Vigilant Catalog u Section 06-27-13Page 1 of 4 D A T A S H E E T M85001-0623 Not to be used for installation purposes. Issue 1 Sounder base for CO and fire detectors GSA-SBT, GSA-T3T4 Description The GSA-SBT Fire/CO sounder base, which requires the use of a GSA-T3T4 Temporal Pattern Generator, adds an audible output function to the V-PCOS intelligent combination fire/CO detector. The GSA-T3T4 requires VS series control panel V2.2 or higher. It uses the same address and programming label as the detector it supports. The GSA-SBT sounder base is field-configurable for output vol- ume (low or high dBA). By default, the GSA-SBT sounder base is set for high dBA. GSA-SBT sounder bases on the same circuit may be activated through programming or as a group or zone with the use of a GSA-CRR polarity reversal module. Additionally, the fire/CO sounder base can simply operate according to the state of its detector, or it can be configured through system programming to operate in conjuction with all sounder bases on the same circuit, or it can be controlled by program rules. The base generates a loud piercing tone that has excellent wall penetration qualities. It uses the same tone generator found in the award-winning Genesis line of wall and ceiling horns. Standard Features • Compatible with CO and smoke detectors Approved audible output facilitated by the GSA-T3T4 Temporal Pattern Generator module. • High or low dB output Jumper selects low or high dBA output. • Single or group operation Optional programming and polarity reversing module configures base for group alarm output. • UL268, UL464, and UL2075 listed UL listing under smoke detector, CO detector, and audible signal standards allows application as smoke alarm, CO alarm and/or audible signal. • Attractive installation Flush mount to a wide selection of North American boxes or surface mount to optional custom-matched box. GSA-SBT GSA-T3T4 Page 2 of 4 D A T A S H E E T M85001-0623 Not to be used for installation purposes. Issue 1 Application The GSA-SBT sounder base is for use with V-PCOS detectors in applications where localized or group alarm signaling is required. The base uses the same address and programming label as the detector it supports. The base is listed by Underwriters Laboratories under the UL268, UL464, and UL2075 standards, allowing its application where smoke alarms, CO alarms, and/or notification appliances are required. This makes the GSA-SBT ideal for hotels, dormitories, and other residential occupancies where supplementary audible output is required to meet required sound levels for sleeping areas or areas subject to high levels of ambient noise. CO Applications When a GSA-SBT gets a signal from its detector to activate, there is a delay so the sounder doesn’t immediately go in steady tone. When it detects pulses on the coded riser, it activates the sounder. If there are no pulses, the GSA-SBT just sounds steady after the short delay expires. Depending on the type of alarm, the panel can select the cor- responding pattern and send the activation command to the GSA-T3T4. All sounder bases in the loop are controlled through panel pro- gramming. A GSA-CRR module can also be used. Configuration T3T4 Riser + T3T4 Riser - SLC + SLC - T3T4 Riser + T3T4 Riser - SLC + SLC - 4 1. Volume setting. Default is high volume. For low volume, cut trace per item 4. 2. Reserved for future use. Do not cut. 3. Reserved for future use. Do not cut. 4. To configure output volume, cut trace as shown. 5. To next GSA-SBT sounder base or EOL relay. 6. SLC_OUT to next intelligent addressable device. 7. SLC_IN from intelligent addressable controller or previous device. 8. From GSA-T3T4 Temporal Pattern Generator or previous GSA-SBT sounder base. GSA-T3T4 Temporal Pattern Generator The GSA-T3T4 Temporal Pattern Generator is an addressable device that generates sound patterns for carbon monoxide (CO) and fire signals for the GSA-SBT sounder base. The control panel sends synchronization and channel commands to the GSA-T3T4; the channel selection determines the pattern. In the U.S. Channel 1 is TC3 and Channel 2 is TC4. Temporal patterns Name Code Used for TC4 UL2075 CO TC3 NFPA 72 Fire The GSA-T3T4 module uses two addresses on the signaling line circuit (SLC). Address 1 is tied to Channel 1; Address 2 is tied to Channel 2. SLC_IN + AUX_RISER_IN +AUX_RISER_OUT + A SLC_OUT + 1 2 From previous device To next device 1. Use a power-limited and regulated 24 VDC primary or auxiliary power supply that is UL/ULC listed for fire protective signaling systems. 2. Power out to Fire/CO sounder base or listed EOL relay and supervising module Page 3 of 4 D A T A S H E E T M85001-0623 Not to be used for installation purposes. Issue 1 Base Plate Trim Ring Electrical Box Detector AB4G-SB Optional Surface Box (6.8” diameter x 1.8” deep) Installation and Mounting Flush Mounting: The GSA-SBT sounder base flush mounts into 2-1/8 inch (54 mm) deep standard North American 4 inch square electric box, North American 4 x 4 inch octagonal concrete ring (mud box), and standard European 100 mm square electric boxes. The terminal block makes field wire connections fast and efficient. After wiring, a simple push and twist motion locks the detector into the base. Sound Level Output Signal Voltage Low dBA High dBA Reverberant room per UL 464 1 TC3 (fire pattern)16 VDC 80.5 85.2 TC4 (CO pattern)16 VDC 73.9 77.5 Reverberant room per UL 268 and FM 2 TC3 (fire pattern)16 VDC 86.5 90.8 TC4 (CO pattern)16 VDC 77.5 84.1 Sound pressure level per CAN/ULC-S525 3 Temporal 24 VDC 95 91 Steady 24 VDC 93 89 1 For UL 464 applications, low dBA settings are for private mode only. 2 For UL 268 applications, the high setting must be used for evacuation. 3 Voltage is regulated and filtered. Audible directional characteristics Angle (degrees)Output sound pressure level 90 (ref)0 dBA 75 and 110 −3 dBA 55 and 115 −6 dBA ULC anechoic room Edwards recommends that life safety systems and their devices always be installed in accordance with the latest recognized edition of national and local fire alarm codes. CO system wiring for detector operation of bases Typical Wiring CO system wiring for detector and system operation of bases 1. Data from the loop controller 2. Use a 24 VDC primary or auxiliary power supply that is UL/ULC Listed for fire protective signaling systems 3. Listed 24 V EOL supervising equipment Fire/CO sounder operating current in mA (RMS) Voltage Low dBA High dBA 16 VDC 17 28 24 VDC 24 41 33 VDC 31 52 16 VFWR 41 48 24 VFWR 51 60 33 VFWR 60 66 VDC = Volts direct current, regulated and filteredVFWR = Volts full wave rectified AB4GTAB4GT AUX_RISER +AUX_RISER - SLC +SLC -1 2 3 SBT SBT 1. Data from the loop controller 2. Use a 24 VDC primary or auxiliary power supply that is UL/ULC Listed for fire protective signaling systems 3. Listed 24 V EOL supervising equipment AB4GT AUX_RISER +AUX_RISER - SLC +SLC -1 2 3 AB4GTSBT SBT 06-27-13Page 4 of 4 D A T A S H E E T M85001-0623 Not to be used for installation purposes. Issue 1 Contact us... Email: edwards.fire@fs.utc.comWeb: www.vigilant-fire.com Vigilant is an EDWARDS brand. 1016 Corporate Park Drive Mebane, NC 27302 © 2013 UTC Fire & Security Americas Corporation, Inc. All rights reserved. Specifications subject to change without notice. Edwards is part of UTC Climate, Controls & Security, a unit of United Technologies Corporation. Fire/CO Sounder Base Specifications Riser operating voltage 16 to 33 VDC Current (RMS) Operating Supervisory 31 mA (low dBA); 52 mA (high dBA) DC = 1.46 mA, FWR = 2.15 mA Default output volume High dBA Resonant frequency 3.2 kHz Temporal pattern As determined by the GSA-T3T4 Compatible detectors V-PCOS only Compatible electrical boxes AB4G-SB surface box for audible base; 4 in. square by 2-1/2 in. (64 mm) deep box; 3-1/2 in. octagonal by 2-1/2 in. (64 mm) deep box; Standard European 100 mm² box Wire size 12 to 18 AWG (0.75 to 2.50 mm²) Base diameter 6.8 in. (173 mm) Base height from box 0.8 in. (21 mm) Maximum distance from ceiling Wall mount — 12 in. (305 mm) Environment type Indoor only Operating environment Temperature Relative humidity 32 to 120°F (0 to 49°C) 0 to 93% noncondensing Storage temperature −4 to 140°F (−20 to 60°C) Ordering Information Catalog Number Description Ship Wt., lb. (kg) GSA-SBT Audible (Sounder) Base for CO and Fire Detectors 0.3 (0.15) GSA-T3T4 Temporal Pattern Generator 0.2 (0.1) AB4G-SB Surface Box for Audible Base 1.0 (0.45) Related Equipment GSA-MCRR Polarity Reversal Relay (Plug-in UIO module)0.18 (0.08) GSA-CRR Polarity Reversal Relay (Standard mount module)0.2 (0.1) GSA-MCR Control Relay Module (Plug-in UIO module)0.18 (0.08) GSA-CR Control Relay Module (Standard mount module)0.2 (0.1) GSA-RM1 Riser Monitor Module 0.2 (0.1) G1M-RM Signal Master (1-gang remote mount)0.2 (0.1)