B17-0441_Bock Residence Solar Calculations_1510689648.pdf
ACTI ENE ' 'lir t _ SOL SOLAR INSTALLATION INFORMATION � D �tk Vendor: Active Energies Solar LLC 11/14/17 PO Box 7627 Avon, CO 81620 (970-306-4233/info@ac tiveenergies.c om) Site: Bock Residence 1700 Lions Ridge Loop Vail CO 81657 System Layout: Single Panel: 5.32ft tall X 3.47ft wide System Size: 15.99ft tall x 36ft wide Panel Arrangement: see layout below;all panels oriented in the portrait position, mounted flush on the roof. Net Meter, _ Production Meter VtIOPP EL1 4 NILel f* • • = 3' Firecode Setback Holy Cross electric meter is located on the north side of the house adjacent to the front door. The PV production meter will be adjacent to the Holy Cross net meter. The inverter will be adjacent to the production meter. Minimum Designed Temperature: -40°F Maximum Ambient Design Temperature: 140°F All AC wiring to be completed by project Colorado licensed master electrician All DC wiring to be overseen by NABCEP certified installer Page 1 of 4 10/19/2017 P.O.B13:01 AE it,J30)1.814E0 11F209)70P2.29:11E700.3033014884,E.4ff13. $.l[3 3,435.4ctilac ui gee ies.c orn AcT1 ENE SOL CALCULATIONS°' 11/14/17 9.75kW System Size (STC) • 30 Solaria PowerXT 325 solar panels @ 325 watts • 30 SolarEdge P370 Optimizers • 1 SolarEdge SE7600A-US inverter(2 strings of 15 modules/optimizers) • Fixed array tilt angle: 22.62° • Array azimuth: 150°& 235° (where 180° is south) • Estimated annual power production: 14,193kWh Maximum PV System Voltage: 690.7 Voc =44.5V/module 44.5V x 1 module= 44.5V Temperature correction factor 690.7(A) Temperature Coefficient(Voc) =-0.32%/°C (-65C° x (-.0032C°))= .208% ((.208%x 44.5V) x 1 panels) +44.5V= 53.76V Maximum PV Source Circuit(String) Current: 690.8 (A)(1) Ise=9.4A 9.4A x 1.25 = 11.75A Maximum PV Output Circuit(Array) Current: 690.8 (A)(2) SE7600A-US inverter limit 23A combined string Inverter Output Circuit Current: 690.8 (A)(3) 32A @ 240V Page 2 of 4 10/19/2017 P.0.EJ3:71 .kE it,J30) 314E0 1 F20910P229 7M 33 IJj4g.r[,61 4)3 3716X03 i .4ct.nrvriar w oee ies.corn AcTI .4,:‘°A.0411&‘ ENE ' -lir 111_ SOL CONDUCTOR SIZING , vitn 11/14/17 Pass Thru Box from Optimizers to Inverter (combined strings): SE7600A-US inverter limit 23A combined string 23A x 1.25 = 28.8A #10 THWN-2 Table 310.16 40A (90°C column, see note 240.4(D)) Temperature correction factor Table 310.15 (B)(2)(b) 40A x .78 = 31.2A No conduit fill adjustment Inverter to Disconnect to Production Meter: Nameplate maximum continuous output current: 32A @ 240V 32A x 125% = 40A 210.19 (A)(1) #8 THWN-2 Table 310.16 55A (75°C column) No temperature correction factor No conduit fill adjustment Overcurrent Protection Device 40A two pole breaker Per Manufacturer Specification Conductors may be oversized for voltage drop Page 3 of 4 10/19/2017 P.O.B13:0704 AE it,J30) 314E0 1 F20910P229 7M 33 01148:[,61 4)3 3716X03 i4ta5 4c1wwwiar w me ies.c orn M fe lair C 17h Z3 tk " IQ07lbs 11 Line Diagram Backfeed breaker at same level as main breaker: ' Placard on meter and main panel stating Bock Residence "Photovoltaic System Connected°& 9.75kW Utility Interactive Photovoltaic 1700 Lions Ridge Loop Indicate that breakers must be turned off in order System Vail, Co 81657 Array mounted on roof to remove all load and generation so the meter Modules: 30 X Solaria PowerXT 325 30 Solaria PowerXT 325 Solar Panels 30 SolarEdge P370 DC Optimizers may be changed safely Voc=44.5V per Holy Cross specifications Isc=9.4A ' Optimizers:30 SolarEdge P370 // 2 Strings X 15 Modules Inverter:SolarEdge SE7600A-US Second Main for Backfeed Breaker 1 2 3 .• xi Operating Voltage: 350V - --- --- i aolta Operating C :11.75A mi_ x Main Breaker Max System Voltage: 500V MaxMIMax Output C urrent:30A ■ 16 17 1830 1 Tilt Angle:22.62° 4#10 PV Wire -I ilk • i Array Azimuth: 150° &235° 1#6G Bare C u ^ ^ w Conductors in Free Air - i . rli___ • )) Production: 14,193kWh/yr 'd I Net Meter r , Pass-Thru Box Located on `40' Notes: house roof 34"C EMT Backeed -See CalculationSheetfor conductor sizing. 2#10 THWN-2 Breaker 1#10 G THWN-2 40A - copper conductors are co er unless otherwise 2P noted. 'A"C EMT/PVC/other %"C EMT/PVC/other — 240V -Inverter listed(UL-1741)to de-energize RAPID SHUTDOWN 3#8 THWN-2 3#8 THWN-2 • upon loss of utility voltage per NEC 690.61. I SWITCH FOR 1#8 G THWN-2 1#8 G THWN-2 •: -Inverter has integral ground-fault protection SOLAR PV SYSTEM /� PV GHO°URION MnR., - per NEC 690.5 1 Production n n -240V 1 Phase Service Panel rating of 200A • • I Meter 40A n (bus rating 250 amp to accommodate 40A Within 10'of n n (PV)+200A(Main) =240A supply(up to ♦ / meter J (m rm 120% of connected power sources from �J installations per NEC 705(D)(2)(3)(b) SolarEdge SE7600A-US Inverter w/Integrated Disconnect Main Panel and Net Meter NEMA 3R — To the right of the front door , Max AC Output:32A @ 240V With ARC Fault Protection&Rapid Shutdown DC Grounding Electrode Conductor compliant-adj to prod meter solid bare#6 C u,per NEC 250.66(C) Page 4 of 4 10/19/2017 P.O.Box 7627,Avon,CO 81620 I P: 970.306.4233 I F: 866.403.3485 I www.activeenergies.com *IA OFge, .5,0400454.. SO LAR I A Solaria PowerXTTM I R: • 11/14/17 • Solaria PowerXTTM-330R-PX 1 Solaria PowerXTTM-325R-BX Achieving over 19% efficiency, Solaria PowerXT solar modules are one of the highest power modules in the residential solar market. Compared to conventional modules, Solaria PowerXT modules have fewer gaps between the solar cells; this leads to higher power and superior aesthetics. Solaria PowerXT residential modules are manufactured with black backsheet and frames, giving them a striking appearance. Developed in California,Solaria's patented cell cutting and module assembly form high-density sub-strings,which are packed more efficiently and reduce inactive space between cells. By utilizing a ribbon-less interconnection process, cells are cut and overlaid without soldering, which creates highly reliable sub-string assemblies in a cost effective manner. Higher Efficiency, Higher Power Solaria PowerXT modules achieve over 19%efficiency;conventional modules achieve 15%—17%efficiency. Solaria PowerXT modules are one of the highest power modules available. Lower System Costs Solaria PowerXT modules produce more power per square meter area. This reduces installation costs due to fewer balance of system components. Improved Shading Tolerance Sub-strings are interconnected in parallel,within each of the four module quadrants, which dramatically lowers the shading losses and boosts energy yield. Improved Aesthetics Compared to conventional modules,Solaria PowerXT modules have a more uniform appearance and superior aesthetics. Durability and Reliability Solder-less cell interconnections are highly reliable and designed to far exceed the industry leading 25 year warranty. About Solaria Established in 2000,The Solaria Corporation has created one of the industry's most respected IP portfolios,with over 100 patents encompassing materials,processes, applications,products,manufacturing automation and equipment. Headquartered in Fremont,California,Solaria has developed a technology platform that unlocks the potential ❑ N V-G L TUVRheinla d of solar energy allowing it to be ubiquitous and universally accessed. Precisely Right. The Solaria Corporation 6200 Paseo Padre Parkway,Fremont,CA 94555 P:(510)270-2500 www.solaria.com Copyright©2017 The Solaria Corporation Product specifications are subject to change without notice. Rev 2G 1-26-2017 "so s OF X44! Solaria PowerXTTM- & � SOLARIA Solaria PowerXTTM- I cp. er 16 t:b Performance at STC(1000W/m2,25°C,AM 1.5) Solaria PowerXT- 320R-BX 325R-BX 325R-PX 330R-PX Cell Type Monocrystalline Silicon Max Power(Pmax) [W] 320 325 325 330 Dimensions(L x W x H) 1621 mm x 1056mm x 40mm Efficiency [%] 18.7 19.0 19.0 19.3 Weight 20 kg/44 lbs Open Circuit Voltage(Voc) [V] 44.3 44.5 44.3 44.5 Glass Type/Thickness AR Coated,Tempered/3.2mm Short Circuit Current(Isc) [A] 9.36 9.40 9.46 9.49 Frame Type Anodized Aluminum Max Power Voltage(Vmp) [V] 36.5 36.7 36.4 36.6 Cable Type/Length 12 AWG PV Wire(UL)/1000mm Max Power Current(Imp) [A] 8.77 8.86 8.93 9.02 Connector Type Amphenol H4(MC4 compatible) Power Tolerance [%] -0/+3 -0/+3 -0/+3 -0/+3 Junction Box IP67/4 diodes Performance at NOCT(800W/m2,20°C Amb,Wind 1 m/s,AM 1.5) Front Load(UL 1703) 5400 Pa/113 psf Max Power(Pmax) [W] 235 239 239 243 Rear Load(UL 1703) 3600 Pa/75 psf Open Circuit Voltage(Voc) [V] 40.7 41.0 40.7 41.0 Certifications/Warranty Short Circuit Current(Isc) [A] 7.54 7.58 7.63 7.66 Certifications UL 1703/IEC 61215/IEC 61730/CEC Max Power Voltage(Vmp) [V] 33.2 33.4 33.1 33.3 (Imp) Fire Type(UL 1703) 1 Max Power Current ( p) [A] 7.08 7.16 7.23 7.30 Power&Product Warranty 25 years* Temperature Characteristics *Warranty details at www.solaria.com NOCT [°C] 45+/-2 Packaging Temp.Coeff.of Pmax [%/°C] -0.40 Temp.Coeff.of Voc [%/°C] -0.32 Stacking Method Horizontal/Palletized Temp.Coeff.of Isc [%/°C] 0.05 Pcs/Pallet 25 Pallet Dims 1668 x 1120 x 1254 mm Design Parameters Pallet Weight 560 kg/1235 lbs Operating temperature [°C] -40 to+85 Pallets/40-ft Container 28 Max System Voltage [V] 1000 Pcs/40-ft Container 700 Max Fuse Rating [A] 15 Bypass Diodes [#] 4 IV Curves vs. Irradiance(330W Module) 1a 1000 W/m2 9 1621mmt5 [63.Bi°19.2] 48mm 0 800 W/m2 [5.8h1 JUNCTION 80x LABEL -.� [5gin] 7 25mm i A B B A -c 1 600 W/mIi.OEn] 6 Hl s 99mm [3.9in] w 5 1IY 400 W/m2 o 4 - - 1055mm±5 100 rum 3 [41.6in30.2] [39.6in] 200 W/m2 NEGATIVE(- P°SRIVErr+ 1 1000mm[3.3 f[� 1009mm($.3 nJ 25mm 0 0 5 10 15 20 25 30 35 40 45 50 , Lt cm]-I. A B B A ` VOLTAGE(V) ��360mm 905.4mm [Sd.2in] (35.43in] 045mm Authorized Dealer [0.11In] 7.0mm[0.281r]x 15 Omm[9.39in I 40 MOUNTING SLOTS'B' 42 GNO'A' 7111m 10.0mm [i731a] [0.39ird 1 • 40.0rnm MOUNTING HOLE 14mTn [1.57in] [min] 1.7mm �`" 35_0mm j0.07in ] [1.3Bin] The Solaria Corporation 6200 Paseo Padre Parkway,Fremont,CA 94555 P:(510)270-2500 www.solaria.com Copyright©2017 The Solaria Corporation Product specifications are subject to change without notice. Rev 2G 1-26-2017 CIF I/4 4.7401111110410. . Z.41pr la IA solar - • • z c4 6741:2 11/14/17 SolarEdge Power Optimizer ► Module Add-On For North America P300 / P320 / P400 / P405 MD Ni •powerO warran�l 1 °'•aagmp /// j/fr /f -/ f PV power optimization at the module-level — Up to 25%more energy — Superior efficiency(99.5%) — Mitigates all types of module mismatch losses,from manufacturing tolerance to partial shading — Flexible system design for maximum space utilization — Fast installation with a single bolt — Next generation maintenance with module-level monitoring — Module-level voltage shutdown for installer and firefighter safety USA - GERMANY - ITALY - FRANCE - JAPAN - CHINA - ISRAEL - AUSTRALIA www.solaredge.us OF ! Z.4( ille V z- 4 _ solar4.- • • ' SolarEdge Power Optimizer Module Add-On for North America -"ins P300 / P320 / P400 / P405 11/14/17 P300 P320 P400 P405 (for 60-cell modules) (for high-power (for 72&96-cell (for thin film 60-cell modules) _ modules) modules) INPUT Rated Input DC Powerlll 300 I 320 I 400 405 W Absolute Maximum Input Voltage 48 80 125 Vdc (Voc at lowest temperature) MPPT Operating Range 8-48 8-80 12.5-105 Vdc Maximum Short Circuit Current(Isc) 10 11 10 Adc Maximum DC Input Current 12.5 13.75 12.5 Adc Maximum Efficiency 99.5 Weighted Efficiency 98.8 Overvoltage Category II OUTPUT DURING OPERATION(POWER OPTIMIZER CONNECTED TO OPERATING SOLAREDGE INVERTER) Maximum Output Current15 Adc Maximum Output Voltage 60 I 85 Vdc OUTPUT DURING STANDBY(POWER OPTIMIZER DISCONNECTED FROM SOLAREDGE INVERTER OR SOLAREDGE INVERTER OFF) Safety Output Voltage per Power 1 Vdc Optimizer STANDARD COMPLIANCE EMC FCC Part15 Class B,IEC61000-6-2,IEC61000-6-3 Safety IEC62109-1(class II safety),UL1741 RoHS Yes INSTALLATION SPECIFICATIONS Maximum Allowed System Voltage 1000 Vdc Compatible inverters All SolarEdge Single Phase and Three Phase inverters Dimensions(WxLxH) 128x152x27.5/ 128x152x35/ 128x152x48/ mm/in 5x5.97x1.08 5x5.97x1.37 5x5.97x1.89 Weight(including cables) 770/1.7 930/2.05 930/2.05 gr/lb Input Connector MC4 Compatible Output Wire Type/Connector Double Insulated;MC4 Compatible .Output Wire Length 0.95/3.0 I 1.2/3.9 m/ft . Operating Temperature Range -40-+85/-40-+185 °C/°F Protection Rating IP68/NEMA6P Relative Humidity 0-100 % I'I Rated STC power of the module.Module of up to+5%power tolerance allowed. PV SYSTEM DESIGN USING SINGLE PHASE THREE PHASE 208V THREE PHASE 480V A SOLAREDGE INVERTER(2) Minimum String Length 8 10 18 (Power Optimizers) Maximum String Length 25 25 50 (Power Optimizers) Maximum Power per String 5250 6000 12750 W Parallel Strings of Different Lengths or Orientations Yes mit is not allowed to mix P405 with P300/P400/P600/P700 in one string. CE ETA ©SolarEdge Technologies,Inc.All rights reserved.SOLAREDGE,the SolarEdge logo,OPTIMIZED BY SOLAREDGE are trademarks or registered trademarks of SolarEdge Technologies,Inc.All other trademarks mentioned herein are trademarks of their respective owners.Date:02/2015 V.01.Subject to change without notice. °F I/4 i65; 11111101:15.% 4 solar - • • •b 11114117 SolarEdge Single Phase Inverters For North America SE3O0OA-US / SE38O0A-US / SE5000A-US / SE600OA-US / SE76O0A-US / SE1O000A-US / SE114O0A-US \co erte,. 1V15' Vear my Warta •Ja},anJ\. a I7� � 4 I ■# - -�I • The best choice for SolarEdge enabled systems ▪ Integrated arc fault protection (Type 1)for NEC 2011 690.11 compliance — Superior efficiency(98%) — Small, lightweight and easy to install on provided bracket — Built-in module-level monitoring — Internet connection through Ethernet or Wireless — Outdoor and indoor installation — Fixed voltage inverter, DC/AC conversion only — Pre-assembled Safety Switch for faster installation — Optional—revenue grade data,ANSI C12.1 USA-GERMANY-ITALY-FRANCE-JAPAN-CHINA-AUSTRALIA-THE NETHERLANDS- ISRAEL www.solaredge.us solar - 69z Single Phase Inverters for North America SE3000A US/SE3800A US/SE5000A US/SE6000A US/ WI% TSE7600A-US/SE10000A-US/SE11400A-US jVp7 VI SE3000A-US SE3800A-US SE5000A-US SE6000A-US SE7600A-US SE10000A-US SE114001,14d817 OUTPUT _ Nominal AC Power Output 3000 3800 5000 6000 7600 9980 @ 208V 11400 VA 10000 @240V Max.AC Power Output 3300 4150 5400 @ 208V 6000 8350 10800 @ 208V 12000 VA 5450 @240V 10950 @240V AC Output Voltage Min:Nom:Max.ltl 183-208-229 Vac AC Output Voltage Min:Nom:Max.ltl 211-240-264 Vac AC Frequency Min.-Nom.-Max.ltl 59.3-60-60.5(with HI country setting 57-60-60.5) 1 Hz • GMax.FDI Continuous Output Current r 12.5 16 I 21 @ 240V f 25 32 1 42 @ 240V f 47.5 A • I 1 A Utility Monitoring,Islanding Protection,Country Configurable Thresholds Yes Yes INPUT Recommended Max.DC PowerlZl 3750 I 4750 1 6250 I 7500 I 9500 I 12400 14250 W °(STC) 111 111 111 111 111 Transformer-less,Ungrounded I Yes Max.Input Voltage 500 Vdc Nom.DC Input Voltage I 325 @ 208V/350 f@ 240V Vdc Max.Input Currentl3l 9.5 I 13 115.5 @ 240V 8V 1 18 I 23 3035 @2240V 08V I 34.5 Adc Max.Input Short Circuit Current !!!! 45 Adc Reverse-Polarity Protection Yes Ground-Fault Isolation Detection 600ko Sensitivity • Maximum Inverter Efficiency 97.7 98.2 98.3 98.3 98 98 98 • CEC Weighted Efficiency 97.5 98 97.5 @ 208V 97.5 97.5 97 @ 208V 97.5 % 98 @ 240V 97.5 @ 240V • Nighttime Power Consumption <2.5 <4 W ADDITIONAL FEATURES Supported Communication Interfaces I RS485,RS232,Ethernet,ZigBee(optional) Revenue Grade Data,ANSI C12.1 Optionall4l Rapid Shutdown-NEC 2014 690.12 [ Functionality enabled when SolarEdge rapid shutdown kit is installedlsl STANDARD COMPLIANCE Safety UL1741,UL1699B,UL1998,CSA 22.2 Grid Connection Standards IEEE1547 Emissions FCC partly class B INSTALLATION SPECIFICATIONS AC output conduit size/AWG range I 3/4"minimum/16-6 AWG I 3/4"minimum/8-3 AWG • I DC input conduit size/#of strings/ AWG range 3/4"minimum/1-2 strings/16-6 AWG 3/4"minimum/1-2 strings/14-6 AWG Dimensions with Safety Switch 30.5x12.5x7/ 30.5 x 12.5 x 7.5/ 30.Sx12.5x10.5/775x315x260 in/ .(HxWxD) 775 x 315 x 172 775 x 315 x 191 mm . Weight with Safety Switch 51.2/23.2 54.7/24.7 88.4/40.1 lb/kg Cooling Natural Convection Fans(user replaceable) Noise <25 <50 dBA Min.-Max.Operating Temperature -13 to+140/-25 to+60(-40 to+60 version availablelb)) 'F/"C Range . Protection Rating NEMA 3R ° For other regional settings please contact SolarEdge support. lil IZi Limited to 125%for locations where the yearly average high temperature is above 77°F/25'C and to 135%for locations where it is below 7rF/25°C. For detailed information,refer to Jrttp://www.solaredae.us/files/pdfs/inverter dc oversizing euide.pdf (3)A higher current source may be used;the inverter will limit its input current to the values stated. 14i Revenue grade inverter P/N:SExxxxA-US000NNR2 Isi Rapid shutdown kit P/N:SE1000-RSD-S1 161-40 version P/N:SExxxxA-USOCONNU4 Ery [-=---,,,,.„,,,...,F, RoHs ©SolarEdge Technologies,Inc.All rights reserved.SOLAREDGE,the SolarEdge logo,OPTIMIZED BY SOLAREDGE are trademarks or registered trademarks of SolarEdge Technologies,Inc.All other trademarks mentioned herein are trademarks of their respective owners.Date:07/2014.V.01.Subject to change without notice.