HomeMy WebLinkAboutF17-0003_Data Submittal_1487719680.pdf2264 G Road, Grand Junction, CO 81505 Phone: (970) 434-4803 Fax: (970) 434-0802           16-184 PROJECT SUBMITTAL Fire Sprinkler 1414 Moraine Drive Vail, CO Hydraulic Overview Job Number: 16-184 - 16-184 Report Description: Residential (1) Node Flow(gpm)Hose Flow(gpm)Static(psi)Residual(psi)Name 1 2430.0 100.0 154.0 110.0Water Supply Identifier Pressure(psi)K-Factor(K)Flow(gpm) Job System Supplies Check Point Gauges 16-184 Ron McCurdy 1414 Moraine 970-434-4803 970-434-0802 1414 Moraine 16-184 Vail Fire Job Name: Address 1 Address 2 Design Engineer Phone FAX State Certification/License Number AHJ Job Site/Building Most Demanding Sprinkler Data Coverage Per Sprinkler Total Demand Area of Application Hose Streams Number Of Sprinklers Calculated Pressure Result Job Number 220.4 @ 138.2 Water Supply at Node 1 (2430.0, 100.0, 154.0, 110.0) 0.10gpm/ft² 4.9 K-Factor 40.0 at 66.6 400.00ft² 900.00ft² (Actual 566.87ft²) 100.0 3 Density +15.3 (10.0%) Address 3 System Pressure Demand System Flow Demand 138.2 120.4 © M.E.P.CAD, Inc.2/21/2017 Page 1AutoSPRINK® 12 v12.0.48.0 3:13:33PM Hydraulic Summary Report Description: Residential (1) Job Number: 16-184 - 16-184 Node Flow(gpm) Total Hose Streams 100.0 Safety MarginRequiredAvailable Node Hose Flow Static Residual Flow Total Demand (gpm)(psi)(psi)(gpm)(psi)(gpm)(psi)(psi)@@Name 1 153.5 138.2 15.32430.0100.0 110.0154.0 220.4Water Supply Design EngineerJob Number Total Water Required (Including Hose Allowance) 220.4 Maximum Pressure Unbalance In Loops 0.0 Additional Hose Supplies 100.0 Hose Allowance At Source Supplies 151.1gal Residential 0.10gpm/ft² 400.00ft² 900.00ft² (Actual 566.87ft²) 3 Occupancy Area of Application Coverage Per SprinklerNumber Of Sprinklers Calculated Density 16-184 Job Suffix AutoPeak Results: Pressure For Remote Area(s) Adjacent To Most Remote Area Left: 138.0 Volume capacity of Dry PipesVolume capacity of Wet Pipes Maximum Velocity Under Ground 18.5 between nodes 1 and 30 Maximum Velocity Above Ground 4.9 K-Factor 40.0 at 66.6 Most Demanding Sprinkler Data System Job Site/Building Vail Fire AHJ 1414 Moraine Job State Certification/License NumberJob Name: Ron McCurdy16-184 Contractor Contractor Number Name of Contractor: Excel Fire Protection Address 1 2264 G Road Address 2 Grand Junction, CO 81505 Contact Name Contact TitleDesigner ExtensionPhone 970-434-4803 FAX 970-434-0802 E-mail ronm@excelfire.com Web-Site Ron McCurdy Address 3 Address 1 Address 2 Drawing Name 1414 Moraine 16-184 System Flow Demand 120.4 Remote Area(s) Address 3 2/21/2017© M.E.P.CAD, Inc.Page 2AutoSPRINK® 12 v12.0.48.0 3:13:35PM Hydraulic Graph Report Description: Residential (1) Job Number: 16-184 - 16-184 110.0 @ 2430.0 Residual: Pressure 154.0 Static: Pressure Water Supply at Node 1 Hydraulic Graph Water Supply at Node 1 138.2 @ 120.4 138.2 @ 220.4 Available Pressure at Time of Test East, West Hydrant Numbers Hydrant Elevation Date of Test Time of Test East 10' AFF Lower Level Garage 02/06/2017 1:00 pm Test Conducted By Test Witnessed By Ron McCurdy Clint Janowicz 1414 Moraine Location 153.5 @ 220.4 System Demand System Demand (Including Hose Allowance at Source) © M.E.P.CAD, Inc.2/21/2017 Page 3AutoSPRINK® 12 v12.0.48.0 3:13:36PM Device (gpm) Actual Flow Minimum Flow (gpm)(K) K-Factor (psi) Pressure Summary Of Outflowing Devices Report Description: Residential (1) Job Number: 16-184 - 16-184 Sprinkler 221 40.3 40.0 4.9 67.7 Sprinkler 234 40.0 40.0 4.9 66.6 Sprinkler 242 40.1 40.0 4.9 66.9 Most Demanding Sprinkler Data © M.E.P.CAD, Inc.2/21/2017 Page 4AutoSPRINK® 12 v12.0.48.0 3:13:38PM FittingsNodeElevation(Foot)Pressure(psi)Discharge(gpm) Node Analysis Report Description: Residential (1) Job Number: 16-184 - 16-184 1 4-0 S 138.2 120.4 221 27-0½Spr(-67.7)67.7 40.3 234 27-0½Spr(-66.6)66.6 40.0 242 27-0½Spr(-66.9)66.9 40.1 25 2-1½PO(12-3½), C(12-3½), Z 122.1 27 2-7½122.9 30 1-0 BFP 123.8 66 27-6 T(12-3½)68.6 67 27-6 E(2-0)68.4 80 27-6 69.6 81 27-6 T(5-0)68.8 88 27-6 T(12-3½)67.5 89 27-6 E(2-0)67.3 97 20-0½E(9-0)102.9 98 20-0½T(5-0)78.6 99 21-0½EE(2-0)79.1 118 27-6 E(2-0)67.5 © M.E.P.CAD, Inc.2/21/2017 Page 5AutoSPRINK® 12 v12.0.48.0 3:13:39PM Pipe Type Diameter Flow Velocity Friction Loss Length Pressure Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq. Length Summary Upstream Total Length HWC Hydraulic Analysis Job Number: 16-184 - 16-184 Report Description: Residential (1) • • • • • Route 1 • • • • • Pf Pe Pv DR 1.025 40.0 15.6 0.347500 0-5½0.9 234 27-0½40.0 4.9 66.6 2-0 -0.2 89 27-6 67.3 2-5½ 150 Sprinkler, E(2-0) Pf Pe Pv BL 2.157 40.0 3.5 0.014016 4-9 0.2 89 27-6 67.3 12-3½ 88 27-6 67.9 67.5 17-0½0.3 120 T(12-3½) Pf Pe Pv BL 2.157 80.1 7.0 0.050606 5-5½0.9 88 27-6 40.1 67.9 67.5 12-3½ 81 27-6 68.8 17-9 120 Flow (q) from Route 2 T(12-3½) Pf Pe Pv BL 1.985 120.4 12.5 0.106735 7-6½0.8 81 27-6 40.3 68.8 80 27-6 69.6 7-6½ 150 Flow (q) from Route 3 Pf Pe Pv BL 2.003 120.4 12.3 0.102145 64-0½6.7 80 27-6 69.6 2-0 2.8 99 21-0½79.1 66-0½ 150 EE(2-0) Pf Pe Pv BL 1.985 120.4 12.5 0.106735 1-0 0.1 99 21-0½79.1 0.4 98 20-0½79.7 78.6 1-0 1.0 150 Pf Pe Pv BL 2.003 120.4 12.3 0.102145 209-5½23.2 98 20-0½79.7 78.6 18-0 0.0 97 20-0½102.9 227-5½ 150 2E(9-0) Pf Pe Pv BL 1.985 120.4 12.5 0.106735 95-10½12.5 97 20-0½102.9 21-0 7.5 27 2-7½122.9 116-10½ 150 5LtE, 2T(5-0), 11Tr(1-0) Pf Pe Pv BL 2.157 120.4 10.6 0.107606 0-6 0.1 27 2-7½122.9 0.2 25 2-1½123.2 122.1 0-6 1.0 120 f(-0.0), Z Pf Pe Pv BL 1.985 120.4 12.5 0.106735 1-1½0.1 25 2-1½123.2 122.1 0.5 30 1-0 123.8 1-1½ 150 BFP Pf Pe Pv BL 1.629 120.4 18.5 0.279477 44-2 15.7 30 1-0 123.8 12-0 -1.3 1 4-0 138.2 56-2 150 2E(5-0), EE(2-0), S 220.4 100.0 Hose Allowance At Source 1 • • • • • Route 2 • • • • • Pf Pe Pv DR 1.025 40.1 15.6 0.348601 0-5½0.9 242 27-0½40.1 4.9 66.9 2-0 -0.2 118 27-6 67.5 2-5½ 150 Sprinkler, E(2-0) Pf Pe Pv BL 2.157 40.1 3.5 0.014060 18-1 0.3 118 27-6 67.5 6-2 88 27-6 67.9 67.5 24-2½0.3 120 E(6-2) • • • • • Route 3 • • • • • Pf Pe Pv DR 1.025 40.3 15.7 0.352542 0-5½0.9 221 27-0½40.3 4.9 67.7 2-0 -0.2 67 27-6 68.4 2-5½ 150 Sprinkler, E(2-0) Pf Pe Pv BL 2.157 40.3 3.5 0.014219 4-9 0.2 67 27-6 68.4 12-3½ 66 27-6 68.6 17-0½ 120 T(12-3½) Pf Pe Pv BL 1.985 40.3 4.2 0.014104 7-0½0.2 66 27-6 68.6 5-0 81 27-6 68.8 12-0½ 150 T(5-0) 1.51 4.87 )(150 1.33 140 1.16 130 0.713 100 Equivalent Pipe Lengths of Valves and Fittings (C=120 only) Actual Inside Diameter Schedule 40 Steel Pipe Inside Diameter = Factor C Value Multiplier Value Of C Multiplying Factor © M.E.P.CAD, Inc.2/21/2017 Page 6AutoSPRINK® 12 v12.0.48.0 3:13:41PM Pipe Type Diameter Flow Velocity Friction Loss Length Pressure Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq. Length Summary Upstream Total Length HWC Hydraulic Analysis Job Number: 16-184 - 16-184 Report Description: Residential (1) Pipe Type Legend AO Arm-Over BL Branch Line CM Cross Main DN Drain DR Drop DY Dynamic FM Feed Main FR Feed Riser MS Miscellaneous OR Outrigger RN Riser Nipple SP Sprig ST Stand Pipe UG Underground Units Legend Diameter Inch Elevation Foot Flow gpm Discharge gpm Velocity fps Pressure psi Length Foot Friction Loss psi/Foot HWC Hazen-Williams Constant Pt Total pressure at a point in a pipe Pn Normal pressure at a point in a pipe Pf Pressure loss due to friction between points Pe Pressure due to elevation difference between indicated points Pv Velocity pressure at a point in a pipe Fittings Legend ALV Alarm Valve AngV Angle Valve b Bushing BalV Ball Valve BFP Backflow Preventer BV Butterfly Valve C Cross Flow Turn 90° cplg Coupling Cr Cross Run CV Check Valve DelV Deluge Valve DPV Dry Pipe Valve E 90° Elbow EE 45° Elbow Ee1 11¼° Elbow Ee2 22½° Elbow f Flow Device fd Flex Drop FDC Fire Department Connection fE 90° FireLock(TM) Elbow fEE 45° FireLock(TM) Elbow flg Flange FN Floating Node fT FireLock(TM) Tee g Gauge GloV Globe Valve GV Gate Valve Ho Hose Hose Hose HV Hose Valve Hyd Hydrant LtE Long Turn Elbow mecT Mechanical Tee Noz Nozzle P1 Pump In P2 Pump Out PIV Post Indicating Valve PO Pipe Outlet PRV Pressure Reducing Valve PrV Pressure Relief Valve red Reducer/Adapter S Supply sCV Swing Check Valve Spr Sprinkler St Strainer T Tee Flow Turn 90° Tr Tee Run U Union WirF Wirsbo WMV Water Meter Valve Z Cap © M.E.P.CAD, Inc.2/21/2017 Page 7AutoSPRINK® 12 v12.0.48.0 3:13:41PM ES-A-LF2000B 3⁄4" LF2000B (20mm) Job Name ________________________________________________Contractor ______________________________________________ Job Location ______________________________________________Approval _______________________________________________ Engineer _________________________________________________Contractor’s P.O. No. ______________________________________ Approval _________________________________________________Representative ___________________________________________ Ames product specifications in U.S. customary units and metric are ap prox i mate and are pro vid ed for ref er ence only. For precise mea sure ments, please contact Ames Technical Ser vice. Ames reserves the right to change or modify prod uct de sign, con struc tion, spec i fi ca tions, or ma te ri als with out prior notice and without in cur ring any ob li ga tion to make such chang es and mod i fi ca tions on Ames products previously or sub se quent ly sold.www.amesfirewater.com Features • Ease of maintenance with only one cover • Top entry • Replaceable seats and seat discs • Modular construction • Compact design • 1⁄2" – 2" (15 – 50mm) Lead Free* cast silicon copper alloy body construction • Top mounted ball valve test cocks • Low pressure drop • No special tools required • 1⁄2" – 1" (15 – 25 mm) have tee handles Available Models Suffix: B - Quarter turn ball valves LBV - less ball valves Pressure — Temperature Temperature Range: 33°F – 140°F (0.5°C – 60°C) Maximum Working Pressure: 175psi (12.06 bar) Standards AWWA Std. C510, IAPMO PS31 * The wetted surface of this product contacted by consumable water contains less than 0.25% of lead by weight. 1015 B64.5 3⁄4” - 2”(LBV Models Only) Series LF2000B Double Check Valve Assemblies Sizes: 1/2" – 2" (15 – 60mm) LEAD FREE* Series LF2000B Double Check Valve Assemblies shall be installed at ref er enced cross-con nec tions to prevent the backflow of polluted water into the po ta ble water supply. Only those cross-con nec tions identified by local in spec tion au thor i ties as non-health hazard shall be allowed the use of an ap proved double check valve as sem bly. Check with local authority having jurisdiction regarding ver ti cal ori en ta tion, fre quen cy of test ing or other in stal la tion re quire ments. These valves meet the requirements of ASSE Std. 1015 and AWWA Std. C510 and are approved by the Foun da tion for Cross-Con nec tion Control and Hy drau lic Re search at the University of South ern California. The LF2000B features Lead Free* construction to com- ply with Lead Free* installation requirements. Specifications A Double Check Valve Assembly shall be installed at each not ed lo ca tion. The Double Check Valve Assemblies shall be constructed using Lead Free* materials. Lead Free* valves shall comply with state codes and standards, where applicable, requiring reduced lead content. The as sem bly shall con sist of two positive seat ing check mod ules with cap tured springs and rubber seat discs. The check module seats and seat discs shall be re place able. Ser vice of all internal com po nents shall be through a sin gle ac cess cover se cured with stainless steel bolts. The as sem bly shall also in clude two resilient seat ed iso-la tion valves and four top mount ed, re sil ient seat ed test cocks. The as sem bly shall meet the re quire ments of ASSE Std. 1015 and AWWA Std. C510. Ap proved by the Foun da tion for Cross-Con nec tion Control and Hy drau lic Re search at the Uni ver si ty of South ern Cal i-for nia. As sem bly shall be an Ames Company Series LF2000B. Approvals Approved by the Foundation for Cross-Connection Control and Hy drau lic Research at the University of Southern California. LBV models not listed. Horizontal and vertical “flow up” approval on all sizes. Capacities As compiled from documented Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California lab tests. *Typical maximum system flow rate (7.5 feet/sec., 2.3 meters/sec.) kPa psi 83 12 69 10 55 8 41 6 28 4 14 2 0 0 ∆P 0 2 4 6 8 10 12 gpm0 7.6 15.2 22.8 30.4 38 45.6 lpm 5 7.5 10 fps 1.5 2.3 3.0 mps ∆ ∆P * ∆P ∆ kPa psi 110 16 83 12 69 10 55 8 41 6 28 4 14 2 0 5 10 15 20 25 30 35 40 45 50 55 60 gpm0 19 38 57 76 95 114 133 152 171 190 209 228 lpm 5 7.5 10 15 fps 1.5 2.3 3.0 4.6 mps ∆P ∆ kPa psi 96 14 83 12 69 10 55 8 41 6 28 4 14 2 0 0 0 10 20 30 40 50 60 70 80 90 100 110 120 gpm0 38 76 114 152 190 228 266 304 342 380 418 456 lpm 5 7.5 10 15 fps 1.5 2.3 3.0 4.6 mps kPa psi 83 12 69 10 55 8 41 6 28 4 14 2 0 0 ∆P0 10 20 30 40 50 60 70 80 90 100 110 120 gpm 0 38 76 114 152 190 228 266 304 342 380 418 456 lpm 5 7.5 10 15 fps 1.5 2.3 3.0 4.6 mps ∆ ∆P ∆ kPa psi 83 12 69 10 55 8 41 6 28 4 14 2 0 0 0 25 50 75 100 125 150 175 200 gpm0 95 190 285 380 475 570 665 760 lpm 5 7.5 10 15 fps 1.5 2.3 3.0 4.6 mps 1⁄2" (15mm) 1" (25mm) 11⁄4" (32mm) 11⁄2" (40mm) 2" (50mm) kPa psi 152 22 124 18 96 14 69 10 41 6 14 2 3⁄4" (20mm) 0 5 10 15 20 25 30 35 40 45 50 gpm0 19 38 57 76 95 114 133 152 171 190 lpm 7.5 15 fps 2.3 4.6 mps ∆ Dimensions – Weights H G I C B F A Pressure LossPressure LossPressure LossPressure LossPressure LossPressure LossFlow Rate Flow Rate Flow Rate Flow Rate Flow Rate Flow Rate LF2000B SIze (dn) dIMenSIOnS WeIGHt A B C F G H I in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm lbs. kgs. 1⁄2 15 10 254 45⁄8 117 27⁄16 62 5 127 33⁄8 85 25⁄16 59 21⁄16 52 4.5 2 3⁄4 20 111⁄8 282 4 102 31⁄8 79 63⁄16 157 37⁄16 87 21⁄8 54 15⁄16 33 5 2.3 1 25 131⁄4 337 51⁄8 130 4 102 71⁄2 191 33⁄8 85 111⁄16 43 111⁄16 43 12 5.4 11⁄4 32 163⁄8 416 5 127 35⁄16 84 91⁄2 241 5 127 3 76 2 50 15 6.8 11⁄2 40 163⁄4 425 47⁄8 124 31⁄2 89 93⁄4 248 513⁄16 148 31⁄8 79 211⁄16 68 15.86 7.2 2 50 191⁄2 495 61⁄4 159 4 102 133⁄8 340 61⁄8 156 37⁄16 87 211⁄16 68 25.75 11.7 Strainer sold separately ES-A-LF2000B 1322 © 2013 Ames Fire & Waterworks www.amesfirewater.com A Watts Water Technologies Company USA: Backflow- Tel: (916) 928-0123 • Fax: (916) 928-9333 Control Valves- Tel: (713) 943-0688 • Fax: (713) 944-9445 Canada: Tel: (905) 332-4090 • Fax: (905) 332-7068 General Description The Figure 513 (13) Riser Manifolds described in this technical data sheet provide the necessary waterflow alarm, pressure gauge, alarm test ori- fice, drain, and sight glass equipment in a single assembly for use in NFPA 13 sprinkler systems as follows: NFPA 13* •1-1/2 Inch (DN40) Male Thread x Female Thread •1-1/2thru6Inch(DN40thruDN150) Groove x Groove *Although the Riser Manifold described in this data sheet is intended for NFPA 13 sprinkler systems, it may be used for NFPA 13D or 13R residential sprinkler systems, where a test orifice of 5.6K (80K) is accept- able. The variety of sizes and grooved end connections allow cost effective and easy transition tocheck valves,control valves, and system piping. The Riser Manifoldsmaybeinstalledineitherthe horizontal (flow switch on top) or verti- cal (flow going up) for both single sprinkler rises and floor control in high rises. WARNING The Riser Manifolds described herein must be installed and maintained in compliance with this document, as well as with the applicable standards of the National Fire Protection Asso- ciation, in addition to the standards of any other authorities having jurisdic- tion.Failure to do so may impair the performance of these devices. The owner is responsible for maintain- ing their fire protection system and de- vices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. Technical Data Approvals The Figure 513 (13) Riser Manifolds with a cover tamper switch for the wa- terflow alarm switch are UL Listed, ULC Listed, and FM Approved. The Figure 513 (13) Riser Manifolds without a cover tamper switch for the waterflow alarm switch are UL Listed and FM Approved. Maximum Working Pressure 175 psi (12,1 bar) Test Orifice 5.6K (80K) Assembly The manifold body of the Figure 513 is ductile iron, whereas the manifold body of the Figure 13 is cast iron. The two assemblies are completely inter- changeable in function, application, and end-to-end laying length. Finish Red painted. Installation The Riser Manifolds may be installed in either the horizontal (flow switch on top) or vertical (flow going up). The inlet of the Riser Manifold may be di- rectly connected to a shut-off control valve. NOTES Where applicable pipe thread sealant is to be applied sparingly. Use of a non-hardening pipe thread sealant is recommended. Never remove any piping component nor correct or modify any piping defi- ciencies without first depressurizing and draining the system. Step 1.Install the manifold body with the flow arrow pointing in the down- stream position using threaded con- nections and/or listed mechanical grooved connections, as applicable Step 2.Connect the drain line, and then close the drain valve. Step 3.Refer to Figure 3 for wiring guidance. All wiring must be per- formed in accordance with the Author- ity Having Jurisdiction and/or the Na- tional Electrical Code. Step 4.Refer to Figure 4 for optional relief valve. Step 5.Place the system in service by filling the system with water. When fill- ing the system, partially open the con- trol valve to slowly fill the system.Fill- ing the system slowly will help avoid damaging the waterflow alarm switch. After the system is fully pressurized, completely open the control valve. Step 6.Secure all supply valves open. Model 513 (13) Riser Manifold 1-1/2 thru 6 Inch (DN40 thru DN150) For NFPA 13 Sprinkler Systems Page 1 of 6 TFP962APRIL, 2006 Technical Services:Tel: (800) 381-9312 / Fax: (800) 791-5500 Page2of6 TFP962 FIGURE 1 1-1/2 INCH (DN40) RISER MANIFOLD ASSEMBLY AND DIMENSIONS to the Waterflow Alarm Switches. 6-1/8" (155,6 mm) 12-5/8" (320,7 mm) (131,8 mm) Male x Male NPT 1. Approximate weight, 11.2 lbs. (5,1 kg). Cover Tamper Switches installed internal ULC Listed Manifolds are equipped with2. NOTES: 3/4" (19,1 mm) 1"5-3/16" NPT 1 Male x Female NPT, Manifolds Groove x Groove 10" (254,0 mm) Manifolds 14-1/4" 11-1/8" (282,6 mm) (362,0 mm) 2Waterflow3 3. CH: Common Hardware 3-1/2" (88,9 mm) QTY. UL/FM Waterflow Alarm Switch: VSR-SF with Paddle, VSR-SF with Paddle and Cover Tamper Switch, ULC/FM DESCRIPTION 1-1/2" Manifold Body, Groove x Groove Male x Female NPT 2 NO. 1 ............... .............. 1..... ....... 1 1 1 N/A 976-519-02 971-096-00 N/A P/N Water Pressure Gauge 300 psi/2000 kPa3 . . 1 2341 Closed) (Normally Drain Valve Inspector's Test & Drain Valve (Normally set to "Drain") TFP962 Page3of6 FIGURE 2 2 thru 6 INCH (DN50 thru DN150) RISER MANIFOLD ASSEMBLY AND DIMENSIONS 9/16 1 (14,3) C Nominal Installation Dimensions in Inches and (mm) 1 4-5/16 (25,4) 4-5/16 (109,5) (109,5) (25,4) 133 Inch 17-3/16 Cover Tamper Switches installed internal to the Waterflow Alarm Switches. ULC Listed Manifolds are equipped with NOTES: CH: Common Hardware2. 1. H C E D 4 Inch (DN80) 6 Inch (DN150) (DN100) A B Drain Valve (Normally Closed) 20-1/2 (436,6) 20-1/2 (520,7) (520,7) (330,2) (330,2) (330,2) 13 13 QTY. 2 INCH (DN50) MANIFOLD DESCRIPTION ULC/FM UL/FM Waterflow Alarm Switch: VSC with Paddle, VSC with Paddle and Cover Tamper Switch, 2" Manifold Body, Groove x Groove 300 psi/2000 kPa Water Pressure Gauge 3 2 NO. 1 1............... .............. ..1 1 .......1 Manifold 2 Inch 2-1/2 Inch (DN50) (DN65) 976-357-01 976-520-01 2341 Size N/A P/N 16-3/4 17-3/16 (425,5) (436,6) A (330,2) (330,2) 13 13 B 3-1/2 18.77-1/86 14-1/4 1-1/4" NPT to "Drain") (Normally set & Drain Valve F Test (422,3) 16-5/8 (469,9) 18-1/2 (362,0)Waterflow1 7-9/16 (152,4) (215,9) (192,1) 8-1/2 3 9-1/16 (181,0) 10 (254,0) (230,2) 2 4-1/2 (88,9) 6-5/8 (168,3) (114,3) 2" NPT 2" NPT G 32.7 (8,5) (18,9) 41.6 (14,8) Drain Size 1-1/4" NPT13-3/4 (331,8) 13-1/16 (349,3) (136,5) (146,1) 5-3/8 5-3/4 D 6-3/8 6-7/8 (161,9) (174,6) E 3-1/2 3-1/2 (88,9) (88,9) FG 1" NPT H Weight (6,1) 13.5 16.8 lbs. (kg) (7,6) 2 Waterflow Alarm Switch: 976-520-05 2341 976-357-05 VSC with Paddle, VSC with Paddle and Cover Tamper Switch, ULC/FM UL/FM Water Pressure Gauge 300 psi/2000 kPa3 1.. .............. ............... 1 1 P/N N/A 2341 976-520-04 976-357-04 N/A P/N 1...............UL/FM 300 psi/2000 kPa Water Pressure Gauge Cover Tamper Switch, VSC with Paddle and ULC/FM Groove x Groove 6" Manifold Body, DESCRIPTIONNO. 1 3 ....... 6 INCH (DN150) MANIFOLD QTY. 1 .............. 1.. 1 Groove x Groove 4" Manifold Body, DESCRIPTION Waterflow Alarm Switch: VSC with Paddle, 2 NO. 1 .......1 QTY. 4 INCH (DN100) MANIFOLD 1..............ULC/FM 976-520-02 2341Water Pressure Gauge 300 psi/2000 kPa3 ..1 976-357-02............... Groove x Groove 2-1/2" Manifold Body, Cover Tamper Switch, VSC with Paddle and VSC with Paddle, Waterflow Alarm Switch: DESCRIPTION 2-1/2 INCH (DN65) MANIFOLD 1 UL/FM 2 NO. ....... 1 N/A1 P/NQTY. 1..............ULC/FM 976-520-03 300 psi/2000 kPa Water Pressure Gauge 3 1. . 2341 ............... 3" Manifold Body, Groove x Groove Waterflow Alarm Switch: VSC with Paddle, VSC with Paddle and Cover Tamper Switch, DESCRIPTION 3 INCH (DN80) MANIFOLD 1 2 UL/FM NO. 1 .......1 976-357-03 N/A QTY. P/N Page4of6 TFP962 FIGURE 3 WIRING GUIDANCE INCOMING OUTGOING SINGLE CONDUCTOR TERMINAL PLATE LOOPED SECTION UNINSULATED CLAMPING CONDUCTORS SEPARATE STRIPPED ENDS SWITCH TERMINAL CONNECTIONS CLAMPING TERMINAL PLATE IMPROPER CONNECTION METHOD PROPER CONNECTION METHOD SEVERED CAUTION: An uninsulated section of a single conductor is not permitted to be looped around the terminal and serve as two separate connections. The wire must be severed to serve as two separate connections, thereby providing supervision of the connection in the event that the wire becomes dislodged from the terminal. WATERFLOW SWITCH TYPICAL ELECTRICA CONNECTIONS COM NCNO NO FLOW CONTACTS SPDT (Form C) 5A @ 125 VACCONTACT RATING 2.5A @ 30 VDC .......... .... COM NO NC POWER SIGNAL LOCAL DEVICE NON-SUPERVISED CIRCUITCONDITION END OF LINE RESISTOR COM SUPERVISED CIRCUIT STYLE B/CLASS B CONTROL NO NC PANEL signaling unit, while the other contact is used to operate a local audible or visual annunciator. Switch has two switches, one can be used to operate a central station, proprietary or remove For supervised circuits, see "Switch Terminal Connections" above. The Waterflow Alarm NOTE: (SEE NOTE) COVER TAMPER SWITCH (ULC ASSEMBLIES ONLY) CONTACTS SHOWN WITH COVER IN PLACE COM .......... ....CONTACT RATING NO CONTACTS 3A @ 250 VAC 5A @ 125 VAC NC SPDT (Form C) 1mA @ 5 VDC min. Care and Maintenance The following inspection procedure must be performed as indicated, in ad- dition to any specific requirements of the NFPA, and any impairment must be immediately corrected. The owner is responsible for the in- spection, testing, and maintenance of their fire protection system and de- vices in compliance with this docu- ment, as well as with the applicable standards of the National Fire Protec- tion Association (e.g., NFPA 25), in addition to the standards of any authority having jurisdiction. The in- stallingcontractor orproductmanufac- turer should be contacted relative to any questions. It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspection Service in accordance with local requirements and/or national codes. NOTES Noattemptistobemadetorepairany Riser Manifold component in the field. Only the pressure gauge, waterflow alarm switch, or relief valve can be replaced. If any other problems are encountered the entire riser manifold must be replaced. The alarm/flow test procedure will re- sult in operation of the associated alarms. Consequently, notification must be given to the owner and the fire department, central station, or other signal station to which the alarms are connected, and notification must be given to the building occupants. Before closing a fire protection system control valve for inspection or mainte- nance work on the fire protection sys- tem that it controls, permission to shut down the effected fire protection sys- tem must first be obtained from the proper authorities and all personnel who may be affected by this action must be notified. After placing a fire protection system in service, notify the proper authorities and advise thoseresponsibleformoni- toring proprietary and/or central sta- tion alarms. Alarm/Flow Test Procedure Step 1.Place the test & drain Valve in the “test” position. Step 2.Fully open the drain valve. Make certain that drainage water will not cause any damage or injury. Step 3.Verify operation of associated alarms. Step 4.Close the drain valve. Step 5.Place the test & drain Valve in the “drain” position. Step 6.Verify that the residual (flow- ing) pressure indicated by the pres- sure gauge is no less that originally recorded for the system when it was first installed. Step 7.Close the drain valve. Step 8.Verify that the static (not flow- ing) pressure indicated by the pres- sure gauge is no less that originally recorded for the system when it was first installed. TFP962 Page5of6 FIGURE 4 OPTIONAL PRESSURE RELIEF VALVE 1 system outlet piping, and a connection back 3/8" Copper Tubing, 2" (DN50) Manifolds 6" (DN150) Manifolds 4" (DN100) and 3" (DN80) Manifolds To install optional Pressure Relief Trim on must be provided by the installer on the a 1-1/2" (DN40) Manifold, a 1/2" NPT outlet 2-1/2" (DN65) and 1 1 1 .... ... .... 971-124-02 971-124-01 971-124-03 Pressure Relief Valve, DESCRIPTION 175 psi, Nonadjustable NO. 2 QTY. 1. . 198-066-00 P/N CH: Common Hardware with installer supplied 3/8" copper tubing. to the manifold drain trim must be fabricated 3 2 134 2 3 1-1/2" (DN40) Manifold Discard unused trim components. Fabricated 3/8" Copper Tubing Installer 1/2" NPT Outlet 90° Compression Fitting .............. 1" x 1/2" Reducing Hex4 Bushing 1 CH DESCRIPTIONNO. 3 QTY. P/N CH2................Fitting Manifold Drain Trim 3 Provided System Outlet Installer Piping 1-1/2" (DN40) Manifold Only: 2" (DN50), 2-1/2" (DN65), 6" (DN150) Manifold 3" (DN80), 4" (DN100), or Limited Warranty Products manufactured by Tyco Fire & Building Products (TFBP) are war- ranted solely to the original Buyer for ten (10) years against defects in mate- rial and workmanship when paid for and properly installed and maintained under normal use and service. This warranty will expire ten (10) years from date of shipment by TFBP. No warranty is given for products or com- ponents manufactured by companies not affiliated by ownership with TFBP or for products and components which havebeensubjecttomisuse,improper installation,corrosion, or which have not been installed, maintained, modi- fied or repaired in accordance with ap- plicable Standards of the National Fire Protection Association, and/or the standards of any other Authorities Having Jurisdiction. Materials found by TFBP to be defective shall be either repaired or replaced, at TFBP’s sole option. TFBP neither assumes, nor authorizes any person to assume forit, any other obligation in connection with the sale of products or parts of prod- ucts. TFBP shall not be responsible for sprinkler system design errors or inac- curate or incomplete information sup- plied by Buyer or Buyer’s repre- sentatives. In no event shall TFBP be liable, in contract, tort, strict liability or under any other legal theory, for incidental, indirect,specialorconsequentialdam- ages, including but not limited to labor charges, regardless of whether TFBP was informed about the possibility of such damages, and in no event shall TFBP’s liability exceed an amount equal to the sales price. Theforegoingwarrantyismadeinlieu of any and all other warranties, ex- press or implied, including warranties ofmerchantabilityandfitnessforapar- ticular purpose. This limited warranty sets forth the ex- clusive remedy for claims based on failure of or defect in products, materi- als or components, whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full ex- tent permitted by law. The invalidity, in whole or part, of any portion of this warranty will not affect the remainder. Ordering Information Riser Manifold: Specify; Size (specify), Figure 513, (specify connection type inlet x outlet) Riser Manifold (specify - without or with) a cover tamper switch for the waterflow alarm switch, P/N (specify). NOTES Orders for Figure 513 may be filled with a Figure 13. The two assemblies are completely interchangeable in function, application, and end-to-end laying length. If a ULC Listing is required, the Riser Manifold must be ordered with a cover tamper switch for the waterflow alarm switch. UL/ULC/FM Assemblies With Cover Tamper Switch 1-1/2 Inch (DN40) MT x FT . . . . . . . . . . . . . . P/N 4086 1-1/2 Inch (DN40) MT x MT . . . . . . . . . . . . . . P/N 4087 2 Inch (DN50) G x G . . . . . . . . . . . . . . . . P/N 4090 2-1/2 Inch (DN65) G x G . . . . . . . . . . . . . . . . P/N 4091 3 Inch (DN80) G x G . . . . . . . . . . . . . . . . P/N 4092 4 Inch (DN100) G x G . . . . . . . . . . . . . . . . P/N 4095 6 Inch (DN150) G x G . . . . . . . . . . . . . . . . P/N 4096 UL/FM Assemblies Without Cover Tamper Switch 1-1/2 Inch (DN40) MT x FT . . . . . . . . . . . . . . P/N 4055 1-1/2 Inch (DN40) MT x MT . . . . . . . . . . . . . . P/N 4056 2 Inch (DN50) G x G . . . . . . . . . . . . . . . . P/N 4060 2-1/2 Inch (DN65) G x G . . . . . . . . . . . . . . . . P/N 4061 3 Inch (DN80) G x G . . . . . . . . . . . . . . . . P/N 4062 4 Inch (DN100) G x G . . . . . . . . . . . . . . . . P/N 4065 6 Inch (DN150) G x G . . . . . . . . . . . . . . . . P/N 4066 Optional Pressure Relief Valve: Specify: Operational Pressure Relief Valve and Trim for use with (specify size) Figure 513 or 13 Series Riser Manifold, P/N (specify). 1-1/2" or 2". . . . . . . . . . . . . . . P/N 4063 2-1/2" or 3". . . . . . . . . . . . . . . P/N 4072 4" or 6" . . . . . . . . . . . . . . . . . . P/N 4073 Replacement Parts: Specify: (description) for use with Fig- ure 513 or 13 Riser Manifold,P/N (Ref. Figure 1 or 2, as applicable). Page6of6 TFP962 TYCO FIRE & BUILDING PRODUCTS,451 North Cannon Avenue, Lansdale, Pennsylvania 19446 RAPID RESPONSE Series LFII Residential 4.9 K-factor Concealed Pendent Sprinkler Flat Plate, Wet Pipe and Dry Pipe Systems Page 1 of 6 FEBRUARY 2015 TFP442 IMPORTANTAlways refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal-lation of sprinkler systems and com-ponents. Improper handling and installation can permanently damage a sprinkler system or its compo-nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Worldwide Contacts www.tyco-fire.com General Description TYCO RAPID RESPONSE Series LFII Residential 4.9K Concealed Pendent Sprinklers (TY3596) are decorative, fast response, fusible solder sprinklers designed for use in residential occu-pancies such as homes, apartments, dormitories, and hotels. The cover plate assembly conceals the sprinkler operating components above the ceiling. The flat profile of the cover plate provides the optimum aes-thetically appealing sprinkler design. In addition, the concealed design of the Series LFII Residential Concealed Pendent Sprinklers (TY3596) provides 1/2 inch (12,7 mm) vertical adjustment. This adjustment provides a measure of flexibility when cutting fixed sprinkler drops. The Series LFII Residential Concealed Sprinklers are intended for use in the following scenarios: • wet and dry pipe residential sprin-kler systems for one- and two-fam-ily dwellings and mobile homes per NFPA 13D • wet and dry pipe residential sprinkler systems for residential occupancies up to and including four stories in height per NFPA 13R • wet and dry pipe sprinkler systems for the residential portions of any occupancy per NFPA 13 The Series LFII Residential Concealed Pendent Sprinklers (TY3596) has been designed with heat sensitivity and water distribution characteristics proven to help in the control of residen-tial fires and to improve the chance for occupants to escape or be evacuated. The Series LFII Residential Con-cealed Pendent Sprinklers (TY3596) are shipped with a Disposable Pro-tective Cap. The Protective Cap is temporarily removed for installation, and then it can be replaced to help protect the sprinkler while the ceiling is being installed or finished. The tip of the Protective Cap can also be used to mark the center of the ceiling hole into plaster board, ceiling tiles, etc. by gently pushing the ceiling product against the Protective Cap. When the ceiling installation is complete the Pro-tective Cap is removed and the Cover Plate Assembly installed. Dry Pipe System ApplicationThe Series LFII Residential Concealed Pendent Sprinklers offers a laboratory approved option for designing dry pipe residential sprinkler systems, whereas, most residential sprinklers are labora-tory approved for wet systems only. Through extensive testing, it has been determined that the number of design sprinklers (hydraulic design area) for the Series LFII Residential Concealed Pendent Sprinklers (TY3596) need not be increased over the number of design sprinklers (hydraulic design area) as specified for wet pipe sprinkler systems, as is accustomed for density/area sprinkler systems designed per NFPA 13. Consequently, the Series LFII Residen-tial Concealed Pendent Sprinklers offer the features of non-water filled pipe in addition to not having to increase the number of design sprinklers (hydraulic design area) for systems designed to NFPA 13, 13D, or 13R. NOTICE The Series LFII Residential Concealed Pendent Sprinklers (TY3596) described herein must be installed and main-tained in compliance with this docu-ment and with the applicable standards of the National Fire Protection Associa-tion (NFPA), in addition to the standards of any authorities having jurisdiction. Failure to do so may impair the perfor-mance of these devices. The owner is responsible for main-taining their fire protection system and devices in proper operating con-dition. Contact the installing contrac-tor or product manufacturer with any questions. Sprinkler Identification Number (SIN) TY3596 TFP442 Page 2 of 6 3-3/16" DIA. (81,0 mm) 1/2" NPT 2-1/2" DIA.(63,5 mm) MOUNTINGSURFACE3/16"(4,8 mm) 1/8" GAP (3,2 mm) FACE OF SPRINKLER FITTING 7/8" (22,2 mm) 1-1/8" (28,6 mm) TIP DEFLECTOR IN OPERATED POSITION 1/2" (12,7 mm) THREADED ADJUSTMENT SPRINKLER-SUPPORT CUPASSEMBLY OPERATEDSPRINKLER 1-7/8"±1/4" (47,6 mm ±6,4 mm) SPRINKLER-SUPPORT CUPASSEMBLY COVER-RETAINERASSEMBLY COVERPLATERETAINER DISPOSABLE PROTECTIVE CAP WRENCHRECESS PUSH WRENCH IN TO ENSURE ENGAGEMENT WITH SPRINKLER WRENCHING AREA SPRINKLER/SUPPORT CUPASSEMBLY COVER PLATE/RETAINERASSEMBLY COVER PLATE EJECTIONSPRING RETAINER WITH THREAD DIMPLES SOLDER TAB SEALINGASSEMBLY COMPRESSION SCREW DEFLECTOR(OPERATEDPOSITION) SPRINKLER WRENCHING AREA SOLDER LINK ELEMENT LEVER DEFLECTOR CAP BODY(1/2" NPT) SADDLE SUPPORT CUP WITH ROLL FORMED THREADS GUIDE PIN GUIDE PINHOUSING THREAD INTO SUPPORT CUP UNTIL MOUNTING SURFACE IS FLUSH WITH CEILING FIGURE 1 RAPID RESPONSE SERIES LFII RESIDENTIAL CONCEALED PENDENT SPRINKLER (TY3596) FIGURE 2 W-TYPE 18 SPRINKLER WRENCH FIGURE 3 RAPID RESPONSE SERIES LFII RESIDENTIAL CONCEALED PENDENT SPRINKLER (TY3596) INSTALLATION DIMENSIONS/PROTECTIVE CAP/ACTIVATED DEFLECTOR TFP442 Page 3 of 6 Dry Pipe System Water DeliveryWhen using the Series LFII Residen-tial Concealed Pendent Sprinklers (TY3596) in dry pipe sprinkler systems, the time for water delivery must not exceed 15 seconds for the most remote operating sprinkler. Obstruction to Water DistributionSprinklers are to be located in accor-dance with the obstruction rules of NFPA 13D, 13R, and 13 as applicable for residential sprinklers as well as with the obstruction criteria described within the Technical Data Sheet TFP490. Operational SensitivityThe sprinklers are to be installed rela-tive to the ceiling mounting surface as shown in Figure 3. Sprinkler SpacingThe minimum spacing between sprin-klers is 8 feet (2,4 m). The maximum spacing between sprinklers cannot exceed the length of the coverage area (Ref. Table A or B) being hydraulically calculated (e.g., maximum 12 feet for a 12 ft. x 12 ft. coverage area, or 20 feet for a 20 ft. x 20 ft. coverage area). The Series LFII must not be used in applications where the air pres-sure above the ceiling is greater than that below. Down drafts through the Support Cup could delay sprinkler operation in a fire situation. Technical Data ApprovalsUL and C-UL Listed NYC Approved under MEA 44-03-E-2NSF Certified to NSF/ANSI 61 The TYCO RAPID RESPONSE Series LFII Residential Concealed Pendent Sprinklers are only Listed with the Series LFII Con-cealed Cover Plates having a factory-ap-plied finish. Cover Plates can be ordered by following the instructions in the Ordering Procedure section. Maximum Working Pressure175 psi (12,1 bar) Discharge CoefficientK=4.9 gpm/psi1/2 (70,6 lpm/bar1/2) Temperature Rating160°F (71°C) Sprinkler with 139°F (59°C) Cover Plate Vertical Adjustment1/2 inch (12,7 mm) FinishesRefer to Ordering Procedure section. Physical Characteristics Body.........................Brass Cap.........................Bronze Saddle .......................Brass Sealing Assembly.......Beryllium Nickel w/TEFLON Soldered Link Halves. . . . . . . . . . . .Nickel Lever........................Bronze Compression Screw. . . . . . . . . . . . . Brass Deflector...................Copper or Brass Guide Pin Housing . . . . . . . . . . . . . Bronze Guide Pins .............Stainless Steel or Bronze Support Cup . . . . . . . . . . . . . . . . . . .Steel Cover Plate ..................Copper Retainer ......................Brass Cover Plate Ejection Spring..........Stainless Steel Operation When exposed to heat from a fire, the Cover Plate, which is normally soldered to the Support Cup at three points, falls away to expose the sprinkler assembly. At this point the Deflector supported by the Arms drops down to its operated position. The fusible link of the sprin-kler assembly is comprised of two link halves that are soldered together with a thin layer of solder. When the rated temperature is reached, the solder melts and the two link halves separate allowing the sprinkler to activate and flow water. Design Criteria TYCO RAPID RESPONSE Series LFII Residential Concealed Pendent Sprin-klers (TY3596) are UL and C-UL Listed for installation in accordance with this section. Note: When conditions exist that are outside the scope of the provided cri-teria, refer to the Residential Sprinkler Design Guide TFP490 for the manu-facturer's recommendations that may be acceptable to the authority having jurisdiction. System TypesPer the UL Listing, wet pipe and dry pipe systems may be utilized. Per the C-UL Listing, only wet pipe systems may be utilized. Refer to Technical Data Sheet TFP485 about the use of residential sprinklers in residential dry pipe systems. Ceiling TypesSmooth flat horizontal, or beamed, or sloped, in accordance with the 2013 Edition of NFPA 13D, 13R, or 13 as applicable. Hydraulic Design (NFPA 13D and 13R)For systems designed to NFPA 13D or NFPA 13R, the minimum re quired sprinkler flow rates are given in Tables A and B as a function of tem-perature rating and the maximum allowable coverage areas. The sprinkler flow rate is the minimum required discharge from each of the total number of “design sprinklers” as specified in NFPA 13D or NFPA 13R. The number of “design sprinklers” specified in NFPA 13D and 13R for wet pipe systems is to be applied when designing dry pipe systems. Hydraulic Design (NFPA 13)For systems designed to NFPA 13, the number of design sprinklers is to be the four most hydraulically demanding sprinklers. The minimum required dis-charge from each of the four sprinklers is to be the greater of the following: • the flow rates given in Tables A and B as a function of temperature rat-ing and the maximum allowable cov-erage area • a minimum discharge of 0.1 gpm/ft.2 over the design area comprised of the four (4) most hydraulically demanding sprinklers for actual coverage areas protected by the four (4) sprinklers The number of design sprinklers speci-fied in NFPA 13 for wet pipe systems is to be applied when designing dry pipe systems. TFP442 Page 4 of 6 Maximum Coverage Area 1 Ft. x Ft. (m x m) Maximum Spacing Ft. (m) DRY PIPE SYSTEM Minimum Flow and Residual Pressure 2, 3 Ordinary Temp. Rating 160°F (71°C)Deflector to Ceiling Installation Type Minimum Spacing Ft. (m) Flow gpm (lpm) Pressure psi (bar) 12 x 12(3,7 x 3,7)12(3,7)13 (49,2) 7.0 (0,48)Smooth Ceilings 7/8 to 1-1/8 inches Beamed Ceilings per NFPA 13D or 13R, or 13. Installed in beam 7/8 to 1-1/8 inches below bottom of beam Concealed 8(2,4) 14 x 14(4,3 x 4,3)14(4,3)14 (53,0)8.2 (0,57) 16 x 16(4,9 x 4,9)16(4,9)15 (56,8)9.4 (0,65) 18 x 18(5,5 x 5,5)18(5,5)18 (68,1)13.5 (0,93) 20 x 20(6,1 x 6,1)20(6,1)21 (79,5)18.4 (1,27) Notes:1. For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated.2. Requirement is based on minimum flow in gpm (lpm) from each sprinkler. The associated residual pressures are calculated using the nominal K-factor. Refer to Hydraulic Design under the Design Criteria section.3. For NFPA 13 residential applications, the greater of 0.1 gpm/ft.2 over the design area or the flow in accordance with the criteria in this table must be used. Maximum Coverage Area 1 Ft. x Ft. (m x m) Maximum Spacing Ft. (m) WET PIPE SYSTEM Minimum Flow and Residual Pressure 2, 3 Ordinary Temp. Rating 160°F (71°C)Deflector to Ceiling Installation Type Minimum Spacing Ft. (m) Flow gpm (lpm) Pressure psi (bar) 12 x 12 (3,7 x 3,7)12 (3,7)13 (49,2) 7.0 (0,48)Smooth Ceilings 7/8 to 1-1/8 inches Beamed Ceilings per NFPA 13D or 13R, or 13. Installed in beam 7/8 to 1-1/8 inches below bottom of beam Concealed 8(2,4) 14 x 14 (4,3 x 4,3)14 (4,3)13 (49,2) 7.0 (0,48) 16 x 16 (4,9 x 4,9)16 (4,9)13 (49,2)7.0 (0,48) 18 x 18 (5,5 x 5,5)18 (5,5)17 (64,3)12.0 (0,83) 20 x 20 (6,1 x 6,1)20 (6,1)20 (75,7)16.7 (1,15) Notes:1. For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated.2. Requirement is based on minimum flow in gpm (lpm) from each sprinkler. The associated residual pressures are calculated using the nominal K-factor. Refer to Hydraulic Design under the Design Criteria section.3. For NFPA 13 residential applications, the greater of 0.1 gpm/ft.2 over the design area or the flow in accordance with the criteria in this table must be used. TABLE A WET PIPE SYSTEM SERIES LFII RESIDENTIAL 4.9 K-FACTOR FLAT PLATE CONCEALED PENDENT SPRINKLER (TY3596) NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA TABLE B DRY PIPE SYSTEM RAPID RESPONSE SERIES LFII RESIDENTIAL 4.9 K-FACTOR FLAT PLATE CONCEALED PENDENT (TY3596) NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA TFP442 Page 5 of 6 Step 6. Screw on the Cover Plate Assembly until its flange comes in contact with the ceiling. Do not continue to screw on the Cover Plate Assembly such that it lifts a ceiling panel out of its normal position. If the Cover Plate Assembly cannot be engaged with the Mounting Cup or the Cover Plate Assembly cannot be engaged sufficiently to contact the ceiling, the Sprinkler Fitting must be repositioned. Care and Maintenance TYCO RAPID RESPONSE Series LFII Residential Concealed Pendent Sprin-klers (TY3596) must be maintained and serviced in accordance with this section. Before closing a fire protection system main control valve for maintenance work on the fire protection system which it controls, permission to shut down the affected fire protection system must be obtained from the proper authorities and all personnel who may be affected by this action must be notified. Absence of a Cover Plate may delay the sprinkler operation in a fire situation. When properly installed, there is a nominal 1/8 inch (3,2 mm) air gap between the lip of the Cover Plate and the ceiling, as shown in Figure 3. This air gap is necessary for proper opera-tion of the sprinkler by allowing heat flow from a fire to pass below and above the Cover Plate to help assure appropriate release of the Cover Plate in a fire situation. If the ceiling is to be repainted after the installation of the Sprinkler, care must be exercised to ensure that the new paint does not seal off any of the air gap. Factory painted Cover Plates must not be repainted. They should be re placed, if necessary, by factory painted units. Non-factory applied paint may adversely delay or prevent sprinkler operation in the event of a fire. Do not pull the Cover Plate relative to the Enclosure. Separation may result. Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated, or otherwise altered after leaving the factory. Modi-fied or over heated sprinklers must be replaced. Care must be exercised to avoid damage before, during, and after instal-lation. Sprinklers damaged by drop-ping, striking, wrench twist/slippage, or the like, must be replaced. The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Asso-ciation (e.g., NFPA 25), in addition to the standards of any other authorities having jurisdiction. Contact the install-ing contractor or product manufacturer with any questions. The owner must assure that the sprin-klers are not used for hanging any objects and that the sprinklers are only cleaned by means of gently dusting with a feather duster; otherwise, non-operation in the event of a fire or inad-vertent operation may result. Automatic sprinkler systems should be inspected, tested, and maintained by a qualified Inspection Service in accor-dance with local requirements and/or national codes. Installation TYCO RAPID RESPONSE Series LFII Residential Concealed Pendent Sprin-klers (TY3596) must be installed in accordance with this section. General InstructionsDamage to the fusible Link Assembly during installation can be avoided by handling the sprinkler by the support cup only (i.e., do not apply pressure to the fusible Link Assembly). A 1/2 inch NPT sprinkler joint should be obtained with a minimum to maximum torque of 7 to 14 lbs.-ft. (9,5 to 19,0 Nm). Higher levels of torque may distort the sprinkler inlet with consequent leakage or impairment of the sprinkler. Do not attempt to compensate for insufficient adjustment in the Cover Plate / Retainer Assembly by under-or over-tightening the Sprinkler. Read-just the position of the sprinkler fitting to suit. Step 1. The sprinkler must only be installed in the pendent position and with the centerline of the sprinkler per-pendicular to the mounting surface. Step 2. Remove the Protective Cap. Step 3. With pipe thread sealant applied to the pipe threads, and using the W-Type 18 Wrench shown in Figure 2, install and tighten the Sprinkler / Support Cup Assembly into the fitting. The W-Type 18 Wrench will accept a 1/2 inch ratchet drive. Step 4. Replace the Protective Cap by pushing it upwards until it bottoms out against the Support Cup. The Protec-tive Cap helps prevent damage to the Deflector and Guide Pins during ceiling installation and/or during application of the finish coating of the ceiling. It may also be used to locate the center of the clearance hole by gently pushing the ceiling material against the center point of the Cap. Note: As long as the protective Cap remains in place, the system is consid-ered to be “Out Of Service.” Step 5. After the ceiling has been completed with the 2-1/2 inch (63 mm) diameter clearance hole and in prep-aration for installing the Cover Plate Assembly, remove and discard the Pro-tective Cap, and verify that the Deflec-tor moves up and down freely. If the sprinkler has been damaged and the Deflector does not move up and down freely, replace the entire sprinkler assembly. Do not attempt to modify or repair a damaged sprinkler. GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700 TFP442 Page 6 of 6 Copyright © 2015 Tyco Fire Products, LP. All rights reserved.TEFLON is trademark of The DuPont Corporation. Limited Warranty For warranty terms and conditions, visit www.tyco-fire.com. Ordering Procedure Contact your local distributor for availability. When placing an order, indicate the full product name and part number (P/N). Sprinkler AssembliesSpecify: Series LFII (TY3596) 4.9K Residential Concealed Pendent Sprin-kler without Cover Plate Assembly, P/N 51-112-1-160 Cover Plate AssembliesSpecify: Cover Plate Assembly with (specify) finish for the Series LFII (TY3596) 4.9K Residential Concealed Pendent Sprinkler, P/N (specify): Ivory (RAL1015) ...........P/N 56-202- 0-135 Beige (RAL1001)...........P/N 56-202- 2-135 Pure White * (RAL9010) .....P/N 56-202- 3-135 Signal White ** (RAL9003)...P/N 56-202- 4-135 Grey White (RAL9002)......P/N 56-202- 5-135 Brown (RAL8028)..........P/N 56-202- 6-135 Black (RAL9005) ..........P/N 56-202- 7-135 Brushed Brass............P/N 56-202- 8-135 Brushed Chrome ..........P/N 56-202- 9-135 Custom Paint .............P/N 56-202- X-135 * Eastern Hemisphere sales only ** Previously known as Bright White Note: All Custom Cover Plates are painted using Sherwin Williams Interior Latex Paint. Contact Tyco Customer Service with any questions related to custom orders. Sprinkler WrenchSpecify: W-Type 18 Sprinkler Wrench, P/N 56-000-1-265 FIRE DEPT. INLET CONN. FLUSH TYPE6341-6345 SERIES SINGLE INLET An inlet connection with 250 G.P.M. minimum inlet capacity to supplement the fire protection water supply. Provides unobstructed water supply. Flush round design enhances appearance and provides unobstructed passage. STANDARD EQUIPMENT:Cast Brass round plate with double female adapter; plug and chain; branding as selected. SPECIFY THREAD AND BRANDING. BRANDING: "Standpipe", "Auto Spkr." FINISH: Cast Brass OPTIONAL FINISH:PB-Polished Brass PC-Polished Chrome RESIDENTIAL FIRE DEPT. CONNECTION An inlet connection to supplement the water supply to a residential sprinkler system. STANDARD EQUIPMENT: 1 1/2" cast brass round plate assembly with integral pin lug swivel inlet. Hose thread inlet swivel, 1 1/2" NPT female outlet on back of plate. Cast brass plug and brass chain. Overall outside Diameter 4 3/8". SPECIFY THREAD AND BRANDING. U/L LISTED. BRANDING: "Auto Spkr." FINISH: Cast Brass OPTIONAL FINISH:PB-Polished Brass PC-Polished Chrome Figure No. 6341 Figure No. 6342 Figure No. 6345 Page 6-12 Round Plate Figure No. Size 6341 2 1/2 X 2 1/2 6342 3 X 2 1/2 6343 3 X 3 ___________________________________________________