTRACTOR SHALL
SECURE AND PAY ALL FEES AND PERMITS PERTAINING TO THIS CONTRACT, SHALL BE
RESPONSIBLE FOR WORKER'S IDENTIFICATION AND BADGING, SAFETY, AND LIABILITY
INSURANCE. PROVIDE BARRICADES, WARNING SIGNS, AND TRASH REMOVAL FOR THE SAFETY
OF THE WORKERS UNDER THIS CONTRACTOR'S EMPLOY.
5. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT/ENGINEER/OWNER OF ANY MATERIALS OR
APPARATUS BELIEVED TO BE INADEQUATE, UNSUITABLE, IN VIOLATION OF LAWS, ORDINANCES,
RULES OR REGULATIONS OF AUTHORITIES HAVING JURISDICTION.
6. THE CONTRACTOR SHALL PREPARE THE DOCUMENTS, INCLUDING DRAWINGS, REQUIRED TO
OBTAIN APPROVAL OF THE EQUIPMENT AND LOCATIONS OF THE DEVICES THAT COMPRISE THE
FIRE ALARM LIFE SAFETY SYSTEM. WHERE REQUIRED, THE DRAWINGS AND CUT SHEETS SHALL
BE PROVIDED TO A PROFESSIONAL ENGINEER FOR REVIEW AND APPROVAL. THE APPROVED
DRAWINGS WILL BE STAMPED, SIGNED AND RETURNED TO E.C. TO SUBMIT TO THE BUILDING
DEPARTMENT.
7. THE CONTRACTOR SHALL CAREFULLY EXAMINE THE CONTRACT DOCUMENTS, VISIT THE SITE,
AND THOROUGHLY BECOME FAMILIAR WITH THE BUILDING STANDARDS, LOCAL JURISDICTIONAL
CODES AND REQUIREMENTS, AND LOCAL CONDITIONS RELATING TO THE WORK. FAILURE TO
DO SO WILL NOT RELIEVE THE CONTRACTOR OF THE OBLIGATIONS OF THE CONTRACT.
SUBMISSION OF PROPOSAL IN CONNECTION WITH THIS WORK SHALL IMPLY THAT THE BIDDER
HAS EXAMINED THE JOB SITE. NO EXTRA CHARGE WILL BE ALLOWED FOR CHANGES AS A
RESULT FROM FAILURE TO EXAMINE THE JOB SITE.
8. THE CONTRACTOR SHALL PROVIDE TEMPORARY POWER AND WIRING FOR THE PERFORMANCE
OF ALL TRADES, FOR THE ENTIRE PERIOD OF CONSTRUCTION AND SHALL REMOVE ALL
TEMPORARY WIRING AT THE COMPLETION OF CONSTRUCTION.
9. ALL MATERIALS AND EQUIPMENT SHALL BE ERECTED, INSTALLED, CONNECTED, CLEANED,
ADJUSTED, TESTED, CONDITIONED, AND PLACED IN SERVICE IN ACCORDANCE WITH THE
MANUFACTURER'S DIRECTIONS AND RECOMMENDATIONS.
10. ALL CUTTING, DRILLING AND PATCHING OF MASONRY, STEEL OR IRON WORK BELONGING TO
THE BUILDING MUST BE DONE BY THIS CONTRACTOR IN ORDER THAT HIS WORK MAY BE
PROPERLY INSTALLED, BUT UNDER NO CONDITIONS MAY STRUCTURAL WORK BE CUT, EXCEPT
AT THE DIRECTION OF THE ARCHITECT-DESIGNER OR THEIR REPRESENTATIVE.
11. ALL WORK REQUIRED FOR THE INSTALLATION AS SHOWN ON DRAWINGS INCLUDING LABOR,
EQUIPMENT AND MATERIALS SHALL BE IN STRICT COMPLIANCE WITH THE BUILDING
STANDARDS.
12. PROVIDE COMPLETE METAL RACEWAY SYSTEMS AND ENCLOSURES FOR ALL WIRING
THROUGHOUT THE EXTENT OF THE REQUIRED SYSTEM.
13. ALL TELE/ DATA BOXES SHALL BE PROVIDED WITH A 1/2” CONDUIT AND BUSHING WITH PULL
STRING RUN TO ACCESSIBLE LOCATION. ELECTRICAL METALLIC TUBING (EMT) SHALL BE USED
FOR ALL WALL OUTLETS & TELEPHONE WIRING RUNNING IN WALLS OR ABOVE HARD CEILINGS.
14. ALL RECEPTACLES NOTED AS ISOLATED GROUND (IG) OR DEDICATED OR CIRCUITED AS
DEDICATED SHALL BE PROVIDED WITH A DEDICATED GROUND AND NEUTRAL.
15. MINIMUM CONDUIT SIZE SHALL BE 3/4" UNLESS OTHERWISE INDICATED. CONDUITS LARGER
THAN 2" DIAMETER OR CONDUITS OF ANY SIZE ROUTED OUTDOORS SHALL BE INTERMEDIATE
METAL CONDUIT (IMC).
16. FLEXIBLE CONDUIT CONNECTIONS TO RECESSED LIGHTING FIXTURES SHALL BE MADE WITH
FLEXIBLE STEEL CONDUIT, 3/8 INCH MINIMUM.
17. FINAL CONNECTIONS TO MOTORS SHALL BE MADE WITH LIQUID TIGHT FLEXIBLE STEEL
CONDUIT, 1/2 INCH MINIMUM.
18. WIRE NO. 8 AND SMALLER INSTALLED IN DRY LOCATIONS SHALL BE TYPE THWN OR THHN
THERMOPLASTIC 600V INSULATED COPPER CONDUCTORS. NO WIRE SMALLER THAN NO.12
SHALL BE USED FOR LIGHTING OR POWER WIRING. WIRE NO. 8 AND LARGER SHALL BE
STRANDED. ALL CONDUCTORS INSTALLED IN EXTERIOR OR WET LOCATIONS SHALL BE TYPE
THWN 600V INSULATED COPPER CONDUCTORS.
19. ALL NEW CIRCUIT BREAKERS FOR NEW PANELBOARDS SHALL MATCH NEW BUILDING STANDARD
PANELBOARD MANUFACTURER AND BREAKER TYPE. THE CONTRACTOR SHALL PROVIDE NEW
ACCURATE AND DETAILED TYPE WRITTEN PANEL DIRECTORIES PER NEC 408.4 FOR ALL NEW
PANELS. NUMBERED CIRCUITS ARE FOR CONVENIENCE OF DESIGN ONLY. E.C. TO FIELD VERIFY
ACTUAL CIRCUIT NUMBERS USED AND CORRECTLY INDICATE ON "AS-BUILT" DRAWINGS. THE
E.C. SHALL REMOVE ALL ABANDONED CIRCUITS.
20. PROVIDE #10 FOR BRANCH CIRCUITS OVER 75' AT 120V. E.C. TO FIELD VERIFY BRANCH CIRCUIT
LENGTHS AND SIZE CONDUCTORS FOR VOLTAGE DROP PER NEC.
21. EACH SWITCH, LIGHT, RECEPTACLE AND ALL OTHER DEVICES SHALL BE PROVIDED AND
INSTALLED WITH A GALVANIZED OR SHERARDIZED PRESSED STEEL JUNCTION BOX OF NOT
LESS THAN NO. 14 U.S. GAUGE STEEL. CONDUITS SHALL BE FASTENED WITH LOCKNUTS AND
BUSHINGS AND ALL UNUSED KNOCKOUTS MUST BE LEFT SEALED. THERE MUST BE SUFFICIENT
ROOM FOR WIRES AND BUSHINGS AND DEEP BOXES SHALL BE INSTALLED WHERE REQUIRED.
BOXES SHALL BE SECURELY AND ADEQUATELY SUPPORTED.
22. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL SPECIAL OUTLET BOXES THAT MAY BE
REQUIRED TO ENCLOSE RECEPTACLES.
23. PROVIDE LOCAL DISCONNECT SWITCHES FOR ALL MOTORS (PLENUM APPROVED WHERE
REQUIRED).
25. THE E.C. SHALL INCLUDE IN HIS COST THE REMOVAL OF ALL EXISTING ELECTRICAL DEVICES,
CONDUITS, FIXTURES
26. AND EQUIPMENT THAT IS NOT TO BE REUSED DISCARD ALL EQUIPMENT AS REQUIRED. E.C.
SHALL BE RESPONSIBLE FOR DISCONNECTING PRIMARY SERVICE AND TEMPORARY POWER.
27. PROVIDE WARRANTY GUARANTEED FOR A PERIOD OF ONE YEAR AFTER COMPLETION AND
ACCEPTANCE. REPLACE ALL DEFECTIVE WORKMANSHIP, EQUIPMENT AND MATERIALS WITHOUT
ADDITIONAL CHARGES.
28. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR THE SAFEKEEPING OF HIS/HER OWN PROPERTY
ON THE JOB SITE. THE OWNER OR TENANT ASSUMES NO RESPONSIBILITY FOR PROTECTION OF
THIS CONTRACTOR'S PROPERTY AGAINST FIRE, THEFT, OR ENVIRONMENTAL CONDITIONS.
29. WHERE CONDUIT, CABLES, DUCTWORK OR PIPING PASSES THROUGH FIRE RATED FLOORS,
WALLS, OR PARTITIONS, THE SLEEVES SHALL BE COMPLETELY SEALED WITH A FIRE STOP
MATERIAL THAT IS U.L. LISTED (EQUAL TO DOW CORNING) AND ACCEPTED BY THE BUILDING
DEPARTMENT AND FIRE DEPARTMENT AS BEING SUITABLE FOR THE SERVICE. THIS MATERIAL
SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S PUBLISHED INSTRUCTIONS IN
ORDER TO MAINTAIN THE FIRE RATING OF THE PENETRATED WALL, FLOOR, OR PARTITION.
INSTALLATION SHALL BE A THROUGH-PENETRATION FIRESTOP SYSTEM INSTALLED AS TESTED IN
ACCORDANCE WITH ASTM AND UL . THE FIRE RATING SHALL MATCH THE RATING OF THE BARRIER
BEING PENETRATED.
30. SUBMIT AN ELECTRONIC COPY OR SIX (6) SETS OF SHOP DRAWINGS, CONTROL DIAGRAMS, AND
EQUIPMENT CUTS TO THE ENGINEER FOR APPROVAL PRIOR TO STARTING RELATED WORK. SHOP
DRAWINGS SHALL INCLUDE MANUFACTURER'S NAMES, CATALOG NUMBERS, CUTS, DIAGRAMS
AND OTHER SUCH DESCRIPTIVE DATA AS MAY BE REQUIRED TO IDENTIFY AND REVIEW THE
EQUIPMENT. SUBMITTALS SHALL BE IN LOGICAL GROUPS, PARTIAL SUBMITTALS WILL NOT BE
REVIEWED.
31. UPON COMPLETION OF CONSTRUCTION, SUPPLY THE ENGINEER WITH ONE COMPLETE SET OF
FULL SIZE AS-BUILT DRAWINGS. PROVIDE THE OWNER WITH THREE (3) SETS OF OPERATION AND
MAINTENANCE MANUALS FOR EACH TYPE OF EQUIPMENT INSTALLED.
32. THIS CONTRACTOR SHALL ASSUME ALL ADDED EXPENSES TO ALL TRADES ASSOCIATED WITH
THE INSTALLATION OF SUBMITTED AND APPROVED ALTERNATE EQUIPMENT.
33. THE CONTRACTOR SHALL COORDINATE THE LAYOUT OF THE FIRE ROOM WITH ALL OTHER
DISCIPLINES, ESPECIALLY THE FIRE ALARM AND FIRE PROTECTION DESIGN-BUILD CONTRACTORS
PRIOR TO ANY WORK.
34. IF ANY CHANGES ARE MADE TO ACCOMMODATE FIELD CONDITIONS NOTIFY THE ENGINEER
IMMEDIATELY OF WHAT THE CHANGES WERE, THE REASON FOR THE CHANGES, AND THE COST
IMPACTS.
35. LOCATE ALL ELECTRICAL SWITCHBOARDS, PANELBOARDS AND ELECTRICAL DISTRIBUTION
EQUIPMENT IN DEDICATED SPACES AND PROTECTED FROM DAMAGE WITH ADEQUATE WORKING
CLEARANCE ACCORDANCE WITH NEC 110 REQUIREMENTS. PROVIDE PROTECTION FROM ANY
FOREIGN SYSTEM INSTALLED ABOVE THE DEDICATED EQUIPMENT SPACE PER NEC 110.26(E).
36. LIGHTING CONTROLS TO INCLUDE TIMECLOCK/PHOTOCELL FOR EXTERIOR LIGHTING WITH
MANUAL OVERRIDE CAPABILITY, OCCUPANCY SENSORS, DIMMING SWITCHES, AND TOGGLE
SWITCHES.
10/03/17