HomeMy WebLinkAboutA111TV
TV
GFI
GFI GFI
GFI
GFI
GFI GFI
3
1
2
3
A B C
B
C
D
F
B
B
B
E E
F
B B B
B
B
B
5' - 6" 5' - 6 1/4"
4' - 1 1/2"
4' - 1 3/4" EQ EQ EQ EQ
EQ EQ
A A
TYPICAL OF (6) ONE BEDROOM UNITS TYPICAL OF (5) TWO-BEDROOM UNITS
+ ONE RECESSED, LENSED CAN
LIGHT CENTERED O/STORAGE
LOFT, EACH UNIT
CEILING FAN
4' FLUORESCENT LIGHT
EXTERIOR SCONCE
COMBINATION SMOKE
AND CARBON MONOXIDE
DETECTOR
FLUSH MOUNT KEYLESS
SOCKET
UNDER CABINET LIGHT
LIGHTED MIRROR
4" RECESSED
ADJUSTABLE CAN LIGHT
OWNER SUPPLIED
DECORATIVE PENDANT
DUPLEX OUTLET, +9" U.O.N.
SWITCH
LIGHTING LEGEND
EXHAUST FAN
4" RECESSED LENSED
CAN LIGHT L
OS
PER IECC, "a minimum of 75 percent of the lamps in permanently installed lighting fixtures shall be
high-efficacy lamps."
LIGHTING CONTROL KEY
PAD
KP
STEP LIGHT
SL
SP
FLUSH MOUNTED
CEILING SPEAKER
D
CEILING MOUNTED
DOME SURVEILLANCE
CAMERA
ELECTRONIC LOCK WITH
DIGITAL KEYPAD ENTRY
SURFACE MOUNTED
CEILING LIGHT
CALC LOAD FOR 1552 MATTERHORN CIRCLE (WITH RANGES)
5009sf TOTAL AREA / 11 UNITS = 455sf EACH
455 X 3 VA = 1365VA
2 S.A. & 1 LAUNDRY = 4500VA
= 5865
-3000 @ 100%
= 2865 @ 35%
X 35%
= 1002 VA
+3000 @100%
= 4002 VA GEN LIGHT EA UNIT
RANGE 10000 X 262 (11 UNIT DEMAN FACTORS) = 2600VA
DRYER 5000 X 47% = 2350 VA
WATER HEATER & HEAT = 11,000 VA
= 19952 KVA / 240
= 83.13 AMPS PER UNIT
5009sf TOTAL AREA / 11 UNITS = 455sf EACH
455 X 3 VA = 1365 VA
2 S.A. & 1 LAUNDRY = 4500 VA
=5865
-3000 @ 100%
= 2865 @35%
X 35%
= 1002 VA
+3000 @ 100%
=4002 VA GEN LIGHT AT EACH UNIT
UNITS
11 X 4002 GEN LIGHT = 44022 VA
11 X 5000 DRYERS = 55000 VA
11 X 11000 WATER HEATER & HEAT = 121000 VA
11 X 10000 = 110000 VA
= 330022 KVA X 42% [USING OPT CALC. (220.84)]
= 138609 KVA / 240 VOLTS
= 577.5 AMPS FOR BUILDING
CALC LOAD FOR 1552 MATTERHORN CIRCLE (NO ELECTRIC RANGES)
5009sf TOTAL AREA / 11 UNITS = 455sf EACH
455 X 3 VA = 1365VA
2 S.A. & 1 LAUNDRY = 4500VA
= 5865
-3000 @ 100%
= 2865 @ 35%
X 35%
= 1002 VA
+3000 @100%
= 4002 VA GEN LIGHT EA UNIT
NO RANGE
DRYER = 2350 VA
WATER HEATER & HEAT = 11,000 VA
= 17352 KVA / 24 VOLTS
= 72.3 AMPS PER UNIT
5009sf TOTAL AREA / 11 UNITS = 455sf EACH
455 X 3 VA = 1365 VA
2 S.A. & 1 LAUNDRY = 4500 VA
=5865
-3000 @ 100%
= 2865 @35%
X 35%
= 1002 VA
+3000 @ 100%
=4002 VA GEN LIGHT AT EACH UNIT
UNITS
11 X 4002 GEN LIGHT = 44022 VA
11 X 5000 DRYERS =55000 VA
11 X 11000 WATER HEATER & HEAT = 121000 VA
NO ELEC RANGE = 220022 KVA X 42% [USING OPT CALC. (220.84)]
= 92409 / 240
= 385 AMPS FOR BUILDING
1
2
3
A B C
PROVIDE POWER
FOR FUTURE RADON
EXHAUST FAN
PER IRC R408.3 -
PROVIDE 6.5 CFM
(1CFM/50SF)
CONTINUOUS
CIRCULATION
FAN, TYP. 1
BDRM UNITS
PER IRC R408.3 -
PROVIDE 10 CFM
(1CFM/50SF)
CONTINUOUS
CIRCULATION
FAN, TYP. 2
BDRM UNITS
THRU FLOOR
TRANSFER GRILLE
THRU FLOOR
TRANSFER GRILLE
CRAWL SPACE
ACCESS
1
2
3
A B C
SLOPING SLOPING
EQ EQ EQ EQ
VFY
7' - 6"
VFY
7' - 6"
FOR CONSTRUCTION
Project number
Date
Drawn by
5/27/2016
11:36:14 AM
A111
REFLECTED CEILING PLAN
MAT-15
1552
MATTERHORN
CIRCLE
VAIL,
COLORADO
MATTERHORN INN
CONDOMINIUMS
05.26.2016
WMC
1/4" = 1'-0" 1
LEVEL 1
1/4" = 1'-0"
ELECTRICAL LEGEND
1/4" = 1'-0"
ELEC LOAD CALCS - WITH RANGES
1/4" = 1'-0"
ELEC LOAD CALCS - NO RANGES
No. Description Date
1/4" = 1'-0"
2
CRAWL SPACE
1/4" = 1'-0" 3
LOFT LEVEL
06/15/16