HomeMy WebLinkAboutA17-0027_VVMC Ctr Wing Submittal_1494619260.pdfSIMPLEXGRINNELL 14200 E. Exposition Avenue Aurora, Colorado 80012 www.simplexgrinnell.com Tele: (303) 355-0500 Fax: (303) 355-0615 Prepared for: ENCORE ELECTRIC 77 METCALF ROAD AVON, COLORADO 81620 Fire Alarm Product Data Submittal for: VAIL VALLEY MEDICAL CENTER CENTER WING RENOVATION 181 WEST MEADOW DRIVE VAIL, COLORADO 81657 PROJECT:VAIL VALLEY MEDICAL CENTER CENTER WING RENOVATION PREPARED FOR:ENCORE ELECTRIC TYPE: DESCRIPTION: 4009-9602 IDNAC REPEATER 120V RED UL/ULC 2081-9274 BATTERIES - 10AH (2x) 4099-9006 ADDRESSABLE DOUBLE ACTION MANUAL STATION, PUSH 4098-9792 TRUEALARM SENSOR BASE 4098-9714 TRUEALARM PHOTO SMOKE SENSOR 4098-9756 TRUEALARM DUCT SMOKE SENSOR W/ RELAY OUTPUT 2098-9806 REMOTE TEST STATION W/ LED AND KEY SWITCH 4098-9858 SAMPLING TUBE 97" 4090-9001 IDNET SUPERVISED IAM 4090-9807 COVER-ADDRESS MODULE SURFACE 4090-9002 IDNET RELAY IAM 2088-9021 ENCAPSULATED RELAY PAM-1 59VO-WWF VO LED WALL, WHITE, FIRE 4906-9204 ADDRESSABLE CEILING MNT MC V/O, WHITE 49SV-APPLC S/V APPLIANCE ONLY, CEILING MT 49SVC-CWFIRE SV COVER, CEIL MT, WITE, FIRE LABEL 4081-9004 EOL, 6.8K, 1/2W 4081-9008 EOL, 10K, 1/2W Fax: (303) 355-0615 14200 E. Exposition Avenue Aurora, Colorado 80012 Sales: (303) 355-0500 Service: (303) 355-0500 Features 4009 IDNAC Repeaters provide enhanced power delivery to TrueAlert/TrueAlert ES addressable notification appliances controlled by IDNAC SLCs: • Output voltage in alarm is maintained by an efficient switching regulator at 29 VDC during both AC input and battery backup conditions allowing strobes to operate at lower current • With lower current strobes and regulated output voltage, wiring distance can be extended 2 to 3 times that of conventional notification, appliance loading can be increased, or smaller wire gauge can be used, all resulting in installation savings with high assurance that appliances that operate during normal system testing will operate during worst case alarm conditions 4009 IDNAC Repeaters receive an IDNAC SLC input and provide a repeated 3 A SLC output to extend SLC distance and power: • Appliance control and address limit remains with the host IDNAC control panel. Repeater status is communicated to the control panel for system diagnostics and also locally indicated • Repeater output extends supervisory capacity by up to 139 additional unit loads or 3 A • Input SLC connection can be Class B or Class A • Repeater output can be a Class A loop or a Class B output with internal connections for up to four (4) T-tapped output branches (Class A output requires 4009-9814 Class A Adapter) • Operation requires one IDNAC SLC address; Repeaters can be connected as one in series, or up to five (5) in parallel • AC power input is 120 VAC or 220-240 VAC, 50/60 Hz, auto-select • An on-board battery charger is provided with low AC battery disconnect selectable per Repeater (required for ULC listed applications) • Operation is compatible with TrueAlert ES and TrueAlert addressable notification appliances and accessories • Available with platinum or red cabinet • Listed to UL 864 and ULC S527 Multiple wiring options are available: • Wiring options include Class B multiple branch (up to 4) output, Class A loop extension, and Class A riser to Class B branches or a Class A loop output • When the Repeater is part of a Class A loop from the IDNAC SLC source panel, up to twice the distance for the loop is available; (Class A loop repeating requires 4009-9814 Class A Adapter) * This product has been approved by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7165 0026:0378 for allowable values and/or conditions concerning material presented in this document. NYC Fire Dept COA #6151. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products. 4009 IDNAC Repeater Extends Distance and Current of IDNAC SLC Features (Continued) Class A Adapter 4009-9814: • Required when extending a Class A loop or to provide a Class A local loop SLC output • Operation provides short circuit isolation between input and output terminals for improved IDNAC SLC survivability Built-in battery Charger • Power supply charges up to 12.7 Ah batteries for in cabinet mounting and up to 25 Ah batteries with model 4009-9801 external battery cabinet Available auxiliary output: • A 200 mA, 29 VDC constant auxiliary output is available; operation is maintained during battery backup TrueAlert Addressable Notification UL, ULC, CSFM Listed; 4009 IDNAC Repeater; FM, NYC Fire Dept Approved* Power and Distance Extender S4009-0004-5 6/2015 Introduction Repeating IDNAC SLCs. Simplex fire alarm control panels with IDNAC SLC outputs provide individual address and control of TrueAlert and TrueAlert ES addressable notification appliances. When an IDNAC SLC reaches the current limit or the distance limit of the source IDNAC SLC, use of 4009 IDNAC Repeaters extends the IDNAC SLC with an additional 3 A of SLC current and up to 139 unit loads of additional supervisory capacity. With IDNAC SLCs, a constant 29 VDC source voltage is maintained in alarm, even during battery standby, allowing strobes to operate at higher voltage with lower current and ensuring a consistent current draw and voltage drop margin under both primary power and secondary battery standby. Efficiencies include wiring distances up to 2 to 3 times farther than with conventional notification, or support for more appliances per IDNAC SLC, or use of smaller gauge wiring, or combinations of these benefits, all providing installation and maintenance savings with high assurance that appliances that operate during normal system testing will operate during worst case alarm conditions. Description Three wiring configurations are available to provide a variety of system solutions: Class B branch extension, Class A loop extension, and Class A riser to Class B branch extension or Class A loop output. Description (Continued) Class B branch input wiring allows T-tapped connections to up to five (5) parallel connected 4009 IDNAC Repeaters. Each Repeater has on-board output terminal connections for up to four (4) output branch circuits, and additional branch circuits can be externally T-tapped as required. (Refer to diagram on page 3 for additional details.) Class A loop extensions use a single 4009 IDNAC Repeater to extend the current and distance of a single Class A loop allowing the loop distance to be doubled. The Repeater communicates and repeats bi-directionally allowing Class A loop operation to be maintained in the event of an open circuit. This wiring connection requires use of the 4009-9814 Class A adapter. (Refer to diagram on page 4 for additional details.) Class A Riser to Class B Branches or Class A Loops. For applications requiring a combination of wiring types, a Class A riser can drive up to five (5) 4009 IDNAC Repeaters with each Repeater capable of driving either single or multiple Class B branch output(s) or a Class A loop output. In this wiring application, the Repeater does not repeat in the Class A riser loop, it is connected as an appliance with Class A in/out wiring. To create a Class A loop output, the Repeater must be equipped with a 4009-9814 Class A Adapter. (Refer to diagram on page 5 for additional details.) 2 S4009-0004-5 6/2015 Model* Cabinet Color Description 4009-9601(BA) Platinum 4009 IDNAC Repeater with cabinet; provides a single 3 A IDNAC SLC output, 200 mA auxiliary power output, and battery charger; 120/240 VAC, 50/60 Hz input, auto-select 4009-9602(BA) Red * Add suffix BA to select 4009 IDNAC Repeaters assembled in the USA. Aftermarket Accessories (installed on-site, select per system requirements) Model Description 4009-9814 Class A Adapter Module, mounts on repeater controller board; required for Class A output 2975-9813 Platinum semi-flush box trim 1 7⁄16” (37 mm) wide, four corners and trim pieces for top, bottom, and sides; (will need to be cut to fit 4009 IDNAC Repeater cabinet) 2975-9812 Red semi-flush box trim External Accessories (select per system requirements) Model Description Comments 4905-9929 Remote TrueAlert Communications Isolator Refer to data sheet S4905-0001 for details 4009-9801 External Battery Cabinet for 25 Ah batteries 16 ¼” W x 13 ½” H x 5 ¾” D (413 mm x 343 mm x 146 mm); refer to data sheet S2081-0006 for details Battery Selection (select battery size per system requirements; two batteries are required for 24 VDC operation) Model Description Model Description 2081-9272 6.2 Ah Battery, 12 VDC 2081-9275 18 Ah Battery, 12 VDC Requires 4009-9801 External Battery Cabinet 2081-9274 10 Ah Battery, 12 VDC 2081-9287 25 Ah Battery, 12 VDC 2081-9288 12.7 Ah Battery, 12 VDC Product Selection 3 S4009-0004-5 6/2015 Wiring Reference, Class B Input with Class B Branch Circuit Outputs 4 S4009-0004-5 6/2015 Wiring Reference, Class A Loop Extension 5 S4009-0004-5 6/2015 Wiring Reference, Class A Riser Input with Class A Loop and Class B Branch Outputs 4009 IDNAC Repeater Mounting and Module Placement Reference Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S4009-0004-5 6/2015 www.simplex-fire.com © 2014 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. Input Ratings Input Ratings Voltage Range 120 VAC, 50/60 Hz, or 220/230/240 VAC, 50/60 Hz, +10%, -15%, auto-select 120 VAC Current 2.5 A 220/230/240 VAC Current 1.25 A 24 VDC Requirements for Battery Calculations Panel IDNAC Appliances Auxiliary Load Standby Currents 70 mA 0.8 mA each Output current (voltage is from battery) Alarm Currents 96 mA 4.5 A maximum with 3 A IDNAC SLC load and 200 mA Auxiliary output load (actual alarm current depends on connected and activated appliances and devices) 1.37 x output current (voltage converter is on when in Alarm) IDNAC Input Ratings 17 VDC minimum 1 address, 4 unit loads Output Ratings IDNAC SLC Output 3 A maximum @ 29 VDC for Special Application appliances Compatible Special Application Appliances Simplex TrueAlert ES and TrueAlert addressable notification appliances; contact your Simplex product representative for compatible appliances IDNAC Repeater Loading and SLC Address Usage Each repeater uses four unit loads on the EPS it receives power from and supports up to 139 additional unit loads. Most appliances are 1 unit load; Multi-Tone appliances are 2 unit loads; Repeaters and Isolators are 4 unit loads. Refer to individual appliance and device specifications for unit load requirements and rated SLC loading specifications. Each repeater uses one IDNAC SLC device address - the IDNAC Repeater does not increase the IDNAC channel device address capacity. Refer to the Host IDNAC SLC specifications for the device address capacity specifications on the IDNAC channel. Auxiliary Output Current 200 mA maximum Voltage 29 VDC nominal with AC present or when Repeater is on battery standby and in Alarm 24 VDC nominal when on battery standby and not in Alarm IDNAC SLC Wiring Specifications (refer to installation instructions for more information) Recommended wire type UTP, unshielded twisted pair Maximum wire length allowed with “T-Taps” for class B wiring 10,000 ft (3048 m) Maximum wire length to any appliance 4000 ft (1219 m) Wiring Connections Terminal blocks for 18 to 12 AWG Repeater Status Indicators Green AC Power LED On with AC present, off during brownout or no AC condition Red Communications LED (COMM) Blinks when Repeater is communicating with the host control panel Yellow System Status LEDs 4 LEDs provide up to 16 different trouble status indications; an on-board trouble scroll button allows review should multiple troubles occur 4009-9814 Class A Adapter Module Option (required for Class A loop extension or for Class A output) IDNAC SLC Output Voltage 3 A maximum @ 29 VDC for Special Application appliances Two connections, Port A and Port B, function varies by application (loop extension or local loop), Port A and Port B are isolated from each other Status LEDs Two yellow trouble LED indicators, one per Port Environmental and Technical Publications Reference Operating Temperature 32° to 120° F (0° to 49° C) Operating Humidity Range Up to 93% RH at 90° F (32° C) Installation Instructions 4009 IDNAC Repeater 579-1019 Class A Adapter Module 579-1080 4009 IDNAC Repeater Specifications Features Rechargeable, sealed lead-acid batteries:  Lead-calcium grid structure with immobilized electrolyte in absorbent separator  Low maintenance with no need to add water  Low self-discharge characteristics  One-piece, high impact polystyrene cell cover with high reliability dual seal construction  UL 924 recognized pressure relief valves Available in a variety of capacities:  Batteries for internal mounting range from 6.2 Ah up to 50 Ah, depending on control panel cabinet size  Larger batteries, up to 110 Ah, mount in external battery cabinets with models available with internal chargers Battery cabinets with chargers:  Battery cabinets with charger communicate with their connected fire alarm control panel and are available for 4100ES/4010ES/4100U Series and 4010 Series panels Description Simplex® rechargeable sealed-lead acid batteries provide reliable and repeatable discharge and recharge characteristics for use in fire alarm and other systems applications. They are designed with immobilized electrolyte in an absorbent separator, allowing them to provide rated capacity on the first cycle. Because of their sealed construction, packaging is allowed within the system electronics enclosure (see illustration on page 2). When this is applicable, the quantity of system cabinets and the battery wiring distances are both minimized. Where required, external battery cabinets can be close-nippled to the control panel to house larger batteries with battery chargers available in some battery cabinet sizes. Battery Details Charging. These batteries are intended to be used with compatible Simplex battery chargers. Series Connections. These batteries are required to be connected in series to produce 24 V system voltage. Battery sets must be of identical voltage, model number, appearance, and approximately the same date of manufacture for proper operation. Testing. Battery capacity testing is recommended to be performed by using a sealed lead-acid battery tester designed to withdraw a minimum of battery charge. The preferred tester applies a variety of amplitude and duration controlled test pulses that compares terminal voltage against those predicted for the specific battery size. (Testing is available through your local Simplex product supplier.) Compatible Sealed Lead-Acid Batteries can be Installed Inside Fire Alarm Control Panel Cabinets Remote Battery Cabinets are Available for Larger Battery Requirements Battery Details (Continued) Shipping. Sealed lead-acid batteries are shipped via ground or sea transportation only. They are not shipped via air. Disposal. Battery chemicals and materials can be recycled. Refer to information shipped with the battery or on its case. Return to the battery manufacturer or to a similarly qualified battery processing facility for proper disposal. Seismic Activity Applications. Battery brackets are available for systems tested for compliance with specific batteries. Please refer to data sheet S2081-0019 for details. * Refer to details on page 4 and to the referenced individual product data sheets for agency listing status of battery cabinets and chargers. The batteries detailed in this document meet the requirements of UL, ULC, and Factory Mutual for use with respective equipment battery chargers as listed on page 3. Contact your local Simplex product supplier for proper battery selection per system requirements. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products. Fire Alarm Control Panel Accessories Listings* System Batteries, Sealed Lead-Acid; with Applications Reference for Battery Cabinets, and Battery Cabinets with Charger S2081-0006-22 10/2016 Actual appearance will vary with battery size. 2 S2081-0006-22 10/2016 Nominal Voltage Rating 12 Volts per battery Discharge Rating 20 Hour Rate Typical Charge/Discharge Cycles 100 to 150 Preferred Charge Temperature Range 60° F to 90° F (15.6°C to 32.2° C) Quick connect or post type terminal (type varies with battery size) Inner cover Absorbent separator used to immobilize electrolyte Lead-calcium grids Cell group Cell case (high impact polystyrene) Sealed outer cover Vent hole Potting material, black for negative, red for positive (polarity is also clearly marked with + and -) Pressure relief valve Semi-permeable membrane separator Battery Model Capacity @ 20 Hour Discharge Rate Width* Depth* Height with Terminals Approximate Weight* 2081-9272 6.2 Ah 6-1/8” (156 mm) 2-5/8” (67 mm) 4” (102 mm) 5.75 lbs (2.6 kg) 2081-9274 10 Ah 6” (153 mm) 4-1/16” (103 mm) 4” (102 mm) 9.2 lbs (4.2 kg) 2081-9288 12.7 Ah 6” (153 mm) 4” (102 mm) 4” (102 mm) 9 lbs (4.1 kg) 2081-9275 18 Ah 7-1/4” (184 mm) 3-3/8” (86 mm) 6-5/8” (168 mm) 14.3 lbs (6.5 kg) 2081-9287 25 Ah 6-5/8” (168 mm) 5” (127 mm) 7” (178 mm) 19.4 lbs (8.8 kg) 2081-9271 (rectangular case, typically for service) 33 Ah 12-1/2” (318 mm) 3-3/8” (86 mm) 7-1/16” (179 mm) 26.6 lbs (12.1 kg) 2081-9276 (“square” case, use for new) 33 Ah 7-3/4” (197 mm) 5-1/4” (133 mm) 6-3/4” (171 mm) 26.5 lbs (12 kg) 2081-9296 50 Ah 9” (229 mm) 5-1/2” (140 mm) 8-7/8” (225 mm) 41.8 lbs (19 kg) 2081-9279 110 Ah 11-3/16” (284 mm) 10-1/2” (267 mm) 9” (230 mm) 82 Lbs (37 kg) * Dimensions and weight are per battery and are for reference only. Exact size may vary. Refer to the tables on page 3 for mounting compatibility. These batteries are 12 V each and series connected for 24 V system use. NOTE: When wired in series for 24 V output, these batteries are to be of identical voltage, appearance, model number, and approximately the same date of manufacture. Battery Construction Reference Battery Size Specifications General Battery Specifications 3 S2081-0006-22 10/2016 Battery Cabinets without Chargers (connects to charger in panel) Cabinet Panel Compatibility Battery 2081-9275 18 Ah* 2081-9287 25 Ah 2081-9271 Rectangular 33 Ah 2081-9276 Square 33 Ah 2081-9296 50 Ah 2081-9279 110 Ah 2081-9280 4100ES, 4010ES, 4100U, and 4100+ NA NA NA NA NA 2081-9281 2081-9282 multiple NA 4009-9801 multiple ** NA NA NA NA 4009-9802 multiple NA NA NA NA Battery Cabinets with Chargers Cabinet Panel Compatibility 2081-9275 18 Ah* 2081-9287 25 Ah 2081-9271 Rectangular 33 Ah 2081-9276 Square 33 Ah 2081-9296 50 Ah 2081-9279 110 Ah 4081-9301 4081-9302 4004R and 4010 NA 4081-9306 4081-9308 4100ES, 4010ES, and 4100U NA NA NA NA * Batteries smaller than those listed are normally mounted in the product cabinet ** 25 Ah capacity was effective as of 7/2005. = Can be placed in the respective equipment cabinet NA = Not applicable/not compatible NOTE: Refer to individual fire alarm control panel product data sheets for additional battery application information Battery Model Capacity Simplex Control Panel Model Series (see legend and notes below) 4003EC 4004R 4007ES & 4005 4006 & 4008 4009 (all models)4010 4010ES 4100ES/ 4100U 4100 & 4120 (2, 4 or 6-Unit) 2081-9272 6.2 Ah 2081-9274 10 Ah 2081-9288 12.7 Ah 2081-9275 18 Ah Ext Note 3 Ext Ext Note 2 2081-9287 25 Ah Ext Note 3 Ext Ext NA 2081-9271 rectangular 33 Ah Ext Note 3 Ext NA NA Note 3 Ext 2081-9276 “square” 33 Ah Ext Note 3 NA NA NA Note 3 2081-9296 50 Ah NA Note 3 NA NA NA Note 3 Note 6 2 or 3 bay Ext 2081-9279 110 Ah Requires external battery cabinet, compatible with 4100ES, 4010ES, 4100, and 4120 Series only = Can be placed in the respective equipment cabinet Ext = External battery cabinet is required, refer to selection chart on page 4 NA = Not applicable/not compatible NOTES: 1. These batteries meet the requirements of UL, ULC, and Factory Mutual for use with respective equipment battery chargers listed above. Contact your local Simplex product supplier for proper battery selection per system requirements. 2. 4010 Cabinets will accommodate 2081-9275, 18 Ah batteries, but will not allow bottom entry conduit. 3. Use 4081 series companion cabinet and charger, refer to page 4. 4. Some control panel models are listed for battery replacement reference only. 5. For 2 bay international applications only, 50 Ah batteries will fit in the cabinet. Battery Compatibility for Fire Alarm Control Panel Mounting External Battery Cabinet Compatibility Reference Battery Cabinets Without Chargers; Shallow Design with Front Door Model Color Listings Description Dimensions 2081-9281 Beige UL and FM 2-Unit, 4100 style cabinet without charger; with locking solid door and battery shelf, primarily for use with 50 Ah batteries 25-3/4” W x 20-3/4” H x 6-3/4” D (654 mm x 527 mm x 171 mm) 2081-9282 Red 4003-9860 Beige Multiple Intended for use with 4003EC systems, for up to 33 Ah batteries (refer to 4003EC data sheet S4003-0002) 9-1/2” H x 24” W x 9” D (241 mm x 610 mm x 229 mm) 4009-9801* Beige UL and FM For up to 25 Ah batteries* External battery cabinet without charger, with locking solid door and battery harness; for close-nippled mounting to fire alarm control panel cabinet 16-1/4” W x 13-1/2” H x 5-3/4” D (413 mm x 343 mm x 146 mm)* 4009-9802 Beige UL For up to 33 Ah batteries 25-3/4” W x 20-3/4” H x 4-1/8” D (654 mm x 527 mm x 105 mm) * Depth increased for 25 Ah batteries effective 7/2005. Chargers for use with 4010 Fire Alarm Control Panels and 4004R Suppression Release Systems (refer to data sheet S4081-0001) Model Color Input Voltage Description Dimensions 4081-9301 Beige 120 VAC Battery cabinet with charger for the 4010 and 4004R fire alarm control panel; for up to 50 Ah batteries; with front door Listings include: UL, ULC, FM, CSFM, and MEA (NYC), see data sheet for details 22-1/2” W x16-3/4” H x 8-3/8” D (572 mm x 425 mm x 213 mm) 4081-9302 Red Battery Cabinet Without Charger for 110 Ah Batteries; for use with compatible panel mounted chargers (refer to data sheet S2081-0012) Model & Listings Color Cabinet Description Compatible Chargers Charger Description Dimensions 2081-9280 Listings include: UL and CSFM Red Battery cabinet for 2081-9279, 110 Ah batteries; includes 80 A battery fuse, terminals and battery connection cables; see data sheet for details 4010-9xxx Series 4010ES Main System Supply (MSS) 26-1/2” W x 12” H x 12” D (673 mm x 305 mm x 305 mm) 4100-9xxx Series 4100ES/4100U System Power Supplies (SPS) 4100-5111 4100-5112 4100-5113 4100ES/4100U Additional SPS 4100-5125 4100-5126 4100-5127 4100ES/4100U Remote Power Supply (RPS) 4100-5120 4100-5121 4100-5122 4100ES/4100U TrueAlert Addressable Power Supply (TPS) 4100-0104 4100-0114 4100-0124 4100 Legacy power supplies 4100ES/4010ES/4100U Compatible Battery Cabinet With Charger for 110 Ah Batteries (for ULC listed systems and for other applications unable to use panel mounted power supply charger; refer to data sheet S4081-0002) Model Color Input Voltage Description Dimensions 4081-9306 Red 120 VAC Battery cabinet with charger for up to 110 Ah batteries; NOTE: Required for ULC listed charging of 110 Ah batteries; Listings include: UL, ULC, FM, CSFM, and MEA (NYC), see data sheet for details 27-7/8” W x 13-1/2” H x 14-5/8” D (708 mm x 343 mm x 371 mm) 4081-9308 Red 220/230/240 VAC, multi-tapped 4100-9837 Green LED Power-on Indicator Kit, required for ULC listing, mounts above access panel using knockout provided Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S2081-0006-22 10/2016 www.simplex-fire.com © 2014 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. External Battery Cabinet Specification Reference Features Individually addressable manual fire alarm stations with:  Power and data supplied via IDNet or MAPNET II addressable communications using a single wire pair  Operation that complies with ADA requirements  Visible LED indicator that flashes during communications and is on steady when the station has been activated  The NO GRIP Single Action Station and Retrofit Kit are available with a more easily operated pull lever for applications where anticipated users may find the standard station lever difficult to activate  Pull lever that protrudes when alarmed  Break-rod supplied (use is optional)  Models are available with single or double action (breakglass or push) operation  UL listed to Standard 38 Compatible with the following Simplex® control panels:  Model Series 4007ES, 4008, 4010, 4010ES, 4100ES, 4100U, 4020, 4100, and 4120 fire alarm control panels equipped with either IDNet or MAPNET II communications  Model Series 2120 Communicating Device Transponders (CDTs) equipped with MAPNET II communications Compact construction:  Electronics module enclosure minimizes dust infiltration  Allows mounting in standard electrical boxes  Screw terminals for wiring connections Tamper resistant reset key lock (keyed same as Simplex fire alarm cabinets) Multiple mounting options:  Surface or semi-flush with standard boxes or matching Simplex boxes  Flush mount adapter kit  Adapters are available for retrofitting to commonly available existing boxes Description The Simplex addressable manual station combines the familiar Simplex manual station housing with a compact communication module that is easily installed to satisfy demanding applications. Its integral individual addressable module (IAM) constantly monitors status and communicates changes to the connected control panel via IDNet or MAPNET II communications wiring. * Refer to page 2 for specific model listings. This product has been approved by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7150-0026:224 for allowable values and/or conditions concerning material presented in this document. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products. 4099-9004 Single action 4099-9021 NO GRIP Single action 4099-9805 NO GRIP Retrofit kit ALARMFIRE PULL DOWN PUSH ALARMFIRE KEY OPERATED ONLY ALARMFIRE KEY OPERATED ONLY 4099-9005 Breakglass 4099-9006 Push With 2099-9828 Institutional Cover kit Operation Activation of the 4099-9004 single action manual station requires a firm downward pull to activate the alarm switch. Completing the action breaks an internal plastic break-rod (visible below the pull lever, use is optional). The use of a break-rod can be a deterrent to vandalism without interfering with the minimum pull requirements needed for easy activation. The pull lever latches into the alarm position and remains extended out of the housing to provide a visible indication. Single Action NO GRIP Station 4099-9021. For applications such as California Building Code, Title 24, which requires “Controls and operating mechanisms shall be operable with one hand and shall not require tight grasping, pinching or twisting of the wrist” the model 4099-9021 station provides a more easily operated pull lever compared to standard stations. Retrofit of existing stations is available using the 4099-9805 Retrofit kit. Double Action Stations (Breakglass) require the operator to strike the front mounted hammer to break the glass and expose the recessed pull lever. The pull lever then operates as a single action station. Double Action Stations (Push Type) require that a spring loaded interference plate (marked PUSH) be pushed back to access the pull lever of the single action station. Station reset requires the use of a key to reset the manual station lever and deactivate the alarm switch. (If the break-rod is used, it must be replaced.) Station testing is performed by physical activation of the pull lever. Electrical testing can be also performed by unlocking the station housing to activate the alarm switch. Multi-Application Peripherals UL, ULC, CSFM Listed; IDNet or MAPNET II Communicating Devices FM Approved * Addressable Manual Stations S4099-0005 10/2014 2 S4099-0005 10/2014 Addressable Manual Stations, Red Housing with White Letters and White Pull Lever Model Description Housing Pull Lever Listings 4099-9004 Single Action, English FIRE ALARM PULL DOWN UL, ULC, FM, CSFM 4099-9004CB Single Action, Bilingual English and French FEU FIRE TIREZ PULL ULC 4099-9004CF Single Action, French ALARME FEU ABAISSEZ 4099-9004PO Single Action, Portuguese FOGO ALARME PUXE UL, FM 4099-9004SP Single Action, Spanish ALARMA FUEGO JALE 4099-9005 Double Action, Breakglass operation, English FIRE ALARM PULL DOWN UL, ULC, FM, CSFM 4099-9005PO Double Action, Breakglass operation, Portuguese FOGO ALARME PUXE UL, FM 4099-9005SP Double Action, Breakglass operation, Spanish ALARMA FUEGO JALE 4099-9006 Double Action, Push operation, English FIRE ALARM PUSH PULL DOWN UL, ULC, FM, CSFM 4099-9006PO Double Action, Push operation, Portuguese FOGO ALARME EMPURRE PUXE UL, FM 4099-9006SP Double Action, Push operation, Spanish ALARMA FUEGO EMPUJE JALE 4099-9021 Single Action NO GRIP operation, English FIRE ALARM PULL DOWN UL, ULC, FM, CSFM Accessories (refer to pages 3 and 4 for details) Model Description Model Description 2975-9022 Cast aluminum surface mount box, red 2099-9803 Replacement breakglass 2975-9178 Surface mount steel box, red 2099-9804 Replacement break-rod 2099-9813 Semi-flush trim plate for double gang switch box, red 2099-9828 Institutional cover kit for field installation on 4099-9004; Note: Covers LED indicator 2099-9819 Flush mount adapter kit, black 2099-9814 Surface trim plate for Wiremold box V5744-2, red 2099-9820 Flush mount adapter kit, beige 4099-9805 Retrofit Kit for field conversion of a single action station to a NO GRIP station; refer to Installation Instructions 579-1007 for details Power and Communications IDNet or MAPNET II communications, 1 address per station Address Means DIP switch, 8 position Wire Connections Screw terminal for in/out wiring, for 18 to 14 AWG wire (0.82 mm2 to 2.08 mm2) UL Listed Temperature Range 32° to 120° F (0° to 49° C) intended for indoor operation Humidity Range Up to 93% RH at 100° F (38° F) Housing Color Red with white raised lettering Material Housing and pull lever are Lexan polycarbonate or equal Pull Lever Color White with red raised lettering Housing Dimensions 5” H x 3 ¾” W x 1” D (127 mm x 95 mm x 25 mm) Single gang cover plate, 3/4" (19 mm) extension, RACO #773 or equal (supplied by others) Station side view Wall surface Single gang box outline 4" Square box with cover plate Semi-Flush Mount Side View Single Gang Box Mount Single gang box, 2 1/2" deep (64 mm), RACO #500 or equal (supplied by others) Mount flush or with 1/16" (2 mm) maximum extension DO NOT RECESS ALARMFIRE PULL DOWN LED Indicator 4" Square Box Mount 4" (102 mm) square box, 2 1/8" (54 mm) minimum depth, RACO #231 or equal (supplied by others) Addressable Manual Station Semi-Flush Mounting Specifications (refer to Installation Instructions 579-1135 for additional information) Addressable Manual Station Product Selection Preferred Mounting. For surface mounting of these addressable manual stations, the preferred electrical boxes are shown in the illustration to the right. Additional Mounting Reference. Refer to page 4 for Wiremold box mounting compatibility. 3 S4099-0005 10/2014 Application Reference Refer to NFPA 72, the National Fire Alarm and Signaling Code, and all applicable local codes for complete requirements for manual stations. The following summarizes the basic requirements. 1. Stations shall be located in the normal path of exit and distributed in the protected area such that they are unobstructed and readily accessible. 2. Mounting shall be with the operable part not less than 42 in (1.07 m) and not more than 48 in (1.22 m) above floor level. 3. At least one station shall be provided on each floor. Additional stations shall be provided to obtain a travel distance not more than 200 ft (61 m) to the nearest station from any point in the building. 4. When manual station coverage appears limited in any way, additional stations should be installed. 2975-9178 Box 5-3/16" H x 4" W x 2-3/16" D (132 mm x 102 mm x 56 mm) (ordered separately) Knockouts located top and bottom 2975-9022 Cast Box 5" H x 3-7/8" W x 2-3/16" D (127 mm x 98 mm x 56 mm) (ordered separately) Access for 3/4" threaded conduit located top and bottom5" (127 mm) FIR E ALARMFIRE PULL DOWN 4099 Series Addressable Manual Station 1" (25.4 mm) 3-3/4" (95 mm) Station cover hinges open for installation access Simplex 2975-9178 box (shown for reference) Address setting under resealable label (accessible with cover open) Switch wiring (prewired) Field wiring (shown for reference) 1-1/4" (32 mm) 2-5/8" (67 mm) Addressable Manual Stations Surface Mounting Surface Mount Side View with Internal Detail For retrofit and new installations, additional compatible mounting boxes and the required adapter plates are shown in the illustration to the right. TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm and Signaling Code are trademarks of the National Fire Protection Association (NFPA). Lexan is a trademark of the General Electric Co. Wiremold is a trademark of the Wiremold Company. 8" (203 mm) 6" (152 mm) 4-3/4" (121 mm) 6-3/4" (171 mm) Front View Flush mount adapter kit 2099-9819, Black 2099-9820, Beige Wall surface 4-11/16" (119 mm) square box, 2-1/8" (54 mm) minimum depth (by others) Side View Box must be recessed into wall 1" to 1-1/8" (25.4 mm to 29 mm) Hole cutout must be a minimum of 6" H by 5" W (152 mm by 127 mm) 2099-9814 Surface trim for Wiremold box 5-1/8" H x 5" W (130 mm x 127 mm) Addressable station Two gang switch box, each 3" H x 2" W x 2-3/4" D (76 mm x 51 mm x 70 mm) (supplied by others) 2099-9813 Semi-flush trim for 2 gang switch box, 6" H x 4-1/2" W (152 mm x 114 mm) Wiremold receptacle box model V5744-2 (supplied by others) Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S4099-0005 10/2014 www.simplex-fire.com © 2014 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. Addressable Manual Station, Additional Mounting Information Addressable Manual Station, Flush Mounting Information Features TrueAlarm analog sensing provides:  Digital transmission of analog sensor values via IDNet or MAPNET II two-wire communications For use with the following Simplex® products:  4007ES, 4010, 4010ES, 4100ES, and 4100U Series control panels; and 4008 Series control panels with reduced feature set (refer to data sheet S4008-0001 for details)  4020, 4100, and 4120 Series control panels, Universal Transponders, and 2120 TrueAlarm CDTs equipped for MAPNET II operation Fire alarm control panel provides:  Peak value logging allowing accurate analysis of each sensor for individual sensitivity selection  Sensitivity monitoring satisfying NFPA 72 sensitivity testing requirements; automatic individual sensor calibration check verifies sensor integrity  Automatic environmental compensation, multi-stage alarm operation, and display of sensitivity directly in percent per foot  Ability to display and print detailed sensor information in plain English language Photoelectric smoke sensors provide:  Seven levels of sensitivity from 0.2% to 3.7% (refer to additional information on page 3) Heat sensors provide:  Fixed temperature sensing  Rate-of-rise temperature sensing  Utility temperature sensing  Listed to UL 521 and ULC-S530 General features:  Operation is for ceiling or wall mounting  Listed to UL 268 and ULC-S529  Louvered smoke sensor design enhances smoke capture by directing flow to chamber; entrance areas are minimally visible when ceiling mounted  Designed for EMI compatibility  Magnetic test feature is provided  Different bases are available to support a supervised or unsupervised output relay, and/or a remote LED alarm indicator Additional base reference:  For isolator bases, refer to data sheet S4098-0025  For sounder bases, refer to data sheet S4098-0028  For photo/heat sensors, refer to data sheet S4098-0024 (single address) and S4098-0033 (dual address) * These products have been approved by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listings 7272-0026:218, 7271-0026:231, 7270-0026:216, and 7300-0026:217 for allowable values and/or conditions concerning material presented in this document. Accepted for use – City of New York Department of Buildings – MEA35-93E. Additional listings may be applicable, contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products. 4098-9714 TrueAlarm Photoelectric Sensor Mounted in Base Description Digital Communication of Analog Sensing. TrueAlarm analog sensors provide an analog measurement digitally communicated to the host control panel using Simplex addressable communications. At the control panel, the data is analyzed and an average value is determined and stored. An alarm or other abnormal condition is determined by comparing the sensor’s present value against its average value and time. Intelligent Data Evaluation. Monitoring each sensor’s average value provides a continuously shifting reference point. This software filtering process compensates for environmental factors (dust, dirt, etc.) and component aging, providing an accurate reference for evaluating new activity. With this filtering, there is a significant reduction in the probability of false or nuisance alarms caused by shifts in sensitivity, either up or down. Control Panel Selection. Peak activity per sensor is stored to assist in evaluating specific locations. The alarm set point for each TrueAlarm sensor is determined at the host control panel, selectable as more or less sensitive as the individual application requires. Timed/Multi-Stage Selection. Sensor alarm set points can be programmed for timed automatic sensitivity selection (such as more sensitive at night, less sensitive during day). Control panel programming can also provide multi-stage operation per sensor. For example, a 0.2% level may cause a warning to prompt investigation while a 2.5% level may initiate an alarm. Sensor Alarm and Trouble LED Indication. Each sensor base’s LED pulses to indicate communications with the panel. If the control panel determines a sensor is in alarm, or is dirty or has some other type of trouble, the details are annunciated at the control panel and that sensor base’s LED will be turned on steadily. During a system alarm, the control panel will control the LEDs such that an LED indicating a trouble will return to pulsing to help identify the alarmed sensors. TrueAlarm Analog Sensing UL, ULC, CSFM Listed; FM Approved; TrueAlarm Analog Sensors – Photoelectric MEA (NYC) Acceptance* and Heat; Standard Bases and Accessories S4098-0019-22 10/2016 ALARM Sensor Base Features Base mounted address selection:  Address remains with its programmed location  Accessible from front (DIP switch under sensor) General features:  Automatic identification provides default sensitivity when substituting sensor types  Integral red LED for power-on (pulsing), or alarm or trouble (steady on)  Locking anti-tamper design mounts on standard outlet box  Magnetically operated functional test Sensor Bases 4098-9792, Standard Sensor Base 4098-9789, Sensor Base with wired connections for:  2098-9808 Remote LED alarm indicator or 4098-9822 relay (relay is unsupervised and requires separate 24 VDC) Supervised Relay Bases (not compatible with 2120 CDT):  4098-9791, 4-Wire Sensor Base, use with remote or locally mounted 2098-9737 relay, requires separate 24 VDC  4098-9780, 2-Wire Sensor Base, use with remote or locally mounted 4098-9860 relay, no separate power required  Supervised relay operation is programmable and can be manually operated from control panel  Includes wired connections for remote LED alarm indicator or 4098-9822 relay (relay is unsupervised and requires separate 24 VDC) Sensor Base Options 2098-9737, Remote or local mount supervised relay:  DPDT contacts for resistive/suppressed loads, power limited rating of 3 A @ 28 VDC; non-power limited rating of 3 A @ 120 VAC (requires external 24 VDC coil power) 4098-9860, Remote or local mount supervised relay:  SPDT dry contacts, power limited rating of 2 A @ 30 VDC, resistive; non-power limited rating of 0.5 A @ 125 VAC, resistive 4098-9822, LED Annunciation Relay:  Activates when base LED is on steady, indicating local alarm or trouble  DPDT contacts for resistive/suppressed loads, power limited rating of 2 A @ 28 VDC; non-power limited rating of 1/2 A @ 120 VAC, (requires external 24 VDC coil power) 4098-9832, Adapter plate:  Required for surface or semi-flush mounting to 4” square electrical box and for surface mounting to 4” octagonal box  Can be used for cosmetic retrofitting to existing 6-3/8” diameter base product 2098-9808, Remote red LED Alarm Indicator:  Mounts on single gang box (shown in illustration to right) Description TrueAlarm sensor bases contain integral addressable electronics that constantly monitor the status of the detachable photoelectric or heat sensors. Each sensor’s output is digitized and transmitted to the system fire alarm control panel every four seconds. Since TrueAlarm sensors use the same base, different sensor types can be easily interchanged to meet specific location requirements. This feature also allows intentional sensor substitution during building construction. When conditions are temporarily dusty, instead of covering the smoke sensors (causing them to be disabled), heat sensors may be installed without reprogramming the control panel. Although the control panel will indicate an incorrect sensor type, the heat sensor will operate at a default sensitivity providing heat detection for building protection at that location. Mounting Reference Electrical Box Requirements: (boxes are by others) Without relay in the box:4" octagonal or 4" square, 1-1/2" deep; single gang, 2" deep With relay in the box :4" octagonal or 4" square, 1-1/2" deep, with 1-1/2" extension ring TrueAlarm Bases 4098-9780, 4098-9789, 4098-9791, & 4098-9792 4-7/8" (124 mm) 15/16" (24 mm) 6-3/8" (162 mm) 1/4" (6.4 mm) 4098-9832 Adapter Plate, required for mounting to surface mounted boxes and 4"squareflush box 2098-9737 Supervised Relay (mounts in base electrical box or remotely) 4098-9822 Relay (mounts in base electrical box) NOTE:Review total wire count, wire size, and accessories being wired to determine required box volume. Relay Size: 2-1/2" X 1-1/2" X 1" (3.75 in3 ) (64 mm X 38 mm X 25.4 mm) 4098-9860 Supervised Relay (mounts in base electrical box or remotely; 2-3/8" X 1-1/4" X 11/32" (1 in3 ) (60.4 mm X 31.8 mm X 8.6 mm) Surface mount reference 4" (102 mm) Square Box 4" (102 mm) Octagonal Box Flush mount reference, mount even with final surface, or with up to 1/4" (6.4 mm) maximum recess 1-1/2" (38 mm) minimum box depth 2 S4098-0019-22 10/2016 TrueAlarm Sensor Bases and Accessories TrueAlarm Sensors Features Sealed against rear air flow entry Interchangeable mounting EMI/RFI shielded electronics Heat sensors:  Selectable rate compensated, fixed temperature sensing with or without rate-of-rise operation  Rated spacing distance between sensors: Fixed Temp. Setting UL & ULC Spacing FM Spacing, Either Fixed Temperature Setting 135° F (57.2° C) 60 ft x 60 ft (18.3 m) 20 ft x 20 ft (6.1 m) for fixed temperature only; RTI = Quick 50 ft x 50 ft (15.2 m) for fixed temperature with either rate-of-rise selection; RTI = Ultra Fast 155° F (68° C) 40 ft x 40 ft (12.2 m) Smoke Sensors:  Photoelectric technology sensing  360° smoke entry for optimum response  Built-in insect screens 4098-9714 Photoelectric Sensor TrueAlarm photoelectric sensors use a stable, pulsed infrared LED light source and a silicon photodiode receiver to provide consistent and accurate low power smoke sensing. Seven levels of sensitivity are available for each individual sensor, ranging from 0.2% to 3.7% per foot of smoke obscuration. Sensitivities of 0.2%, 0.5%, and 1% are for special applications in clean areas. Standard sensitivities are 1.5%, 2.0%, 2.5%, 3.0%, and 3.7%. Application type and sensitivity are selected and then monitored at the fire alarm control panel.* The sensor head design provides 360° smoke entry for optimum response to smoke from any direction. Due to its photoelectric operation, air velocity is not normally a factor, except for impact on area smoke flow. 2-1/8" (54 mm) LED status indicator 4-7/8" (124 mm) 4098-9714 Photoelectric Sensor with Base 4098-9733 Heat Sensor TrueAlarm heat sensors are self-restoring and provide rate compensated, fixed temperature sensing, selectable with or without rate-of-rise temperature sensing. Due to its small thermal mass, the sensor accurately and quickly measures the local temperature for analysis at the fire alarm control panel. Rate-of-rise temperature detection is selectable at the control panel for either 15° F (8.3° C) or 20° F (11.1° C) per minute. Fixed temperature sensing is independent of rate-of-rise sensing and programmable to operate at 135° F (57.2° C) or 155° F (68° C). In a slow developing fire, the temperature may not increase rapidly enough to operate the rate-of-rise feature. However, an alarm will be initiated when the temperature reaches its rated fixed temperature setting. TrueAlarm heat sensors can be programmed as a utility device to monitor for temperature extremes in the range from 32° F to 155° F (0° C to 68° C). This feature can provide freeze warnings or alert to HVAC system problems. Refer to specific panels for availability. 2-3/8" (60 mm) LED status indicator 4-7/8" (124 mm) 4098-9733 Heat Sensor with Base WARNING: In most fires, hazardous levels of smoke and toxic gas can build up before a heat detection device would initiate an alarm. In cases where Life Safety is a factor, the use of smoke detection is highly recommended. Application Reference Sensor locations should be determined only after careful consideration of the physical layout and contents of the area to be protected. Refer to NFPA 72, the National Fire Alarm and Signaling Code. On smooth ceilings, smoke sensor spacing of 30 ft (9.1 m) may be used as a guide.* * For detailed application information including sensitivity selection, refer to Installation Instructions 574-709. 3 S4098-0019-22 10/2016 TrueAlarm Sensor Bases (for use with Sensors 4098-9714 and 4098-9733) (Refer to Application Manual 574-709 and Installation Instructions 574-707 for additional information) Model* Color Description Compatibility Mounting Requirements 4098-9792 White Standard Sensor Base No options 4” octagonal or 4” square box, 1-1/2” min. depth; or single gang box, 2” min. depth 4098-9776 Black 4098-9789 White Sensor Base with connections for Remote LED Alarm Indicator or Unsupervised Relay 2098-9808 Remote Alarm Indicator or 4098-9822 Unsupervised Relay 4” octagonal or 4” square box Note: Box depth requirements depend on total wire count and wire size, refer to accessories list below for reference. ** NOTE: 4098-9791 and 4098- 9780 are NOT compatible with the 2120 CDT 4098-9789 IND White 4098-9775 Black 4098-9791** White 4-Wire Sensor Supervised Relay Base with connections for LED Indicator or Unsupervised Relay 2098-9737 Supervised Remote Relay 2098-9808 Remote Alarm Indicator or 4098-9822 Unsupervised Relay 4098-9780** White 2-Wire Sensor Supervised Relay Base with connections for LED Indicator or Unsupervised Relay 4098-9860 Supervised Remote Relay 2098-9808 Remote Alarm Indicator or 4098-9822 Unsupervised Relay TrueAlarm Sensors Model* Model* Description Compatibility Mounting Requirements 4098-9714 White Photoelectric Smoke Sensor Bases 4098-9775, 4098-9776, 4098- 9792, 4098-9789, 4098-9791, and 4098-9780 Refer to base requirements 4098-9714 IND 4098-9774 Black 4098-9733 White Heat Sensor 4098-9778 Black TrueAlarm Sensor/Base Accessories Model Description Compatibility Mounting Requirements 2098-9737 Supervised Relay, mounts remote or in base electrical box For use with 4098-9791 base Remote Mounting requires 4” octagonal or 4” square box, 1-1/2” minimum depth Base Mounting requires 4” octagonal box, 2-1/8” deep with 1-1/2” extension ring 4098-9860 Supervised Relay, mounts remote or in base electrical box For use with 4098-9780 base 2098-9808 Remote Red LED Alarm Indicator on single gang stainless steel plate Bases 4098-9789, 4098-9791, and 4098-9780 Single gang box, 1-1/2” minimum depth 4098-9822 Unsupervised Relay, tracks base LED status; Note: Mounts only in base electrical box Bases 4098-9789, 4098-9791, and 4098-9780 4” octagonal box, 2-1/8” deep with 1-1/2” extension ring 4098-9832 Adapter Plate Bases 4098-9792, 4098-9789, 4098-9791, and 4098-9780 Required for surface or semi-flush mounted 4” square box and for surface mounted 4” octagonal box * Note: Model numbers ending in IND are assembled in India. TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm and Signaling Code are trademarks of the National Fire Protection Association (NFPA). Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S4098-0019-22 10/2016 www.simplex-fire.com © 2016 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. General Operating Specifications Communications and Sensor Supervisory Power IDNet or MAPNET II communications, auto-selected, 1 address per base Communications Connections Screw terminals for in/out wiring, 18 to 14 AWG (0.82 mm2 to 2.08 mm2) Remote LED Alarm Indicator Current 1 mA typical, no impact to alarm current Remote LED Alarm Indicator and Relay Connections Color coded wire leads, 18 AWG (0.82 mm2 ) UL Listed Operating Temperature Range 32° to 100° F (0° to 38° C) Operating Temperature Range with 4098-9733 Heat Sensor 32° to 122° F (0° to 50° C) with 4098-9714 Smoke Sensor 15° to 122° F (-9° to 50° C) Storage Temperature Range 0° F to 140° F (-18° C to 60° C) Humidity Range 10 to 95% RH 4098-9714 Smoke Sensor Air Velocity Rating 0-4000 ft/min (0-1220 m/min) Housing Color Frost White or Black 4098-9791 Base With Supervised Remote Relay 2098-9737 (see page 2 for contact ratings) Externally Supplied Relay Coil Voltage 18-32 VDC (nominal 24 VDC) Supervisory Current 270 A, from 24 VDC supply Alarm Current with 2098-9737 Relay 28 mA, from 24 VDC supply 4098-9780 Base With Supervised Remote Relay 4098-9860 (see page 2 for contact ratings) Power Supplied from communications 4098-9822 Unsupervised Relay, Requirements for Bases 4098-9789. 4098-9791, and 4098-9780 (see page 2 for contact ratings) Externally Supplied Relay Coil Voltage 18-32 VDC (nominal 24 VDC) Supervisory Current Supplied from communications Alarm Current 13 mA from separate 24 VDC supply TrueAlarm Analog Sensing Product Selection Chart Specifications Features Compact air duct sensor housing with clear cover to monitor for the presence of smoke** Includes factory installed TrueAlarm photoelectric smoke sensor and features:  Individual sensor information processed by the host control panel to determine sensor status  Digital transmission of analog sensor values via IDNet or MAPNET II, 2-wire communications  Programmable sensitivity, consistent accuracy, environmental compensation, status testing, and monitoring of sensor dirt accumulation Model 4098-9755:  Basic duct sensor housing (no relay output) powered by IDNet/MAPNET II communications Model 4098-9756:  Duct sensor housing with supervised output for multiple remote relays; requires separate 24 VDC; includes one relay  Relay output is under panel control  At the panel, relay output can be activated manually or in response to a separate alarm or other input General features:  UL listed to Standard 268A  Clear cover allows visual inspection  Test ports provide functional smoke testing access with cover in place  Mounts to rectangular ducts or round ducts; minimum size is 8” (203 mm) square or 18” (457 mm) diameter  Magnetic test feature for alarm initiation at housing  Optional weatherproof enclosure is available separately (refer to data sheet S4098-0032) Diagnostic LEDs (on interface board):  Red Alarm/Trouble LED for sensor status and communications polling display  Yellow LED for open or shorted trouble indication of supervised relay control (4098-9756 only) Sampling tubes (ordered separately):  Available in multiple lengths to match duct size  Installed and serviced with housing in place Remote module options (ordered separately):  Remote red status/alarm LED (2098-9808)  Remote test station with LED (2098-9806)  4098-9843 remote relays (refer to page 2 for details) * These products have been approved by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 3240-0026.241 for allowable values and/or conditions concerning material presented in this document. Accepted for use – City of New York Department of Buildings – MEA35-93E. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products. This device is a duct smoke housing. When provided with detector, it is designed to sample the air flowpassing by it in the air duct to determine whether it contains unacceptable levels of smoke. Theeffectiveness of a duct smoke detector is highly dependent upon: the design and operating conditions of theair handling system in which it is installed, variables such as smoke dilution and stratification over whicheven the best designed systems have no control, and proper placement and positioning of the duct smokedetector, which is often compromised for practical reasons. For the reasons stated above, the effectivenessof this duct smoke detector cannot be warranted or guaranteed. Under no circumstances should this ductsmoke detector be used or regarded to be a substitute for the building's Fire alarm and detection system towhich this device is attached as a secondary detection device.DO NOT REMOVE THIS NOTICE! Duct Sensor Housing, Front and Bottom View ALARM TEST NORM ALARM 2098-9808 2098-9806 Remote Status/Alarm Indicator and Test Station Introduction Operation. Simplex® compact air duct smoke sensor housings provide TrueAlarm operation for the detection of smoke in air conditioning or ventilating ducts. Sampling tubes are installed into the duct allowing air to be directed to the smoke sensor mounted in the housing. TrueAlarm Sensor Operation Digital Communication of Analog Sensing. Analog information from the sensor is digitally communicated to the control panel where it is analyzed. Sensor input is stored and tracked as an average value with an alarm or abnormal condition being determined by comparing the sensor’s present value against its average. Intelligent Data Evaluation. Monitoring each photoelectric sensor’s average value provides a software filtering process that compensates for environmental factors (dust, dirt, etc.) and component aging, providing an accurate reference for evaluating new activity. The result is a significant reduction in the probability of false or nuisance alarms caused by shifts in sensitivity, either up or down. ** Please note that smoke detection in air ducts is intended to provide notification of the presence of smoke in the duct. It is not intended to, and will not, replace smoke detection requirements for open areas or other non-duct applications. TrueAlarm Analog Sensing UL, ULC, CSFM Listed; FM Approved; Addressable Duct Sensor Housings with TrueAlarm MEA (NYC) Acceptance* Photoelectric Sensor; Available with Multiple Relay Control S4098-0030-10 11/2014 TrueAlarm Sensor Operation (Continued) Control Panel Selection. Peak activity per sensor is stored to assist in evaluating specific locations. The alarm set point for each sensor is determined at the control panel, selectable as the individual application requires. Sensor Status LED. Each sensor housing’s red status LED (located on the electrical interface board) pulses to indicate communications with the panel. If the control panel determines that a sensor is in alarm, or that it is dirty or has some other type of trouble, the details are annunciated at the control panel and that sensor housing’s status LED will be turned on steadily. During a system alarm, the control panel will control the LEDs such that an LED indicating a trouble will return to pulsing to help identify any alarmed sensors. (Remote Status/Alarm LEDs track the operation of the sensor housing LED.) Photoelectric Sensing TrueAlarm photoelectric sensors use a stable, pulsed infrared LED light source and a silicon photodiode receiver to provide consistent and accurate low power smoke sensing. Photoelectric Sensing (Continued) Typically duct sensor applications require less sensitive settings (such as 2.5% per foot obscuration) due to the ducts being a relative dirty environment. However, the standard seven levels of TrueAlarm sensor sensitivity are available for each individual sensor, ranging from 0.2% to 3.7% per foot of smoke obscuration. Sensitivity is selected and monitored at the fire alarm control panel. Fire Alarm Control Panel Features  Individual smoke sensitivity selection  Sensitivity monitoring that satisfies NFPA 72 sensitivity testing requirements  Peak value logging allows accurate analysis for sensitivity selection  Automatic, once per minute individual sensor calibration check verifies sensor integrity  Automatic environmental compensation  Smoke sensitivity is displayed in percent per foot  Ability to display and print detailed sensor information in plain English language  Relays of model 4098-9756 are under panel control for ON, OFF, or override 2 S4098-0030-10 11/2014 Duct Smoke Sensor Housing with Photoelectric Sensor* Model Description Compatibility 4098-9755 Basic Duct Sensor Housing; operating power is supplied by either IDNet or MAPNET II communications (no relay output) 4007ES, 4008, 4010, 4010ES, 4020, 4100, 4100ES, 4100E, and 4120. Also 2120 CDT if configured for MAPNET II, TrueAlarm operation 4098-9756 Duct Sensor Housing with supervised multiple relay output, requires separate 24 VDC fire alarm power and 4081-9008 end-of-line resistor harness; includes one 4098-9843 relay Same as above except relay operation is not compatible with 2120 CDT; Relay output is for up to 15 total 4098-9843 Relays (additional relays are ordered separately) Remote LED Indicator and Test Station, Select One if Required Model Description Compatibility Mounting 2098-9808 Red LED status indicator on single-gang stainless steel plate 4098-9755 4098-9756 Use single gang box, 3” H x 2” W x 2” D (76 mm x 51 mm x 51 mm) 2098-9806 Test Station with keyswitch and red LED status indicator, on single-gang stainless steel plate; (turning switch to “TEST” initiates alarm for system testing) Epoxy Encapsulated Remote Relay and End-of-Line Resistor Model Description Compatibility Location 4098-9843 Relay; single Form C (7 A @ 120 VAC); refer to pages 3 and 4 for additional relay information; one included with 4098-9756; wiring is 18 AWG (0.82 mm2 ) color coded wire leads 4098-9756 only; connect up to 15 Locate relays within 3 ft (1 m) of device being controlled per NFPA 72 4081-9008 End-of-Line Resistor Harness; 10 k, 1/2 W; (ref. 733-894); required to supervise remote relay coil connection 4098-9756 At last relay location * Each duct housing includes an internally mounted model 4098-9714 TrueAlarm photoelectric sensor and an exhaust tube. A correctly sized sampling tube (ordered per application) is required, refer to chart below. Overall Duct Width Tube Required Suggested Cut Length 12” (305 mm) 4098-9854 1/2” (12.7 mm) longer than duct width 13” to 23” (330 mm to 584 mm) 4098-9855 1/2” (12.7 mm) longer than duct width 24” to 46” (610 mm to 1168 mm) 4098-9856 3 in” (76 mm) longer than duct width 46” to 71” (1168 mm to 1803 mm) 4098-9857 3 in” (76 mm) longer than duct width 71” to 95” (1803 mm to 2413 mm) 4098-9858 3 in” (76 mm) longer than duct width Duct Sensor Selection Chart Sampling Tube Selection Chart, Ordered Separately Per Duct Width, Select One NOTE: Refer to Installation Instructions 574-776 for additional installation detail and maintenance information. 3 S4098-0030-10 11/2014 This device is a duct smoke housing. When provided with detector, it is designed to sample the air flow passing by it in the air duct to determine whether it contains unacceptable levels of smoke. The effectiveness of a duct smoke detector is highly dependent upon: the design and operating conditions of the air handling system in which it is installed, variables such as smoke dilution and stratificationover which even the best designed systems have no control, and proper placement and positioning of the duct smoke detector, which is often compromised for practical reasons. For the reasons stated above, the effectiveness of this duct smoke detector cannot be warranted or guaranteed. Under no circumstances should this duct smoke detector be used or regarded to be a substitute for the building's Fire alarm and detection system to which this device is attached as a secondary detection device.DO NOT REMOVE THIS NOTICE! 6-3/4" (171 mm ) 11-3/8" (289 mm) 3-3/8" (86 mm) Exhaust tube access hole Captive fastening screws (4) Metal plate with dual holes for 3/4" (19 mm) conduit, plug supplied for unused hole Wiring terminals Gaskets (supplied) Conduit (by others) Stationary baffle (built-in) 4098-9714 Smoke sensor, mounted in special interface base (supplied) Magnetic test area Test ports (2) provided for measuring airflow and for aerosol injection 13/16" (21 mm) Sampling tube, ordered separately per duct width Exhaust tube (supplied) NOTE: Orientation shown is for reference only, refer to General Location Notes and End View illustration below for alternate mounting reference. Red sensor status LED Transparent cover Gasketed sensor area Sampling tube access hole Duct wall Front View Bottom view Yellow LED, relay control trouble indicator (4098-9756 only) Side of duct 4098-9843 Remote Relay (7 A @ 120 VAC, for use with 4098-9756 only) NOTE: Mount in separate electrical box within 3 ft (1 m) of device being controlled per NFPA 72 AP&C-PAM SD WHT BLUYEL RED ORG 1-3/16" (30 mm) 1-1/2" (38 mm) 13/16" (21 mm) Sampling tube, keyed for proper hole alignment with holes facing into airflow (template is provided for proper tube installation). (Housing is shown as position 2 per note 2 below.) 8" Square duct outline (minimum width) 18" Round duct outline (minimum diameter) End View with Ducts and Tubes General Location Notes: 1. Testing performed under the auspices of the Fire Detection Institute (FDI) recommended when sampling tubes are not located vertically, that they be positioned horizontally in the upper half of the duct to account for possible stratification. 2. Three duct side mounting options are available as shown below. Mount housing at 90° to airflow for all orientations. Arrows indicate allowed airflow directions. Exhaust tube Duct housing Alternate location (if appropriate) Square duct reference outline This device is a duct smoke housing. When provided with detector, it is designed to sample the air flowpassing by it in the air duct to determine whether it contains unacceptable levels of smoke. Theeffectiveness of a duct smoke detector is highly dependent upon: the design and operating conditions of theair handling system in which it is installed, variables such as smoke dilution and stratification over whicheven the best designed systems have no control, and proper placement and positioning of the duct smokedetector, which is often compromised for practical reasons. For the reasons stated above, the effectivenessof this duct smoke detector cannot be warranted or guaranteed. Under no circumstances should this ductsmoke detector be used or regarded to be a substitute for the building's Fire alarm and detection system towhich this device is attached as a secondary detection device.DO NOT REMOVE THIS NOTICE! This device is a d u c t s m o k e h o u s i n g . W h e n p r o v i d e d w i t h d e t e c t o r , i t i s d e s i g n e d t o s a m p l e t h e a i r f l o w passing b y i t i n t h e a i r d u c t t o d e t e r m i n e w h e t h e r i t c o n t a i n s u n a c c e p t a b l e l e v e l s o f s m o k e . T h e effectiveness of a duct smoke detector is highly dependent upon: the design and operating conditions of theair hand l i n g s y s t e m i n w h i c h i t i s i n s t a l l e d , v a r i a b l e s s u c h a s smoke d i l u t i o n a n d s t r a t i f i c a t i o n over wh i c h even th e b e s t d e s i g n e d s y s t e m s h a v e n o c o n t r o l , a n d p r o p e r p l a c e m e n t a n d p o s i t i o n i n g o f t h e d u c t s m o k e detector, which is often compromised for practical reasons. For the reasons stated above, the effectivenessof this d u c t s m o k e d e t e c t o r c a n n o t b e w a r r a n t e d o r g u a r a n t e e d . U n d e r n o c i r c u m s t a n c e s s h o u l d t h i s d u c t smoke detector be used or regarded to be a substitute for the building's Fire alarm and detection system towhich this device is attached as a secondary detection device.DO NOT R E M O V E T H I S N O T I C E !1 2 3 This device is a duct smoke housing. When provided with detector, it is designed to sample the air flowpassing by it in the air duct to determine whether it contains unacceptable levels of smoke. The effectiveness of a duct smoke detector is highly dependent upon: the design and operating conditions of theair handling system in which it is installed, variables such as smoke dilution and stratificationover which even the best designed systems have no control, and proper placement and positioning of the duct smoke detector, which is often compromised for practical reasons. For the reasons stated above, the effectivenessof this duct smoke detector cannot be warranted or guaranteed. Under no circumstances should this duct smoke detector be used or regarded to be a substitute for the building's Fire alarm and detection system towhich this device is attached as a secondary detection device.DO NOT REMOVE THIS NOTICE! DO NOT MOUNT ON BOTTOM OF DUCT Duct Sensor Housing Detail Reference Duct Sensor Location Reference Return Air Supply Air Return air damper Filter bank Fresh air Do not locate sensor here Sensor OK Exhaust Exhaust Damper Sensor OKDo not locate sensor here Additional Information. Refer to NFPA 90A, Standard for the Installation of Air Conditioning and Ventilating Systems; NFPA 72, the National Fire Alarm and Signaling Code; and the NEMA Guide for Proper Use of Smoke Detectors in Duct Applications, and Installation Instructions 574-776. Duct Sensor Location Considerations: 1. Proper duct smoke detection location must ensure adequate airflow within the duct housing. 2. Duct air velocity rating is 300 to 4000 ft/min (91 to 1220 m/min). Pressure differential between intake and exhaust tubes is required to be between 0.015 to 1.55 inches of water (0.381 to 39.37 mm). 3. Ensure accessibility for test and service. 4. Proper Locations: downstream side of filters to detect fires in the filters; in return ducts, ahead of mixing areas; upstream of air humidifier and cooling coil. 5. Other locations and orientations may be required for proper duct smoke detection depending on duct access, system design, and duct airflow testing. Contact your local Simplex product supplier for assistance. Locations to Avoid: 1. Where dampers closed for comfort control would interfere with airflow. 2. Next to outside air inlets (unless the intent is to monitor smoke entry from that area). 3. In return air damper branch ducts and mixing areas where airflow may be restricted. TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm and Signaling Code are registered trademarks of the National Fire Protection Association (NFPA). General Mechanical and Environmental Air Velocity Range (linear ft/min) 300 to 4000 ft/min (91 to 1220 m/min) Sensor Sensitivity Range 0.2% to 3.7% per foot of obscuration, selectable at host control panel UL Listed Temperature Range 32° F to 100° F (0° C to 38° C) Operating Temperature Range 32° F to 122° F (0° C to 50° C) Storage Temperature Range 0 F to 140 F (-18 C to 60 C) Humidity Range 10% to 95% RH, non-condensing Wiring Connections Terminal blocks, 18 to 12 AWG (0.82 mm2 to 3.31 mm2 ) Housing Color and Material Black ABS base with clear polycarbonate cover Sampling and Exhaust Tube Material Black CPVC, custom extrusion; sampling tubes are pre-drilled Remote Status/Alarm LED and Test Station with Remote Status/Alarm LED Remote Alarm LED Current 1.2 mA, no impact to 24 VDC alarm current (2098-9808 or 2098-9806) Test Station Keyswitch Current 3.3 mA, no impact to 24 VDC alarm current (2098-9806) Remote Alarm LED and Test Station Distance 250 ft (76 m) maximum Addressable Operation Data Communications IDNet or MAPNET II communications, auto-select, one address per housing; provides operating power to model 4098-9755 Model 4098-9756 with Supervised Multiple Relay Control, Requires Separate Fused 24 VDC from Fire Alarm Power Supply Input Voltage 18-32 VDC (24 VDC nominal) Standby Current 3 mA @ 24 VDC Alarm Current 15 mA @ 24 VDC; add 15 mA for each 4098-9843 relay Supervised Remote Relay Control Output For use with 4098-9843 relay only, quantity of 15 maximum; distance of 500 ft (152 m) maximum; requires 4081-9008 (ref. 733-894) 10 k, 1/2 W end-of-line resistor 4098-9843 Relay Output Ratings, Single Form C, use with Model 4098-9756 Only Coil Current 15 mA @ 24 VDC, up to 15 maximum per relay control output Relay Contacts 7 A at 0.35 PF @ 28 VDC & 120 VAC; 250 A @ 5 VDC Location Distance 500 ft (152 m) maximum to relay coils; locate relays within 3 ft (1 m) of device being controlled per NFPA 72 Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S4098-0030-10 11/2014 www.simplex-fire.com © 2014 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. Specifications S4090-0001-10 Features IDNet or MAPNET II addressable communications supply both data and power over a single wire pair to provide**: Supervised Class B monitoring of normally open, dry contacts Total wiring distance from IAM to supervision resistor(s) of up to 500 ft (152 m) Monitored connection is compatible with Simplex® 2081-9044 Overvoltage Protectors for outdoor wiring or electrically noisy applications For use in indoor locations up to 158° F (70° C) such as attic spaces or similar applications For use with following Simplex control panels: Model Series 4008, 4010, 4010ES, 4100U and 4100ES fire alarm control panels for IDNet communications Model Series 4100/4100U/4100ES, 4120, 4020, and 2120 Communicating Device Transponders (CDTs) equipped with MAPNET II communications Model 4090-9001: Enclosed design minimizes dust infiltration Mounts in standard single gang electrical box Screw terminals for wiring connections Visible LED flashes to indicate communications Optional covers are available to allow LED to be viewed after installation (requires mounting bracket, ordered separately) Model 4090-9051: Encapsulated design for extended exposure to high humidity (LED is not present on this model) Color coded 18 AWG leads for wiring IDNet communications provides current limited monitoring: Provides monitoring of tamper switch (supervisory) and waterflow switch (alarm) on same circuit using one point Available with IDNet communications only Multiple operation modes are available and are selectable at the control panel: Contact closure status can be tracked Momentary contact closure conditions can be selected at the panel to be latched or tracked (not available with the 2120 CDT) UL listed to Standard 864 * These products have been approved by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7300-0026:223 for allowable values and/or conditions concerning material presented in this document. It is subject to re-examination, revision, and possible cancellation. Accepted for use – City of New York Department of Buildings – MEA35-93E. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Safety Products Westminster. - IDNET IN ++IDNET IN - 4090-9001 Supervised IAM (shown approximately 3/4 size) LISTED SIGNALING DEVICE ISSUE NO. 4090-9051 Supervised IAM (shown approximately 3/4 size) Description Individual addressable modules (IAMs) receive both power and communications from a two-wire MAPNET II or IDNet circuit. They provide location specific addressability to a single initiating device (such as single station smoke detector alarm contacts or heat detector contacts) or multiple devices at the same location by monitoring normally open dry contacts and the wiring to an end-of-line resistor. Model 4090-9001 is packaged in a thermoplastic housing and provides screw terminal connections and a status indicating LED. Model 4090-9051 is an encapsulated package with wire leads. It does not provide a status indicating LED. Multi-Application Peripherals UL, ULC, CSFM Listed; FM Approved; IDNet™ and MAPNET II® Communicating Devices, MEA (NYC) Acceptance* Individual Addressable Modules (IAMs) 2 S4090-0001-10 Operation Contact Closure. Closure of the monitored contact(s) initiates an alarm or other response as programmed at the fire alarm control panel. An open in the monitored circuit wiring will cause a trouble to be reported. Panel Selections. Selections can be made at the control panel to maintain the alarm condition if the initiating device contacts are momentary, such as from a rate-of-rise heat detector, or to track the device contact status (not available with the 2120 CDT). Current Limited Operation Applications For use with IDNet communications only, these IAMs can provide quad-state sensing of normal, open circuit, short circuit, and current limited conditions. (Program type is “T-sense.”) With the proper end-of-line and current limiting resistors, dual functions such as tamper switch and waterflow switch monitoring can be determined and communicated by a single addressable point. Model Description 4090-9001 Supervised IAM, mounted in thermoplastic housing with screw terminals; see applicable options below 4090-9051 Supervised IAM, encapsulated with wire leads Optional Trim Plates and Mounting Bracket for Model 4090-9001 Model Description 4090-9806 For semi-flush mounted box Trim plate with LED viewing window, requires 4090-9810 mounting bracket, includes mounting screws; galvanized steel 4090-9807 For surface mounted box 4090-9810 Mounting bracket, mounts IAM to electrical box and provides screw holes for trim plate, required for optional trim plates End-of-Line Resistor Harnesses (ordered separately as required) Model Reference No. Description 4081-9004 733-886 6.8 k , 1/2 W; Standard end-of-line resistor harness for N.O. contact supervision 4081-9003 733-896 4.7 k , 1/2 W Use for current limited monitoring applications 4081-9005 733-984 1.8 k , 1/2 W Electrical Power and Communications MAPNET II or IDNet, auto selected, 1 address per IAM Input Requirements Normally open, dry contacts Wire Connections 4090-9001 Screw terminals for in/out wiring, 18 to 14 AWG wire (0.82 mm2 to 2.08 mm2) 4090-9051 Color coded wire leads, 18 AWG (0.82 mm2), 8” long (203 mm) Reference Documents Installation Instructions 574-331 for 4090-9001; 579-572 for 4090-9151 Field Wiring Diagrams 842-073 for IDNet operation; 841-804 for MAPNET II operation Wiring Distances Distance from IAM to Contacts 500 ft (152 m) maximum without protectors 400 ft (122 m) maximum with 2081-9044 Overvoltage Protectors Wiring Distance Reference per channel, MAPNET II or IDNet Communications 2500 ft (762 m) maximum from fire alarm control panel 10,000 ft (3048 m) maximum total wiring distance (including T-Taps) Mechanical Dimensions 4090-9001 1-9/16” W x 1-3/4” H x 1-1/4” D (40 mm x 44 mm x 32 mm) 4090-9051 1-9/16” W x 1-9/16” H x 9/16” D (40 mm x 40 mm x 14 mm) Housing Material, 4090-9001 Black thermoplastic Encapsulation Material, 4090-9051 Epoxy, beige Temperature Range 32° to 158° F (0° to 70° C); intended for indoor operation Humidity Range Up to 93% RH at 100° F (38° C) IAM Product Selection Specifications 3 S4090-0001-10 Optional Trim Plates and Mounting Bracket for Visible LED Single gang electrical box 2-1/2" (64mm) minimum depth (supplied by others) Single gang blank cover plate and mounting screws, for use when LED is not required to be externally viewed (supplied by others) 4090-9001 IDNet supervised IAM Field wiring shown for reference Address setting under resealable label - IDNET IN ++IDNET IN - LED viewing port 4090-9806, Trim plate for semi-flush mounted box 4090-9807, Trim plate for surface mounted box 4-1/4" (108 mm) 2-1/2" (64 mm) 2-13/16" (72 mm) 4-1/2" (114 mm) Light pipe for LED viewing NOTE: These mounting plates require mounting bracket 4090-9810. 4090-9810 Mounting bracket, ordered separately Mounting Reference, Single Gang Blank Cover Plate Mounting Information Single gang electrical box 2-1/2" (64mm) minimum depth (supplied by others) Single gang blank cover plate and mounting screws (supplied by others) 4090-9051 Encapsulated Supervised IAM Address setting is at rear of housing LISTED SIGNALING DEVICEISSUE NO. SimplexGrinnell LP Westminster • Westminster, MA • 01441-0001 • USA S4090-0001-10 www.simplexgrinnell.com © 2011 Tyco. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. Tyco is a registered trademark of Tyco International Services GmbH and is used under license. Simplex, the Simplex logo, IDNet, and MAPNET II are trademarks of Tyco International Ltd. and its affiliates and are used under license. 4090-9051 Mounting Information Features Individual Addressable Relay Module (Relay IAM):  IDNet addressable control for use with Simplex® fire alarm control panel models 4007ES, 4008, 4010, 4010ES, 4100ES, and 4100U  A single addressable point provides control and status tracking of a Form “C” contact  Low power latching relay design allows IDNet communications to supply both data and module power  Relay is set to OFF on initial power up and upon loss of IDNet communications Compact, sealed construction:  Enclosed design minimizes dust infiltration  Mounts in standard 4” (102 mm) square electrical box, optional adapter bracket is available to mount in a 4 11⁄16” (119 mm) square electrical box  Screw terminals for wiring connections  Visible LED flashes to indicate communications  Optional covers are available to allow LED to be viewed after installation UL listed to Standard 864 Description IDNet Relay IAMs allow fire alarm control panels to control a remotely located Form “C” contact using IDNet addressable communications for both data and module power. Typical applications would be for switching local power for control functions such as elevator capture, or control of HVAC components, pressurization fans, dampers, etc. Relay status is also communicated requiring only one device address. Product Selection Model Description 4090-9002 Relay IAM Optional Adapter and Trim Plates Model Description 4090-9813 Adapter plate to fit 4 11⁄16” (119 mm) square electrical box 4090-9801 For semi-flush mounted box Trim Plate, galvanized steel, with LED viewing window; includes mounting screws 4090-9802 For surface mounted box * This product has been approved by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7300-0026:223 for allowable values and/or conditions concerning material presented in this document. Accepted for use – City of New York Department of Buildings – MEA35-93E. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products. 4090-9002 IDNet Relay IAM Package (shown approximately 1/2 size) Specifications Communications IDNet communications, 1 address per device Relay IAM Power Supplied by IDNet communications Contact Ratings* (not rated for incandescent switching) Type Form C, SPDT Power-Limited 2 A @ 24 VDC, resistive from listed fire alarm supply 1 A @ 24 VDC, inductive Nonpower-Limited 0.5 A @ 120 VAC, resistive * Provide circuit fusing and transient suppression as required per application. DC inductive loads can typically be diode suppressed; 120 VAC loads may require RC networks or varistors, depending on device type. Refer to the installation instructions for additional information. Wire Connections Screw terminals for in/out wiring, 18 to 14 AWG wire (0.82 to 2.08 mm2) IDNet Communications Wiring Reference Up to 2500 ft (762 m) from control panel Up to 10,000 ft (3048 m) total wiring distance (including T-Taps) Compatible with Simplex 2081-9044 Overvoltage Protectors Dimensions 4 ⅛” H x 4 ⅛” W x 1 ⅜” D (105 mm x 105 mm x 35 mm) Housing Material Black thermoplastic Mounting Plate Sheet metal, galvanized Temperature Range 32° to 120° F (0° to 49° C), intended for indoor operation Humidity Range Up to 93% RH at 100° F (38° C) Installation Instructions 574-184 Multi-Application Peripherals UL, ULC, CSFM Listed; FM Approved; IDNet Communicating Devices MEA (NYC) Acceptance* Model 4090-9002 Relay IAM S4090-0002-10 11/2014 TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S4090-0002-10 11/2014 www.simplex-fire.com © 2014 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. 4" (102 mm) square box, 2-1/8" (54 mm) minimum depth, RACO 232 or equal (supplied by others) Double gang blank cover plate and mounting screws, for use when LED is not required to be externally viewed (supplied by others) 4090-9002 Relay IAM Address setting under resealable label Optional Trim Plates for Visible LED 4090-9802, Trim plate for surface mounted box 4090-9801, Trim plate for semi-flush mounted box Mounting Reference, Double Gang Blank Cover Plate 4-9/16" (116 mm) 4-9/16" (116 mm) 4-5/16" (109 mm) Light pipe for LED viewing 4-5/16" (109 mm) Relay IAM Mounting Information Features UL listed under Standard 864 as Control Unit Accessory (UOXX) Track mount package availability:  Single relay module or four relay module, with or without cover, with SPDT or DPDT contacts  LED indicates relay module status  Cover provide status LED viewing ports  Multiple coil voltage inputs, diode polarized for DC  Modules are track mounted with snap-apart feature design allowing the four relay module to be separated Single encapsulated SPDT relay package with color coded 18 AWG wire leads, available in two versions:  2088-9021 (PAM-1) Provides diode polarized multiple input voltage ability and LED indication  4098-9843 (PAM-SD) Provides a diode polarized 24 VDC coil with in/out wiring Description These multi-purpose control relays offer SPDT or DPDT, 10 A (or 7 A) contacts in a variety of mechanical packages. Models are available for coil operation by one of four input voltages allowing a single relay to be energized from a voltage source of 18-35 VDC or VAC, 120 VAC, or 230 VAC (not available with 4098-9843). Voltage selection is made by wiring to the appropriate input terminals or wire leads. Each relay model (except model 4098-9843) contains a red LED which indicates that the relay is energized. Mounting options are varied for application flexibility. Track mounted relays may be “snapped apart” from a standard four-module assembly and used independently if desired. Specifications Track Mount Relays, see page 2 for dimensions Coil Voltage 18-35 VAC/VDC, 120, or 230 VAC Coil Current SPDT models = 18 mA DPDT models = 40 mA Terminal Blocks Up to 14 AWG (2.08 mm2 ) Contact Ratings 10 A @ 120 VAC N.O. rated 1/6 HP, N.C. rated 1/8 HP 7A @ 28 VDC and @ 230 VAC Temperature Ratings UL Listed Range 32° F to 120° F (0° C to 49° C) Humidity 85% RH Non-condensing NC C NO NC C NO NC C NO NC C NOON T1D2 + C1 0 18/24 115 230 R2 R1 NC C NO NC C NO NC C NO NC C NOON T1D2 + C1 0 18/24 115 230 R2 R1 NC C NO NC C NO NC C NO NC C NOON T1D2 + C1 0 18/24 115 230 R2 R1 NC C NO NC C NO NC C NO NC C NOON T1D2 + C1 0 18/24 115 230 R2 R1 2088-9020, MR204/C, Four DPDT Relay Package with Enclosure (shown with cover removed) AP&C-PAM SD WHT BLU YELRED ORG Encapsulated Relay Package (typical of 2088-9021, PAM-1 and 4098-9843, PAM-SD) Specifications Continued Encapsulated Relays, see page 2 for dimensions Connections 18 AWG (0.82 mm2 ) color-coded wire leads Relay 2088-9021 Contact Ratings 10 A @ 120 VAC, resistive Coil Ratings Voltage 18-35 VAC/VDC, 120, or 240 VAC Current 15 mA @ 24 VAC/VDC, & @ 120 or 230 VAC Relay 4098-9843 Coil Ratings 18-32 VDC input, polarized, 15 mA @ 24 VDC Contact Ratings 7 A at 0.35 p.f @ 28 VDC & 120 VAC 250 µA @ 5 VDC Temperature Ratings UL Listed Range 32° F to 120° F (0° C to 49° C) Humidity 100% RH, condensing * Listings are under Apollo America Inc. per model numbers shown on page 2. See CSFM Listing 7300-1004:0101 for allowable values and/or conditions concerning material presented in this document. System Accessories UL, CSFM Listed; Fire Alarm Control Relays, Track Mount and MEA (NYC) Acceptance* Encapsulated; Model 4098-9843 and 2088 Series S2088-0010-10 11/2014 Module Positions Reference Number Model Number Relay Type Packaging Dimensions One 2088-9007 MR-101/T SPDT Track mount, without cover 3-1/4” H x 2-1/8” W x 1-1/2” D (83 mm x 54 mm x 38 mm) 2088-9009 MR-201/T DPDT 2088-9008 MR-101/C SPDT Track mount with cover 5-1/8” H x 3-1/8” W x 2-1/2” D (131 mm x 79 mm x 64 mm) 2088-9010 MR-201/C DPDT Four 2088-9017 MR-104/T SPDT Track mount, without cover 3-1/4” H x 8-1/2” W x 1-1/2” D (83 mm x 216 mm x 38 mm) 2088-9019 MR-204/T DPDT 2088-9018 MR-104/C SPDT Track mount with cover 5-1/8” H x 9-1/2” W x 2-1/2” D (131 mm x 241 mm x 64 mm) 2088-9020 MR-204/C DPDT NA 2088-9021 PAM-1 SPDT Encapsulated, multi-voltage coil, color coded 18 AWG (0.82 mm2 ) wire leads, with coil status LED 1-1/2” H x 1” W x 7/8” D (38 mm x 25.4 mm x 22 mm) 4098-9843 PAM-SD Encapsulated, 24 VDC coil, color coded 18 AWG (0.82 mm2 ) wire leads (no LED) 1-1/2” H x 1-3/16” W x 13/16” D (38 mm x 30 mm x 21 mm) NC C NO Coil voltage (note polarity for DC) (-)(+) AC AC N V V V (18-35) VDC (18-35) VAC 120 VAC 230 VAC 0 18/24 115 230 SPDT contacts rated 10 A @ 120 VAC, resistive NC C NO (-)(+) AC AC N V V V (18-35) VDC (18-35) VAC 120 VAC 230 VAC 0 18/24 115 230 DPDT contacts rated 10 A @ 120 VAC, resistive NC C NO Terminal strip connections SPDT models Relay energized LED Coil voltage (note polarity for DC) Terminal strip connections DPDT models Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S2088-0010-10 11/2014 www.simplex-fire.com © 2014 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. Relay Selection Chart Track Mount Relay Wiring Reference Features Individually addressed and controlled multi-candela TrueAlert ES V/O (visible only) notification appliances  Multi candela LED strobe available in low (15, 30, and 75 cd) and high (110, 135 and 185 cd) range candela models  Small compact design and low current draw due to energy efficient strobe LEDs  Advanced addressable notification controlled by IDNAC SLCs providing regulated 29 VDC allows strobes to operate with lower current even under battery backup  Wiring supervision to each appliance allowing “T tapped” connections for Class B circuits to simplify wiring (Class A circuits require in/out wiring)  Self-Test Mode allows on-board sensors to detect the LED strobe output and then report their status to the control panel  TrueAlert Device Reports at the control panel detailing appliance point ID, custom label, type, and candela setting (see sample on page 3)  Magnet Test diagnostics to assist checkout and testing of appliances and wiring  Compatibility with ADA requirements  Strobe operation is listed to UL Standard 1971 and ULC Standard S526  Synchronized LED strobe operation on the same IDNAC channel LED Indicator and Magnet Test  Indicator LED indicates magnet test acknowledgment, 3 digit IDNAC address, and candela rating  Indicator LED can be configured to blink each polling cycle to indicate appliance supervision  When the controller is in diagnostic mode, the magnet test pulses the LED to indicate appliance address and can also briefly flash the strobe Mechanical design features  Rugged, high impact, flame retardant thermoplastic housing in red and white colors  Various covers options are available – red with white letters or white with red letters  Available with English/Arabic FIRE lettering  Covers can be easily removed without disturbing the connected housing and avoiding trouble conditions  In/out wiring terminals for 18 AWG to 12 AWG wiring  Mounts to single gang US electrical boxes  Optional mounting adapter plate to adapt to European electrical boxes TrueAlert ES 59VO Series LED Addressable Strobes are Available in Red with White Lettering and White with Red Lettering Description TrueAlert ES LED Addressable Strobes are individually addressed visible notification appliances that receive power, supervision, and control signals from a Simplex fire alarm control panel providing IDNAC Signaling Line Circuits. LED and xenon tube strobes require operation on separate IDNAC channels. Strobe Application Reference Proper selection of visible notification is dependent on occupancy, location, local codes, and proper applications of: the National Fire Alarm Code (NFPA 72), ANSI A117.1; the appropriate model building code: BOCA, ICBO, or SBCCI; and the application guidelines of the Americans with Disabilities Act (ADA). TrueAlert ES Operation Advantage Increased circuit integrity TrueAlert ES Visual Only LED addressable appliances on IDNAC SLCs provide visible notification using a single two- wire circuit that also confirms connection to the individual notification appliance’s electronic circuit. This provides supervision that extends beyond the appliance wiring connections. Reduced current usage on IDNAC SLCs A constant 29 VDC source voltage is maintained, even during battery standby. This allows strobes to operate at higher voltage with lower current and ensuring a consistent current draw and voltage drop margin under both primary power and secondary battery standby. * These products have been approved by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7125-0026:0383 for allowable values and/or conditions concerning material presented in this document. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are TrueAlert LED Addressable Notification Appliances UL, ULC, CSFM Listed* Visible Notification Appliances, Wall Mount FM Approved* Multi-Candela Strobes, Model Series 59VO S59VO-0001-2 9/2016 the property of Tyco Fire Protection Products. TrueAlert Operation Advantage (Cont’d) Reduced installation and testing time Installation time and expense for retrofit or new construction can be significantly reduced with separate controls on the same two wire SLC. When Class B wiring is used, wiring can be “T” tapped, allowing more savings in distance, wire, conduit (size and utilization), and overall installation efficiency. Use of Self-Test and Magnet Test features improves installation efficiency. TrueAlert device reports conveniently identify information about each connected appliance. TrueAlert ES Diagnostics Self-Test and Magnet Test diagnostic features provide individual appliance testing for IDNAC SLCs. With the Self-Test feature, appliance operation can be confirmed without leaving the control panel. Additionally, each appliance’s indicator LED can be selected to pulse when it receives a supervision poll during normal operation. Self-Test allows on-board sensors to detect strobe output on the device and report the strobe status to the control panel. Operation is by selected VNAC appliance groups and is either automatic (all briefly simultaneously activated) or individually activated by applying a magnet. Refer to control panel data sheet for more Self-Test information, see list on page 4. Diagnostics (Cont’d) Silent Appliance Magnet Test pulses the indicator LED sequentially in response to the application of a magnet to conveniently indicate the appliance’s address. Operational Appliance Magnet Test briefly flashes the strobe to indicate proper operation after the address is indicated by pulsing the indicator LED. TrueStart Instrument Two (TSIT) helps with testing of IDNAC SLC wiring and TrueAlert ES appliances. Use it to test IDCs, NACs, and IDNet communications before connection to the control panel. Please contact your local Simplex representative for additional information. TrueAlert Addressable Wiring Isolator Isolator Model 4905-9929 is available for remote mounting on TrueAlert addressable circuits to isolate short circuited wiring from functioning wiring. See data sheet S4905-0001 for more information. 2 S59VO-0001-2 9/2016 TrueAlert ES LED Wall Mount Addressable Strobe Appliances Appliance and cover (dimensions with cover = 5 ¼” H x 3 ½ ” W x 1 ⅝” D / 132 mm x 86 mm x 39 mm) Model* Color Wording Candela rating Model* Color Wording Candela rating 59VO-WRF (-BA) Red FIRE Low (15, 30 and 75 cd) 59VO-WRFH-BA Red FIRE High (110, 135 and 185 cd) 59VO-WWF (-BA) White 59VO-WWFH-BA White 59VO-WRFAB(-BA) Red FIRE / قيرح 59VO-WRFABH-BA Red FIRE / قيرح 59VO-WWFAB(-BA) White 59VO-WWFABH-BA White Appliance only Model Color Candela rating Model Color Candela rating 59VO-APPLWR Red Low 59VO-APPLWRH Red High 59VO-APPLWW White 59VO-APPLWWH White Separate cover Model Color Wording Model Color Wording 59VOC-WRF Red FIRE 59VOC-WWFAB White FIRE / قيرح 59VOC-WWF White 59VOC-WRAAB Red ALERT / راذѧѧѧنإ 59VOC-WRA Red ALERT 59VOC-WWAAB White 59VOC-WWA White 59VOC-WRS Red Logos only 59VOC-WRFAB Red FIRE / قيرح 59VOC-WWS White Separate European adapter back plate Model Color Description 59AP-EUROBB Black Wall mounting plate for mounting to UK (Deta DB164), Swiss (Kaiser 9063-01), or German (HSB, NIS Kombi 372501686) back boxes. * Note: (-BA) indicates model is available either with or without the -BA suffix. Model numbers ending in –BA are assembled in the USA. Product Selection 3 S59VO-0001-2 9/2016 Service Port Page 1 REPORT 5 : TrueAlert Device Report 12:34:56am TUE 16-Mar-15 POINT ID CUSTOM LABEL DEVICE TYPE CANDELA T14-1-1 Location Label . . . up to 40 characters AV-LH 15 T14-1-2 Break Room 5 AV-L 110 T14-1-3 Boiler Room VO-LH 75 T14-1-4 Elec. Room 7 VO-LH 135 Adapter Plate Installation Reference Installation Reference TrueAlert Device Reports Reference Electrical Ratings Typical Operating Voltage Range 23 - 29.5 VDC, Special Application Supervisory Requirements 1 unit load (= 0.8 mA control panel current) IDNAC SLC Loading Maximum of 127 addresses per SLC, 139 unit loads Candela Setting 15 cd 30 cd 75 cd 110 cd 135 cd 185 cd 23 VDC RMS Current Ratings, for typical design of IDNAC Addressable SLCs (6 VDC drop) 31 mA 44 mA 60 mA 125 mA Percentage of rated light output at room temperature Angle On-Axis Vertical, Below Axis Horizontal, Left/Right of Axis 0° 45° 90° 45° 90° UL required output 100% 34% 12% 75% 25% Typical output 145% 84% 21% 102% 47% General Specifications Temperature Range 32 to 120 F (0 to 49 C) Humidity Range 10% to 93%, non-condensing @ 104° F (40° C) IDNAC SLC Wiring Specifications (refer to control panel installation instructions for more information) UTP, unshielded twisted pair recommended Maximum wire length allowed with “T-Taps” for Class B wiring per SLC = 10,000 ft (3048 m) Maximum wire length to any appliance = 4000 ft (1219 m) Connections Terminal blocks on mounting plate for 18 AWG to 12 AWG (0.82 mm2 to 3.31 mm2); two wires per terminal for in/out wiring Installation Instructions 579-1162 Notes: Refer to compatibility table above for fire alarm control panel and power supply operation type. TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm Code are trademarks of the National Fire Protection Association (NFPA). Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S59VO-0001-2 9/2016 www.simplex-fire.com © 2015 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. Compatible Controllers Data Sheet Reference Controller Output IDNAC SLC Output Voltage Appliance Voltage Design Reference 4100ES with EPS+ or EPS Power Supply S4100-0100 IDNAC SLC 29 VDC (regulated) 23 VDC (with 6 VDC drop) 4009 IDNAC Repeater S4009-0004 4007ES with IDNAC Notification S4007-0002 4010ES with ESS Enhanced System Supply S4010-0011 TrueAlert ES Strobe Specifications IDNAC SLC Controller Compatibility Reference Features Individually addressed and controlled multi-candela V/O (visible only) notification appliances provide:  Multi-candela xenon strobe with synchronized 1 Hz flash rate and with intensity programmable from the control panel or jumper selected as 15, 30, 75, or 110 cd  Advanced addressable notification controlled by IDNAC SLCs providing regulated 29 VDC allowing strobes to operate with lower current even under battery backup  Wiring supervision to each strobe allowing “T-tapped” connections for Class B circuits to simplify wiring (Class A circuits require in/out wiring)  TrueAlert Device Reports at the control panel detailing appliance point ID, custom label, type, and candela setting (see sample on page 2)  Magnet test diagnostics to assist checkout and testing of appliances and wiring  Compatibility with ADA requirements  Compatibility with legacy TrueAlert addressable systems for upgrade and replacement (see page 3)  UL listed to Standard 1971 and ULC-S526* LED indicator and magnet test feature:  Appliance LED can be selected to display each polling cycle to indicate appliance supervision  In diagnostic mode, the magnet test pulses the LED to indicate appliance address AND pulses to indicate the intensity selection; a brief output of the strobe is also selectable to confirm operation Mechanical design features:  Rugged, high impact, flame retardant ceiling mount thermoplastic housings are available in red or white  Rear of housing does not extend into box and easily mounts to standard electrical boxes  Mounting options include red wire guards and adapters for surface mounted electrical boxes * See page 2 for wire guard listings. This product has been approved by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7125-0026:235 for allowable values and/or conditions concerning material presented in this document. Accepted for use – City of New York Department of Buildings – MEA35-93E. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Safety Products Westminster. Ceiling Mount Addressable V/Os Description Multi-Candela TrueAlert addressable strobes provide convenient installation to standard electrical boxes. The strobe is individually addressed and individually controlled with power, supervision, and control supplied from a Simplex fire alarm control panel providing IDNAC Signaling Line Circuits (SLCs). (See compatibility list on page 3.) Strobe Application Reference Proper selection of visible notification is dependent on occupancy, location, local codes, and proper applications of: the National Fire Alarm and Signaling Code (NFPA 72), ANSI A117.1; the appropriate model building code: BOCA, ICBO, or SBCCI; and the application guidelines of the Americans with Disabilities Act (ADA). IDNAC SLC Operation Advantage TrueAlert addressable appliances on IDNAC SLCs provide separate visible (and audible) notification using a single two-wire circuit that also confirms connection to the individual notification appliance’s electronic circuit. This operation increases circuit supervision integrity by providing supervision that extends beyond the appliance wiring connections. Reduced current allows efficient IDNAC SLC operation. With IDNAC SLCs, a constant 29 VDC source voltage is maintained, even during battery standby, allowing strobes to operate at higher voltage with lower current and ensuring a consistent current draw and voltage drop margin under both primary power and secondary battery standby. Efficiencies include wiring distances up to 2 to 3 times farther than with conventional notification, or support for more appliances per IDNAC SLC, or use of smaller gauge wiring, or combinations of these benefits, all providing installation and maintenance savings with high assurance that appliances that operate during normal system testing will operate during worst case alarm conditions. TrueAlert Addressable Notification Appliances UL, ULC, CSFM Listed; FM Approved; Multi-Candela Visible Only (V/O) MEA (NYC) Acceptance* Appliances (Strobes), Ceiling Mount S4906-0004-4 2/2015 IDNAC SLC Operation Advantage (Cont’d) Reducing Installation and Testing Time. With separate controls on the same two-wire SLC, installation time and expense for both retrofit and new construction can be significantly reduced. When Class B wiring is used, wiring can be “T” tapped, allowing more savings in distance, wire, conduit (size and utilization), and overall installation efficiency. Use of the magnet test feature improves installation efficiency. TrueAlert device reports conveniently identify information about each connected appliance. TrueAlert Addressable Wiring Isolator Isolator Model 4905-9929 is available for remote mounting on TrueAlert addressable circuits to isolate short circuited wiring from functioning wiring. (Refer to data sheet S4905-0001 for additional information.) TrueAlert Addressable Diagnostics Test Features. Controllers can be selected to pulse each appliance’s LED when it receives a supervision poll. When the controller is selected for diagnostic mode, the appliance magnet test feature provides a response at the individual appliance being tested. Silent Appliance Magnet Test. In this test mode, in response to the magnet test, the appliance LED pulses sequentially to conveniently indicate the appliance’s address. Operational Appliance Testing. In this test mode, after the address is indicated by pulsing the appliance LED, the strobe will briefly flash to indicate proper operation. TrueStart Instrument Two (TSIT). The 2nd generation of the Simplex TrueStart Test Instrument adds testing of IDNAC SLC wiring and TrueAlert (and TrueAlert ES) appliances to its ability to test IDCs, NACs, and IDNet communications before connection to the control panel. Please contact your local Simplex representative for additional information. 2 S4906-0004-4 2/2015 Multi-Candela Ceiling Mount Addressable Strobe Model Housing Color “FIRE” Lettering Dimensions Description 4906-9202 Red White 4 ¾” x 2 5⁄16” x 2 ⅝” D (121 mm x 75 mm x 67 mm) Multi-Candela Addressable Strobe; intensity selectable as: 15, 30, 75, or 110 candela 4906-9204 White Red V/O Adapters (see diagram on page 3) Model Description Dimensions 4905-9910 Ceiling Mount, Surface Mount Adapter Plate, zinc plated; required for ceiling surface mount 4 ⅞” x 3 ⅛” (124 mm x 79 mm) Wire Guards (see diagram on page 3) Model Description Dimensions 4905-9926* Ceiling Mount Red wire guard with mounting plate, compatible with semi-flush or surface mounted boxes 6 ⅛” x 4 ⅜” x 2 ⅞” (156 mm x 111 mm x 73 mm) * UL listed by Space Age Electronics Inc. Service Port Page 1 REPORT 5 : TrueAlert Device Report 12:34:56am TUE 27-Jan-15 POINT ID CUSTOM LABEL DEVICE TYPE CANDELA T14-1-1 Location Label . . . up to 40 characters V/O 15 T14-1-2 Break Room 5 A/V 110 T14-1-3 Boiler Room A/V 75 T14-1-4 Elec. Room 7 A/V 30 Product Selection TrueAlert Device Reports Reference 3 S4906-0004-4 2/2015151107530FACPStrobe intensity viewing slot Intensity selection plug, accessible only from rear of lens housing; factory setting is FACP, controlled by panel 4905-9910 Adapter Plate, required for surface mount with handy box unless using the 4905-9926 wire guard Handy box, 1-1/2" ( 38 mm) deep (RACO 650 or equal) or single gang box, 2-1/2" (64 mm) deep (RACO 519 or equal) supplied by others Also can be attached to boxes mounted to drop ceiling T-bar with clips (ERICO No. 512 or equal) Ceiling mount strobe Optional 4905-9926 wire guard with mounting plate Magnetic test location Bottom view LED indicator Address setting DIPswitch is behind strobe assembly, select address and strobe candela setting before inserting into housing Single gang box (Wiremold V5744S) 2-1/4" (57 mm) deep, supplied by others Compatible Controller Data Sheet Reference Controller Output Available Strobe Intensity Appliance Voltage Minimum 4100ES or 4100U with TrueAlert Power Supply S4100-0031 TrueAlert Addressable SLC 15, 30, 75, and 110 cd 17 VDC 4009 TPS, Remote TrueAlert Power Supply S4100-0037 TrueAlert Addressable Controller (4009T) S4009-0003 Electrical Ratings Difference for Retrofit Applications Voltage Range 17 VDC to 31 VDC, Special Application Candela Setting 15 cd 30 cd 75 cd 110 cd 17 VDC RMS Current Ratings, use when connected to TrueAlert Addressable SLCs per above 76 mA 128 mA 242 mA 328 mA General Specifications (see page 2 for dimensions) Environmental 32° to 122° F (0° to 50° C); 10% to 93%, non-condensing at 100° F (38° C) Connections Terminal blocks for 18 AWG to 12 AWG (0.82 mm2 to 3.31 mm2); two wires per terminal for in/out wiring Installation Instructions 579-808 Strobe Specifications Typical Operating Voltage Range 23 VDC to 31 VDC, Special Application (see below for 17 VDC rating) Supervisory Requirements 1 unit load (= 0.8 mA control panel current) Flash Rate and Synchronized SLC Loading 1 Hz; with up to 46 synchronized strobes maximum per NAC Candela Setting 15 cd 30 cd 75 cd 110 cd 23 VDC RMS Current Ratings, for connection to IDNAC Addressable SLCs 60 mA 92 mA 180 mA 240 mA Compatible Controllers Data Sheet Reference Controller Output IDNAC SLC Output Voltage Appliance Voltage Design Reference 4100ES with EPS+ or EPS Power Supply S4100-0100 IDNAC SLC 29 VDC (regulated) 23 VDC (with 6 VDC drop) 4009 IDNAC Repeater S4009-0004 4007ES with IDNAC Notification S4007-0002 4010ES with ESS Enhanced System Supply S4010-0011 Ceiling Mount V/O and Guard Installation Reference TrueAlert Strobe LEGACY Compatibility Reference Specifications IDNAC SLC Controller Compatibility Reference TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm and Signaling Code are registered trademarks of the National Fire Protection Association (NFPA). Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S4906-0004-4 2/2015 www.simplexgrinnell.com © 2015 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. Ceiling Mount Addressable Speaker Visible (S/V) Notification Appliances are individually powered, addressed, and controlled from a Simplex fire alarm control panel IDNAC Signaling Line Circuit (SLC). S/V notification appliances use a multi-tapped speaker for audio/tone notification and a multi-candela strobe with synchronized 1 Hz flash rate and selectable candela rating. Wiring supervision is electronically monitored and allows audio wiring to be T-tapped for class B wiring, reducing wiring costs and wiring distances. Ceiling mount speaker visible appliances are available in 400 - 4000 Hz models and high fidelity models capable of operating between 200 – 10000 Hz. Separate appliance and cover selection greatly simplifies the ordering and installation process. For more detailed information, please consult datasheet S49SWC-0001. Ceiling Mount Addressable Speaker/Visible Notification Appliance * Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire TrueAlert Addressable Notification Appliances UL, ULC Listed; FM Approved* Ceiling Mount Addressable Speaker Visible (S/V) Notification Appliances S49SVC-0001-2 11/2016 Ceiling Mount Addressable Speaker S/V Appliances TrueAlert ES Addressable S/V appliance dimensions with cover: 8 ⅛ ” H x 7 ⅛” W x 3” D ( 206 mm x 180 mm x 76 mm) Model Description 49SV-APPLC(-BA) Speaker Visible appliance only. Select cover separately. High Fidelity Appliances Model Description 49HFV-APPLC(-BA) High Fidelity appliance only. Select cover separately. High Candela Appliances Model Description 49SVH-APPLC(-BA) High Candela appliance only. Select cover separately. High Fidelity High Candela Appliances Model Description 49HFVH-APPLC(-BA) High Fidelity High Candela appliance. Select cover separately. 49HFVH-APLCA-BA High Fidelity High Candela appliance with amber colored lens. Select cover separately. 49HFVH-APLCB-BA High Fidelity High Candela appliance with blue colored lens. Select cover separately. S/V Covers (Required when ordering APPLC models) Model Color Wording Model Color Wording 49SVC-CRALT Red ALERT 49SVC-CWALT White ALERT 49SVC-CRBA قيرѧѧѧѧح/FIRE 49SVC-CWBA قيرѧѧѧѧح/FIRE 49SVC-CRBC 火警/FIRE ALARM 49SVC-CWBC 火警/FIRE ALARM 49SVC-CRBF FEU/FIRE 49SVC-CWBF FEU/FIRE 49SVC-CRFEU FEU 49SVC-CWFEU FEU 49SVC-CRFIRE FIRE 49SVC-CWFIRE FIRE 49SVC-CRS Simplex logo only 49SVC-CWS Simplex logo only 49SVC-CK Black No logo or lettering * Note: (-BA) indicates model is available either with or without the -BA suffix. Model numbers ending in –BA are assembled in the USA Product Selection Compatible Controllers Data Sheet Reference Controller Output IDNAC SLC Output Voltage Appliance Voltage Design Reference 4100ES with EPS+ or EPS Power Supply S4100-0100 IDNAC SLC 29 VDC (regulated) 23 VDC (with 6 VDC drop) 4009 IDNAC Repeater S4009-0004 4100ES Flex 35, 50, and 100 Amplifiers S4100-0034 4100ES Constant Supervision and Signal Cards Specifications (see page 1 for appliance dimensions) Environmental 32° to 120° F (0° to 49° C); 10% to 93%, non-condensing at 104° F (40° C) Connections Terminal blocks for 18 AWG to 12 AWG (0.82 mm2 to 3.31 mm2); two wires per terminal for in/out wiring. Use Unshielded Twisted Pair (UTP) for IDNAC and audio wiring. IDNAC SLC Loading Maximum of 127 addresses per SLC, 139 unit loads. See device and compatible Fire Panel Installation Instructions for circuit current load limits. Installation Instructions 579-1203 (49SV, 49SVH and 49HFV models) 579-1206 (Amber/Blue 49HFVH model) Speaker General Specifications Input Voltage 25 or 70.7 Vrms Power Taps ¼, ½, 1, and 2 W Frequency Response 400 to 4000 Hz (S/V, S/VH), 200 to 10000 Hz (H/F, HF/VH) General Signaling = 125 to 12 kHz Speaker Output Ratings 25 or 70.7 Vrms @ 10 ft (3 m) Wattage Tap ¼ W ½ W 1 W 2 W Model S/V H/F S/V H/F S/V H/F S/V H/F Reverberant Chamber Test, per UL 1480 (dBA) 79 76 83 80 86* 84 89* 87* Anechoic Chamber Test, per ULC-S541 (dBA)* 79 78 83 82 86* 85* 89* 88* * Select taps as indicated to satisfy the ULC fire alarm applications requirement of 85 dBA minimum Polar Dispersion Reference (per ULC-S541 Anechoic Chamber Testing) Attenuation Angle Attenuation Angle -3 dB 70° -6 dB 80° Percentage of rated light output at room temperature Angle On-Axis Vertical, Below Axis Horizontal, Left/Right of Axis 0° 45° 90° 45° 90° UL required output 100% 45% 25% 45% 25% Typical output 327% 134% 83% 129% 47% Appliance Specifications Operating Voltage Range 23 VDC to 30 VDC, Special Application Supervisory Requirements 1 unit load (= 0.8 mA control panel current) Flash Rate and Synchronized SLC Loading 1 Hz; with up to 63 synchronized strobes maximum per powered circuit, max 127 S/V appliances per IDNAC channel Current consumption** Candela Setting 15 cd 30 cd 75 cd 110 cd 135 cd 185 cd 49SV and 49HFV models 59 mA 82 mA 145 mA 193 mA N/A N/A 49SVH and 49HFVH models N/A N/A N/A 235 mA 255 mA 295 mA ** Measured at 23VDC on IDNAC Addressable SLC Note: Speakers are for connection to compatible fire alarm audio circuits. Anechoic speaker output ratings are typically more representative of actual installed sound output. 2 S49SVC-0001-2 11/2016 IDNAC SLC Controller Compatibility Reference Celing Mount S/V Specifications 3 S49SVC-0001-2 11/2016 Ceiling Mount S/V Installation Reference TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm and Signaling Code are registered trademarks of the National Fire Protection Association (NFPA). Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S49SVC-0001-2 11/2016 www.simplex-fire.com © 2016 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. Features For use as Class B end-of-line resistor: xConnect these resistor harnesses where end-of-line resistors are required at remote locations to monitor wiring continuity xRefer to specific circuit specifications for end-of-line resistor requirements UL Listed to Standard 864 Product Selection Model Reference Number Description** 4081-9001 733-892 2.2 k:, 1/2 W 4081-9002 733-893 3.3 k:, 1 W 4081-9003 733-896 4.7 k:, 1/2 W 4081-9004 733-886 6.8 k:, 1/2 W 4081-9005 733-984 1.8 k:, 1/2 W 4081-9006 733-890 560 :, 1 W 4081-9007 733-891 1.2 k:, 1 W 4081-9008 733-894 10 k:, 1/2 W 4081-9009 733-912 20 :, 1 W 4081-9010 733-973 1 k:, 1 W 4081-9011 733-974 100 :, 1/2 W 4081-9012 733-985 22 k:, 1/2 W 4081-9013 734-086 4.99 k:, 1/2 W, ± 1% 4081-9014 734-092 2.4 k:, 1/2 W 4081-9015 734-093 1.5 k:, 1/2 W 4081-9016 734-149 150 k:, 1/2 W 4081-9017 734-171 3.9 k:, 1 W 4081-9018 734-168 10 k:, 1 W ** ± 5% tolerance except as noted. * This product was not approved by ULC, FM, MEA (NYC), or CSFM as of document revision date. Additional listings may be applicable, contact your local Simplex® product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Safety Products Westminster. ~ 9-1/2" (241 mm) Typical 4081 Series Resistor Harness Assembly (full size except for lead length) Specifications Overall Length Approximately 9-1/2” (241 mm) Wire Length 7” (178 mm) ± 1” (25 mm) Wire Size 18 AWG (0.82 mm2) Insulation 600 V, black Leads Stripped 0.5” (13 mm); tinned Resistor Attachment Resistor leads are crimped to wires and covered with heat shrink tubing System Accessories UL Listed* 4081 Series End-of-Line Resistor Harnesses S4081-0003 7/2004 Tyco, Simplex, and the Simplex logo are trademarks of Tyco International Services AG or its affiliates in the U.S. and/or other countries. Tyco Safety Products Westminster • Westminster, MA • 01441-0001 • USA S4081-0003 7/2004 www.tycosafetyproducts-usa-wm.com © 2004 Tyco Safety Products Westminster. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.