HomeMy WebLinkAboutB16-0254_M002_signed_1507144347.pdfELASTOMERIC RUBBER IN SHEAR VIBRATION ISOLATORS (TYP. 4) AIR HANDLER HANGER RODS SECURED TO STRUCTURE HOT WATER PIPING TO BOILER. FLEX CONNECTION RETURN AIR 1-1/2" DEEP 18 GAUGE GALVANIZED AUXILIARY DRAIN PAN SUSPENDED BELOW UNIT. SUPPLY AIR FLEXIBLE P-TRAP CONNECTION DISCHARGE TO PLUMBING DRAIN FILTERS REFRIGERANT PIPING TO CONDENSING UNITS. HOT WATER COIL PACKAGED ROOFTOP UNIT SCHEDULE UNIT TAG LOCATION SERVICE TO SUPPLY FAN DATA DX COOLING COIL DATA @ 90°F AMBIENT FLOWRATE STATIC PRES. MOTOR DATA MAX. (CFM) MIN. (CFM) OA MIN. (CFM) EXT./ TOTAL (IN. H20) QUAN. HP RPM VOLT PH VFD FLOWRATE (CFM) EAT LAT TOTAL COOLING (MBH) SENSIBLE (MBH) EER (ARI) MAX. dP (FT. H2O) (°F DB) (°F WB) (°F DB) (°F WB) MAU-1 ROOF 151 KITCHEN 3600 2000 100% 0.29 / 0.96 1 2 1480 208 3 YES N/A N/A N/A N/A N/A N/A N/A N/A N/A RTU-A1 ROOF 151 KITCHEN 4500 2250 500 0.75 / 1.46 1 5 830 208 3 YES 4500 87.1 58.1 52.5 43.2 168.4 168.4 13.4 0.1 PACKAGED ROOFTOP UNIT SCHEDULE (CONTINUED) NATURAL GAS HEAT DATA FILTER DATA ELECTRICAL DATA SELECTION BASED ON REMARKS MANUFACTURER MODEL INPUT (MBH) OUTPUT (MBH) STAGES FLOW RATE (CFM) EAT ( º F) LAT ( º F) UNIT FILTER (MERV) VOLT PH MCA MOP DISCONNECT PROVIDED BY 312 287 5 3600 1 75 7 208 3 11 15 YES DIV. 23 CAPTIVAIRE A2-D.500-20D 3 300 240 2 4500 53 105 7 208 3 80.1 90 YES DIV. 23 TEMPMASTER ZWT15S30 1, 2 GENERAL NOTES: 1) PROVIDE 4 STAGE COMPRESSOR, ASHRAE 90.1 COMPLIANT MULTISPEED FAN CONTROLLER (INTELLISPEED), HIGH ALTITUDE STAINLESS STEEL 2 STAGE NATURAL GAS BURNER, 24" CURB. 2) PROVIDE LOW AMBIENT COOLING DOWN TO 0°F AND ECONOMIZER WITH BAROMETRIC RELIEF AND FULLY MODULATING OUTDOOR AIR CONTROL. 3) PROVIDE KITCHEN DEMAND CONTROL SYSTEM TO VARY AIRFLOW BASED ON KITCHEN LOAD, LOW FIRE START CAPABILITY WITH 30:1 TURNDOWN, AND MOTORIZED BACKDRAFT DAMPER. FAN SCHEDULE UNIT TAG LOCATION SERVICE TO FLOWRATE (CFM) STATIC PRES. TOTAL (IN. H20) TYPE DRIVE FAN RPM SONES MOTOR DATA SELECTION BASED ON REMARKS WATTS HP VOLT PH VFD STARTER/ DISCONNECT FURNISHED BY MANUFACTURER MODEL EF-5 ABOVE CEILING 136/137 LOCKER, 138/139 RR'S 760 0.25 INLINE CENTRIFUGAL DIRECT 810 3.7 306 --- 120 1 NO YES DIV. 23 TWIN CITY FAN T900L 2, 3, 4, 5 EF-6 ABOVE CEILING 149/150 RESTROOMS 900 0.25 INLINE CENTRIFUGAL DIRECT 1055 8.6 468 --- 120 1 NO YES DIV. 23 TWIN CITY FAN T1500L 2,3 ,4, 5 EF-7 ROOF GENERAL PRESSURE RELIEF 1335 0.125 CENTRIFUGAL DOWNBLAST DIRECT 700 5.2 93 --- 120 1 NO YES DIV. 23 TWIN CITY FAN 150B DCRD 1, 2, 3, 5 EF-8 ROOF ECONOMIZER PRESSURE RELIEF 5080 0.125 CENTRIFUGAL DOWNBLAST BELT 550 9.7 373 --- 120 1 NO YES DIV. 23 TWIN CITY FAN 240D BCRD 1, 2, 3 EF-9 ROOF DISHWASHER HOOD 400 0.25 CENTRIFUGAL UPBLAST BELT 1249 8.5 --- 1/4 208 1 NO YES DIV. 23 PENNBARRY FX08B 2, 3, 5, 7 KEF-1 ROOF KITCHEN EXHAUST HOOD 4500 1.5 UTILITY SET DIRECT 1066 22 --- 3 208 3 YES --- DIV. 23 CAPTIVEAIRE USBI24DD-RM 2, 6 GENERAL NOTES: 1) PROVIDE ROOF CURB 2) PROVIDE DISCONNECT SWITCH 3) PROVIDE BACKDRAFT DAMPER 4) PROVIDE VIBRATION DAMPENING HANGERS 5) PROVIDE UNIT-MOUNT SOLID STATE SPEED CONTROL 6) PROVIDE KITCHEN RATED EXHAUST CURB (MIN. 40" FROM COMBUSTIBLES), GREASE COLLECTOR, KITCHEN DEMAND CONTROL SYSTEM AND VFD, AND UL 762 CONSTRUCTION AND LABEL 7) PROVIDE MIN. 30" TALL ROOF CURB MECHANICAL DUCTWORK AND PIPE INSULATION SCHEDULE INSULATION ITEMS SYSTEM LOCATION MATERIAL THICK REMARKS -NESS DUCTWORK: DW - DUCTWRAP; FE - FLEXIBLE ELASTOMERIC SUPPLY AIR DUCT ALL INDOOR DW OR FE 2" RETURN AIR DUCT ALL INDOOR DW OR FE 2" HOT WATER SUPPLY AND RETURN PIPING ALL INDOOR FE 1-1/2" AC CONDENSATE ALL INDOOR FE 1" REFRIGERANT SUCTION AND HOT GAS PIPING AND TUBING ALL OUTDOOR FE 2" NOTES: 1. REFER TO PROJECT SPECIFICATION AND/OR SPECIFICATION NOTES ON DRAWINGS FOR PRODUCT MATERIAL INFORMATION, AND INSTALLATION REQUIREMENTS. 2. PAINT INSULATION WITH 2 COATS OF MANUFACTURER'S RECOMMENDED PROTECTIVE COATING. REFRIGERANT SUCTION AND HOT GAS PIPING AND TUBING ALL INDOOR FE 1" SEE NOTE 2 SEE NOTE 2 D1 D2 STAINLESS STEEL ROUND SPIRAL DUCT EXTERNAL DUCT JACKET DUCT INSULATION D2 END VIEW SIDE VIEW D1: DUCT DIAMETER AS INDICATED ON PLANS D2: OVERALL DIMENSION INCLUDING DUCT INSULATION AND EXTERIOR DUCT JACKET NOTE: REFER TO DIVISION 23 SPECIFICATIONS "METAL DUCTS" AND "DUCT INSULATION" FOR REQUIRED FIRE RATING AND INSULATION DESIGN. BASIS OF DESIGN IS SELKIRK "ZERO CLEARANCE" GREASE DUCT. 1 A 2 3 4 5 6 A B C D E 1 3 4 5 6 2 COPYRIGHT 2016 BASKERVILL. USE OF THIS WORK IN WHOLE OR IN PART IS FORBIDDEN WITHOUT EXPRESSED WRITTEN CONSENT. B C D E DRAWING NO. P.O. BOX 400, RICHMOND, VA 23218-0400 DRAWING TITLE ISSUE PROJECT OWNER ® 9/19/2017 4:50:17 AM DETAILS AND SCHEDULES THE WIDEWATERS GROUP 2.160036.0 DOUBLETREE VAIL, CO CONVERSION GUESTROOMS & PUBLIC SPACES RENOVATION 08/25/16 - CONSTRUCTION DOCUMENTS M002 2211 N FRONTAGE RD, VAIL, COLORADO 81657 NOT TO SCALE 3AINSULATION SCHEDULE NOT TO SCALE 3BAIR HANDLER HANGER DETAIL 1 8/25/2016 FOR CONSTRUCTION SET 10 9/15/17 CCD-06 SCALE: 12" = 1'-0" 3CKITCHEN EXHAUST DUCT DETAIL 09/07/2017 201709/0 10/04/17