HomeMy WebLinkAboutB16-0254_M002_signed_1507144347.pdfELASTOMERIC RUBBER IN SHEAR
VIBRATION ISOLATORS (TYP. 4)
AIR HANDLER
HANGER RODS
SECURED TO
STRUCTURE
HOT WATER PIPING TO
BOILER.
FLEX CONNECTION
RETURN AIR
1-1/2" DEEP 18 GAUGE GALVANIZED
AUXILIARY DRAIN PAN SUSPENDED
BELOW UNIT.
SUPPLY AIR
FLEXIBLE
P-TRAP
CONNECTION
DISCHARGE TO PLUMBING DRAIN
FILTERS
REFRIGERANT PIPING TO
CONDENSING UNITS.
HOT WATER COIL
PACKAGED ROOFTOP UNIT SCHEDULE
UNIT TAG LOCATION SERVICE TO
SUPPLY FAN DATA
DX COOLING COIL DATA @ 90°F AMBIENT
FLOWRATE STATIC PRES. MOTOR DATA
MAX.
(CFM)
MIN.
(CFM)
OA MIN.
(CFM)
EXT./ TOTAL
(IN. H20) QUAN. HP RPM VOLT PH VFD FLOWRATE
(CFM)
EAT LAT
TOTAL COOLING (MBH)
SENSIBLE
(MBH)
EER
(ARI)
MAX. dP
(FT. H2O)
(°F DB) (°F WB) (°F DB) (°F WB)
MAU-1 ROOF 151 KITCHEN 3600 2000 100% 0.29 / 0.96 1 2 1480 208 3 YES N/A N/A N/A N/A N/A N/A N/A N/A N/A
RTU-A1 ROOF 151 KITCHEN 4500 2250 500 0.75 / 1.46 1 5 830 208 3 YES 4500 87.1 58.1 52.5 43.2 168.4 168.4 13.4 0.1
PACKAGED ROOFTOP UNIT SCHEDULE (CONTINUED)
NATURAL GAS HEAT DATA FILTER DATA ELECTRICAL DATA
SELECTION BASED ON
REMARKS
MANUFACTURER MODEL
INPUT
(MBH)
OUTPUT
(MBH)
STAGES FLOW
RATE
(CFM)
EAT
( º F)
LAT
( º F)
UNIT FILTER (MERV) VOLT PH MCA
MOP DISCONNECT PROVIDED BY
312 287 5 3600 1 75 7 208 3 11 15 YES DIV. 23 CAPTIVAIRE A2-D.500-20D 3
300 240 2 4500 53 105 7 208 3 80.1 90 YES DIV. 23 TEMPMASTER ZWT15S30 1, 2
GENERAL NOTES:
1) PROVIDE 4 STAGE COMPRESSOR, ASHRAE 90.1 COMPLIANT MULTISPEED FAN CONTROLLER (INTELLISPEED), HIGH ALTITUDE STAINLESS STEEL 2 STAGE NATURAL GAS BURNER, 24" CURB.
2) PROVIDE LOW AMBIENT COOLING DOWN TO 0°F AND ECONOMIZER WITH BAROMETRIC RELIEF AND FULLY MODULATING OUTDOOR AIR CONTROL.
3) PROVIDE KITCHEN DEMAND CONTROL SYSTEM TO VARY AIRFLOW BASED ON KITCHEN LOAD, LOW FIRE START CAPABILITY WITH 30:1 TURNDOWN, AND MOTORIZED BACKDRAFT DAMPER.
FAN SCHEDULE
UNIT TAG LOCATION SERVICE TO FLOWRATE
(CFM)
STATIC PRES.
TOTAL
(IN. H20)
TYPE DRIVE FAN RPM SONES
MOTOR DATA SELECTION BASED ON
REMARKS
WATTS HP VOLT PH VFD
STARTER/
DISCONNECT
FURNISHED
BY
MANUFACTURER MODEL
EF-5 ABOVE CEILING
136/137 LOCKER,
138/139 RR'S
760 0.25
INLINE
CENTRIFUGAL
DIRECT 810 3.7 306 --- 120 1 NO YES DIV. 23 TWIN CITY FAN T900L 2, 3, 4, 5
EF-6 ABOVE CEILING 149/150 RESTROOMS 900 0.25
INLINE
CENTRIFUGAL
DIRECT 1055 8.6 468 --- 120 1 NO YES DIV. 23 TWIN CITY FAN T1500L 2,3 ,4, 5
EF-7 ROOF
GENERAL PRESSURE
RELIEF
1335 0.125
CENTRIFUGAL
DOWNBLAST
DIRECT 700 5.2 93 --- 120 1 NO YES DIV. 23 TWIN CITY FAN 150B DCRD 1, 2, 3, 5
EF-8 ROOF
ECONOMIZER
PRESSURE RELIEF
5080 0.125
CENTRIFUGAL
DOWNBLAST
BELT 550 9.7 373 --- 120 1 NO YES DIV. 23 TWIN CITY FAN 240D BCRD 1, 2, 3
EF-9 ROOF DISHWASHER HOOD 400 0.25
CENTRIFUGAL
UPBLAST
BELT 1249 8.5 --- 1/4 208 1 NO YES DIV. 23 PENNBARRY FX08B 2, 3, 5, 7
KEF-1 ROOF
KITCHEN EXHAUST
HOOD
4500 1.5 UTILITY SET DIRECT 1066 22 --- 3 208 3 YES --- DIV. 23 CAPTIVEAIRE USBI24DD-RM 2, 6
GENERAL NOTES:
1) PROVIDE ROOF CURB
2) PROVIDE DISCONNECT SWITCH
3) PROVIDE BACKDRAFT DAMPER
4) PROVIDE VIBRATION DAMPENING HANGERS
5) PROVIDE UNIT-MOUNT SOLID STATE SPEED CONTROL
6) PROVIDE KITCHEN RATED EXHAUST CURB (MIN. 40" FROM COMBUSTIBLES), GREASE COLLECTOR, KITCHEN DEMAND CONTROL SYSTEM AND VFD, AND UL 762 CONSTRUCTION AND LABEL
7) PROVIDE MIN. 30" TALL ROOF CURB
MECHANICAL DUCTWORK AND PIPE INSULATION SCHEDULE
INSULATION
ITEMS SYSTEM LOCATION MATERIAL THICK REMARKS
-NESS
DUCTWORK: DW - DUCTWRAP; FE - FLEXIBLE ELASTOMERIC
SUPPLY AIR DUCT ALL INDOOR DW OR FE 2"
RETURN AIR DUCT ALL INDOOR DW OR FE 2"
HOT WATER SUPPLY AND RETURN PIPING ALL INDOOR FE 1-1/2"
AC CONDENSATE ALL INDOOR FE 1"
REFRIGERANT SUCTION AND HOT GAS PIPING AND TUBING ALL OUTDOOR FE 2"
NOTES:
1. REFER TO PROJECT SPECIFICATION AND/OR SPECIFICATION NOTES ON DRAWINGS FOR PRODUCT MATERIAL INFORMATION, AND INSTALLATION REQUIREMENTS.
2. PAINT INSULATION WITH 2 COATS OF MANUFACTURER'S RECOMMENDED PROTECTIVE COATING.
REFRIGERANT SUCTION AND HOT GAS PIPING AND TUBING ALL INDOOR FE 1" SEE NOTE 2
SEE NOTE 2
D1
D2
STAINLESS STEEL
ROUND SPIRAL DUCT
EXTERNAL DUCT JACKET
DUCT INSULATION
D2
END VIEW SIDE VIEW
D1: DUCT DIAMETER AS INDICATED ON PLANS
D2: OVERALL DIMENSION INCLUDING DUCT INSULATION AND EXTERIOR DUCT JACKET
NOTE:
REFER TO DIVISION 23 SPECIFICATIONS "METAL DUCTS" AND "DUCT INSULATION" FOR REQUIRED FIRE
RATING AND INSULATION DESIGN. BASIS OF DESIGN IS SELKIRK "ZERO CLEARANCE" GREASE DUCT.
1
A 2 3 4 5 6 A B C D E
1
3 4 5 6
2
COPYRIGHT 2016 BASKERVILL. USE OF THIS WORK IN WHOLE OR IN
PART IS FORBIDDEN WITHOUT EXPRESSED WRITTEN CONSENT.
B C D E
DRAWING
NO.
P.O. BOX 400, RICHMOND, VA 23218-0400
DRAWING TITLE
ISSUE
PROJECT
OWNER
®
9/19/2017
4:50:17 AM
DETAILS AND
SCHEDULES
THE WIDEWATERS
GROUP
2.160036.0
DOUBLETREE VAIL,
CO CONVERSION
GUESTROOMS &
PUBLIC SPACES
RENOVATION
08/25/16 -
CONSTRUCTION
DOCUMENTS
M002
2211 N FRONTAGE
RD, VAIL, COLORADO
81657
NOT TO SCALE
3AINSULATION SCHEDULE
NOT TO SCALE
3BAIR HANDLER HANGER DETAIL
1 8/25/2016 FOR CONSTRUCTION SET
10 9/15/17 CCD-06
SCALE: 12" = 1'-0"
3CKITCHEN EXHAUST DUCT DETAIL
09/07/2017
201709/0