HomeMy WebLinkAboutB17-0282_P100_1507064554.pdf399 CFH 199 CFH 199 CFH
(E)BOILER (E)BOILER
(N)B-1
HW, CW & RECIRC. LINES
UP TO LEVEL ABOVE
GENERAL NOTES:
1. CONTRACTOR TO FIELD VERIFY ALL EXISTING PLUMBING CONDITIONS
PRIOR TO ORDERING AND INSTALLATION OF NEW PLUMBING
EQUIPMENT/SYSTEMS. NOTIFY ENGINEER IN WRITING WITH ANY
DRAWING/DESIGN DISCREPANCIES.
2. FIELD VERIFY LOCATIONS OF ALL SANITARY WASTE, GAS AND WATER
RISERS IN/ON WALLS PRIOR TO INSTALLATION.
DEMO (E) 3/4" DCW METER & WATER ENTRY & REPLACE W/ (N) 1-1/2" DCW METER, TAP
& SERVICE LINE, FIELD VERIFY EXACT LOCATION OF WATER LINE ENTERING BUILDING W/
OWNER/ARCHITECT/CIVIL PRIOR TO DEMO & INSTALLATION
(E) FLOOR DRAIN TO BE CLEANED OUT
AND TO BE IN OPERATING CONDITION
(N) IWH1
REMOVE ALL EXISTING PIPING, ZONE VALVES. PUMPS,
ETC. FROM EXISTING BOILERS. RE-ROUTE EXISTING ZONE
VALVES FROM THIS MECHANICAL ROOM THAT SERVE THE
RETAIL SPACE TO OTHER MECHANICAL ROOM BOILER
MANIFOLD. PROVIDE ALL NEW PIPING, PUMPS, ETC. PER
BOILER PIPING SCHEMATIC, SHEET M002
RCP1
ROUTE AS HIGH AS POSSIBLE
AND FIELD VERIFY BEST ROUTING
W/ OWNER/ARCHTIECT PRIOR TO
INSTALLATION
(N) 1-1/4"
GAS LINE
M
RELOCATE (E) WATER
SOFTENER AS NECESSARY
(N) 1-1/4"
TIE (E) 1" GAS
INTO (N) 1-1/4" (E) 1"
(N) 1-1/2"
GAS LINE
GPRV1, 797 CFH, 30 FEET
(N) 1-1/2" DCW METER
(N) 1-1/2" DCW REDUCED PRESSURE BACKFLOW
PREVENTER, WILKINS MODEL 375XL W/ AG-6 AIR
GAP, 1-1/2" RPBFP TO BE LOCATED UNDER 1-1/2"
DCW METER, SHOWN TO THE SIDE FOR CLARITY
FIELD VERIFY WITH OWNER/ARCHITECT/
STRUCTURAL (N) GAS & DCW PIPE ROUTING
OUT OF ROOM PRIOR TO INSTALLATION
TIE ALL (E) WATER LINES IN ROOM BACK
INTO (N) 1-1/2" DISNTRIBUTION LINE
GAS LINE FROM ABOVE
DCW DCW DHW
DCW
DHC
GG G
G WILKINS MODEL
705 DOUBLE CHECK
BACKFLOW PREVENTER
3/4" DCW TO
BOILER SYSTEM
181 CFH 181 CFH
(E)BOILER (E)BOILER
(E) GAS
LINE
TIE (E) GAS LINE INTO NEW GAS LINE
(E) HTP INDIRECT
WATER HEATER
PRV
1
1
1
PROVIDE 3"FS1 IF EXISTING DRAIN DOES NOT EXIST,
TIE NEW 3" INTO CLOSEST SANITARY WASTE, 3" MIN.,
FIELD VERIFY LOCATION PRIOR TO INSTALLATION
1
MM KK JJ II GG EEA EE CC AA A B
3
5
Z
YA
Y
XN
X
15
ZA
6A
K.5
13.5
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
2
C D E F G H I J K L M
2
E.5 L.5
OWNER
PROJECT NO.: 21074.00
VAIL, COLORADO
81657
311 BRIDGE
STREET
LANDSCAPE SHERRY DORWARD
P.O. BOX 3766
VAIL, CO 81658
ARCHITECT
ARCHITECT 4240 ARCHITECTURE
3507 RINGSBY CT. STUITE 117
DENVER, CO 80216
HILL BUILDING
RENOVATION
39°38'24"N
106°22'25"W
STRUCTURAL MONROE NEWELL
70 BENCHMARK RD. SUITE 204
AVON, CO 81620
ENGINEER
MEP DMCE ENGINEERING
5737 6TH AVE.
LAKEWOOD, CO 80214
ENGINEER
CIVIL ALPINE ENGINEERING, INC.
34510 HIGHWAY 6 UNIT A-9
EDWARDS, CO 81632
ENGINEER
TOWN OF VAIL USE
ISS.# DESCRIPTION DATE
S BUILDING PERMIT ISSUE 2017-07-07
01 BUILDING DEPT COMM. 2017-08-16
1
02 PERMIT REVISIONS 2017-08-25
2
P100
BASEMENT
PLUMBING PLAN
1
SCALE: 1/4" = 1'-0"
BASEMENT PLUMBING PLAN
10/03/17