HomeMy WebLinkAboutResponse to corrections.pdfCorrections letter response Permit: 816-0042 El&-0019 See answers below in bold and in drawings provided Please provide the following information in reference to unit 217/267 manor vail remodel. Identify building code (IBC 2015) Building const type: SA-1 hr rated Occupancy type: R-2 Number of floors/stories: 4 story building Which building it is located in ( A,B,C,D,E): Building D Plans will need to be stamped by architect, due to fire penetrations. Provide listed assemblies/details: Assemblies shown in drawings with architects stamp Fire damper in new bath fan? To be provided-shown in drawings Can lights in shower and living room? See drawings for RCP and new vs. existing can lights. Fire hats @ all lights and J-boxes 2 hr UL fire rated light cover FF109X by tenmat or similar Electrical load calcs, adding heat mats? No new loads added. No load calcs required Our new system is having issues ,so I thought I'd email your corrections, You may also get another notice thru Magnet, but wanted you to be aware of the corrections. Thank you I never received the corrections letter via email, facsimile, fax or mail Thank you The status will show u Contractor: Matt Hansen ECE Design I Build 9704011100 matt@ecedb.com Architect: Michael Current, AIA CURRENT ARCHITECTS 970.331.6345 PO BOX5293 VAIL, CO 81657 www.currentarchitects.com