HomeMy WebLinkAboutResponse to corrections.pdfCorrections letter response
Permit: 816-0042 El&-0019
See answers below in bold and in drawings provided
Please provide the following information in reference to unit 217/267 manor vail remodel.
Identify building code (IBC 2015)
Building const type: SA-1 hr rated
Occupancy type: R-2
Number of floors/stories: 4 story building
Which building it is located in ( A,B,C,D,E): Building D
Plans will need to be stamped by architect, due to fire penetrations. Provide listed
assemblies/details: Assemblies shown in drawings with architects stamp
Fire damper in new bath fan? To be provided-shown in drawings
Can lights in shower and living room? See drawings for RCP and new vs. existing can lights. Fire
hats @ all lights and J-boxes 2 hr UL fire rated light cover FF109X by tenmat or similar
Electrical load calcs, adding heat mats? No new loads added. No load calcs required
Our new system is having issues ,so I thought I'd email your corrections,
You may also get another notice thru Magnet, but wanted you to be aware of the corrections.
Thank you I never received the corrections letter via email, facsimile, fax or mail
Thank you