HomeMy WebLinkAboutD17-0012_A-520_1512591357.pdfINSULATION TO BE
CONTINOUS TO EXISTING
INSULATION SYSTEM
1 HOUR FIRE RESISTIVE WALL
ASSEMBLY
- 1" MIN. THICKNESS 3-PART
STUCCO SYSTEM; BASIS OF
DESIGN: "DRYVIT CCP-4" WITH
EXTERIOR FINISH TO MATCH
EXISTING BUILDING
- 5/8" EXTERIOR SHEATHING
- 2" RIGID POLYISO WITH TAPED
SEAMS
- 5/8" SHEATHING
- 6" GALV C-H STUD, FILLED WITH
BATT INSULATION
- 1" SHAFT LINER IN C-H STUD; SIZE
SPACING AND GAUGE TO PROVIDE
L/240 DEFLECTION LIMITS
07 1416 - FLUID APPLIED
FLASHING MEMBRANE,
PER STUCCO SYSTEM
EXISTING EXTERIOR WALL
INSULATION TO BE
CONTINOUS TO EXISTING
INSULATION SYSTEM
1 HOUR FIRE RESISTIVE
WALL ASSEMBLY
- 1" MIN. THICKNESS 3-PART
STUCCO SYSTEM; BASIS OF
DESIGN: "DRYVIT CCP-4"
WITH EXTERIOR FINISH TO
MATCH EXISTING BUILDING
- 5/8" EXTERIOR SHEATHING
- 2" RIGID POLYISO WITH
TAPED SEAMS
- 5/8" SHEATHING
- 6" GALV C-H STUD, FILLED
WITH BATT INSULATION
- 1" SHAFT LINER IN C-H
STUD; SIZE SPACING AND
GAUGE TO PROVIDE L/240
DEFLECTION LIMITS
EXISTING WALL ASSEMBLY;
PATCH AS NEEDED TYP
ACROSS EXISTING EXTERIOR WALL
EXISTING CONCRETE
STRUCTURE
9 5/8"
EDGE OF EXISTING
SLAB TO REMAIN
(BEYOND)
07 1416 - FLUID APPLIED
FLASHING MEMBRANE,
PER STUCCO SYSTEM
GALV SHEET METAL
FLASHING
6" J-TRACK
SEALANT
EDGE OF EXISTING
SLAB TO REMAIN
10 1/4"
CEMENT PLASTER SYSTEM;
BASIS OF DESIGN: "DRYVIT CCP-4"
- 'BACKSTOP NT' AIR / WATER
RESISTIVE BARRIER
- GALV SELF FURRING LATH
- CEMENT PLASTER BASE
- REINFORCING MESH IN
LEVELING COAT
- FINISH OVER PRIMER
06 1600 - WALL
SHEATHING
WS-STUCCO1A
GASKETED FASTENERS, TYP
COUNTERFLASHING
NEW SEALANT APPLIED TO
EXISTING TERMINATION BAR
INSULATION TO BE
CONTINOUS TO EXISTING
INSULATION SYSTEM
EXTERIOR 1 HOUR RATED UL
LISTED HORIZONTAL ASSEMBLY
REPLACE EXISTING EDPM
FLASHING AT JOINT
05 4000 - COLD-FORMED
METAL FRAMING
NOTE: 6" METAL STUD,
18 GA. @ 16" O.C.
GRAY REGION INDICATES
EXISTING CONDITION
SEALANT
SELF ADHERED FLASHING
CEMENT PLASTER SYSTEM;
BASIS OF DESIGN: "DRYVIT CCP-4"
- 'BACKSTOP NT' AIR / WATER
RESISTIVE BARRIER
- GALV SELF FURRING LATH
- CEMENT PLASTER BASE
- REINFORCING MESH IN
LEVELING COAT
- FINISH OVER PRIMER
AQUAFLASH SYSTEM OVER
EXTERIOR SHEATHING
CASING BEAD WITH WEEPS
GALV FLASHING IN
CONTINUOUS SEALANT
INTERIOR
GRAY REGION INDICATES
EXISTING CONDITION
GALV METAL COUNTER FLASHING
WITH END DAMS
SEALANT ON CLOSED CELL
BACKER ROD
GALV METAL FLASHING
TREATED NAILER
AND PLASTER STOP
SEALANT
EXTERIOR SHEATHING
GALV METAL COUNTER FLASHING
1"
MI
N
AQUAFLASH SYSTEM OVER SHEATHING;
EXTEND OVER TOP OF PARTITION
GALV METAL FRAMING; SEE STRUCTURAL
CEMENT PLASTER SYSTEM;
BASIS OF DESIGN: "DRYVIT CCP-4"
- 'BACKSTOP NT' AIR / WATER
RESISTIVE BARRIER
- GALV SELF FURRING LATH
- CEMENT PLASTER BASE
- REINFORCING MESH IN
LEVELING COAT
- FINISH OVER PRIMER
AQUAFLASH SYSTEM OVER
EXTERIOR SHEATHING
SHIM
SEALANT AND BACKER ROD
GRAY REGION INDICATES
EXISTING WALL ASSEMBLY
09 2900 - GYPSUM
BOARD, TYPE X
SECTION 09 2216 -
NON-STRUCTURAL
METAL FRAMING
NOTE: PROVIDE THIS CONDITION TYPICAL
FOR BOTH SIDES OF WALL INFILL
MECHANICAL
DUCT,
RE:
MECHANICAL
PARAPET
BEYOND
TOP OF EXISTING
ROOF ASSMEBLY
MEMBRANE PAD
ADHERED TO
EXISTING ROOF
WITH SPLICE
ADHESIVE; SEAL
PERIMETER WITH
POURABLE
SEALER
ROOF PIPE
SUPPORT
METAL ROOF
CURB AND
FRAMING
SECURED TO
EXISTING
STRUCTURAL
DECK
CONTINUOUS LAP
SEALANT
FULLY ADHERED
FLASHING
MEMBRANE
CONTINUOUS
BEAD OF LAP
SEALANT
GC TO VIFPER MFR, BUT NOT LESS THAN 8"FASTER & SEAM
FASTENING PLATE
BONDING ADHESIVE
FULLY ADHERED SHEET
METAL COUNTER
FLASHING
ROOF TOP MECHANICAL
EQUIPMENT, RE: MECH
EPDM 6" PRESSURE -
SENTITIVE CURB WRAP
WITH 6" FACTORY-
APPLIED TAPE
INSULATED METAL
CURB, RE: MECH
FIRE TREATED WOOD
BLOCKING AS REQUIRED.
TREATED WOOD TO BE
COATED AS TO PREVENT
GALVANIC ACTION WITH
FASTENERS AND
ADJACENT METAL
SURFACES
MODIFY EXISTING ROOF FOR NEW
MECHANICAL CURB INSTALLATION.
PATCH AND REPAIR ROOF TO
MAINTAIN WARRANTY, FIRE
RESISTIVITY, THERMAL PROPERTIES,
AND WATER RESISTIVITY
EXISTING ROOF ASSEMBLY
CONTINUE ROOF
MEMBRANE
COVER BOARD
PER MFR
INTERMEDIATE FR WOOD
FRAMING; TREATED WOOD
TO BE COATED AS TO
PREVENT GALVANIC
ACTION WITH FASTENERS
AND ADJACENT METAL
SURFACES
CONTINUOUS
SEALANT
FLASHING
SECURE ROOF CURB TO
EXISTING METAL DECK.
RE: STRUCTURAL.ABOVE ROOF MEMBRANE AT LOWEST ELEVATION
8" MIN. CURB2901 Blake Street, Suite 100
Denver, CO 80205
303.861.8555
Denver
DPA Project:
Sheet Number:
COPYRIGHT - DAVIS PARTNERSHIP,
1 2 3 4 5 6
A
B
C
D
E
1 2 3 4 5 6
A
B
C
D
E
Sheet Title:
Consultant
Revision Date
No.
Sheet Information
Project Information
Original Issuance
Date
9/28/2017 5:29:29 PM15924.00
A-520
2017 EAST WING ADDITION
180 S. Frontage Road West, Vail, CO 81657EXTERIOR
DETAILS
09/28/17DP1 VAIL HEALTH
3" = 1'-0"B2 PLAN DETAIL
3" = 1'-0"A2 PLAN DETAIL
3" = 1'-0"A4 SECTION DETAIL
3" = 1'-0"B4 SECTION DETAIL
3" = 1'-0" A5 INFILL WALL BASE DETAIL
3" = 1'-0"B5 INFILL WALL HEADER DETAIL
3" = 1'-0" C5 INFILL WALL PLAN DETAIL
6" J-TRACK
1 1/2" = 1'-0"D2 ROOF PENETRATION SECTION DETAIL
1 1/2" = 1'-0"D4 ROOF CURB DETAIL
1 1/2" = 1'-0"D5 EQUIPMENT SUPPORT CURB
SET BOLT IN SEALANT
GASKET
SHEET METAL COVER
EPDM CURB FLASHING
EXISTING ROOF SYSTEM8"NOTE: REMOVE ANY
EXISTING STUCCO SYSTEM OR
EXISTING VAPOR RETARDER
THAT WILL BE CONCEALED
BY THE NEW STUCCO SYSTEM.
AVOID ANY DUPLICATE VAPOR
RETARDING CONDITIONS BETWEEN
THE NEW AND EXISTING ASSEMBLIES.
METAL STUDS TO BE MINIMUM
18 GAUGE, 16" ON CENTER
12/06/17