SIGA-CR Control Relay Module
Installation Sheet
Description
The SIGA-CR Control Relay Module is an addressable device
that provides one Form C dry contact output relay. The relay
contacts transfer when the module is activated,
The module requires one address on the signaling line circuit
(SLC). Addresses are assigned electronically. ttrere are no
address switches.
Diagnostic LEDs provide visible indication of the state of the
module through the cover plate:
. Normal: Green LED flashes
. Alarm/active: Red LED flashes
Personality codes
lse the personality codes described below to configure the
SIGA-CR module. See Tabte 1 for listing information.
Table 1: Personality code listing information
Installation
Installthis device in accordane.e with applicable national andlocal codes, ordinances, and regulations.
WARNING: Connecting a device that exceeds this module,spilot duty contact ratings may cause activation failure. Thismodule does not support capacitive loads. See.specifications"
on page 3 for contact ratings.
Notes
. The module is shipped from the factory as an assembled
unit; it contains no user-seryiceable parts and should not
be disassembled.
. This module does not operate without electrical power. As
fires frequently cause power intenuption, discuss further
safeguards with the local fire protection specialist.
. Install the module within the same room as the device it is
c€ntrolling.
To installthe module:
1. Write the address assigned to the module on the label
provided, and then apply the label to the module. Remove
the serial number label from the module, and then attach it
to the project documentation.
2. Wire in accordance with.Wiring'on page 2.
3. Using the self-tapping screw provided, aftach the wallplate to the module. See Figure 1.
4, Using the two rnachine screws provided, attach the wall
plate and module to the electrical box.
Code Description UL 864 CAN/ULC- EN 54-18
s527
Signal - dry contact output
Personality code 8: Signal - dry contact output. Configures
the module as a dry relay contact to control external
appliances (door c{osers, fans, dampers) or equipment
shutdown.
.***.
@ 2014 UTC Fire & Security Americas Corporation, Inc.1t4 P/N 3B7O23P-EN . REV 1 1 . ISS 23JAN14
Figure 1: lnstatling the SIGA-CR modute Figure 2: Wiring diagram
(1)
(4)
-\to'
-\tu'
rv'I rsl
(1)
(2)
(3)
Compatible electrical box
SIGA-CR module
Wall plate
(4) #6-32 x 5/8 machine screw
(2x)
(5) #4 x 1/2 self-tapping screw
Wiring
Wire this device in accordance with applicable national and
local codes, ordinances, and regulations.
Notes
. Refer to the Signature loop controller installation sheet for
SLC wiring specifi cations.
. Each terminal on the module is limited to a single
conductor.
To wire the module:
1. Verify that all field wiring is free of opens, shorts, and
ground faults.
2. Strip 1/4 in. (about 6 mm) from the ends of alt wires that
connect to the terminal block of the module.
When stripping wire ends, exposing more wire may cause
a ground fault; exposing less wire may result in a faulty
connection.
3. Make all wiring connections as shown in Figure 2.
(1) Normally open contact (NO)(2) Common contact (C)
{3) Normally closed contact (NC)(4) Not supervised. Power-limited unless connected to a nonpower_limited source. lf the source is nonpower-lirnited, eliminate thepower{imited mark and maintain a minimum of 0.25 in. (6.4 mm)
space from power-limited wiring. For other mounting methods,
see enclosure and bracket installation sheets to mainlain
separation of power-limited and nonpower-limited wiring. The wiresize must be capable of handling fault cunernt from nonpower-limited source.*or-
Use type FPL, FPLR, FpLp, or permitted substitute cables,provided these power-limited cable conduclors extendlng beyond
the jacket are separated by a minimum of 0.25 in. (6.4 mm) ipaceor by a nonconductive sleeve or nonconductive banier from all
other conductors. Refer to the NFpA 7O Naitional Electicat Code
(6) "
for more details.
Signaling line circuit (SLC) to ne)'t device
Signaling line circuit (SLC) from previous device
PowerJimited and supervised
(5)
(o)
(7)
2t4 P/N 387023P-EN. REV 11 . ISS 23JAN14
Specifications
9q_"'$,.ry"$:99
Current
Standby
Activated
15.20 to 19.95 VDC
Ground fault impedance
Contact ratings (pilot duty)24YDCat2A
Signaling line circuits Class A, Style 6 or Class B, Stge 4
Wre size 12 to 18 AWG (1,0 to 4.0 mnr2)
LPCB/CPR electrical box
Requirements
YitiT:r:!:9ry: !19
Compatible electrical boxes
Operating environment
Temperafure 32 to 120'F (0 to 49"C)
0 to 93%, noncondensing*l-"l3ly9ly-iqtty-
Storage temperature range -4 to 140'F (-20 to 60"C)
Regulatory information
Manufacturer Edwads, A Division of UTC Fire & Security
Americas Corporation, Inc.
8985 Town Center Parkway, Bradenton, FL
34202, USA
Authorized EU manufacturing representative:
UTC Flre & Security B.V.
Kelvinstraat 7, 6003 DH Weert, Netherlands
Contact information
For contact information, see www,est-fire.corn.
75 pA
_79_"114
10 ko
Plastic box with cover plate, no gaps
or unused holes24: ?:5 x 1:1il: Qo I9?-. !9 TTI
2-112in. (64 mm) deep singlegang
box; Strandard 4 in. square,l-1l2 in.(99_ry19*qb9t
FGC compliance
North American
:tan9ard1
EN 54
EU compliance
CPR certificates
Year of
manufacture
X
I
The first two digits of the DATE MFc number
(locat€d on the product identification label) are
the year of manufacture,
This device complies with part 15 of the FCC
Rules. Operation is subject to the following two
conditions: (1) This device may not cause
harmful interference, and (2) this device must
accept any interference received, including
_ itlgjetg!,cg t3r m_1y ruse yp9:jggp9l3ll91:
GAN/ULC-S527, UL 864
EN 54-18:2005 InpuUoutput devices
_c€
0832-CPR-F0330
20021961EC (WEEE directive): products marked
with this symbol cannot be disposed of as
unsorted municipal waste in the European Union.
For proper rerycling, return thi$ product to your
local supplier upon the purchase of equivalent
new equipment, or dispose of it at designated
collection points. For more information. see:
www. recyclethis. info.
P/N 387023P-EN . REV 1 1 . tSS 23JAN14 3t4
4t4 P/N 387023P.EN . REV 11 . ISS 23UAN14