HomeMy WebLinkAboutcut sheets_5.pdfWsT* SIGA-CR Control Relay Module Installation Sheet Description The SIGA-CR Control Relay Module is an addressable device that provides one Form C dry contact output relay. The relay contacts transfer when the module is activated, The module requires one address on the signaling line circuit (SLC). Addresses are assigned electronically. ttrere are no address switches. Diagnostic LEDs provide visible indication of the state of the module through the cover plate: . Normal: Green LED flashes . Alarm/active: Red LED flashes Personality codes lse the personality codes described below to configure the SIGA-CR module. See Tabte 1 for listing information. Table 1: Personality code listing information Installation Installthis device in accordane.e with applicable national andlocal codes, ordinances, and regulations. WARNING: Connecting a device that exceeds this module,spilot duty contact ratings may cause activation failure. Thismodule does not support capacitive loads. See.specifications" on page 3 for contact ratings. Notes . The module is shipped from the factory as an assembled unit; it contains no user-seryiceable parts and should not be disassembled. . This module does not operate without electrical power. As fires frequently cause power intenuption, discuss further safeguards with the local fire protection specialist. . Install the module within the same room as the device it is c€ntrolling. To installthe module: 1. Write the address assigned to the module on the label provided, and then apply the label to the module. Remove the serial number label from the module, and then attach it to the project documentation. 2. Wire in accordance with.Wiring'on page 2. 3. Using the self-tapping screw provided, aftach the wallplate to the module. See Figure 1. 4, Using the two rnachine screws provided, attach the wall plate and module to the electrical box. Code Description UL 864 CAN/ULC- EN 54-18 s527 Signal - dry contact output Personality code 8: Signal - dry contact output. Configures the module as a dry relay contact to control external appliances (door c{osers, fans, dampers) or equipment shutdown. .***. @ 2014 UTC Fire & Security Americas Corporation, Inc.1t4 P/N 3B7O23P-EN . REV 1 1 . ISS 23JAN14 Figure 1: lnstatling the SIGA-CR modute Figure 2: Wiring diagram (1) (4) -\to' -\tu' rv'I rsl (1) (2) (3) Compatible electrical box SIGA-CR module Wall plate (4) #6-32 x 5/8 machine screw (2x) (5) #4 x 1/2 self-tapping screw Wiring Wire this device in accordance with applicable national and local codes, ordinances, and regulations. Notes . Refer to the Signature loop controller installation sheet for SLC wiring specifi cations. . Each terminal on the module is limited to a single conductor. To wire the module: 1. Verify that all field wiring is free of opens, shorts, and ground faults. 2. Strip 1/4 in. (about 6 mm) from the ends of alt wires that connect to the terminal block of the module. When stripping wire ends, exposing more wire may cause a ground fault; exposing less wire may result in a faulty connection. 3. Make all wiring connections as shown in Figure 2. (1) Normally open contact (NO)(2) Common contact (C) {3) Normally closed contact (NC)(4) Not supervised. Power-limited unless connected to a nonpower_limited source. lf the source is nonpower-lirnited, eliminate thepower{imited mark and maintain a minimum of 0.25 in. (6.4 mm) space from power-limited wiring. For other mounting methods, see enclosure and bracket installation sheets to mainlain separation of power-limited and nonpower-limited wiring. The wiresize must be capable of handling fault cunernt from nonpower-limited source.*or- Use type FPL, FPLR, FpLp, or permitted substitute cables,provided these power-limited cable conduclors extendlng beyond the jacket are separated by a minimum of 0.25 in. (6.4 mm) ipaceor by a nonconductive sleeve or nonconductive banier from all other conductors. Refer to the NFpA 7O Naitional Electicat Code (6) " for more details. Signaling line circuit (SLC) to ne)'t device Signaling line circuit (SLC) from previous device PowerJimited and supervised (5) (o) (7) 2t4 P/N 387023P-EN. REV 11 . ISS 23JAN14 Specifications 9q_"'$,.ry"$:99 Current Standby Activated 15.20 to 19.95 VDC Ground fault impedance Contact ratings (pilot duty)24YDCat2A Signaling line circuits Class A, Style 6 or Class B, Stge 4 Wre size 12 to 18 AWG (1,0 to 4.0 mnr2) LPCB/CPR electrical box Requirements YitiT:r:!:9ry: !19 Compatible electrical boxes Operating environment Temperafure 32 to 120'F (0 to 49"C) 0 to 93%, noncondensing*l-"l3ly9ly-iqtty- Storage temperature range -4 to 140'F (-20 to 60"C) Regulatory information Manufacturer Edwads, A Division of UTC Fire & Security Americas Corporation, Inc. 8985 Town Center Parkway, Bradenton, FL 34202, USA Authorized EU manufacturing representative: UTC Flre & Security B.V. Kelvinstraat 7, 6003 DH Weert, Netherlands Contact information For contact information, see www,est-fire.corn. 75 pA _79_"114 10 ko Plastic box with cover plate, no gaps or unused holes24: ?:5 x 1:1il: Qo I9?-. !9 TTI 2-112in. (64 mm) deep singlegang box; Strandard 4 in. square,l-1l2 in.(99_ry19*qb9t FGC compliance North American :tan9ard1 EN 54 EU compliance CPR certificates Year of manufacture X I The first two digits of the DATE MFc number (locat€d on the product identification label) are the year of manufacture, This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including _ itlgjetg!,cg t3r m_1y ruse yp9:jggp9l3ll91: GAN/ULC-S527, UL 864 EN 54-18:2005 InpuUoutput devices _c€ 0832-CPR-F0330 20021961EC (WEEE directive): products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union. For proper rerycling, return thi$ product to your local supplier upon the purchase of equivalent new equipment, or dispose of it at designated collection points. For more information. see: www. recyclethis. info. P/N 387023P-EN . REV 1 1 . tSS 23JAN14 3t4 4t4 P/N 387023P.EN . REV 11 . ISS 23UAN14