Loading...
HomeMy WebLinkAboutE18-0039_332 Mill Creek Circle Load Calculation_1524603709.pdf CIF I/4 ii:p1; 1111 ,11111 4 53 kliP' Load Calculation: 332 Mill Creek Circle General Loads: o4114118 1. General Lighting and General-Use Receptacles 8,000 SFx3VA/SF 24,000 VA 2. Small Appliance and Laundry Loads Laundry Circuit 1 x 1,500VA 1,500 VA Appliance Circuit 4 x 1,500VA 6,000 VA 3. a. Appliance Loads Dishwashers (2) 2,400 VA Disposal 1,000 VA Microwave 1,000 VA Refrigerators (2) 1,000 VA Wine Room 3,000 VA Garage Door Opener 500 VA Jetted Tub 960 VA Fire Pit 250 VA Steam Generator (2) 35,300 VA BBQ 250 VA Elevator 6,420 VA Humidifiers (2) 4,000 VA 3. b. Electric Ranges and Other Cooking Appliances Range 5,000 VA Cook Top 5,000 VA 3. c. Electric Clothes Dryers Dryers (1) 3,500 VA Sub-Total 101,080 VA 10,000 VA at 100% 10,000 VA ' Remainder at 40% 36,432 VA Sub-Total #1 46,164 VA Heating and Air Conditioning Loads 1. Air Conditioning Load** 6,000 VA 2. General Mechanical 16,000 VA Sub-Total #2 16,000 VA Total Design Load: 62,164 VA System Voltage: 240 Volts, 1-phase 260 A Notes: **Air conditioning load not included because heating load exceeds it