Code review for :
Project Id . : Cummings / Reske Residence
Address : 5146 Gore Circle
Town of Vail
Building Safety & Inspection Services Div . , Comm . Dev . Dept .
75 South Frontage Road
Vail , CO 81657
( 970 ) 479 - 2321 FAX ( 970 ) 479 - 2452
Plan analysis based on
the 1997 Uniform Building Code
Project Number : B00 - 0096 Date : June 7 , 2000
Project Name : Cummings / Reske Residence
Address : 5146 Gore Circle
Contractor : G & J Const . Inc .
Occupancy : R3 , U1 Designer : Greg Cummings
Construction : V - N Engineer : Tim Boyle
Report By : Gary Goodell
NOTE : The code items listed in this report are not intended to be a
complete listing of all possible code requirements in the 1997 UBC .
It is a guide to selected sections of the code .
Portions of the material contained in this program are reproduced
from the Uniform Building Code with the permission of the
International Conference of Building Officials .
SEPARATION
DIRECTION BOUNDARY AREA INCREASE FIRE PROTECTION
NORTH Public way 83 . 0 Feet 58 . 0 Feet
EAST Property line 37 . 0 Feet 37 . 0 Feet
SOUTH Property line 40 . 0 Feet 40 . 0 Feet
WEST Property line 17 . 0 Feet 17 . 0 Feet
EXTERIOR WALL FIRE RATINGS AND OPENING PROTECTION
Table 5 - A
NORTH
For Bearing Non - Bearing Opening Construction Parapet
Occupancy Wall Wall Protection Material Required
R3 0 hour 0 hour None Any No
U1 0 hour 0 hour None Any No
" EAST
s For Bearing Non - Bearing Opening Construction Parapet
�; Occupancy Wall Wall Protection Material Required
R3 0 hour 0 hour None Any No
U1 0 hour 0 hour None Any No
SOUTH
For Bearing Non - Bearing Opening Construction Parapet
Occupancy Wall Wall Protection Material Required
R3 0 hour 0 hour None Any No
U1 0 hour 0 hour None Any No
WEST
For Bearing Non - Bearing Opening Construction Parapet
�_ Occupancy Wall Wall Protection Material Required
R3 0 hour 0 hour None Any No
�
<
i
�
,
=
: �
Page # 3
Code review for :
Project Id . : Cummings / Reske Residence
Address : 5146 Gore Circle
U1 0 hour 0 hour None Any No
None - - No fire protection requirements for openings .
3 / 4 hour - - Openings are to be protected with 3 / 4 hr fire assemblies .
50 % of the area of the wall maximum . - - Table 5 - A ,
Footnote 5 & Sec . 503 . 2 . 2
Maximum sinqle window size is 84 sq . ft . with no dimension
greater than 12 feet . - - Sec . 713 . 8
Not Allowed - - Openings are not permitted in this wall .
FL NAME AREA MIN . LIGHT MIN . VENT NO . EXITS EGRESS
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
2 Hallway 56 . 0 . 0 1 No
2 Bedroom # 4 190 19 . 0 9 . 5 1 Yes
2 Bedroom # 4 183 18 . 3 9 . 15 1 Yes
2 Bathroom 50 . 0 2 . 5 1 No
TOTAL FOR FLOOR 479 1
1 Living room 1145 114 . 5 57 . 25 1 No
1 Dining room 270 27 . "0 13 . 5 1 No
1 Kitchen 283 . 0 14 . 15 1 No
1 Bedroom 753 75 . 3 37 . 65 1 Yes
1 Bathroom 46 . 0 2 . 3 1 No
1 Storage room 81 . 0 . 0 1 No
1 Garage 587 . 0 . 0 1 No
1 Garage 76 . 0 . 0 1 No
TOTAL FOR FLOOR 3241 2
B Bedroom # 1 185 18 . 5 9 . 25 1 Yes
B Closet ( s ) 22 . 0 . 0 1 No
B Bathroom 126 . 0 6 . 3 1 No
B Bedroom # 2 159 15 . 9 7 . 95 1 Yes
B Closet ( s ) 22 . 0 . 0 1 No
B Laundry room 49 . 0 2 . 45 1 No
B Family room 450 45 . 0 22 . 5 1 No
B Bedroom # 3 156 15 . 6 7 . 8 1 Yes
B Closet ( s ) 22 . 0 . 0 1 No
B Bathroom 81 . 0 4 . 05 1 No
TOTAL FOR FLOOR 1272 1 Yes
BUILDING TOTAL 3720 2
r
1
�
/'
�
Page # 4
Code review for :
Project Id . : Cumminqs / Reske Residence
Address : 5146 Gore Circle
FOOTNOTES :
1 ) EGRESS - An operable window or door that opens directly to the
exterior is required from this room . The minimum clear openable
area must meet the following . - - Sec . 310 . 4
1 ) The minimum clear height is 24 inches
2 ) The minimum clear width is 20 inches
3 ) The minimum clear area is 5 . 7 square feet
4 ) The maximum sill height is 44 inches
Escape and rescue windows with a finished sill below ground shall have
a window well . The clear horizontal dimension shall allow the the
window to be fully opened and provide a minimum clear accessible net
opening of 9 square feet with a minimum dimension of 36 inches .
Window wells with a vertical depth of more than 44 inches shall be
equipped with an approved permanently affixed ladder or stairs .
2 ) The number of exits is based on Table 10 - A ( Dwellings )
3 ) A mechanical ventilation system may be used in lieu of exterior
openings for ventilation . - - Sec . 1203 . 3 Such system shall be
capable of providing two air changes per hour .
4 ) The requirement for an egress window in the basement is based on
Sec . 310 . 4
ROOM DIMENSIONS :
Habitable space shall have a ceiling height of not less than 7 feet
6 inches . Kitchens , halls , bathrooms and toilet compartments may have
a ceiling height of 7 feet measured to the lowest projection . If the
ceiling is sloping , then the minimum height is required in only 1 / 2
of the area . - - Sec . 310 . 6 . 1
Every dwelling unit shall have at least one room which has not less
than 120 square feet of floor area . Other habitable rooms except
kitchens shall have an area of not less than 70 square feet .
- - Sec . 310 . 6 . 2
Habitable rooms other than a kitchen shall not be less than 7 feet
in any dimension . - - Sec . 310 . 6 . 3
r
1
r
<
e
.
Paqe # 5
Code review for :
Project Id . : Cummings / Reske Residence
Address : 5146 Gore Circle
STAIR REQUIREMENTS :
1 ) A stairway in a dwelling must be at least 36 inches wide .
- - Sec . 1006 . 2
2 ) The maximum rise of a step is 8 inches and the minimum run is 9
inches - - Sec . 1006 . 3 exc . # 1
3 ) A handrail is required on one side a stairway 34 to 38 inches above
the nosing if there is 4 or more risers . - - Sec . 1006 . 9 exceptions
4 ) Provide a guard rail where drop off is greater than 30 inches .
The minimum height = 36 inches , maximum opening size = 4 inches .
- - Sec . 509 . 1 & 509 . 2 exc . # 1
5 ) The minimum headroom is 6 ft . - 8 inches . - - Sec . 1006 . 15
6 ) Enclosed usable space under the stairs is required to be protected
as required for 1 hr . fire - resistive construction . - - Sec . 1006 . 12
d
,
�
_
Page # 6
Code review for :
Project Id . : Cummings / Reske Residence
Address : 5146 Gore Circle
GLAZING REQUIREMENTS
Al1 glazing in hazardous locations is required to be of safety
glazing material . - - Sec . 2406 . 3 & 2406 . 4
Locations :
1 ) Glazing in ingress and egress doors except jalousies .
2 ) Glazing in fixed and sliding panels of slidinq door assemblies
and panels in swinging doors other than wardrobe doors .
3 ) Glazing in storm doors .
4 ) Glazing in all unframed swinging doors .
5 ) Glazing in doors and enclosures for hot tubs , whirlpools , saunas ,
steam rooms , bathtubs and showers . Glazing in any portion of a
building wall enclosing these compartments where the bottom exposed
edge of the glazing is less than 60 inches above a standing surface
and drain inlet .
6 ) Glazing in fixed or operable panels adjacent to a door where the
nearest exposed edge of the glazing is within a 24 - inch arc of
either vertical edge of the door in a closed position and where the
bottom exposed edge of the glazing is less than 60 inches above the
walking surface .
7 ) Glazing in an individual fixed or operable panel , other than those
locations described in items 5 and 6 above , than meets all of the
following conditions :
A . Exposed area of an individual pane greater than 9 square feet .
B . Exposed bottom edge less than 18 inches above the floor .
C . Exposed top edge greater than 36 inches above the floor .
D . One or more walking surfaces within 36 inches horizontally of
the plane of the glazinq .
8 ) Glazing in railings regardless of height above a walking surface .
Included are structural baluster panels and nonstructural in - fill
panels .
9 ) Glazing in walls and fences used as the barrier for indoor and
outdoor swimming pools and spas when the bottom edges is less than
60 inches above the pool side and the glazing is within 5 feet
of the pool or spa water ' s edge .
10 ) Glazing in walls enclosing stairway landings or within 5 feet of
then bottom and top of stairways where the bottom edge is less
than 60 inches above the walking surface .
J
�,
b'�
Page # 7
Code review for :
Project Id . : Cummings / Reske Residence
Address : 5146 Gore Circle
SMOKE DETECTOR REQUIREMENTS :
1 ) A smoke detector is required on the ceiling or wall at a point
centrally located in the corridor or area giving access to each
sleeping area . - - Sec . 310 . 9 . 1 . 4
2 ) A smoke detector is required on the ceiling or wall in each sleeping
area . - - Sec . 310 . 9 . 1 . 4
3 ) A smoke detector is required on all stories . - - Sec . 310 . 9 . 1 . 4
If the upper level contains sleeping room ( s } , a smoke detector is
required in the ceiling of the upper level close to the stairway .
- - Sec . 1210 . ( a ) 4
NOTE : A smoke detector is required in the basement . - - Sec . 310 . 9 . 1 . 4
4 ) Smoke detectors are required to be wired to the building ' s power
source and shall be equipped with a battery backup . - - Sec . 310 . 9 . 1 . 3
5 ) Detectors shall sound an alarm audible in all sleeping area of the
dwelling in which they are located . - - Sec . 310 . 9 . 1 . 4
OCCUPANCY SEPARATION :
Between the garage and the residence , materials approved for 1 hr . fire
resistive construction are required on the garage side only and any
doors between the garage and the residence are to be a self - closing
1 3 / 8 inch solid core door or a 20 minute fire door . - - Table 3 - B &
Sec . 302 . 4 exc . # 3
SHAFT ENCLOSURES :
1 ) Chutes and dumbwaiter shafts with a cross - sectional area of not more
than 9 square feet may lined on the inside with not less than 26 gage
galvanized sheet metal with all joints locklapped . The outside must be
1 hr construction . All openings into any such enclosure shall be
protected by not less than a self - closing solid wood door 1 3 / 8 inches
thick or equivalent . - - Sec . 711 . 6
2 ) Gas vents and noncombustible piping installed in walls passing through
3 floors or less do not need to be in 1 hour shafts , provided the
annular space around the vents or piping is filled at each floor or
ceiling with noncombustible materials . - - Sec . 711 . 3
3 ) Shafts for gas vents , factory - built chimneys , piping , or ducts that
do not extend through not more than 2 floors need not be in 1 hour
shafts , provided the openings around the penetrations are fire stopped
at each floor . - - Sec . 711 . 3
4 ) All other shafts are required to be enclosed in a 1 hour assembly .
- - Sec . 711 . 1 & Table 6 - A
.
8
a
e
Page # 8
Code review for :
Project Id . : Cummings / Reske Residence
Address : 5146 Gore Circle
ATTIC REQUIREMENTS :
1 ) Provide an access to all attic areas with a clear height of 30 inches
or more . The minimum size is 22 inches by 30 inches . There must be 30
inches or more clear height above the access . - - Sec . 1505 . 1
2 ) Provide ventilation in all attic areas . The net free vent area is
to be not less than 1 square foot for each 150 square feet of attic
area . The vent area may be 1 / 300 if at least 50 % of the required
ventilating area is provided by ventilators located in the upper
portion of the attic . The upper ventilators must be at least 3 feet
above the eave or cornice vents . - - Sec . 1505 . 3 exc . # 1
The vent area may be 1 / 300 provided a vapor retarder having a
transmission rate not exceeding 1 perm is installed on the warm side
of the attic insulation . - - Sec . 1505 . 3 exc . # 2
For a 500 . 0 sq . ft . attic area :
Ratio Minimum sq . ft . of vent
1 / 150 3 . 33
1 / 300 1 . 67
3 ) Where eave or cornice vents are installed , insulation shall not block
the free flow of air . A minimum of 1 inch of air space shall be
provided between the insulation and roof sheathing . - - Sec . 1505 . 3
CRAWLSPACE REQUIREMENTS :
1 ) Provide ventilation either by mechanical means or by openings in
exterior walls . Opening shall provide a net area of not less than
1 square foot for each 150 square feet of area in crawl space .
Openings shall be distributed on two opposite sides and be located
as close to corners as practical . - - Sec . 2317 . 7 Note : Vent openings
may be reduced to 10 % of the above if ground surface area is covereci
with an approved vapor barrier and the building official approves .
For a 3241 . 0 sq . ft . crawlspace area :
Ratio Minimum sq . ft . of vent
1 / 150 21 . 61
2 ) Provide 18 - inch by 24 - inch access opening to the crawl space area .
Note : opening may be required to be larger if inechanical equipment
is located in the crawl space . - - Sec . 2317 . 3
3 ) Unless the wood is listed as an approved wood of natural resistance
to decay or treated wood , the minimum clearance between exposed
earth and floor joist is 18 inches . The minimum clearance to beams
and girders is 12 inches . - - Sec . 2317 . 3
�
n
e
d
� �
D
•
� F
Page # 9 "
Code review for :
Project Id . : Cummings / Reske Residence
Address : 5146 Gore Circle
1 ) Provide a window or door to the exterior from every room used for
sleeping and basements . - - Sec . 310 . 4 A window must provide a clear
open area of 5 . 7 sq . ft . , a clear height of 24 inches ( minimum ) , and a
clear width of 20 inches ( minimum ) . - - Sec . 310 . 4
4 ) The minimum ceiling in a habitable space is 7 feet 6 inches except
kitchens , halls , and baths may have a ceiling heiqht of 7 feet .
- - Sec . 310 . 6 . 1
5 ) Provide a smoke detector in all sleeping rooms and areas having
access to sleeping rooms . - - Sec . 310 . 9 . 1 . 4
6 ) If there is a basement , provide a smoke detector that is connected
to an alarm audible in all sleeping areas . - - Sec . 310 . 9 . 1 . 4
7 ) Provide a smoke detector on all floors that is connected to an
alarm audible in all sleeping areas . - - Sec . 310 . 9 . 1 . 4