HomeMy WebLinkAboutE16-0232 load calcs.pdf 1360 Westhaven Dr. #6A
Existing Load Calculation 10/19/16:
1123 sq. ft. @ 3VA 3,369 VA
Kitchen appliance X 2 3,000 VA
Dishwasher 1,200 VA
Disposal 1,200 VA
Refrigerator 1,200 VA
Range 8,200 VA
Washer 1,500 VA
Dryer 5,000 VA
Water Heater X 2 4,800 VA
General Load Sub-Total 29,469 VA
St
1 10kVA @ 100% 10,000 VA
Remainder @ 40% 7,788 VA
Total Net General Load 17,788 VA
Baseboard heat @ 100% 12,000 VA
Total 29,788 VA
Calculated Load for Service 29,788 VA/ 240 volts = 125 Amps
Existing service size 125 Amps 1CCSE - V n
J I
T 2 •.) 2016
`4
TOWN OF` ,JAL 4