A16-0048 scope of work.pdf
CSWC ! Commercial Specialists of Western Colorado, LLC Tuesday, August 16, 2016 Vail Fire 42 West Meadow Drive Vail, CO 81657 Attn: Mike Vaughan, Fire Marshal Pjct: Fleeger Residence Re : Scope of Work for Fire Alarm System Dear Mike, The following is a scope of work to be performed for the Fleeger Residence at 2950 Booth Creek Drive. The scope of work will be to bring the residence up to NFPA standards adopted by Vail Fire. I have included a mark-up set of drawings with this scope of work to better detail the scope. Work performed will be to low frequency notification devices to each level and each bedroom for general alarm notification. 120vac Combination Smoke/CO devices will be added as required throughout. An exterior horn for fire sprinkler activation will be installed by the garage along with a stand alone CO detector in the mud room at the garage entry to the home. Each detection device will have a dedicated 18/6 FPL from the fire control panel and each floor will be provided with a dedicated 14/4 NAC circuit from the power supply. Whatever fire sprinkler devices are installed will be independently monitored at the fire panel location. The fire/security panel that we are providing for this scope is the Bosch B5512. Data sheets for all device that we intend to install are included in submittal. Once work has been completed and tested, CSWC will contact Vail Fire Department and schedule a final fire alarm test of the new area. If there are any questions or concerns about the above information, please feel free to contact me at any time. Sincerely, Commercial Specialists of Western Colorado, LLC 210 Marmot Lane Unit 5B * PO Box 3913 * Eagle, Colorado 81631 Voice (970) 328.1951 Fax (970) 328.1956 www.cswcfire.com CSWC ! Commercial Specialists of Western Colorado, LLC Tim Ward Tim Ward General Manager 210 Marmot Lane Unit 5B * PO Box 3913 * Eagle, Colorado 81631 Voice (970) 328.1951 Fax (970) 328.1956 www.cswcfire.com Intrusion Alarm Systems | B5512 Control Panels B5512 Control Panels www.boschsecurity.com u Provides up to 48 points using a combination of hardwired or wireless points for installation flexibility and up to 4 areas with perimeter and interior control u On-board Ethernet port for Conettix IP alarm communication and remote programming, compatible with modern IP networks including IPv6/ IPv4, Auto-IP, and Universal Plug and Play u Installer-friendly features including on-board USB for easy on-site RPS programming, plus support for Remote Connect Service and plug-in PSTN and cellular communication modules for simple installation and communications u Remote Security Control (RSC) app which allows users to control their security systems - and view system cameras - remotely from mobile devices such as phones and tablets u Programmable keypad shortcuts, situation sensitive on-screen help, and a bilingual user interface make system operation simple and easy The B5512 Control Panel integrates intrusion and residential fire, providing one simple user interface for both systems. The B5512 provides up to 48 individually identified points that can be split into 4 areas. The control panel can communicate through it’s built- in Ethernet port (not applicable to “E” control panels), or through compatible plug-in modules that can send events over the public switched telephone network (PSTN) or over cellular network communications. With the B5512, you can monitor doors, windows, and motion within areas like showrooms or those that hold inventory. Each user can have a personalized passcode, a wireless keyfob, and a credential to control the system. Use programmable authority levels with restricted privileges to provide service, security, and cleaning personnel with full or limited access. Use the three programmable outputs (expandable up to 43) to turn on lights or lock and unlock doors. Users can: • Turn on the system to secure the stockroom while you conduct daily business. • Perform tests to ensure your system is working properly. • Set your system to alarm immediately if a door opens. • Activate the Watch feature so a tone sounds whenever a customer enters. • Set a schedule for your system to automatically turn on at closing time. • Use wireless security options to customize your system. Central monitoring stations provide 24-hour system monitoring with access to vital services. Professional security personnel can test the system, monitor system activity, and alert the police, fire department, or other emergency response teams if necessary. Functions Programmable outputs• Three programmable on-board outputs; one high current using a relay, and two trigger outputs • Output A, with a contact rating of 3 Amps, can supply up to 1.0 A total current from AUX PWR • Outputs B and C sink up to 50 mA at 12 VDC • Four alarm-output patterns • Programmable bell test Point response • 20 custom point indexes • Selectable point response time • Cross point capability • Fire alarm verification • Dangerous gas indicator includes carbon monoxide (NFPA 720) • Watch mode User interface• Supervision of up to 8 keypads • Custom keypad text is fully programmable through RPS • Full function menu including custom functions • Authority by area and 32 character name for each user • 14 custom authority levels to restrict system features that each user can access • Programmable primary and secondary language by user and keypad; select from English, Spanish, French, and Portuguese Area configurations Link multiple areas to a shared area such as a lobby or common entryway. The shared area then automatically turns On (arms) when all associate areas are armed and turns Off (disarms) when any one associate area is disarmed. For higher security applications, the Area Re-Arm feature guarantees that areas are always rearmed, and are disarmed for no longer than a specific, configurable, amount of time (for example, service time). Custom functions For added convenience, the installer can program custom functions that allow customers to complete complex tasks with one simple action. For example, a custom function can bypass a group of points and arm the system, allowing the user to perform these functions with one easy command. Users can activate custom functions with a keypad, keyfob, token, or card, or the control panel can activate a function in reaction to a faulted point, or automatically through a scheduled event (SKED). Passcode security• Two-man rule. Requires two people with two unique passcodes to be present at the time of opening. • Early ambush. Allows users to verify that the facility is safe by requiring two passcodes. The control panel sends a duress event if the user does not enter the passcode a second time after inspecting the premises. • Dual authentication. Requires two forms of identification before processing certain system commands, including turning off the system and opening doors. A standard system user must have a passcode, a credential (token or card), and appropriate command authority permissions. Easy exit controlThe control panel changes from one On (armed) state to another without turning off (disarming) the system. For example, if you change the state from Part On (Perimeter Arm) to All On (Master Arm), the control panel complies and reports the change. Easy Exit Control reduces the number of keystrokes, simplifying system operation. Programmable passcode-controlled menu listPasscode-controlled shortcuts provide users only with the options and information pertinent to them, simplifying system operation. Flexible controlThe system provides the flexibility to choose added convenience or high security. For example, you can restrict to a keypad's immediate local area turning on (arming) and turning off (disarming) the system with a passcode, even if the user has access to other areas. This is particularly useful for high security areas, where a user may have access to the area, but would prefer to only turn off (disarm) the area individually rather than with the rest of the system. Monitor Delay/Delayed ResponseCreate a special point index that delays the reaction of a point for a specified time (up to 1 hour in minutes and seconds). This delay provides time for the specified condition to reset before activating any annunciation. The system can annunciate locally and send a report, if desired. When the system is armed, the point can respond like a normal point – providing dual functionality. Use this feature to ensure that perimeter doors have not been propped open, or to monitor critical areas such as computer rooms and safes, for example. System usersThe system supports up to 50 users. Each user can have a personalized passcode, a wireless keyfob, and a credential to control the system. You can assign passcodes to one of 14 customized authority levels in each area that can be restricted to operate only during certain times. Programmable primary and secondary language by user and keypad; select from English, Spanish, French, and Portuguese. 2 | B5512 Control Panels Communication formatsThe control panel prioritizes and sends reports to four route groups. Network and phone communications can use either the Modem4 or the Contact ID communications formats. Each group has a programmable primary and backup destination. The control panel provides flexible communications for most central stations with reporting capabilities such as: • Individual point numbers • Opening or closing reports by user and area number • Remote programming attempts • Diagnostic reports IP communicationThe control panel can use on-board Ethernet (IP) connection (the on-board Ethernet port is excluded on “E” versions) to communicate with a Conettix D6600 or a Conettix D6100IPv6 Communications Receiver/ Gateway. The control panel can optionally use a Conettix Plug-in Cellular Communicator (B440/B441/B442/B443). Using Conettix IP communication offers a secure path that includes anti-replay/anti-substitution features and provides enhanced security with up to AES 256-bit encryption (using Cipher Block Chaining (CBC)). The control panel supports Domain Name System (DNS) for both remote programming and central station communication. DNS provides ease of use, eliminating the need to use static IP addresses as your reporting destination, and accommodates a simple solution for central station disaster recovery. The control panel supports both IPv6 and IPv4 networks. Communication paths The control panel accommodates up to four separate phone and four separate network paths to the central station receiver. When resetting alarms or turning a system on and off, the user is identified by name and number. Personal notification The control panel can send text messages and emails for personal notification over Ethernet or using a cellular communicator. You can configure up to 16 destinations using a combination of cellular phone numbers and email addresses. The control panel sends notifications in the user’s programmed primary language. Bosch Remote Connect (Cloud)Remote Connect simplifies connections from RPS, and the Remote Security Control app, using Bosch Cloud services. This service creates a secure connection to the control panel without specific router settings or the need for a static IP address or DNS. Firmware updates The system allows remote firmware updates through Remote Programming Software (RPS) using the RPS Firmware Update Wizard. The Firmware Update Wizard uses the on-board USB connection or the on-board Ethernet (IP) connection (the on-board Ethernet port is excluded on “E” versions) to transfer firmware updates. The control panel can optionally receive firmware updates from RPS using a B426 Conettix Ethernet Communication Module or a Conettix Plug-in Cellular Communicator (B440/B441/B442/B443). Notice! Cellular firmware updates require more time than Ethernet updates and carrier data rates apply. • Control panel updates. Remotely update the control panel firmware for easy feature enhancements without replacing ROM chips. • Module update support. Remotely update the firmware on connected SDI2 modules for easy feature enhancements without visiting each individual module. A wide variety of input optionsEach point: • Single 1 kΩ, single 2 kΩ, dual 1 kΩ (1 kΩ + 1 kΩ), and No EOL (end-of-line) (EOL) resistor options (for on- board and B208 inputs) • Programmable for Fire, Intrusion, Gas, and Supervisory devices • Supports hardwired and wireless devices • Supports IP cameras by Bosch as point and output devices IP camera support The control panel can integrate directly with Bosch IP cameras, using them as fully supervised points and outputs. Integration of cameras allows the camera’s video motion detection to activate points on the control panel. The control panel’s virtual outputs can be configured to trigger camera actions, including sending video snapshots via email. Security and fire detectionThe control panel provides eight on-board points, and up to 40 additional off-board points (depending on model and expansion interfaces). You can program individual points to monitor some types of burglar alarms, fire alarms, and supervision devices. Event log The event log stores local and reported events. The event log includes information such as time, date, event, area, point, and user. View the event log from a keypad or use RPS to remotely retrieve event information. When the event log reaches a programmed threshold of stored events, it can send an optional report to a receiver. The event log stores up to 255 local and reported events. Scheduled events (SKEDs) The internal clock and calendar start individually scheduled events (SKEDs). SKEDs perform several functions such as turn on or off, relay control, or point bypassing. The control panel offers: 3 | B5512 Control Panels • Five scheduled events with up to 25 different functions • Four opening windows and four closing windows • Four user group windows • Day-of-week, date-of-month, or holiday only schedules • One holiday schedule of 366 days (leap year) ProgrammingInstallers can perform limited programming on-site with a keypad (critical parameters; such as account IDs, central station and RPS IP addresses and phone numbers, reporting formats, and more). They can also do full programming on-site or remotely (attended or unattended) with RPS. A programmable system passcode prevents unauthorized remote programming. DiagnosticsKeypads and RPS offer diagnostic help for monitoring and troubleshooting. The diagnostics features allow you to view the status of the wired and wireless devices. The features provide the status of the control panel and its connected devices, such as firmware version, power, and missing conditions. View the status of each area. Remote Security Control app The Remote Security Control (RSC) app allows users to control their security systems remotely from their devices. Users can: • Turn their security system On or Off • Turn specific areas On or Off • Control outputs for applications such as lighting control • View live video from Bosch IP cameras • Grant access remotely by unlocking and locking doors The app requires the installing dealer to create a Remote Access Profile for users, and to install the profile on their devices. Bosch Video Management System integrationWith Bosch Video Management System (Bosch VMS) and an intrusion system, the VMS operator has a single user interface to monitor and control the intrusion system combined with video surveillance. With Bosch VMS and a control panel, the operator can, for example: • View videos triggered by intrusion events, including all relevant information such as areas, point, and user show in the display with the event • View areas, points, outputs, and doors – with their statuses – on the Bosch VMS map, providing the exact location in the system. • Turn on (arm) and turn off (disarm) areas. • Bypass and unbypass points. Requirements to integrate Bosch VMS with a control panel: • A licensed Bosch VMS system using Professional Editions v5.5 or higher or Bosch VMS Enterprise • Edition v5.5 or higher. • Expansion license to integrate the intrusion control panel. One license needed per control panel. Order number MBX-XINT-xx for the expansion license added to a Bosch VMS base license. Refer to the Bosch Video Management Software product page on the Bosch website, www.boschsecurity.com. • Access to Remote Programming Software (RPS). Certifications and approvals Region Certification USA ANSI-SIA CP-01-2010-Control Panel Standard -Features for False Alarm Reduction Europe CE B6512, B5512, B5512E, B4512,B4512E, B3512, B3512E USA UL UL UL 365 - Police Station Connected Bur-glar Alarm Units UL UL 609 - Standard for Local BurglarAlarm Units and Systems UL UL 636 - Holdup Alarm Units and Sys-tems UL UL 985 - Household Fire Warning Sys-tem Units UL UL 1023 - Household Burglar Alarm Sys-tem Units UL UL 1076 - Proprietary Burglar AlarmUnits and Systems UL UL 1610 - Central Station Burglar AlarmUnits UL UL 1635 - Standard for Digital AlarmCommunicator System Units CSFM see our website FCC Part 15 Class B Canada ULC ULC CAN/ULC S303 - Local Burglar AlarmUnits and Systems ULC CAN/ULC S304 - Standard for Signal Re-ceiving Center and Premise BurglarAlarm ULC CAN/ULC S545 - Residential Fire Warn-ing System Control Units ULC CAN/ULC S559 - Fire Signal ReceivingCentres and Systems ULC ULC-ORD C1023 - Household BurglarAlarm System Units ULC ULC-ORD C1076 - Proprietary BurglarAlarm Units and Systems IC ICES-003 - Information TechnologyEquipment (ITE) Installation/configuration notes Compatible products Keypads B942/B942W Touch Screen Keypad (SDI2) 4 | B5512 Control Panels B930 ATM Style Alphanumeric Keypad (SDI2) B921C Two-line Capacitive Keypad (SDI2) B920 Two-line Alphanumeric Keypad (SDI2) B915/B915I Basic Keypad (SDI2) Transformers CX4010 Plug-in Transformer (18 VAC 22 VA 60 Hz) ICP‑TR1822‑CAN Plug‑in Transformer (110 VAC primary, 18 VAC 22 VA secondary) Enclosures B10 Medium Control Panel Enclosure B11 Small Control Panel Enclosure B12 Mounting Plate for D8103 Enclosure B8103 Universal Enclosure (requires a B12) D8108A Attack Resistant Enclosure (requires a B12) D8109 Fire Enclosure (requires a B12) Accessories B56 Keypad Surface Mount Box B96 Keypad Trim Bezel B99 USB Direct Connect Cable B501-10 Interconnect wiring cables (pack of 10) Detectors FCC-380 Carbon Monoxide Detector Bosch conventional detectors, including Professional Series, Blue Line Gen2, Blue Line, Classic Line, Commercial Line, and Ceiling Mount motion detectors, as well as glass break, seismic, request-to-exit, photoelectric, heat, and smoke detectors. Modules B201 2-wire Powered Loop Module B208 Octo-input Module B308 Octo-output Module B426 Conettix Ethernet Communication Module B430 Plug-in Telephone Communicator B440 Conettix Plug-in Cellular Communicator (using 3G) B441 Conettix Plug-in Cellular Communicator (using CDMA) B442 Conettix Plug-in Cellular Communicator (using GPRS)* B443 Conettix Plug-in Cellular Communicator (using HSPA+)* B450 Conettix Plug-in Communicator Interface B520 Auxiliary Power Supply Module B810 wireless receiver (RADION) B820 SDI2 Inovonics Interface Module D113 Battery Lead Supervision Module D125B Dual Class B Initiating Module D129 Class A Initiating Module D130 Auxiliary Relay Module D132A Smoke Detector Reversing Relay Module D133/D134 Relay Module D135A Low Battery Disconnect Module D185 Reverse Polarity Signaling Module D192G Class “B”, Style Y Bell Circuit Supervision Applications Remote Programming Software (RPS or RPS-LITE) v6.03 and higher Bosch Video Management System v5.5 and higher Conettix receivers (Managed and configured with Conettix D6200 Programming/ Administration Software v2.00) Conettix D6600 Communications Receiver/Gateway (with only D6641 line cards installed) with CPU version 01.10.00 Conettix D6100IPv6 Communications Receiver/Gateway with CPU version 61.10.00 Conettix D6100i Communications Receiver/Gateway with CPU version 61.10.00 RADION wireless from Bosch B810 wireless receiver (RADION) RFBT-A bill trap RFDL-11-A TriTech motion detector RFDW-RM-A recessed mount door/window contact RFDW-SM-A surface mount door/window contact RFGB-A glass break detector RFIN-A inertia detector RFKF-A two-button keyfob RFKF-FBS-A four-button keyfob RFKF-TBS-A two-button keyfob RFPB-SB-A single-button panic RFPB-TB-A two-button panic RFRP-A repeater RFSM-A smoke detector RFPR-12-A PIR motion detector 5 | B5512 Control Panels RFPR-C12-A PIR curtain motion detector RFUN-A universal transmitter Inovonics Wireless B820 SDI2 Inovonics Interface Module ENKIT-SDI2 SDI2 Inovonics Interface and Receiver Kit. Includes B820 and EN4200 EN1210 Universal Transmitter (Single-input) EN1210EOL Universal Transmitter with EOL Resistor EN1210W Door-Window Transmitter with Reed Switch EN1215EOL Universal Transmitter with Wall Tamper, Reed Switch, and EOL Resistor EN1223D Water‑resistant Pendant Transmitter (Double‑button) EN1223S Water‑resistant Pendant Transmitter (Single‑button) EN1224-ON Multiple-Condition Pendant Transmitter EN1233D Necklace Pendant Transmitter (Double-button) EN1233S Necklace Pendant Transmitter (Single-button) EN1235D Beltclip Pendant Transmitter (Double-button) EN1235DF Fixed-location Transmitter (Double-button) EN1235S Beltclip Pendant Transmitter (Single-button) EN1235SF Fixed-location Transmitter (Single-button) EN1247 Glass-break Detector Transmitter EN1249 Bill Trap Transmitter EN1242 Smoke Detector Transmitter EN1260 Wall Mount Motion Detector EN1261HT High Traffic Motion Detector EN1262 Motion Detector with Pet Immunity EN1265 360° Ceiling Mount Motion Detector EN4200 Serial Receiver EN5040-T High Power Repeater with Transformer *For these cellular modules, check for availability in your region. Parts included Qty.Component 1 Control panel 1 Literature pack • UL Installation Guide • ULC Installation Guide (English and French) • Owner’s Manual • Release Notes • SIA Quick Reference Guide • Quick Installation Guide 1 Literature CD containing product literature 1 Wiring label for enclosure door 1 Hardware pack • Mounting clips • 1 kΩ EOL resistors • Battery wires • Four #6 x 3/4 in self threading screws Quant.Component 1 Control panel (without on-board Ethernet port) 1 Plug-in communicator (telephone or cellular, depending on the kit) 1 Plug-in Transformer (18 VAC 22 VA 60 Hz) 1 Control panel enclosure (kit dependent) 1 Literature pack 1 Literature CD containing product literature 1 Wiring label for enclosure door 1 Hardware pack Technical specifications Communications Ethernet 10/100 full duplex (N/A for “E” control panels) Environmental considerations Relative humidity 5% to 93% at +90℉ (+32℃), non-condensing Temperature (operating)+32°F to +122°F (0°C to +49°C) Number of… Areas 4 Custom functions 4 Events Up to 255 Passcode users 50, plus 1 Installer passcode Points 48 (8 on-board, up to 40 off-board and virtual) Programmable outputs 43 (3 on-board, up to 40 off-board and virtual) RF points 40 IP cameras 4 SKEDs 5 6 | B5512 Control Panels Power Requirements Current draw (maximum)Idle 125 mA; Alarm 155 mA Output (alarm)1.3 A at 12 VDC Output (auxiliary, continuous power, and switched auxiliary combined) 800 mA at 12 VDC nominal Voltage (operating):12 VDC nominal Voltage (AC)CX4010 Plug-in Transformer (18 VAC 22 VA 60 Hz) or ICP‑TR1822‑CAN Plug‑in Transformer (110 VAC primary, 18 VAC 22 VA secondary) Ordering information B5512 Control Panel The B5512 is available individually or in kits. For kits, refer to Quick Selection Guide (B Series Kits) on the Documents tab of the control panel’s Product Page at us.boschsecurity.com. Order number B5512 B5512E Control Panel The B5512E is available only in kits. For kits, refer to Quick Selection Guide (B Series Kits) on the Documents tab of the control panel’s Product Page at us.boschsecurity.com. Order number B5512E Accessories B520 Auxiliary Power Supply Module Provides auxiliary power to 12 VDC devices or to SDI2 modules. Order number B520 B201 2-wire Powered Loop Module The module provides a single powered initiating device circuit. The module supports compatible 12 V 2-wire smoke detectors. It also supports connecting burglary devices to the control panel. Order number B201 B208 Octo-input Module Provides 8 programmable inputs. Order number B208 B308 Octo-output Module Provides 8 programmable relays. Order number B308 RADION receiver SD Receives RF signals from RADION transmitters, repeaters, and glassbreaks. Operates at 433.42 MHz. For use with compatible SDI2 bus control panels. Order number B810 D122 Dual Battery Harness Harness with circuit breaker. Connects two batteries to a compatible control panel. Order number D122 D122L Dual Battery Harness with Long Leads Color-coded harness with circuit breaker and leads measuring 89 cm (35 in.). Connects 12 V batteries to compatible control panels. Order number D122L D126 Standby Battery (12 V, 7 Ah) A rechargeable sealed lead‑acid power supply used as a secondary power supply or in auxiliary or ancillary functions. Order number D126 D1218 Battery (12 V, 18 Ah) A 12 V sealed lead‑acid battery for standby and auxiliary power with two bolt‑fastened terminals. Includes hardware for attaching battery leads or spade connectors Order number D1218 CX4010 Plug‑in Transformer For use in North America. 110 VAC primary voltage input. 18 VAC, 22 VA secondary input. Order number CX4010 ICP‑TR1822‑CAN Plug‑in Transformer For use in Canada. 110 VAC primary voltage input. 18 VAC, 22 VA secondary input. Order number ICP-TR1822-CAN B8103 Enclosure White steel enclosure measuring 41 cm x 41 cm x 9 cm (16 in. x 16 in. x 3.5 in.). Order number B8103 D8103 Enclosure Grey steel enclosure measuring 41 cm x 41 cm x 9 cm (16 in. x 16 in. x 3.5 in.). Order number D8103 D8108A Attack Resistant Enclosure Grey steel enclosure measuring 41 cm x 41 cm x 9 cm (16 in. x 16 in. x 3.5 in.). UL Listed. Includes a lock and key set. Order number D8108A D8109 Fire Enclosure Red steel enclosure measuring 40.6 cm x 40.6 cm x 8.9 cm (16 in. x 16 in. x 3.5 in). UL Listed. Includes a lock and key set. Order number D8109 B10 Medium Control Panel Enclosure White, steel enclosure. Accepts an optional lock and tamper switch. Measures 35.6 cm x 31.8 cm x 7.6 cm (14 in x 12.5 in x 3 in). Order number B10 7 | B5512 Control Panels B11 Small Control Panel Enclosure White, steel enclosure. Accepts an optional lock and tamper switch. Measures 27.8 cm x 25.9 cm x 8.32 cm (10.9 in x 10.2 in x 3.3 in). Order number B11 B12 Mounting Plate for D8103 Enclosure Required for mounting select control panels and other devices in D8103, D8108A, D8109, or BATB Battery Box enclosures. Order number B12 D8004 Transformer Enclosure For applications such as fire alarm that might require a transformer enclosure. Order number D8004 D101 Lock and Key Set Short-body lock set with one key supplied. Uses the D102 (#1358) replacement key. Order number D101 D110 Tamper Switch Screw‑on tamper switch that fits all enclosures. Shipped in packages of two. Order number D110 ICP‑EZTS Dual Tamper Switch Combination tamper switch with a wire loop for additional tamper outputs. Order number ICP-EZTS B99 USB Direct Connect Cable Male A to Male A USB cable for local programming of control panels with on-board USB ports. Order number B99 B915 Basic Keypad Two-line alphanumeric basic keypad with English function keys. Order number B915 B915I Basic Keypad Two-line alphanumeric basic keypad with icon function keys. Order number B915I B920 Two-line Alphanumeric Keypad (SDI2) Two-line alphanumeric keypad Order number B920 B921C Two-line Capacitive Keypad with Inputs (SDI2) Two-line alphanumeric keypad with inputs and capacitive touch keys in black. Order number B921C B930 ATM Style Alphanumeric Keypad (SDI2) Five-line ATM style alphanumeric keypad Order number B930 B942 Touch Screen Keypad Black SDI2 touch screen keypad with inputs and one output. Order number B942 B942W Touch Screen Keypad White SDI2 touch screen keypad with inputs and one output. Order number B942W Software Options RPS Software RPS software is available for free download on the RPS product page. It is also available on DVD-ROM. Order number D5500CU Bosch VMS Enterprise Edition Base license for Enterprise System. 2 Management Server subsystems (1 required for Enterprise Management); 8 cameras; 2 workstations (1 with Forensic Search); 1 CCTV keyboard; 1 DVR. All MBV-X* and MBV-F* options are only available with Base license. Order number MBV-BENT-65 Bosch VMS Professional Edition Base license for Professional Edition. 8 cameras; 2 workstations (1 with Forensic Search); 1 CCTV keyboard; 1 DVR. All MBV-X* and MBV-F* options are only available with Base license. Order number MBV-BPRO-65 8 | B5512 Control Panels 9 | B5512 Control Panels Represented by: Europe, Middle East, Africa:Germany:North America:Asia-Pacific:Bosch Security Systems B.V. P.O. Box 800025600 JB Eindhoven, The NetherlandsPhone: + 31 40 2577 284emea.securitysystems@bosch.com emea.boschsecurity.com Bosch Sicherheitssysteme GmbH Robert-Bosch-Ring 585630 GrasbrunnGermanywww.boschsecurity.com Bosch Security Systems, Inc. 130 Perinton ParkwayFairport, New York, 14450, USAPhone: +1 800 289 0096Fax: +1 585 223 9180 onlinehelp@us.bosch.comwww.boschsecurity.us Robert Bosch (SEA) Pte Ltd, Security Systems 11 Bishan Street 21Singapore 573943Phone: +65 6571 2808Fax: +65 6571 2699 apr.securitysystems@bosch.comwww.boschsecurity.asia © Bosch Security Systems 2016 | Data subject to change without notice 6085453963 | en, V33, 29. Jul 2016 Intrusion Alarm Systems | B942 Touch Screen Keypad B942 Touch Screen Keypad www.boschsecurity.com u Color graphic touch screen display uses a combination of simple icons and text for easy operation u Built-in presence detector lights the display when user approaches keypad u Built-in proximity reader allows use of a token or card as replacement for a passcode, or for use with dual authentication for high security areas u Four inputs and one output provide cost effective expansion u Slim, modern design blends with any decor The B942 keypad is an SDI2 bus compatible device. The keypad features an illuminated touch screen and graphical interface. With an elegant design and low profile, the keypad fits with any modern decor. Each keypad has user adjustable options such as volume and brightness. They have four inputs and one output. The keypad shows system messages for all areas. System overview • For commercial use, install the keypad in building entrances and areas with unrestricted access. Mounting a keypad near exterior doors in hotel or business lobbies allows people to identify the type and location of the emergency. • For residential use, install the keypad near the front and rear entrances to the home. Install additional keypads in a kitchen or in a bedroom. • Use multiple keypads in a large building with many separate areas of security. Program multiple keypads to control multiple areas. • Audible tones from the keypad sounder alert personnel to fire events and assist fire fighters in locating the keypad. Functions DisplayThe touch screen display uses icons, words, numbers, and symbols to show the status of the security system and for interacting with the security system. When several events occur, the keypad shows each event in order of priority. The keypad detects when a user approaches and automatically activates the display. User icons and keys The keypad greets the user with a home screen that shows the system status at one glance using a large icon. The user can change the system status by simply touching this home screen icon. The touch screen display also offers icons on the ribbon bar. These visually pleasing graphical icons are easy to use for accessing menus and other options. The keypad has a variety of keyboards for entering alphanumeric characters. The keypad screen has numeric keys and one function [CMD] key. When pressed, keys emit a muted beep. Use the keyboards for entering passcodes, activating commands, and entering alphanumeric characters. Audible tonesThe keypad has a built-in speaker that produces several distinct warning tones. The tones are differentiated so that the user can recognize an event simply by hearing its associated tone. The keypad backlight illuminates when it emits an audible tone. Users can use a passcode or credential to silence the tone. Status indicatorsThe status indicators on the keypad provide a quick visual reference for system status. The indicator lights when the system is ready to turn on (arm). The indicator lights when the system is on (armed). The indicator lights when there is a trouble condition. The indicator lights when dangerous gases are present including carbon monoxide (NFPA 720). The indicator lights when the system has power. Proximity reader The proximity reader allows users to use a token or card in place of a passcode to turn on or off the security system. The proximity reader supports EM4102 (125 kHz) credentials. The Bosch ACA-ATR13- RFID tag and Bosch ACD-ATR11ISO-RFID card are examples. Certifications and approvals Region Certification Europe CE EMC, LVD, R&TTE, RoHS USA UL UL 365 - Police Station Connected Bur-glar Alarm Units UL UL 609 - Standard for Local BurglarAlarm Units and Systems UL UL 636 - Holdup Alarm Units and Sys-tems UL UL 985 - Household Fire Warning Sys-tem Units UL UL 1023 - Household Burglar Alarm Sys-tem Units UL UL 1076 - Proprietary Burglar AlarmUnits and Systems UL UL 1610 - Central Station Burglar AlarmUnits CSFM see our website FCC Part 15 Class B Canada ULC CAN/ULC S303 - Local Burglar AlarmUnits and Systems ULC CAN/ULC S304 - Standard for Signal Re-ceiving Center and Premise BurglarAlarm Region Certification ULC CAN/ULC S545 - Residential Fire Warn-ing System Control Units ULC ULC-ORD C1023 - Household BurglarAlarm System Units ULC ULC-ORD C1076 - Proprietary BurglarAlarm Units and Systems IC ICES-003 - Information TechnologyEquipment (ITE) Installation/configuration notes Power supplyA compatible control panel supplies the power and data requirements to the keypad through a four-wire connection. Mounting and wiring Mount in dry indoor locations. Includes a slim mounting plate for recessing wiring, and a surface mounting plate for surface mounting and wiring. Compatible control panels B9512G/B9512G-E B8512G/B8512G-E B6512 B5512/B5512E firmware v2.03 and higher B4512/B4512E firmware v2.03 and higher B3512/B3512E firmware v2.03 and higher D9412GV4/D7412GV4 v2.03 and higher Parts included Quant.Component 1 Keypad 2 Mounting plates (slim and surface) 1 Hardware pack 4 1k Ω EOL Resistors 1 Installation Guide 1 User’s Quick Reference Guide Technical specifications Properties Dimensions 6.2 in x 4.7 in x 0.65 in (158 mm x 120 mm x 16.5 mm) Weight 11.3 oz (0.32 kg) Material Acrylonitrile butadiene styrene (ABS) Poly(methyl methacrylate) (PMMA) Display window Touch screen Multi-line messages 2 | B942 Touch Screen Keypad Indicators Power indicator LED Status indicators Main icon Warning and indicating tones Inputs 4 (four) 1k Ω supervised inputs Output 1 (one) NO (normally open) contact Environmental considerations Relative humidity 5% to 93% at +32°C (+90°F) non- condensing Temperature (operating)0°C to +50°C (+32°F to +122°F) Power requirements Current with proximity reader disabled Standby: 200 mA Alarm: 300 mA Current with proximity reader enabled Standby: 300 mA Alarm: 400 mA Voltage (input)12 VDC nominal Wiring Terminal wire size 18 AWG to 22 AWG (1.02 mm to 0.65 mm) SDI2 wiring with prox detector disabled Maximum distance - wire size (unshielded wire only): 200 ft (61 m) - 22 AWG (0.65 mm) 520 ft (159 m) - 18 AWG (1.02 mm) SDI2 wiring with prox detector enabled Maximum distance - wire size (unshielded wire only): 150 ft (46 m) - 22 AWG (0.65 mm) 390 ft (119 m) - 18 AWG (1.02 mm) Inputs and output On-board points voltage ranges Open: 2.2 to 5.0 VDC Normal: 1.4 to 1.8 VDC Short: 0.0 to 1.0 VDC Short circuit current: 2.3 mA Relay contact rating 24 VDC, 1 A, power factor: 1 Ordering information B942 Touch Screen Keypad Black SDI2 touch screen keypad with inputs and one output. Order number B942 B942W Touch Screen Keypad White SDI2 touch screen keypad with inputs and one output. Order number B942W Accessories B56 Keypad Surface Mount Box Surface mount box for mounting a keypad to concrete or block. Order number B56 B96 Keypad Trim Bezel Cover the wall footprint of previous keypads when replacing them with the new, slim design of B Series keypads. The white trim bezel is 8.6 in x 6.3 in x 0.12 in (22 mm x 16 mm x 3 mm). Order number B96 3 | B942 Touch Screen Keypad 4 | B942 Touch Screen Keypad Represented by: Europe, Middle East, Africa:Germany:North America:Asia-Pacific:Bosch Security Systems B.V. P.O. Box 800025600 JB Eindhoven, The NetherlandsPhone: + 31 40 2577 284emea.securitysystems@bosch.com emea.boschsecurity.com Bosch Sicherheitssysteme GmbH Robert-Bosch-Ring 585630 GrasbrunnGermanywww.boschsecurity.com Bosch Security Systems, Inc. 130 Perinton ParkwayFairport, New York, 14450, USAPhone: +1 800 289 0096Fax: +1 585 223 9180 onlinehelp@us.bosch.comwww.boschsecurity.us Robert Bosch (SEA) Pte Ltd, Security Systems 11 Bishan Street 21Singapore 573943Phone: +65 6571 2808Fax: +65 6571 2699 apr.securitysystems@bosch.comwww.boschsecurity.asia © Bosch Security Systems 2016 | Data subject to change without notice 14472973195 | en, V10, 01. Aug 2016 Intrusion Alarm Systems | B208 Octo-input Module B208 Octo-input Module www.boschsecurity.com u Programmable input point functions u Easy to read switch addressing u 2 interconnect wiring connectors u Provides eight points The B208 Octo-input Module is an 8 point expansion device that connects to the control panel through the SDI2 bus. This module is fully supervised and communicates back to the control panel all point status changes. The module expansion points operate the same as the points on the control panel. Industrial, commercial, and institutional facilities are typical installations for the B208 module. The B208 connects to the SDI2 bus on the control panel using SDI2 terminals, or using the interconnect cable. You can connect multiple B208 modules to a single control panel. The B208 address switches allow for ease of use in device addressing. System overview The B208 Octo-input Module connects to a control panel through the SDI2 bus. This module is supervised and communicates back to the control panel all point status changes. The module’s expansion points operate the same as the points on the control panel. Functions Loop inputsThe B208 uses up to eight inputs which may be Normally Open (NO), or Normally Closed (NC) with 1k Ω EOL resistor(s) for supervision. Certifications and approvals Region Certification Europe CE EMC, RoHS B915, B920, B930, B430,B208, B308, B901 USA UL UL UL 365 - Police Station Connected Bur-glar Alarm Units UL UL 609 - Standard for Local BurglarAlarm Units and Systems UL UL 636 - Holdup Alarm Units and Sys-tems UL UL 864 - Standard for Control Units andAccessories for Fire Alarm Systems UL UL 985 - Household Fire Warning Sys-tem Units UL UL 1023 - Household Burglar Alarm Sys-tem Units UL UL 1076 - Proprietary Burglar AlarmUnits and Systems UL UL 1610 - Central Station Burglar AlarmUnits FM FM 3010 - Fire Alarm Signaling Systems CSFM see our website Region Certification FCC Part 15 Class B FDNY-CoA 6174 FDNY-CoA 6196 Canada ULC CAN/ULC S303 - Local Burglar AlarmUnits and Systems ULC CAN/ULC S304 - Standard for Signal Re-ceiving Center and Premise BurglarAlarm ULC ULC-ORD C1023 - Household BurglarAlarm System Units ULC ULC-ORD C1076 - Proprietary BurglarAlarm Units and Systems IC ICES-003 - Information TechnologyEquipment (ITE) Installation/configuration notes Wiring considerationsThe module to the control panel using the PWR, A, B, COM terminals on the control panel using the screw terminal strip or the interconnect wiring connector. Use 12 AWG to 22 AWG (1.5 mm to 0.6 mm) wires from the module to the control panel. Compatibility For UL 864 compliance, use a UL commercial fire approved control panel. Control panels B9512G/B9512G-E (Up to 59 modules) B8512G/B8512G-E (Up to 9 modules) B6512 (Up to 9 modules) B5512/B5512E (Up to 4 modules) B4512/B4512E (Up to 2 modules) D9412GV4 (Up to 24 modules) D7412GV4 (Up to 7 modules) D7212GV4 (Up to 3 modules) Parts included Quantity Component 1 Octo-input module 1 Hardware pack 1 interconnect cable 1 Literature pack Technical specifications Properties Dimensions 2.5 in x 3.8 in x 0.60 in (6.37 cm x 9.6 cm x 1.5 cm) Environmental considerations Relative humidity 5% to 93% at +32°C (+90°F) Temperature (operating)0°C to +49°C (+32°F to +120°F) Power requirements Current 35 mA Voltage 12 VDC nominal Wiring SDI2 wiring Maximum distance – Wire size (unshielded wire only): 1000 ft (305 m) – 22 AWG (0.65 mm) 1000 ft (305 m) – 18 AWG (2 mm) Unshielded wire only Loop inputs Loop Inputs Up to eight inputs. Input contacts may be Normally Open (NO) or Normally Closed (NC) with 1kΩ EOL resistor(s) for supervision. Note: Normally Closed (NC) is not permitted in Fire installations. Ordering information B208 Octo-input Module Provides 8 programmable inputs. Order number B208 2 | B208 Octo-input Module 3 | B208 Octo-input Module Represented by: North America:Europe, Middle East, Africa:Asia-Pacific:China:Latin America and Caribbean:Bosch Security Systems, Inc. 130 Perinton ParkwayFairport, New York, 14450, USAPhone: +1 800 289 0096Fax: +1 585 223 9180 security.sales@us.bosch.comwww.boschsecurity.us Bosch Security Systems B.V. P.O. Box 800025617 BA Eindhoven, The NetherlandsPhone: + 31 40 2577 284Fax: +31 40 2577 330 emea.securitysystems@bosch.comwww.boschsecurity.com Robert Bosch (SEA) Pte Ltd, Security Systems11 Bishan Street 21Singapore 573943Phone: +65 6571 2808 Fax: +65 6571 2699apr.securitysystems@bosch.comwww.boschsecurity.asia Bosch (Shanghai) Security Systems Ltd. 203 Building, No. 333 Fuquan RoadNorth IBPChangning District, Shanghai200335 China Phone +86 21 22181111Fax: +86 21 22182398www.boschsecurity.com.cn Robert Bosch Ltda Security Systems Division Via Anhanguera, Km 98CEP 13065-900Campinas, Sao Paulo, BrazilPhone: +55 19 2103 2860 Fax: +55 19 2103 2862latam.boschsecurity@bosch.comwww.boschsecurity.com © Bosch Security Systems 2016 | Data subject to change without notice 2536957579 | en, V20, 12. Jul 2016 G N -5 0 3 S E R I E S Standard Product Features •GN-503 available in 120VAC with 9VDC battery back-up •Horn frequency 3100 Hz (nominal) •Meets sensitivity requirements of ANSI/UL 2034 •F Model:One (1)set of Form A/Form C contacts that activate for smoke and/or CO events ••FFFF MMooddeell:: TTwwoo ((22)) sseettss ooff FFoorrmm AA//FFoorrmm CC ccoonnttaaccttss tthhaatt aaccttiivvaattee iinnddeeppeennddeennttllyy ffoorr ssmmookkee aanndd CCOO eevveennttss •Relay contacts operate on battery back-up •Push button self test feature •Push button functional test feature •Quick-disconnect wiring harness •Non-latching (self restoring) alarm •Fully insect protected •Red LED pulses every 30 seconds, green LED for AC power on •Mounting hardware adapts to standard junction boxes, including but not limited to 4x4x2-1/8 octagon •Dust cover to prevent contamination during installation •Low or missing battery indicator •1 year warranty from date of purchase •5 year limited warranty on CO sensorAdditional Smoke Alarm Features •Photoelectric smoke sensing technology •Temporal 3 evacuation sounding pattern for smoke annunciation •Nominal 2.5% sensitivity (smoke) •Solid state red LED to indicate smoke presence Additional CO Alarm Features •Electrochemical sensor •Temporal 4 sounding pattern for CO annunciation •End of life signal indicates CO sensor has reached depletion state and unit must be replaced •• AANNSSII//UULL 221177 aanndd AANNSSII//UULL 22003344 LLiisstteedd •• CCSSFFMM ## 55227766--00556699::114444 Combination Photoelectric Smokeand Carbon Monoxide Alarm 120VAC/9VDC Single/Multiple Station Smoke and CO Alarm Product Listings Applications The GN-503 (120VAC/9VDC) Series of combination photoelectric smoke and electrochemical sensor carbon monoxide alarms are for use as evacuation devices in all dwelling units, including but not limited to homes, apartments, hospitals, hotels, motels and other commercial occupancies. The GN-503 Series is listed in compliance with ANSI/UL 217, ANSI/UL 2034, for installation per NFPA 720 and NFPA 72. Available in three models, the GN-503 Series is engineered to virtually eliminate nuisance alarms and deliver outstanding performance wherever reliable smoke and CO protection is required. The GN-503F features one (1) set of Form A/Form C contacts that activate for smoke and/or CO events. TTHHEE GGNN--550033FFFF FFEEAATTUURREESS TTWWOO ((22)) SSEETTSS OOFF FFOORRMM AA// FFOORRMM CC CCOONNTTAACCTTSS TTHHAATT AACCTTIIVVAATTEE IINNDDEEPPEENNDDEENNTTLLYY FFOORR SSMMOOKKEE AANNDD CCOO EEVVEENNTTSS.. Both the GN-503F and GN-503FF provide a connection to a protected premises alarm system to provide a supervisory/trouble signal. The GN-503 Series is provided with a 9VDC alkaline battery for electrical back-up in the event building power is lost. The battery impedance is verified and the alarm provides a low or missing battery warning. The battery drawer provides easy replacement without removing the unit from the wall or ceiling. The GN-503 Series is designed with a self test feature that quickly notifies if the alarm is functioning properly or needs attention (signified by a series of chirps) by simply pressing the test button. The functionality tests that the smoke/CO alarm is operating properly (signified by going into alarm). The self and functionality tests are in compliance with NFPA 72, NFPA 720 and ANSI/UL Standards. The GN-503 Series provides a temporal 3 evacuation tone for smoke alarm annunciation and all units provide a temporal 4 tone for CO alarm annunciation. Per NFPA 720, the temporal 3 evacuation tone for smoke alarm will take precedence over the temporal 4 tone for CO alarm. •• NNFFPPAA 7722 aanndd NNFFPPAA 772200 •• IIBBCC//IIFFCC//IIRRCC •• CCiittyy && SSttaattee OOrrddiinnaanncceess//LLaawwss//RReegguullaattiioonnss •• QQuuaalliittyy MMaannaaggeemmeenntt SSyysstteemm iiss cceerrttiiffiieedd ttoo:: IISSOO 99000011::22000088 Product Compliance NN EE WW FF EE AA TT UU RR EE SS MMooddeell NNuummbbeerr VVoollttaaggee 99VVDDCC BBaatttteerryy BBaacckk--UUpp OOnnee ((11)) SSeett FFoorrmm AA// FFoorrmm CC RReellaayy CCoonnttaaccttss TTwwoo ((22)) SSeettss FFoorrmm AA// FFoorrmm CC RReellaayy CCoonnttaaccttss GN-503 120VAC GN-503F 120VAC GN-503FF 120VAC GN-503 AND GN-503F Wiring Diagrams GN-503 Series Combination Smoke/CO Alarm GN-503/GN-503F ADDITIONAL PRODUCT INFORMATION THE GN-503F AND GN-503FF PRODUCT WIRING HARNESS IS NOT INTERCHANGEABLE. THE GN-503F AND GN-503FFMUST USE PROPER WIRING HARNESS. PRODUCT WILL NOT FUNCTION IF INCORRECT HARNESS IS USED. DO NOT connect Gentex alarms to other manufacturers’ alarms.Per NFPA 72, a maximum of 18 compatible smoke, heat, CO and/or combination smoke/CO alarms may be interconnected. No more than 12 of the 18 can be smoke alarms. All units connected in tandem MUST get their power from the same circuit, that is, all smoke alarms in tandem must be controlled by the same fuse or circuit breaker. NOTICE: PER NFPA 72, A MAXIMUM OF 12 SMOKE/CO ALARMS OF GN-503 WITH THE RELAY OPTION (F) MAY BE TANDEM INTERCONNECTED. The GN-503/GN-503F may be tandem interconnected with other Gentex tandem capable smoke alarms, CO alarms or smoke/COalarms. To interconnect with Gentex 9000 Series, 7000 Series, 710CS Series, 7109CS Series, GN-200 Series & GN-300 Seriesthe LEGACY TANDEM WIRE must be used. Refer to installation manual for detailed information. CCAAUUTTIIOONN::RED/YELLOW & BROWN/YELLOW wire to be capped when not in use. This wire is for tandem connection only. Do notconnect to any other circuit. If a GN-503 Series or CO1209 Series unit is annunciating for a CO event, legacy products that are tandem interconnected will not activate and will remain silent.If smoke alarm portion of device goes into alarm, all smoke alarms, CO alarms or combination smoke/CO alarms tandem wired will sound smoke alarm warning.When both smoke and CO conditions are present, smoke condition will have priority and alarm will sound smoke annunciation. PLUG SMOKE/CO ALARM BLK WHT RED / YEL VIO VIO / BLK BLU ORN YEL GRAY GRAY HOT NEUT POWER TANDEM - LEGACY ALARM CONTACTS ACCESSORY ALARM CONTACTS INTERNAL JUMPER BRN / YEL TANDEM ELECTRICAL BOXSMOKE/COALARM QUICK DISCONNECTTYPE PLUG HOT / BLACK NEUTRAL / WHITE TANDEM WIREBRN / YEL SMOKEALARM SMOKE/COALARMELECTRICAL BOXELECTRICAL BOXTANDEM WIRE RED / YEL(LEGACY) (LEGACY) USING THE GENTEX GN-503FF COMBINATION SMOKE AND CARBON MONOXIDE ALARM ALLOWS THE ABILITY TO: • Interface with a FACP Panel• Interface with NAC Circuits GN-503FF ADDITIONAL PRODUCT INFORMATION Use brown/yellow wire to tandem interconnect GN-503FF alarms to additional GN-503 Series, S1209 Series and CO1209 Series. NOTICE: THE GN-503FF IS ONLY CAPABLE OF TANDEM INTERCONNECT WITH GN-503 SERIES, CO1209 SERIES AND S1209 SERIES. THE GN-503F AND GN-503FF PRODUCT WIRING HARNESS IS NOT INTERCHANGEABLE. THE GN-503F AND GN-503FF MUST USE PROPER WIRING HARNESS. PRODUCT WILL NOT FUNCTION IF INCORRECT HARNESS IS USED. DO NOT connect Gentex alarms to other manufacturers’ alarms. Per NFPA 72, a maximum of 18 compatible smoke, heat, CO and/or combination smoke/CO alarms may be interconnected. No more than 12 of the 18 can be smoke alarms. All units connected in tandem MUST get their power from the same circuit, that is, all smoke alarms in tandem must be controlled by the same fuse or circuit breaker. NOTICE: PER NFPA 72, A MAXIMUM OF 12 SMOKE/CO ALARMS OF GN-503 WITH THE RELAY OPTION (FF) MAY BE TANDEM INTERCONNECTED. CCAAUUTTIIOONN::BROWN/YELLOW wire to be capped when not in use. This wire is for tandem connection only. Do not connect to any other circuit. If smoke alarm portion of device goes into alarm, all smoke alarms, CO alarms or combination smoke/CO alarms tandem wired will sound smoke alarm warning. When both smoke and CO conditions are present, smoke condition will have priority and alarm will sound smoke annunciation. GN-503FF Wiring Diagrams PLUG SMOKE/CO ALARM BLK WHT VIO VIO ORN YEL HOT NEUT POWER SMOKE ALARM CONTACTS (FORM A CONTACT) BRN / YEL TANDEM SMOKE FORM C COMMON SMOKE NORMALLY CLOSED CO ALARM CONTACTS (FORM A CONTACT) PINK PINK BLU GRAY VIO / YEL FORM CALARM CONTACTSSMOKE & CO NORMALLY OPEN CO FORM C COMMON CO NORMALLY CLOSED ELECTRICAL BOXSMOKE/COALARM QUICK DISCONNECTTYPE PLUG HOT / BLACK NEUTRAL / WHITE TANDEM WIREBRN / YEL SMOKE/COALARMELECTRICAL BOXELECTRICAL BOXSMOKE/COALARM G N -5 0 3 S E R I E S 551-0073-04Important Notice: These materials have been prepared by Gentex Corporation ("Gentex") for informational purposes only,are necessarily summary, and are not purported to serve as legal advice and should not be used assuch. Gentex makes no representations and warranties, express or implied, that these materials arecomplete and accurate, up-to-date, or in compliance with all relevant local, state and federal laws, regu-lations and rules. The materials do not address all legal considerations as there is inevitable uncertaintyregarding interpretation of laws, regulations and rules and the application of such laws, regulations and rules to particular fact patterns. Each person's activities can differently affect the obligations that exist under applicable laws, regulations or rules. Therefore, these materials should beused only for informational purposes and should not be used as a substitute for seeking professionallegal advice. Gentex will not be responsible for any action or failure to act in reliance upon the information contained in this material. AArrcchhiitteecctt && EEnnggiinneeeerriinngg SSppeecciiffiiccaattiioonnss The combination photoelectric smoke and carbon monoxide alarm shall be a Gentex Model GN-503/GN-503F/GN-503FF or approved equal which shall provide at least the following features and functions: 1.Nominal smoke sensitivity shall be 2.5%. 2.The smoke alarm portion of device shall utilize an infrared LED sensing circuit which pulses in 4 to 5 second intervals when subjected to smoke. After 2 consecutive pulses in smoke, the alarm shall activate. 3.The CO alarm shall utilize an electrochemical sensing element with a minimum 5-year life. 4.The carbon monoxide alarm portion of device is adjusted not to detect CO levels below 30 PPM and will not alarm when exposed to constant levels of 30 PPM for 30 days. Per ANSI/UL 2034 requirements, the device will alarm at the following levels: 70 PPM CO between 1 to 4 hours, but not less than 1 hour. 150 PPM CO between 10 to 50 minutes. 400 PPM between 4 to 15 minutes. 5. The GN-503 Series device shall have a Duracelll®MN 1604 9VDC alkaline battery as a back-up in the event building power is lost. 6.The 9VDC battery impedance shall be verified by the circuit of the smoke/CO alarm. 7.The alarm shall provide an indicator when the battery is low in power, high impedance or is missing. 8.The CO alarm will provide an audible indicator of 3 quick chirps every 30 seconds at end of life of CO sensor. 9.The sensing chamber shall be fully protected to prevent entrance of small insects, thus reducing the probability of false alarms. 10.The alarm shall include a solid state red color LED that will indicate presence of CO at the unit. 11.The alarm shall include a solid state piezo alarm rated at 85dBA at 10ft. 12.A visual LED monitor (condition indicator) shall slow pulse in normal operation and rapid pulse in alarm (red color) 13.An easily accessible test button shall be provided. Push down on button for 5 seconds causing smoke/CO alarm to activate. If device does not go into alarm, the device is not working properly. 14.The device shall have tandem interconnect capability of up to 12 smoke/CO alarms. 15.The GN-503 and GN-503F alarm shall have the capability to tandem interconnect with all Gentex tandem capable smoke alarms, CO alarms or combination smoke/CO alarms, including 7000/7003 Series, 9000/9003 Series, 710CS/713CS Series, 7109CS/7139CS Series, GN-200/GN-300 Series, S1209 Series and CO1209 Series. 15.The GN-503FF alarm shall have the capability to tandem interconnect with the following Gentex alarms, CO alarms or combination smoke/CO alarms: GN-503 Series, S1209 Series and CO1209 Series. 16.The manufacturer shall provide models with the optional feature of auxiliary Form A/Form C relay contacts for initiating remote functions and annunciation and a relay option that is capable of activation by tandem interconnect wire. 17.The combination smoke/CO alarm shall be non-latching (self-restoring). 18.Unit must be ANSI/UL 217 and ANSI/UL 2034 listed for both wall and ceiling mounting. 19.Unit shall be listed by Underwriters Laboratories and California State Fire Marshal (CSFM). All equipment shall be completely factory assembled, wired and tested, and the contractor shall be prepared to submit a certified letter testifying to this condition. Alarms which do not meet all of the requirements of this specification will not be considered. For complete product specifications, refer to product installation manual.24 units per carton 24 pounds per carton Electrical SpecificationsOperating Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .120VAC, 60HzOperating Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..045 ampsOperating Current (Relay Options) . . . . . . . . . . . . . . . . . . . . . ..070 ampsOperating Ambient Temp Range . . . . . . . . . . . . . . . . . . . . . . . .40°F to 100°F (4.4°C-38°C) Alarm Horn Rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .85dBA at 10 feet (3.048 m)Auxiliary Relay (GN-503F) . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 Form A & 1 Form C (0.5 amp)Auxiliary Relay (GN-503FF) . . . . . . . . . . . . . . . . . . . . . . . . . . .2 Form A & 2 Form C (0.3 amp)Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Diameter at base: 5.75 in. (14.605 cm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Overall diameter 6.25 in. (16.51 cm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Depth: 1.8 in. (4.572 cm)Secondary Power Source . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Alkaline 9VDC battery (Duracell®MN 1604)CO Sensing Cell . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Electrochemical Cell DN-6927:A2 • 5/17/13 — Page 1 of 2 FCPS-24S6(C/E) & FCPS- 24S8(C/E) 6- & 8-Amp 24-Volt Remote Power Supplies Power Supplies DN-6927:A2 General The FCPS-24S6E (6-amp) and FCPS-24S8E (8-amp) areremote power supplies with battery charger. The FCPS-24S6/- 24S8 may be connected to any 12 or 24 volt fire alarm control panel (FACP) or may be used as stand-alone supplies. Pri- mary applications include notification appliance circuit (NAC) expansion (to support ADA requirements and NAC synchroni- zation) or auxiliary power to support 24 volt system accesso- ries. The FCPS-24S6/-24S8 provides regulated and filtered 24 VDC power to four notification appliance circuits configured as either four Class B (Style Y) or Class A (Style Z, with ZNAC-4 option module). Alternately, the four outputs may be config-ured as all non-resettable, all resettable or two non-resettable and two resettable. The FCPS-24S6/-24S8 also contains a battery charger capable of charging up to 18 AH batteries.FCPS-24S6C & FCPS-24S8C are ULC-listed. NOTE: Unless otherwise specified, the terms FCPS-24S6 and FCPS-24S8 used in this document refers to the standard FCPS- 24S6 and FCPS-24S8, FCPS-24S6C and FCPS-24S8C, the FCPS-24S6E and FCPS-24S8E Features • UL-Listed NAC synchronization using System Sensor, Wheelock, or Gentex “Commander2” appliances. • Operates as a “sync-follower” or as a “sync-generator” (default). See note on page 2. • Contains two fully-isolated input/control circuits - triggered from FACP NAC (NAC expander mode) or jumped perma-nently “ON” (stand-alone mode). • Four Class B (Style Y) or four Class A (Style Z, with ZNAC-4 module) NACs. • 6-amp (FCPS-24S6) or 8-amp (FCPS-24S8) full load out- put, with 3 amps maximum/circuit, in NAC expander mode (UL 864). • 4-amp (FCPS-24S6) or 6-amp (FCPS-24S8) continuous output in stand-alone mode (UL 1481). • Compatible with coded inputs; signals passed through. • Optional power-supervision relay (EOLR-1). • In stand-alone mode, output power circuits may be config- ured as: resettable, (reset line from FACP required), non-resettable, or a mix of two and two. • Fully regulated and filtered power output - optimal for pow- ering four-wire smoke detectors, annunciators, and othersystem peripherals requiring regulated/filtered power. • Power-limiting technology meets UL power-limiting require- ments. • Form-C normally-closed trouble relay. • Fully supervised power supply, battery, and NACs. • Selectable earth fault detection. • AC trouble report selectable for immediate 2-hour delay. • Works with virtually any UL 864 fire alarm control which uti- lizes an industry-standard reverse-polarity notification cir- cuit (including unfiltered and unregulated NAC power). • Requires input trigger voltage of 9 - 32 VDC. • Self-contained in compact, locking cabinet - 15”H x 14.5”W x 2.75”D (cm: 38.1H x 36.83W x 6.985D). • Includes integral battery charger capable of charging up to 18 AH batteries. Cabinet capable of housing 7.0 AH batter- ies. • Battery charger may be disabled via DIP switch for applica-tions requiring larger batteries. • Fixed, clamp-type terminal blocks accommodate up to 12 AWG (3.1mm2) wire. Specifications Primary (AC) Power: • FCPS-24S6C/-24S8C: 120 VAC, 60 Hz, 3.2A maximum. • FCPS-24S6E/-24S8E: 240 VAC, 50 Hz, 1.6A maximum. • Wire Size: minimum #14 AWG (2.0mm 2) with 600 V insula- tion. Control Input Circuit: •Trigger Input Voltage: 9 to 32 VDC. •Trigger Current: 2.0 mA (16 - 32 V); Per Input: 1.0 mA (9 - 16 V). Trouble Contact Rating: 5 A at 24 VDC. Auxiliary Power Output: Specific application power 500 mA maximum. Output Circuits: • +24 VDC filtered, regulated. • 3.0 A maximum for any one circuit. • Total continuous current for all outputs (stand-alone mode): –FCPS-24S6: 4.0 A maximum. –FCPS-24S8: 6.0 A maximum. • Total short-term current for all outputs (NAC expander mode): –FCPS-24S6: 6.0 A maximum. –FCPS-24S8: 8.0 A maximum. Secondary Power (Battery) Charging Circuit: • Supports lead-acid batteries only. Page 2 of 2 — DN-6927:A2 • 5/17/13 System Sensor® and NOTIFIER® are registered trademarks of Honeywell International Inc. ©2013 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.www.notifier.com Made in the U.S. A. • Float-charge voltage: 27.6 VDC. • Maximum current charge: 1.5 A. • Maximum battery capacity: 18 AH. Applications Example 1: Expand notification appliance power an additional 6.0 A (FCPS-24S6) or 8.0 A (FCPS-24S8). Use up to four Class B (Style Y) outputs or four Class A (Style Z) outputs (using ZNAC-4). For example, the FACP notification appliancecircuits will activate the FCPS when reverse-polarity activation occurs. Trouble conditions on the FCPS are sensed by the FACP through the notification appliance circuit. Example 2: Use the FCPS to expand auxiliary regulated 24- volt system power up to 4.0 A (FCPS-24S6) or up to 6.0 A (FCPS-24S8). Both resettable and non-resettable power options are available. Resettable outputs are created by con- necting the resettable output from the FACP to one or both of the FCPS inputs. Example 3: Use addressable control modules to activate theFCPS instead of activating it through the FACP notification appliance circuits. This typically allows for mounting the FCPS at greater distances* away from the FACP while expandingsystem architecture in various applications. For example, an addressable control module is used to acti- vate the FCPS, and an addressable monitor module is used to sense FCPS trouble conditions. Local auxiliary power output from the FCPS provides power to the addressable control module. *NOTE: Addressable FACPs are capable of locating control and monitor modules at distances of up to 12,500 feet (3,810 meters). Sync Follower/Generator Note In some installations, it is necessary to synchronize the flashtiming of all strobes in the system for ADA compliance. Strobes accomplish this by monitoring very short timing pulses on the NAC power which are created by the FACP. Wheninstalled at the end of a NAC wire run, the FCPS-24S6/-24S8 can track (i.e. “follow”) the strobe synchronization timing pulses on the existing NAC wire run. This maintains the overall system flash timing of the additional strobes attaches to the FCPS. When the FCPS-24S6/-24S8 is configured (via DIP switch set- tings) as a “sync follower,” the FCPS’s NAC outputs track thestrobe synchronization pulses present at the FCPS’s sync input terminal. The pulses originate from an upstream FACP or other power supply. When the FCPS-24S6/-24S8 are configured (via DIP switch settings) as a “sync generator,” the FCPS’s sync input termi- nals are not used. Rather, the FCPS is the originator of the strobe synchronization pulses on the FCPS’s NAC outputs. In “sync generator” mode, the sync type (System Sensor, Whee- lock, or Gentex) is selectable via DIP switch settings. Standards and Codes The FCPS-24S6 and FCPS-24S8 comply with the following standards: •NFPA 72 National Fire Alarm Code. •UL 864 Standard for Control Units for Fire Alarm Systems (NAC expander mode). •UL 1481 Power Supplies for Fire Alarm Systems. Agency Listings and Approvals These listings and approvals apply to the modules specified inthis document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. •UL Listed: S635, S674 •ULC Listed: S635 (FCPS-24S6C & FCPS-24S8C) •CSFM Approved: 7315-0028:225 •MEA: 299-02-E • FM Approved Ordering Information FCPS-24S6: 6.0 A, 120 VAC remote charger power supply. Includes main printed circuit board, transformers, enclosure(15”H x 14.5”W x 2.75”D [cm: 38.1H x 36.83W x 6.985D]), and installation instructions. FCPS-24S6C: Same as above, ULC-listed. FCPS-24S6R: Same as FCPS-24S6 with red enclosure. FCPS-24S6E: 6.0 A, 240 VAC remote charger power supply. Includes main printed circuit board, transformers, enclosure (15”H x 14.5”W x 2.75”D [cm: 38.1H x 36.83W x 6.985D]), and installation instructions. FCPS-24S8: 8.0 A, 120 VAC remote charger power supply. Includes main printed circuit board, transformers, enclosure(15”H x 14.5”W x 2.75”D [cm: 38.1H x 36.83W x 6.985D]), and installation instructions. FCPS-24S8C Same as above, ULC-listed. FCPS-24S8R: Same as FCPS-24S8 with red enclosure. FCPS-24S8E: 8.0 A, 240 VAC remote charger power supply. Includes main printed circuit board, transformers, enclosure (15”H x 14.5”W x 2.75”D [cm: 38.1H x 36.83W x 6.985D]), and installation instructions. ZNAC-4: Class A (Style Y) NAC option module. EOLR-1: 12/24 VDC end-of-line relay for monitoring four-wiresmoke detector power. BAT-1270: Battery, 12-volt, 7.0 AH (two required, see BAT Series data sheet DN-6933). DN-6933:D • 02/28/2013 — Page 1 of 2 BAT Series Batteries Sealed Lead-Acid Power Supplies DN-6933:D • E-205 General BAT Series Batteries are Power-Sonic brand batteries. BATSeries (or Power-Sonic brand) batteries are recommended for secondary power or backup power for all NOTIFIER fire alarm control equipment. Features • Provide secondary power for control panels. • Sealed and maintenance-free. • Overcharge protected. • Easy handling with leak-proof construction. • Ruggedly constructed, high-impact case (ABS). • Long service life. • Compact design. Agency Listings and Approvals The listings and approvals below apply to BAT Series Batter- ies. In some cases, certain modules may not be listed by cer- tain approval agencies, or listing may be in process. Consultfactory for latest listing status. •UL Recognized Components: MH20845 (Power-Sonic). Ordering Information BAT-1250-BP: 10-unit bulk pack of BAT-1250 (12 V 5 AH). BAT-1270-BP: 5-unit bulk pack of BAT-1270 (12 V 7 AH). BAT-12120-BP: 4-unit bulk pack of BAT-12120 (12V 12 AH). BAT-12180-BP: 2-unit bulk pack of BAT-12180 (12 V 18 AH). BAT-12260-BP: 2-unit bulk pack of BAT-12260 (12 V 26 AH). BAT-12550: single battery (12 V 55 AH). BAT-121000: single battery (12 V 100 AH). Part Number Reference & Specifications 6933cov.jpg Part Number Power-Sonic Part Number Battery Description DIMENSIONS Nominal Voltage V Nominal Capacity @ 20 hr. rate A.H. Width Depth Height Height over terminal Weight in. mm in. mm in. mm in. mm lb. kg. BAT-1250 PS-1250 12 5 sealed 3.54 90 2.76 70 3.98 101 4.21 107 3.50 1.59 BAT-1270 PS-1270 12 7 sealed 5.95 151 2.56 65 3.7 94 3.86 98 4.8 2.18 BAT-12120 PS-12120 12 12 sealed 5.95 151 3.86 98 3.7 94 3.94 100 7.92 3.59 BAT-12180 PS-12180 12 18 sealed 7.13 181 3.00 76 6.59 167 6.59 167 12.6 5.72 BAT-12260 PS-12260 12 26 sealed 6.5 167 6.97 177 4.92 125 4.92 125 17 7.71 BAT-12550 PS-12550 12 55 sealed 9.04 230 5.45 138 8.15 207 8.98 228 36 16.33 BAT-121000 PS-121000 12 100 sealed 12 305 6.6 168 8.15 207 8.98 228 68 30.84 Page 2 of 2 — DN-6933:D • 02/28/2013 NOTIFIER® is a registered trademark of Honeywell International Inc. Batteries display trademarks of the manufacturer.©2013 by Honeywell International Inc. All rights reserved. Unauthorized useof this document is strictly prohibited. This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118. www.notifier.com )%( oitaR yticapaCTemperature (°C) Discharge TimeegatloV lanimreTDischarge Characteristic Curves at 20°C (68°F) Effect of Temperature on Capacity 6933grf1.ai6933grf2.ai6933grf3.aiPS-121000 Shelf-Life and Storage aCpcaiyteteRntnoitaRoi%()Standing Period (Months) 100 80 60 40 00 2 4 6 8 10 12 14 16 18 20 40oC (104oF) 30oC (86oF) 20oC (68oF) 5oC (41oF) Chargingisnot necessary unless 100% of capacity is required. Chargingbefore use is necessary to help recoverfull capacity. Chargemayfailto restore full capacity. Do not let batteries reach this state. 13.0 12.0 11.0 10.0 9.0 8.0 14.0 lanimreT)V( egatloVAmbient Temperature 20 oC(68oF) 1.2 2.4 6 12 24 36 48 1 2 4 6 8 10 20 4 0 Discharge Time Final Voltage min h 5.01020 50 100 200 6933grf4.aiPS-121000 Discharge Characteristics DN-60804:A • 5/21/2014 — Page 1 of 4 SpectrAlert® Advance™ Selectable-Output Low Frequency Sounders & Sounder Strobes Audio Visual Equipment DN-60804:A General The SpectrAlert® Advance™ series offers the most versatile and easy-to-use line of low frequency sounder and low fre- quency sounder strobes in the industry. With white and red plastic housings, dual listed for wall and ceiling mounting, SpectrAlert Advance can meet virtually any application requirement. Like the entire SpectrAlert Advance product line, all-mount low frequency sounder, and low frequency sounder strobes include a variety of features that increase their application ver- satility while simplifying installation. All devices feature plug-in designs with minimal intrusion into the black box, making installations fast and foolproof while virtually eliminating costly and time-consuming ground faults. To further simplify installation and protect devices from con- struction damage, SpectrAlert Advance use a universal mount- ing plate with an onboard shorting spring, so installers can test wiring continuity before the device is installed. Installers can also easily adapt devices to suit a wide range of application requirements using field-selectable candela set- tings, automatic selection of 12 or 24-volt operation, and a rotary switch for low frequency sounder tones. Features • Plug-in design with minimal intrusion into the back box. • Tamper-resistant construction. • Field-selectable candela settings on wall units: 135, 150, 177, and 185. • Rotary switch for low frequency sounder tone. • Universal mounting plate for wall units. • Mounting plate shorting spring checks wiring continuity before device installation. • Electrically compatible with legacy SpectrAlert Advance devices. • Compatible with MDL3 sync module. • Listed for ceiling or wall mounting. Architect/Engineer Specifications GENERAL SpectrAlert Advance low frequency sounder and low fre- quency sounder strobes shall mount to a standard 4x4x1-1/2” back box, 4-inch octagon back box, or double-gang box. Two- wire products shall also mount to a single-gang 2x4x1-7/8” back box. A universal mounting plate shall be used for mount- ing products. The notification appliance circuit wiring shall ter- minate at the universal mounting plate. Also, SpectrAlert Advance products, when used with the Sync·Circuit™ Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync·Circuit Module, 12-volt- rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts.Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full wave recti- fied unfiltered power supply. Low Frequency Sounder strobes shall have field-selectable candela settings including 135, 150, 177, and 185. LOW FREQUENCY SOUNDER The low frequency sounder and the Sync·Circuit™ MDL3 Module accessory, if used, shall be powered from a notification appliance circuit output and shall operate on a nominal 12 or 24 volts (includes fire alarm panels with built in sync). When used with the Sync·Circuit™ MDL3, 12-volt rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt rated notification appliance circuit outputs shall operate between 16.5 to 33 volts. If the notification appliances are not UL 9th edition listed with the corresponding panel or power supply being used, then refer to the compatibility listing of the panel to determine maximum devices on a circuit. The low frequency sounder has an option to switch between tem- poral three pattern, non-temporal (continuous) pattern and coded supply. The low frequency sounder shall operate on a coded or non-coded power supply. LOW FREQUENCY SOUNDER STROBE COMBINATION The low frequency sounder strobe shall be approved for fire protective service. The low frequency sounder strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visi- ble signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The sounder shall have an option to switch between a temporal three pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. The low fre- quency sounder on low frequency sounder strobe models shall operate on a non-coded power supply. Page 2 of 4 — DN-60804:A • 5/21/2014 SYNCHRONIZATION MODULE The module shall synchronize SpectrAlert strobes at 1 Hz and low frequency sounder at temporal three. Also, while operating the strobes, the module shall silence the low frequency sounder on low frequency sounder strobe models over a sin- gle pair of wires. The module shall mount to a 1-11/16x4-11/ 16x2-1/8-inch back box. The module shall also control two Style Y (Class B) circuits or one Style Z (Class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. Physical/Electrical Specifications Standard Operating Temperature: 32°F to 120°F (0°C to 49°C). Humidity Range: 10 - 93% non-condensing. Strobe Flash Rate: 1 flash per second. Nominal Voltage Low Frequency Sounder: Regulated 12 DC/FWR or regulated 24 DC/FWR. Nominal Voltage Range Low Frequency Sounder Strobe: Regulated 24 VDC/FWR Operating Voltage Range: 8 to 17.5V (12V nominal) or 16 to 33 V (24 V nominal). Operating Voltage Range MDL3 Sync Module: 8.5 to 17.5V (12V nominal) or 16.5 to 33 V (24 V nominal). Input Terminal Wire Gauge: 12 to 18 AWG. Wall-Mount Dimensions (including lens): 6.4 inches L x 4.7 inches W x 2.5 inches D (162mm L x 119mm W x 64mm D). Sounder Dimensions: 5.6 inches L x 4.7 inches W x 1.3 inches D (142mm L x 119mm W x 33mm D). Low Frequency Sounder/Strobe with Surface Mount Back Box Dimensions (SBBR, SBBW): 6.4 inches L x 4.7 inches W x 4.3 inches D (162mm L x 120mm X x 108mm D). Low Frequency Sounder with Surface Mount Back Box Dimensions (SBBR, SBBW): 5.7 inches L x 4.8 inches W x 3 inches D (145mm L x 120mm X x 76mm D). UL Current Draw UL MAXIMUM STROBE CURRENT DRAW (MA RMS) UL MAXIMUM LOW FREQUENCY CURRENT DRA (MA RMS) UL MAXIMUM CURRENT DRAW (MA RMS), 2-WIRE LOW FREQUENCY SOUNDER STROBE, HIGH CANDELA RANGE (135 - 185 CD) 8-17.5 Volts 16-33 Volts Candela DC FWR DC FWR High Candela Range 135 N/A N/A 228 207 150 N/A N/A 246 220 175 N/A N/A 281 251 185 N/A N/A 286 258 8-17.5 Volts 16-33 Volts Sound Pattern dB DC FWR DC FWR Temporal High 191 262 138 166 Continuous High 292 384 138 208 Coded High 292 388 153 205 16-33 Volts 16-33 Volts DC Input 135 150 177 185 FWR Input 135 150 177 185 Temporal 277 292 325 344 Temporal 296 309 343 351 Continuous 337 362 387 417 Continuous 393 395 432 433 DN-60804:A • 5/21/2014 — Page 3 of 4 Low Frequency Sounder Tones and Sound Output Data LOW FREQUENCY SOUNDER AND LOW FREQUENCY SOUNDER STROBE OUTPUT (DBA) * Sounder ratings provided are for continuous voltage as provided by the NAC, Agency Listings and Approvals These listings and approvals below apply to the SpectrAlert Advance series. In some cases, certain modules or applica- tions may not be listed by certain approval agencies, or listing may be process. Consult factory for latest listing status. •UL Listed: S4011, S5512 •CSFM: 7135-1653:0223 (HR-LF, HW-LF), 7125-1653:0224 (P2HR-LF, P2WH-LF) •FM: 3047563 Ordering Information P2RH-LF: 2-wire wall low frequency sounder strobe, High cd, red. P2WH-LF:2-wire wall low frequency sounder strobe, High cd, white. HR-LF: low frequency sounder, red. HW-LF: low frequency sounder, white. BBS-2: back box skirt, wall red. BBSW-2: back box skirt, wall, white. SBBR: surface mount back box, wall, red. SBBW: surface mount back box, wall, white. TR-HS: trim ring, wall, red. TRW-HS: trim ring, wall white. NOTE: “High cd” refers to strobes that include 135, 150, 177 and 185 candela settings. 24-Volt Nominal 8-17.5 Volts 16-33 Volts Reverberant Anechoic Switch Position Sound Pattern DC FWR DC FWR DC FWR DC FWR 1 Temporal 76 76 76 76 76 76 86 86 2 Continuous 80 80 80 80 80 80 90 90 3* Coded 80 80 80 80 80 80 90 90 Page 4 of 4 — DN-60804:A • 5/21/2014 Notifier® and SpectrAlert® are registered trademarks of and SpectrAlert® Advance™ is a trademark of Honeywell International, Inc. ©2014 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118. www.notifier.com