Loading...
HomeMy WebLinkAboutB14-0443_B14-0443 load calcs_1415116260 (2).pdfA-Phase Electric, LLC 5194 Main Gore Drive East Vail, CO Load Calculation General Lighting and Receptacle Demand Load: 6367 sq. ft. x 3VA = 19101 1,500 VA x 2= 3000 1,500 VA x 1 = 1500 Total connected load: 23,601 3,000 VA @ 100% = 3,000 VA @ 35% = 7,210.4 2523.62 Total general lighting and Receptacle demand load: 5,524 Range demand load: 12,000VA 8,000 Dryer Load: 5,000 Fixed appliance load: Dishwasher 1 1,200 Garbage disposal 1 800 microwave 1 1,200 UC refrigerator 1 1,200 steam shower 1 8,000 subtotal 12,400 demand factor -25% 3,100 Total fixed appliance load: 9,300 Heating load: heat tape 4800 Total heating load: 4,800 25% of largest motor: 200 continued next page www.aphaseelectricllc.com A-Phase Electric, LLC 5194 Main Gore Drive East Vail, CO Load Calculation Totals: General lighting and receptacles: 5,524 Range: 8,000 Dryer: 5,000 Fixed appliance: 9,300 Heating: 4,800 25% of largest motor: 200 Total:VA 32,824 AMPS 136.77 Installed Service Size: 200A single phase x www.aphaseelectricllc.com