HomeMy WebLinkAboutD17-0012_A-720.1_1512591356.pdfINTERIOR PARTITION TYPES
STRUCTURE
A 7/8" HAT CHANNEL
B 1 5/8" METAL STUD
C 2 1/2" METAL STUD
D 3 5/8" METAL STUD
E 4" METAL STUD
F 6" METAL STUD
G 3 5/8" DOUBLE METAL STUD
J 2 1/2" C-H METAL STUD
K 4" C-H METAL STUD
L 6" C-H METAL STUD
M 2x4 WOOD STUD
N 2x6 WOOD STUD
P 4" CMU
Q 6" CMU
R 8" CMU
S 12" CMU
Z 1 1/2" "Z" FURRING CHANNEL
D1sX
EXAMPLE
D = 3 5/8" METAL STUD
1 = 1 HOUR FIRE RESISTANCE
RATING
s = SOUND PARTITION
FIRE RESISTANCE RATING*
0 NON-RATED
1 1 HOUR
2 2 HOUR
3 3 HOUR
4 4 HOUR
SUB-TYPE
a 6" ABOVE CEILING
b UNDERSIDE OF STRUCTURE
c UNDER SIDE OF CEILING
f FURRING
l LEAD LINED
k SECURITY MESH
p PARTIAL HEIGHT
s SOUND PARTITION
t THERMAL INSULATION
v SOUND PARTITION WITH (2) LAYERS
GYPSUM BOARD EACH SIDE
w SOUND PARTITION WITH (2) LAYERS
GYPSUM BOARD ONE SIDE
(1) LAYER OTHER SIDE
z TILE BACKER BOARD
SMOKE RATED*
X SMOKE PARTITION,
SMOKE BARRIER OR WALL
RESISTING THE PASSAGE
OF SMOKE
STRUCTURE
FIRE RESISTANCE RATING
SUB-TYPE
SMOKE RATED
* SEE RATED PARTITION NOTE 2
GENERAL CONSTRUCTION AND LAYOUT NOTES
1. THE INTERIOR FRAMING SUBCONTRACTOR SHALL PROVIDE A DELEGATED ENGINEERED STUD DESIGN FOR ALL NON-STRUCTURAL METAL FRAMING FOR
WALLS AND CEILINGS. SUBMIT FRAMING SHOP DRAWINGS WITH DETAILS, PRODUCT SELECTIONS, AND ENGINEERING CALCULATIONS STAMPED BY A
LICENSED ENGINEER IN THE PROJECT JURISDICTION. ENGINEERING SHALL INCLUDE PROVISIONS FOR ELEMENTS ATTACHED TO/SUPPORTED BY THE
FRAMING. FASTENER DESIGN AND SELECTION IS ALSO REQUIRED. SUBMIT ICC ES EVALUATION REPORTS FOR EACH FASTENER. USE OF DIMPLED OR
PERFORMANCE ENHANCED SHAPED STUDS IS ACCEPTABLE. UNLESS OTHERWISE INDICATED DESIGN FOR A MAXIMUM DEFLECTION OF L/240 AT 5 PSF. AT
PARTITIONS TO RECEIVE CERAMIC TILE DESIGN FOR A MAXIMUM DEFLECTION OF L/360 AT 5 PSF. REGARDLESS OF DESIGN, PROVIDE 20 GA STUD AT A
MINIMUM.
2. ALL INTERIOR PARTITIONS ARE DIMENSIONED TO FINISHED FACE OF GYPSUM BOARD UNLESS NOTED OTHERWISE.
3. ALL STUDS SHALL BE FULL HEIGHT TO UNDERSIDE OF STRUCTURE UNLESS INDICATED OTHERWISE BY PARTITION TYPE.
4. BOTTOM OF GYPSUM BOARD SHALL BE 1/4” TO 3/8” ABOVE FINISH FLOOR UNLESS OTHERWISE INDICATED.
5. OFFSET STUDS AS NECESSARY TO ALIGN OUTSIDE FACES OF GYPSUM BOARD AT ADJACENT WALL TYPES WITH VARYING LAYERS OF GYPSUM BOARD.
6. PROVIDE DEEP LEG TRACKS (3" FLANGE) AT HEAD OF PARTITIONS AT ALL NON-LOAD BEARING PARTITIONS FOR EACH CONDITION THAT ALLOW FOR 1" OF
UPWARD MOVEMENT AND 1" OF DOWNWARD DYNAMIC MOVEMENT CAPABILITIES.
7. AT SLAB-ON-GRADE CONDITIONS PROVIDE DYNAMIC MOVEMENT REQUIREMENTS CALLED FOR IN THE GEOTECHNICAL INVESTIGATION (SOILS REPORT). IF
NO GEOTECHNICAL INVESTIGATION EXISTS CONTACT THE ARCHITECT FOR DEFLECTION CRITERIA.
8. ALL PARTITION TYPES MARKED BY A "t" SUFFIX (IE. D0t) SHALL BE INSTALLED WITH FULL HEIGHT AND WIDTH CONTINUOUS THERMAL INSULATION AND, IF
INDICATED, CONTINUOUS VAPOR RETARDER.
9. PROVIDE GYPSUM BOARD CONTROL JOINTS PER ASTM C 840 UNLESS OTHERWISE INDICATED ON DRAWINGS.
10. PROVIDE FIRE BLOCKING AND DRAFT STOPS PER CODE.
11. AT LOCATIONS ADJACENT TO GLASS SYSTEMS, GC TO VERIFY IN FIELD AND PROVIDE FASTENERS SUCH THAT THE INSTALLATION OF METAL FRAMING
DOES NOT ADVERSELY IMPACT THE GLASS SYSTEM.
RATED PARTITION NOTES
1. FIRE RATED ASSEMBLY CRITERIA TAKE PRECEDENT OVER ANY OTHER CONSTRUCTION CRITERIA.
2. REFERENCE LIFE SAFETY DRAWINGS FOR LOCATIONS OF FIREWALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE PARTITIONS, SMOKE BARRIERS, AND
WALLS RESISTING THE PASSAGE OF SMOKE. COMPLY WITH IBC AND ANY OTHER APPLICABLE CODES FOR CONSTRUCTION REQUIREMENTS FOR EACH
RATED PARTITION TYPE.
3. REFERENCE SPECIFICATION SECTION 07 8413 –‘PENETRATION FIRESTOP’ FOR TREATMENT OF ANY PENETRATIONS THROUGH A FIRE RATED PARTITION.
NEEDS TO MEET UL LISTED TEST REQUIREMENT.
4. REFERENCE SPECIFICATION SECTION 07 8443 –‘JOINT FIRESTOP’ FOR TREATMENT OF TOP AND BOTTOM OF WALL JOINTS AND JOINTS TO ABUTTING
CONSTRUCTION. NEEDS TO MEET UL LISTED TEST REQUIREMENT.
5. PROVIDE AND SUBMIT FOR APPROVAL U.L. RATED HEAD OF WALL ASSEMBLIES FOR EACH RATED PARTITION CONDITION THAT ALLOWS FOR THE DYNAMIC
MOVEMENT INDICATED. IF ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION (AHJ), OBTAIN ENGINEERING JUDGEMENTS FOR JOB SPECIFIC
CONDITIONS NOT ADDRESSED BY TESTED ASSEMBLIES.
6. PROVIDE FIRE-RATED ACCESS DOORS AND FRAMES TO REACH DAMPERS OR CONTROL VALVES IN RATED PARTITIONS OR CEILING AS REQUIRED TO
MAINTAIN RATING. PROVIDE NONRATED ACCESS DOORS AT NON RATED CONSTRUCTION.
7. WHERE DEVICES ARE RECESSED IN A FIRE RATED PARTITION PROVIDE: A.) DEVICE RATED FOR INSTALLATION IN RATED PARTITIONS, OR B.)
CONSTRUCTION SUCH THAT FIRE RATING IS MAINTAINED BEHIND RECESSED DEVICE.
8. WHERE STRUCTURAL ITEMS SUCH AS HANGERS FOR STAIRS ARE EMBEDDED IN A RATED PARTITION CONSTRUCTION SHALL BE SUCH THAT FIRE RATING IS
MAINTAINED BEHIND EMBEDDED ITEM.
9. MARKING AND IDENTIFICATION: FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL
REQUIRED TO HAVE PROTECTED OPENINGS OR PENETRATIONS SHALL BE LABELED PER CODE.
10. PROVIDE SMOKE PARTITIONS TO LIMIT THE TRANSFER OF SMOKE. FILL JOINTS AND THE SPACE AROUND PENETRATING ITEMS SUCH AS DUCTS, PIPES,
CONDUITS, AND SIMILAR BUILDING SERVICE EQUIPMENT WITH AN APPROVED MATERIAL TO LIMIT THE PASSAGE OF SMOKE.
11. SEE A-720.1 FOR TYPICAL FRAMING DETAILS.
SOUND PARTITION NOTES
1. ALL PARTITION TYPES MARKED BY AN "s" SUFFIX (IE. D1s) SHALL BE INSTALLED AS A SOUND PARTITION INCLUDING: FULL HEIGHT AND WIDTH SOUND
ATTENUATION BLANKETS (SAB), ACOUSTICAL JOINT SEALANT AT TOPS AND BOTTOMS OF ALL WALLS AND PENETRATIONS, DRYWALL TO BE FROM FLOOR
TO DECK BOTH SIDES.
2. PROVIDE ELECTRICAL OUTLET BARRIER PADS IN SOUND PARTITIONS.
3. STAGGER DEVICES THAT PENETRATE OPPOSING WALL SURFACES IN ADJACENT STUD CAVITIES.
RATED ASSEMBLY INFORMATION
TOP OF WALL ASSEMBLY:
• STANDARD INTERIOR NON-BEARING WALL ASSEMBLY: UL HW-D-0495 OR EQUAL
• SHAFTWALL FLAT CONCRETE: UL HW-D-0496
• SHAFTWALL PARALLEL TO BEAM: UL HW-D-0497
• SHAFTWALL PAN DECK: UL HW-D-0504
• SHAFTWALL PROTECTED ROOF DECK: UL HW-D-0559
WALL ASSEMBLY:
• STANDARD INTERIOR NON-BEARING WALL ASSEMBLY : UL U419 OR UL U423
• SHAFTWALL ASSEMBLY: UL U415
SILL TRACK OF WALL ASSEMBLY:
• PROVIDE UL LISTED ASSEMBLY COMPLIANT WITH THE UL WALL ASSEMBLY AND THAT MATCHES FIRE RESISTIVITY OF THE WALL.
DOOR / FRAME MATERIAL:
AL/G - ALUMINUM GLASS
HM - HOLLOW METAL
WD - WOOD
PT - PAINTED
STAIN - STAINED
MFR - MANUFACTURER
DOOR FINISH:
PL# - PLASTIC LAMINATE
ST - STAINED, SEE BELOW
CA - CLEAR ANODIZED
PT - PAINTED
KF - KYNAR FINISH
GL - GLASS
STAIN FINISH CODES
ST0 = MATCH EXISTING ADJACENT FINISH
WITHIN THE SUITE (COMMENT: MSA AREA,
MISC.)
ST1 = TO MATCH VT INDUSTRIES 'RAVINE
RA07' (COMMENT: ADMIN DOORS EXCEPT
NORTH ENTRY DOOR)
ST2 = TO MATCH MARSHFIELD 'NUTMEG'
(COMMENT: CORRIDOR DOORS, BLDG STD)
DOOR NOTES
1. CONTRACTOR TO FIELD COORDINATE ALL ROUGH
OPENINGS.
2. REFER TO SPECIFICATIONS FOR HARDWARE TYPES
AND SCHEDULE.
3. ALL FIRE RATED DOORS SHALL HAVE
UNDERWRITERS LABEL ON DOOR AND FRAME.
4. WHERE EXISTING DOORS TO REMAIN, TOUCH UP
SCUFFING TO MAKE DOOR FINISH LIKE-NEW.
5. AT EXISTING DOORS IN SCOPE: WHERE
SCUFFED,PATCH AND REFINISH TO LIKE-NEW
CONDITION. IN AREA C, REFINISH EXISTING
DAMAGED DOORS AND DOOR FRAMES.
DOOR AND HARDWARE SCHEDULE - ABBREVIATIONS LEGEND/NOTES
FRAME NOTES
1. CONTRACTOR TO FIELD COORDINATE ALL ROUGH
OPENINGS PRIOR TO ORDERING OR FABRICATING
ANY FRAMES.
2. ALL ELEVATIONS ARE DRAWN FACING THE
EXTERIOR OF THE WINDOW FRAME.
3. STOREFRONT FABRICATOR TO PROVIDE
REINFORCING AS REQUIRED
4. ALL DIMENSIONS ARE TO MASONRY OR ROUGH
OPENING UNLESS NOTED OTHERWISE, PROVIDE
PROPER SHIM CLEARANCE AS REQUIRED.
5. AT EXISTING FRAMES IN SCOPE: WHERE SCUFFED,
PATCH AND REFINISH TO LIKE-NEW CONDITION
GLAZING TYPES
S = PROVIDE TEMPERED
GLASS IN NON-RATED
DOORS WHERE INDICATED.
F = PROVIDE FIRE-
PROTECTION-RATED GLASS
MEETING OR EXCEEDING
THE RATING OF THE DOOR
ASSEMBLY WHERE
INDICATED
SEE SPECIFICATION FOR
ACCEPTABLE GLASS
TYPES.
D0b 4 7/8"5/8" 3 5/8" 5/8"SINGLE OR
DOUBLE DOOR
FRAME
HM1RE: SCHEDULE 2"2" RE: SCHED. 2"
/ C1 A-720.1
/C2A-720.1
SINGLE FLUSH
F1 RE: SCHEDULERE: SCHED.
SINGLE NARROW LITE
(TEMPERED OR FIRE
RATED GLASS)
N1RE: SCHEDULERE SCHED. 3' - 4" 8"8"8"
EXTERIOR BUILDING SYSTEMS NAMING
SYSTEM TYPES
PWS = PARAPET WALL SYSTEM
RS = ROOF SYSTEM
SS = SOFFIT SYSTEM
CS = CEILING SYSTEM
WS = WALL SYSTEM
GS = GLAZING SYSTEM
FS = FLOOR SYSTEM
FWS = FOUNDATION WALL
SYSTEM
EXTERIOR BUILDING SYSTEMS
1. EXTERIOR BUILDING SYSTEMS SHEETS SHOW SYSTEM COMPONENTS. REFER
TO SECTION AND DETAILS FOR RELATIONSHIPS BETWEEN BUILDING SYSTEMS
FINISH TYPES
EPDM = EPDM
TPO = TPO
PVC = PVC
STO = STONE
WD = WOOD
MET = METAL
MAS = MAS
STU = STUCCO
CMU = CMU
WW = WINDOW WALL
SF = STOREFRONT
CW = CURTAIN WALL
DP = DAMP PROOFING
WP = WATER PROOFING
EXAMPLE
SYSTEM TYPE
FINISH TYPE
#
- SYSTEM TAG
PWS-MET2A
TYPE
RE: PARTITION
SECTION 09 2900 -
GYPSUM BOARD
08 1113 - INTERIOR
HOLLOW-METAL FRAME
08 1416 - FLUSH WOOD
DOOR
07 9200 - JOINT SEALANT
05 4000 - COLD-FORMED METAL FRAMING
UNO
6" TYP.
TYPE
RE: PARTITION
SECTION 09 2900 -
GYPSUM BOARD
08 1416 - FLUSH WOOD
DOOR
08 1113 - INTERIOR
HOLLOW-METAL FRAME
05 4000 - COLD-FORMED
METAL FRAMING
07 9200 - JOINT SEALANT
WS_STUCCO1A
BASIS-OF-DESIGN: MODIFIED
DOW THERMAX X-ARMOR WALLSYSTEM
WITH LIQUIDARMOR FLASHING AND
SEALANT ON THERMAX XARMOR
INSULATION.
09 2400 - EXTERIOR
PLASTERWORK TO
MATCH EXISTING
09 2900 - EXTERIOR
GYPSUM BOARD
SECTION 07 4265 - 4 MIL
FOIL-FACED
POLYISOCYANURATE
FOAM-PLASTIC BOARD
10 1/4"
WS_STUCCO2A
09 2400 - EXTERIOR
PLASTERWORK TO
MATCH EXISTING
5 7/8"
09 2900 - EXTERIOR
GYPSUM BOARD
1"
5"
5/8"
2"
5/8"
1"
5/8"3 5/8"
5/8"1"
07 2100 - MINERAL-WOOL
BLANKET
09 2116.23 - GYPSUM
SHAFTLINER BOARD,
MOISTURE- AND
MOLD-RESISTANT TYPE X
2901 Blake Street, Suite 100
Denver, CO 80205
303.861.8555
Denver
DPA Project:
Sheet Number:
COPYRIGHT - DAVIS PARTNERSHIP,
1 2 3 4 5 6
A
B
C
D
E
1 2 3 4 5 6
A
B
C
D
E
Sheet Title:
Consultant
Revision Date
No.
Sheet Information
Project Information
Original Issuance
Date
9/28/2017 5:29:30 PM15924.00
A-720.1
2017 EAST WING ADDITION
180 S. Frontage Road West, Vail, CO 81657DOOR
SCHEDULE,
PARTITION
TYPES, WALL
SYSTEMS, AND
DETAILS
09/28/17DP1 VAIL HEALTH
DOOR SCHEDULE
ROOM LEAF FRAME
Hardware
Set Fire Rating
Wall
Width
Remarks REVNAME
Door
Type
Door
Material Finish Width Height Thickness
Door
Glass
Type
Frame
Type
Frame
Material
Frame
Finish
LEVEL 2_CENTRAL
204 CORRIDOR F1 3' - 0" 7' - 0" 1 3/4" HM1 4 7/8"
274 (E) MECHANICAL F1 WD 2' - 8" 6' - 8" - HM1 HM PT 45
PARTITION TYPES SCHEDULE
PARTITION
TYPE USE DESCRIPTION
PARTITION
WIDTH STRUCTURE CONSTRUCTION DESCRIPTION TOP OF WALL TO FIRE RATING
DESIGN
NUMBER
(FIRE)
D0b PARTITION WALL 4 7/8" 3-5/8" STEEL STUDS (1) LAYER 5/8" GYPSUM BOARD EACH SIDE UNDER SIDE OF STRUCTURE NON-RATED N/A
1/4" = 1'-0"
FRAME TYPES
1/4" = 1'-0"
DOOR TYPES
3" = 1'-0"C1 HM INTERIOR DOOR FRAME HEAD
3" = 1'-0"C2 HM INTERIOR DOOR FRAME JAMB
GC TO VERIFY ACTUAL DIMENSION ON SITE
WD ST2
ST2 1 3/4"
- HM PT 44
45
12/06/17