HomeMy WebLinkAboutB17-0282_M002_1507064793.pdfSPIROVENT AIR
NO SCALE
BOILER PIPING SCHEMATIC
P-2
4"Ø PVC
P-4
IWH-1
4"Ø CPVC OR CODE
P-3
SEPARATOR
FLUID POWER ENERGY
MODEL 2012 3-WAY
THERMOSTATIC VALVE
APPROVED PVC VENT, TYP.
EXPANSION TANK (ET-1)
SEE PLBG.
CLOSE COUPLE MAX. 6" SEPARATION SUPPLY AND RETURNS
TO SNOWMELT AND RADIANT FLOOR HEAT LOOP. SEQUENCE
THESE ITEMS IN ORDER SHOWN.
INSULATE ALL PIPING PER 2012 I.E.C.C.REQUIREMENTS.
SIZE ALL BALANCING VALVES TO 12" MIN. 60" MAX. WATER
PRESSURE DROP.
NOTE:
1.
2.
3.
PUMP SHALL CYCLE ON THRU RELAY
FROM END SWITCHES IN MANIFOLDS
P-6
PROVIDE DOMESTIC WATER HEATING
PRIORITY CALL TO BOILER & SHUT OFF P1
CONCENTRIC VENT
KIT THRU WALL, TYP
(E)BOILER (N)B-1
GAS
CA, TYP.
6" MAX., TYP.
TYP.
FIRST FLOOR
BASEMENT
SECOND FLOOR
THIRD FLOOR
(E)BOILER
P-1
SNOWMELT
MANIFOLD #3
SNOWMELT
MANIFOLD #2
SNOWMELT
MANIFOLD #4
SNOWMELT
MANIFOLD #5
SNOWMELT
MANIFOLD #6
SNOWMELT
MANIFOLD #7
SNOWMELT
MANIFOLD #8
SNOWMELT
MANIFOLD #9
PRV MAKE-UP WATER
AV
GF-1
ET-1
P-5
(E)CIRC
PUMP
(E)CIRC
PUMP
SNOWMELT
MANIFOLD #1
RADIANT
MANIFOLD #2
RADIANT
MANIFOLD #8
RADIANT
MANIFOLD #1
RADIANT
MANIFOLD #3
RADIANT
MANIFOLD #4
RADIANT
MANIFOLD #5
RADIANT
MANIFOLD #6
RADIANT
MANIFOLD #7
RADIANT
MANIFOLD #9
RADIANT
MANIFOLD #10
RADIANT
MANIFOLD #11
2" 2-1/2" 2-1/2"
2"
2"
1-1/4"
2"
3/4"
1-1/2"
1-1/2"
1"
2"
3/4"
HX-1: TRIANGLE
TUBE TTP3-40
OWNER
PROJECT NO.: 21074.00
VAIL, COLORADO
81657
311 BRIDGE
STREET
LANDSCAPE SHERRY DORWARD
P.O. BOX 3766
VAIL, CO 81658
ARCHITECT
ARCHITECT 4240 ARCHITECTURE
3507 RINGSBY CT. STUITE 117
DENVER, CO 80216
HILL BUILDING
RENOVATION
39°38'24"N
106°22'25"W
STRUCTURAL MONROE NEWELL
70 BENCHMARK RD. SUITE 204
AVON, CO 81620
ENGINEER
MEP DMCE ENGINEERING
5737 6TH AVE.
LAKEWOOD, CO 80214
ENGINEER
CIVIL ALPINE ENGINEERING, INC.
34510 HIGHWAY 6 UNIT A-9
EDWARDS, CO 81632
ENGINEER
TOWN OF VAIL USE
ISS.# DESCRIPTION DATE
S BUILDING PERMIT ISSUE 2017-07-07
01 BUILDING DEPT COMM. 2017-08-16
1
02 PERMIT REVISIONS 2017-08-25
2
03 FOR CONSTRUCTION 2017-09-01
3
M001
MECHANICAL
COVER SHEET
S
SPECIFIED MANUFACTURER / MODEL
NECESSARILY USED ON THIS PROJECT.
NOTE: NOT ALL VALVES ON THIS LIST ARE
DESCRIPTION SYMBOL EQUALS BY
LEGEND SPECIFICATION LIST
BALL VALVE
AUTO FLOW CONTROL VALVE
CHECK VALVE
GAS COCK
STRAINER
MILWAUKEE / 105 or 115
MILWAUKEE / CL 223 or CL 323
MILWAUKEE / BA 100 H
FLOWSET / AV
POTTROFF / VFD-10
TRERICE / 600C
METRAFLEX / METRASPHERE EPDM
FLOWSET / YR
KEYSTONE / SERIES 500
AMTROL 705
WATTS / SERIES 40, 140, 240, or 340
BY T.C. CONTRACTOR
AMBER-BOOTH / 2600 EPDM
NIBCO
NIBCO
STOCKHAM
MILLIKEN
CENTERLINE
-
ASHCROFT / MAG
PETERSON / PETE's PLUG
-
-
KEYSTONE
RED & WHITE
-
-
-
-
-
NIBCO
DEZURIK
-
GERAND
APOLLO
BURKET
BARCO
KECKLEY
KECKLEY
ASHCROFT / MA
CONBRACO
CONBRACO
-
UNIVERSAL / 45PT-N
NIBCO
-
-
-
-
-
NIBCO
GRISWOLD
STOCKHAM
-
-
MASON / MFNC EPDM
WEKSLER / EA14
WEKSLER / AA5H
-
RED & WHITE
RED & WHITE
-
-
-
-
NIBCO
-
-
-
-
SKINNER
GERAND
TEMPERING VALVE LEONARD LAWLER
VENTURI
REDUCED PRESSURE
MANUAL AIR VENT
AUTOMATIC AIR VENT
FLEXIBLE PIPE CONNECTION
THERMOMETER
PRESSURE GAUGE
SMOKE DAMPER
PRESSURE/TEMP. RELIEF
P-T TAP
STRAINER W/ BLOWOFF VALVE
FIRE DAMPER
FIRE & SMOKE DAMPER
BOILER DRAIN VALVE
FLOWSET / SUPERSEAL
MILWAUKEE / 105 or 115
MILWAUKEE / 590T or 1590T
MILWAUKEE / 509T, 1590T, F2974(M)(A), 548, or 1400 SERIES
-
MILWAUKEE / BA-100 or BA-150
WATTS / ACV 115
FLOWSET / ACCUSETTER
ASCO / RED HAT
BY T.C. CONTRACTOR
WATTS / SERIES 77S with B-6081 VALVE
MAXITROL / BV37 or BV64
WATTS / 909QTS
POTTROFF / FSD-142
POTTROFF / SD-142
WATTS / B-3000 or B-3001 for 1/2" - 3"
FLOWSET / VW
WATTS / SERIES 77S for 1/2" thru 2-1/2"
TRERICE / BX91403 1/2
HOFFMAN FLOWSET
A
PRESSURE REDUCING VALVE
BALANCING VALVE
GATE VALVE
BACKFLOW PREVENTOR
SOLENOID VALVE
WAFER BALANCE VALVE
BUTTERFLY VALVE
STOP/DRAIN VALVE
GATE VALVE IN GROUND BOX
GLOBE VALVE
TEMP. CONTROL - 2-WAY
TEMP. CONTROL - 3-WAY
PLUG VALVE
-
GAS PRESSURE REGULATOR - -SCHLUMBERGER / VARIES
- -AIR ADMITTANCE VALVE STUDOR VENT
NIBCO STOCKHAM BALL DRAIN W/ HOSE END CONNECTIONAPOLLO / 78-103-1 1/2" N.P.T. BY HOSE
ABBREV. DESCRIPTION ABBREV. DESCRIPTION SYMBOL SYMBOL DESCRIPTION
ABBREV.
S
SYMBOL
U.C. SIZE
H
20/16
M
B
W H S
MECHANICAL LEGEND
BUTTERFLY VALVE
PIPE DOWN
PIPE TEE DOWN
SAND OIL WASTE
GREASE WASTE
STORM PIPE
GATE VALVE
BALANCING VALVE
BALL VALVE
COLD WATER
HOT WATER
HOT WATER RECIRCULATE
VENT PIPE
WASTE PIPE
AUTO FLOW CONTROL VALVE
GLOBE VALVE
STOP & DRAIN VALVE
CHECK VALVE
NITROGEN
CHILLED WATER RETURN
REFRIGERANT LIQUID
REFRIGERANT SUCTION
REFRIGERANT HOT GAS
HIGH PRESSURE STEAM
LOW PRESSURE STEAM
HIGH PRESSURE STEAM RETURN
LOW PRESSURE STEAM RETURN
HEATING WATER SUPPLY
PIPE UP
ST
OD
SO
DHW
DHC
FIRE
W
V
AIR
HPSR
LPS
CWS
CWR
CHS
CHR
RH
RS
RL
VAC VACUUM
AIR
FIRE
DCW
LPR
HWS
HWR
HPS
A
HEATING WATER RETURN
CONDENSER WATER SUPPLY
CONDENSER WATER RETURN
CHILLED WATER SUPPLY
PLUG VALVE
MANUAL DAMPER W/ LOCKING
FLEXIBLE DUCT CONNECTOR
VACUUM BREAKER
THERMOMETER
FIRE & SMOKE DAMPER
SMOKE DAMPER
EXISTING FIRE DAMPER
RETURN GRILLE
CONNECTION NEW TO EXISTING.
FLEXIBLE PIPE CONNECTION
DOOR UNDERCUT
FIRE DAMPER
45° DUCT TAKE-OFF
PRESSURE GAUGE
FLOW SENSOR
DUCT SIZE INDICATING SHEET
METAL DIMENSIONS. FIRST
NUMBER WIDTH & SECOND
IS DEPTH.
DUCT ELBOW W/ TURNING VANE
MOTORIZED DAMPER
QUADRANT.
CFM
DIFFUSER I.D.
DEMO ITEM LINE WEIGHT
NECESSARILY USED ON THIS PROJECT.
}
NOTE: NOT ALL SYMBOLS ON THIS LEGEND ARE
FLEX
DIFFUSER
NECK SIZE
DUCT TEE W/ TURNING VANES
EXISTING ITEM LINE WEIGHT
NEW ITEM LINE
WEIGHTS
# x # x #Ø
FLEX SIZE
F.D.
BRK
F.S.
F.S.
CO
CO
R.D.
VTR
O.R.D.
H B
W H
P#
BOILER DRAIN VALVE
SMOKE DETECTOR
PIPE ANCHOR
VENT THRU ROOF
FLOOR DRAIN
WALL HYDRANT
DOWNSPOUT NOZZLE
HOSE BIBB
AIR VENT
P-T TAP
PIPE GUIDE (SLEEVE)
PIPE EXPANSION JOINT
PRESSURE/TEMP. RELIEF
PUMP
PRESSURE REDUCING VALVE
SOLENOID VALVE
MOTORIZED GATE VALVE
REDUCED PRESSURE
BACKFLOW PREVENTOR
WAFER BALANCE VALVE
VENTURI
UNION
PIPE REDUCER
STRAINER
STRAINER W/ BLOWOFF VALVE
EQUIPMENT ROOM DRAIN
FLOOR SINK - HALF GRATE
FLOOR SINK - 1/4 GRATE
DRAIN ABOVE
ROOF DRAIN
CLEANOUT - VERTICAL
CLEANOUT - HORIZONTAL
ROOF DRAIN - OVERFLOW
PIPE CAP
BREAK - MISC.
GAS COCK
TEMP. CONTROL - 2-WAY
TEMP. CONTROL - 3-WAY
3-WAY VALVE
SPIN-IN FITTING W/ DAMPER
RIGID DUCT
(N) NEW
(E)
(R)
EXISTING
RELOCATED
GAS PRESSURE REGULATOR
ACCESS DOOR IN CEILING
CWS
CWR
CHS
CHR
RS
RL
RH
HWS
HWR
HPS
HPSR
LPS
LPSR
N
VAC
A
N
F
W
V
GAS PIPE
GAS
OD
SO
G
ST
PIPE TEE UP
GAS COCK (SHUT-OFF) AND UNION
FS
BALL DRAIN W/ HOSE END
CONNECTION.
REMOTE SENSOR
CARBON DIOXIDE SENSOR
CARBON MONOXIDE SENSOR
THERMOSTAT
T
S
CD
CM
HUMIDISTAT H
M
*NOTE: ALL DASHED PLUMBING LINES INDICATE BELOW FLOOR ELEVATION UNLESS OTHERWISE
NOTED ON DRAWINGS.
DHW
DHC
DCW
OVERFLOW PIPE
ST
ST
(F) FUTURE
DCW METER OR DCW / GASM
SUB-METER
M
GAS METER
AXIOM MODEL SF100 W/ INTERNAL
FLEXIBLE CONNECTOR HOSE, CHECK
MODEL PBLS10 FLOAT
CUT OFF SWITCH
UNISTRUT PIPE CLAMP MINIMUM OF 2
NO SCALE
4" CONCRETE PAD.
FLOOR
TO BOILER FILL LOCATION
FLEX POWER CORDS
MODEL RIA10 ALARM PANEL
W/ ALARM LITES AND BUZZER,
TEST, OFF & FLOAT SWITCHES.
115 V, 1 PHASE PUMP.
VALVE AND STRAINER, AND 1/4 HP,
GLYCOL FEEDER ASSEMBLY
1
1
M002
10/03/17